Have a look at the manual Lucent Technologies DEFINITY Enterprise Communications Server Release 8.2 Upgrades And Additions Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 413 Lucent Technologies manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
DEFINITY Enterprise Communications Server Release 8.2 Upgrades and Additions for R8r 555-233-115 Issue 1 April 2000 Upgrading G3rV2, V3, V4 to R8r and Adding Memory 1-5 Task Tables 1 Verify Interchange (H/C only)1-15 Upgrade other carrier (H/C only)1-15 Affix position label(s)1-15 Verify software version1-16 Save Translations1-16 Save Announcements (if necessary)1-16 Restore Disk1-16 Upgrade Software1-17 Reset SPE status (H/C only)1-17 List Configuration Control1-17 Set Daylight Savings Rules1-18 Set Date and Time1-19 Set Core Dump Vector1-20 Enable TTI1-20 Release MMI (H/C only)1-21 Resolve Alarms1-21 Check Link Status1-21 Enable Scheduled Maintenance1-21 Enable Customer Options and Alarm Origination to INADS1-21 Check SPE status (H/C only)1-22 Save Translations1-22 Save Announcements (if necessary)1-22 Back Up Disk1-23 Return Replaced Equipment1-23 Continued on next page Table 1-2. Tasks to upgrade the software and hardware — Continued ÖTask Description Page
DEFINITY Enterprise Communications Server Release 8.2 Upgrades and Additions for R8r 555-233-115 Issue 1 April 2000 Upgrading G3rV2, V3, V4 to R8r and Adding Memory 1-6 Upgrade the software and hardware 1 Upgrade the software and hardware Check SPE 1. Type status spe and press En t e r to c hec k the health of the SPE. For hig h or c ritic al reliab ility systems: nTh e Standby Refreshed field shows yes nTh e Standby Shadowing field shows on nTh e Standby Handshake field shows up Save Translations 1. Type save translation and press En te r to write all translation information from memory to the d isk, whic h takes ab out 2 minutes. Save Announcements (if necessary) NOTE: The TN750C Announc ement c irc uit p ac k stores announc ements in nonvolatile memory; saving the announc ements is op tional. 1. If the PPN c ontains a TN750/B Announc ement c irc uit p ac k, typ e display announcements and p ress En te r. 2. If administered rec ord ed announc ements are listed , typ e save announcements cabinet carrier slot and press En t e r. For example, 01 D03. This takes ab out 30 minutes. NOTE: For some software load s, type save announcements from cabinet carrier slot . Typ e help and p ress En t e r for c omp lete c ommand usag e. Back Up Disk 1. Type backup disk and p ress En t e r to write all information from the d isk to the b ac kup tap e. This takes 30 to 40 minutes.
DEFINITY Enterprise Communications Server Release 8.2 Upgrades and Additions for R8r 555-233-115 Issue 1 April 2000 Upgrading G3rV2, V3, V4 to R8r and Adding Memory 1-7 Upgrade the software and hardware 1 Disable Scheduled Maintenance and Alarm Origination to INADS 1. To p revent sc hed uled d aily maintenanc e from interfering with the up d ate or up g rad e, typ e change system-parameters maintenance and p ress En t e r. 2. If sc heduled maintenanc e has b eg un, set the Stop Time field to 1 minute after the c urrent time. or If sc hed uled maintenanc e has not b eg un, set the Start Time field to a time after the upgrade is completed. For example, if you start the upgrade at 8:00 p .m. and the up g rad e takes 90 minutes, set the Start Time field to 21:30. !CAUTION: If you d o not d isab le Alarm Orig ination, the system may g enerate alarms, resulting in unnec essary troub le tic kets. 3. Type neither in the Alarm Origination to OSS Numbers field and p ress En t e r . NOTE: For some software load s, set the Alarm Origination Activated field to n and set the Cleared Alarm Notification and Restart Notification fields to disable or n b efore pressing En t e r. Reconfigure the Tape (G3rV2, V3 R31.0 and Earlier) NOTE: Do not issue the list configuration software command before reconfiguring the removable media. For some software load s, use 3-mem instead of large If stand ard reliab ility: 1. Type configure tape large and press En te r to reconfigure the bac kup removab le med ia for the 2 TN1650B Memory c irc uit pac ks. This c ommand takes ab out 1 minute to c omp lete.
DEFINITY Enterprise Communications Server Release 8.2 Upgrades and Additions for R8r 555-233-115 Issue 1 April 2000 Upgrading G3rV2, V3, V4 to R8r and Adding Memory 1-8 Upgrade the software and hardware 1 If hig h or c ritic al reliab ility: 1. Type configure tape spe-a large and press En t e r to rec onfig ure the removable media in c ontrol c arrier “ A” for 2 TN1650B Memory c irc uit p ac ks. This c ommand takes ab out 1 minute to c omp lete. 2. Type configure tape spe-b large and p ress En te r to rec onfigure the removab le media in c ontrol c arrier “ B” for 2 TN1650B Memory c irc uit p ac ks. This c ommand takes ab out 1 minute to c omp lete. Check Link Status 1. Type display communication-interface links and p ress En te r. Write d own all enab led links. 2. Type status link number and p ress En t e r. Rep eat this step for all links. 3. Write d own whic h links are in servic e. Disable TTI NOTE: Do this step only if the Terminal Translation Initialization (TTI) is enab led . !CAUTION: If you d o not d isab le the TTI, the translations c an b e c orrup ted . Make sure the ISDN is in servic e. If not, try to b usy out and release the ISDN D-c hannel/link to b ring the ISDN trunks b ac k into servic e. 1. Type change system-parameters features and press En t e r. 2. On the sec ond sc reen, set the TTI Enabled? field to n to d e-ac tivate the TTI feature. Check Disk Drive 1. Type list configuration control and press En t e r to c hec k the vintag e of the d isk drive. If the d rive is V4 or later, g o to Check TTI Status . or If the d rive is not V4 or later, g o to Install Disk Drive (if not TN1657 V4 or earlier).
DEFINITY Enterprise Communications Server Release 8.2 Upgrades and Additions for R8r 555-233-115 Issue 1 April 2000 Upgrading G3rV2, V3, V4 to R8r and Adding Memory 1-9 Upgrade the software and hardware 1 Install Disk Drive (if not TN1657 V4 or earlier) !CAUTION: When rep lac ing any hardware, b e sure to g round yourself against elec trostatic d isc harg e (ESD) b y wearing a g round ed wrist strap . !CAUTION: If a hig h or c ritic al reliab ility system, rep lac e and restore the d isk d rives one a t a t i m e s t a r t in g w it h t h e s t a n d b y SPE. N e v e r re p la c e t h e a c t iv e a n d stand b y d isk drives at the same time. 1. Type busyout host-adapter [a | b ] and press En t e r to p revent other ap p lic ations from ac c essing the d isk or removab le med ia. 2. Remove the existing TN1657 Disk Drive c irc uit p ac k and p lac e it in antistatic material. 3. Insert a new TN1657 c irc uit p ac k into the DISK DRIVE slot. 4. To p rop erly seat the c irc uit p ac k, p ush firmly on the front of the fac ep late until the latc h reac hes the b ottom rail of the c arrier. Then c lose the latc h until it is fully engaged. 5. Type release host-adapter [a | b ] and p ress En te r to release the d isk from the maintenanc e-b usyout c ond ition and p ut it b ac k into servic e. 6. Type reset host-adapter [a | b ] and press En te r to allow the d isk to sp in up . 7. Type status spe and press En t e r to verify that the d isk is now in servic e. NOTE: If the disk fails to return to servic e, rep eat Step s 1, 3, 4, and 5. For hig h or c ritic al reliab ility, rep eat step s 1 throug h 7 on the ac tive c arrier. Restore Disk NOTE: Until this c ommand finishes, the system p rovid es no user feed b ac k on the manag ement terminal sc reen. Do not p ress En t e r while the c ommand exec utes. Doing so c auses the terminal sc reen to c lear as the c ommand finishes; erasing any suc c ess or failure messag es the system may p rovid e. If stand ard reliab ility: 1. Type restore disk full and p ress En te r to c op y the information on the removab le media to d isk, whic h takes ab out 30 minutes. If hig h or c ritic al reliab ility: 1. Type restore disk full both and press En t e r.
DEFINITY Enterprise Communications Server Release 8.2 Upgrades and Additions for R8r 555-233-115 Issue 1 April 2000 Upgrading G3rV2, V3, V4 to R8r and Adding Memory 1-10 Upgrade the software and hardware 1 Check TTI Status 1. Type status TTI and p ress En te r. Wait until the Percent Complete field shows 100% . Busyout MMI Circuit Packs (H/C only) !CAUTION: Multimed ia-to-voic e station c alls are not p reserved on an up g rade. Failure to b usy-out the TN787 Multimed ia Interfac e (MMI) c irc uit p ac ks results in unusab le TN787 and TN788 Multimed ia Voic e Cond itioner p orts. 1. Type display system-parameters customer-options and press En t e r. On sc reen 2 und er the Multimed ia Call Hand ling (MMCH) op tions, c hec k the Basic and Enhanced fields. 2. If either the Basic or Enhanced field is y , typ e list configuration all and p ress En t e r to loc ate all MMI (TN787) c irc uit p ac ks. 3. If there are MMI c irc uit p ac ks, typ e busyout board cabinet carrier slot and p ress En t e r to remove the c irc uit p ac ks from servic e. Lock the active SPE (H/C only) 1. Type status spe and press En t e r to d etermine whic h c ontrol c arrier is ac tive or ob serve the c ontrol c arrier LEDs. NOTE: For hig h or c ritic al reliab ility systems, we rec ommend that you rep lac e the c irc uit pac ks in the stand b y c arrier first. !CAUTION: When rep lac ing any hardware, b e sure to g round yourself against elec trostatic d isc harg e (ESD) b y wearing a g round ed wrist strap . 2. Move the SPE-SELECT switc hes on b oth Dup lic ation Interfac e (DUPINT) circuit packs, one at a time, to the ac tive c arrier.
DEFINITY Enterprise Communications Server Release 8.2 Upgrades and Additions for R8r 555-233-115 Issue 1 April 2000 Upgrading G3rV2, V3, V4 to R8r and Adding Memory 1-11 Upgrade the software and hardware 1 Check the active tone-clock (H/C only) 1. Type status port-network 1 and verify that the Tone-Cloc k is in the same c a r r ie r a s t h e a c t i v e SPE a n d t h a t t h e Service State field shows in . NOTE: This takes 1 minute to c omp lete. If the servic e state is inc orrec t, rep eat the c ommand until this c ond ition is met. If the ac tive Tone-Cloc k has not migrated to the ac tive c arrier after 1 minute, then a Tone-Cloc k p rob lem exists. Refer to the TDM-CLK Maintenanc e Ob jec ts sec tion of the DEFINITY Enterp rise Communic ations Server Release 8 Maintenanc e for R8r b ook to resolve any p rob lems. Power Down the Processor Carrier !CAUTION: Do not p ower d own the whole c ab inet; it is not nec essary. For stand ard reliab ility, p ower d own the p roc essor c arrier. This c auses a servic e interrup tion. For high or critical reliability, power down the standby carrier. 1. To power down the processor carrier, remove the power plug from the left sid e of the c arrier then remove the p ower p lug from the right side of the carrier. Remove the Circuit Packs NOTE: More detailed information on removing and add ing c irc uit p ac ks is in Chapter 6, ‘‘Adding or Removing Cabinet Hardware’’ . 1. Remove the b lank fac ep late next to the MSSNET slot in the c arrier. 2. Remove the UN332B circuit pack from the carrier and place it in antistatic packing material. 3. Remove the tap e from the tap e d rive. 4. Remove the TN1656 tap e d rive and p lac e it in antistatic p ac king material.
DEFINITY Enterprise Communications Server Release 8.2 Upgrades and Additions for R8r 555-233-115 Issue 1 April 2000 Upgrading G3rV2, V3, V4 to R8r and Adding Memory 1-12 Upgrade the software and hardware 1 Install the Circuit Packs NOTE: To p rop erly seat a c irc uit p ac k, p ush firmly on the front of the fac eplate until the latc h reac hes the b ottom rail of the c arrier. Then c lose the latc h until it is fully engaged. 1. Insert the TN1650B memory c irc uit p ac k in memory slot 3. NOTE: If a hig h or c ritic al reliab ility system, install the TN1650B at the same time as the op tic al d rive. Note that add ing memory to the stand by SPE c a u s e s a n e rro r b e c a u s e t h e m e m o r y n u m b e r b e t w e e n t h e standb y and ac tive c arriers does not matc h. 2. Insert the UN332C c irc uit p ac k into the MSSNET slot. 3. Rep lac e the b lank fac ep late next to the MSSNET c irc uit p ac k. 4. Insert the TN2211 optical drive (Figure 1-1 ) into the rig ht most TAPE DRIVE slot. It only takes up 2 slots. 5. Plac e a b lank fac eplate over the left most TAPE DRIVE slot. Figure 1-1. TN2211 Optical Drive Red Green Yellow fpdf2211 KLC 010600TN2211 OPTICAL DRIVE
DEFINITY Enterprise Communications Server Release 8.2 Upgrades and Additions for R8r 555-233-115 Issue 1 April 2000 Upgrading G3rV2, V3, V4 to R8r and Adding Memory 1-13 Upgrade the software and hardware 1 6. Plac e the formatted removab le med ia, lab el fac ing left, into the op tic al drive. NOTE: Make sure the formatted removab le med ia is not write-p rotec ted b efore p lac ing it into the op tic al drive (see Figure 1-2). Figure 1-2. Make sure the disk is not write-protected. !CAUTION: The removab le media has a slid ing , metal c over to p rotec t the surfac e of the d isk. DO NOT TOUCH THE DISK ( Figure 1-3). Figure Notes 1. Not Write-p rotec ted 2. Write-p rotec ted h1dfdsk KLC 112499 12
DEFINITY Enterprise Communications Server Release 8.2 Upgrades and Additions for R8r 555-233-115 Issue 1 April 2000 Upgrading G3rV2, V3, V4 to R8r and Adding Memory 1-14 Upgrade the software and hardware 1 Figure 1-3. Do not touch the disk inside the cartridge. Power Up the Processor Carrier 1. To restore p ower to the p roc essor c arrier, insert the p ower p lug on the right side of the c arrier then insert the p ower p lug on the left sid e of the carrier. If hig h or c ritic al reliab ility: 2 . M o n it o r t h e SPE a s it re b o o t s b y o b se r vi n g t h e L ED s a n d t h e t e r m in a l. I t is p owered up when the YELLOW LED on the Proc essor c irc uit p ac k b links in a stead y state, whic h takes ab out 10 minutes. Unlock the Active SPE (H/C only) 1. Move the SPE SELECT switc hes to the AUTO position one at a time. 2. Wait 10 minutes. !CAUTION: Allow 10 minutes after unlocking to make sure the standby SPE has fully returned to servic e. 640MB 2048BYTES /S EC TO R h1dfdsk1 KLC 091799