Home
>
Lucent Technologies
>
Communications System
>
Lucent Technologies Octel 100 Implementation And Service Manual
Lucent Technologies Octel 100 Implementation And Service Manual
Have a look at the manual Lucent Technologies Octel 100 Implementation And Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 413 Lucent Technologies manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
24. Testing and Troubleshooting the System Implementation and Service Manual System Troubleshooting Table24-33 System Setup parameters: · Verify that an Intercom Paging Code is specified on the Intercom Paging tab in System Setup. · Verify that the Release Code for Intercom Paging is specified on the Intercom Paging tab. Class of Service dialog box: · Verify that the Intercom Paging checkbox is enabled. Subscriber Settings dialog box: · If intercom paging was activated by the subscriber over the phone, verify that the system manager did not override the setting on the Subscriber Settings dialog box. · Verify that No Answer/Call Blocking is set to Default. Mailboxes are not functioning properly Cannot edit a mailboxResolution Possibilities: · Verify that you have logged in at the necessary level of security. To access all functions except a few on the Options menu, enter the Level 2 security password (default = 12345). To access all functions, including all those on the Options menu, enter the Level 3 security password (default = 67890). · Note that a guest mailbox cannot be edited, nor can a mailbox that is in use. · Note that when using greeting by port, the supervisor mailbox must have either the same company entry as the subscriber’s mailbox or no company entry to edit the mailbox using the supervisor main menu functions over the phone. Cannot change class of serviceResolution Possibilities: · Verify that you have logged in at a Level 3 security level. · Note that a security Level 3 supervisor can change a class of service for an individual mailbox by 1) selecting the View/Edit push button on the Mailbox Entry dialog box, 2) adjusting (if necessary) and applying a default class of service, or 3) designing and applying a custom class of service.
24. Testing and Troubleshooting the System Implementation and Service Manual System Troubleshooting Table24-34 Cannot access mailbox featuresResolution Possibilities: · Verify that the feature in question is enabled on the Class of Service dialog box. · Verify that the sentinel permits the feature. For information on verifying the features enabled on a sentinel, see the topic, Displaying Features Enabled on the Sentinel, later in this section. · Verify that the feature in question is permitted in the class of service assigned to the mailbox. · Verify that the feature is active in the Subscriber Settings dialog box. · Note that a guest mailbox can only send and receive messages. Cannot log into a mailboxResolution Possibilities: · Dial the messaging system’s extension or phone number and press after the system greeting. Enter the mailbox number and, when prompted, the mailbox’s password. · Do not log in using a speakerphone. · If the messaging system is on an integrated system using automatic station login, verify that the Inband Signaling code is correct. · Note that you must enter after the password if the extended security feature is active. Otherwise, the system pauses after you finish entering the password before accessing the mailbox. · Attempt to log in again. You may have entered an invalid password. · Verify that the password contains the minimum number of digits specified in the Minimum Length of Password field on the Subscriber tab in System Setup. · Note that a guest mailbox is deleted with its sponsor mailbox. · Note that the system manager can assign a new password either through the Edit Mailbox dialog box or over the phone if the subscriber cannot remember the password. · Run Quick Assist using the Update Partial option. For information on running the Quick Assist utility, see Chapter 23, “Maintaining the System.” Cannot record mailbox promptsResolution Possibilities: · Verify that the class of service assigned to the mailbox permits recording prompts. · Verify that the Maximum Time to Record Mailbox Prompts parameter is not set to zero on the Message Timing tab in System Setup.
24. Testing and Troubleshooting the System Implementation and Service Manual System Troubleshooting Table24-35 Mailbox is fullResolution Possibilities: · The value specified in the Max Messages field in the class of service assigned to the mailbox has been reached. Delete messages to allow for more recording time in the mailbox or increase the limits. · Assign a new class of service to the mailbox. · Run Quick Assist using the Update Partial option. For information on running the Quick Assist utility, see Chapter 23, “Maintaining the System.” Messages Cannot edit a sent messageResolution Possibilities: · Verify that the Locate Messages Sent checkbox is enabled on the Class of Service dialog box. · Note that a sent message cannot be edited if it does not reside in the recipient’s new message queue. · Note that a message that is in the new message queue cannot be edited if it has been reviewed or skipped. · Note that messages scheduled for dispatch over a network (OctelNet and AMIS) cannot be edited. Cannot save messagesResolution Possibilities: · Verify that the Save Messages checkbox is enabled on the Class of Service dialog box. · Note that listen-only messages cannot be saved. Messages include a clicking noise at the endResolution Possibilities: · By setting the environment variable DIALTONETRIM to the number of seconds the clicking is typically recorded, you can prevent the clicking from being included in messages. To set the DIALTONETRIM variable, type the following line at the end of the CONFIG.SYS file on the PC: SET DIALTONETRIM=# where # is the number of seconds of clicking that is typically heard. The DIALTONETRIM variable removes the last number of seconds (specified as #) from the message when the message is not terminated by a DTMF.
24. Testing and Troubleshooting the System Implementation and Service Manual System Troubleshooting Table24-36 Messages vanishing from mailboxesResolution Possibilities: · Verify that the correct date and time are set on the PC clock. Mailbox Entry dialog box: · Deactivate the Auto Forwarding feature if is active. · Note that the number of days to save messages can be set to 99, allowing saved messages to remain on the messaging system indefinitely. Class of Service dialog box: · Note that a message will be removed from the saved message queue when its age is equal to the days to save saved messages value in the Class of Service. The age is calculated from the time a message was first received in a mailbox. System Setup parameters: · W hen the number of days to save messages has expired, messages are automatically deleted. To warn subscribers of deleted messages, activate the Voice W arning W hen Messages Expire parameter on the Subscriber tab. Message confirmation does not work Resolution Possibilities: · Verify that the Message Confirmation checkbox is enabled on the Class of Service dialog box. · Note that OctelNet confirmations are dispatched during the next connection after the message is initially delivered. Therefore, if no messages have been sent to that node since the original message was sent, the confirmation has not had a chance to be delivered to the sender. · Note that confirmations are only generated for messages tagged for confirmation when they are sent. · Note that subscribers must check message confirmations through the message locator feature. · Note that messages dispatched to remote sites using AMIS cannot be sent with message confirmation activated. This includes messages to mailboxes active for Follow-Me-Forward. Message Indicators do not work Message Indicators do not work for InbandResolution Possibilities: · Disconnect a voice-mail port and attach a 2500 set or the proprietary telephone instrument if using a D/42D NS, D/42D SX, or D/42D SL integration. Go off hook and manually test the message indicator by entering the codes specified on the MI tab in System Setup.
24. Testing and Troubleshooting the System Implementation and Service Manual System Troubleshooting Table24-37 System Setup parameters: · Verify that the Port Parameters tab has at least one port enabled for outbound and that the same port is also enabled for Message Indicators. · Verify that the Permit Message Indicators parameter on the MI tab is enabled. · Verify that the MI prefix and suffix on and off codes are entered in the fields on the MI tab. If using the Dialogic SX or SL integration, see the appropriate Configuration Note for the correct codes to enter in these fields. · Some PBXs require the messaging system to wait for a confirmation tone to complete the message indicator event. For these systems, enter a comma (,) at the end of the MI Suffix OFF or ON code. · Verify that the value for DTONDET is greater than the value for DTONWAIT, unless DTONDET is set to 0. · Verify that the values for DTONW AIT and DTONDET are at least 400 units apart, unless DTONDET is set to 0. Class of Service dialog box: · Verify that the Message Indicator checkbox is enabled. Message Indicators do not work for SMDIResolution Possibilities: · Place a breakout box on the line and verify that message indicator information is being sent over the SMDI link. System Setup parameters: · Verify that COMMW L is enabled on the SMDI tab. · Verify that the Port Parameters tab has at least one port enabled for outbound and that the same port is also enabled for Message Indicators. · Verify that the Permit Message Indicators parameter on the MI tab is enabled. · Verify that the value for DTONDET is greater than the value for DTONWAIT, unless DTONDET is set to 0. · Verify that the values for DTONW AIT and DTONDET are at least 400 units apart, unless DTONDET is set to 0. Class of Service dialog box: · Verify that the Message Indicator checkbox is enabled. Message Indicators do not work for CentrexResolution Possibilities: · Verify that the codes in the SMDI.PFX file in the \CVR directory are correct.
24. Testing and Troubleshooting the System Implementation and Service Manual System Troubleshooting Table24-38 System Setup parameters: · Verify that the message indicator prefix is entered correctly on the MI tab. · Verify that the Permit Message Indicators parameter on the MI tab is enabled. · Verify that COMMMW L is enabled on the Simplified Message Desk Interface tab. · Verify that the Port Parameters tab has at least one port enabled for outbound and that the same port is also enabled for Message Indicators. · Verify that the value for DTONDET is greater than the value for DTONWAIT, unless DTONDET is set to 0. · Verify that the values for DTONW AIT and DTONDET are at least 400 units apart, unless DTONDET is set to 0. Class of Service dialog box: · Verify that the Message Indicator checkbox is enabled. Message Indicators do not work for DIDResolution Possibilities: · Unplug the port from the voice board and attach an analog phone to the port. Verify that the message indicator can be lit. System Setup parameters: · Verify that the Port Parameters tab has at least one port enabled for outbound. · Verify that the MI tab allows Message Indicators and the correct codes are entered in the fields. Class of Service dialog box: · Verify that the Message Indicator checkbox is enabled. Message Notification does not work for a phone Resolution Possibilities: · Attach a digit grabber to monitor a line. Verify that the messaging system can access the line and connect to the phone number. · If Debug displays the error, “W ARNING 18 No Dial tone Detected,” all outbound ports were busy when notification was attempted. You may want to enable more outbound ports on the messaging system. System Setup parameters: · Verify that at least one port is enabled for Outbound and Message Notification in the Port Parameters tab. · Verify that the values entered for DTONWAIT on the Message Delivery tab and DTONDET on the Hangup tab are set at least 400 units apart, unless DTONDET is set to 0. · Verify that the value for DTONDET is greater than the value for
24. Testing and Troubleshooting the System Implementation and Service Manual System Troubleshooting Table24-39 DTONWAIT, unless DTONDET is set to 0. · The value for DTONDET may be set too low. If it is, the messaging system may hang up prematurely. Adjust this parameter only if instructed to by a technical support representative. · The value for SCHDW AIT on the Outbound Calls tab may be set too low. If it is, the messaging system may not detect a dial tone on an outbound line and must reschedule the event. Adjust this parameter only if instructed to by a technical support representative. Subscriber Settings dialog box: · Verify that the Message Notification feature is enabled. Message Notification dialog box: · Verify that the time blocks are configured · Verify that PHONE is entered in the Call Back field. Class of Service dialog box: · Verify that the Message Notification checkbox is enabled. · Verify that the Local or Long Distance option under Delivery Options is selected. Message Notification does not work for a beeper Resolution Possibilities: · Attach a digit grabber to monitor a line. Verify that the messaging system can access the line and connect to the phone number. · If Debug displays the error “W ARNING 18 No Dial tone Detected,” all outbound ports were busy when notification was attempted. You may want to enable more outbound ports on the messaging system. · Some pager companies use three beep tones to indicate a connect. If the messaging system does not recognize this connect signal, configure notification with no call progress: 1. Call the paging company and determine the number of seconds after the digits are dialed and the call is connected. W rite this number down for use in step 3. 2. Remove all data from the call back field on the Mailbox Entry/Message Notification dialog box. 3. In the Phone # field, enter an N followed by a 1, if required, followed by the area code and pager company’s phone number. Insert a comma for every two seconds of time it took to connect that you found in step 1, then enter the call back number. For a company that took ten seconds to connect, a phone number would look like: N+1+Area Code+Pager Company’s #+,,,,,+Callback # 4. Verify the entire callback number displays on the pager. If not, adjust the number of commas in the Phone # field.
24. Testing and Troubleshooting the System Implementation and Service Manual System Troubleshooting Table24-40 System Setup Parameters: · Verify that at least one port is enabled for Outbound and Message Notification in the Port Parameters tab. · Verify that the values entered for DTONWAIT on the Message Delivery tab and DTONDET on the Hangup tab are set at least 400 units apart, unless DTONDET is 0. · Verify that the value for DTONDET is greater than the value for DTONWAIT, unless DTONDET is 0. · The value for DTONDET on the Hangup Detection tab may be set too low. If it is, the messaging system may hang up prematurely. Adjust this parameter only if instructed to by a technical support representative. · The value for SCHDW AIT on the Outbound Calls tab may be set too low. If it is, the messaging system may not detect dial tone on an outbound line and must reschedule the event. Subscriber Settings dialog box: · Verify that the Message Notification feature is enabled. Message Notification dialog box: · Verify that the time blocks are configured. · Verify that the proper phone number for the subscriber to return the call in the Call Back field. · Verify that the Phone # field contains the pager company’s phone number. If it is a long-distance call, verify that a 1 precedes the area code. Class of Service dialog box: · Verify that the Message Notification checkbox is enabled. · Verify that the Long Distance option under Delivery Options is selected. NameNet information is not voiced Resolution Possibilities: · The system may not yet have retrieved the NameNet information from the remote site. · Verify that the node exists on the messaging system. System Setup parameters: · Increase the value for the Maximum Number of Idle Days for Nam eNet Records param eter. Records that have exceeded this value are automatically purged. · Increase the value for the Maximum Number of NameNet Entries parameter on the NameNet tab. NameNet does not retrieve information for new entries if the NameNet list is full.
24. Testing and Troubleshooting the System Implementation and Service Manual System Troubleshooting Table24-41 OctelNet/AMIS messages are returned to mailboxes Resolution Possibilities: · Verify that OctelNet is enabled on the sentinel. For information on verifying the features enabled on a sentinel, see the topic, Displaying Features Enabled on the Sentinel, later in this chapter. · Verify that the access number on the Network Maintenance dialog box is correct. · If using Dial Plan, verify that the Dial Plan database is set up correctly. · Dedicate a line for testing the networking feature and attach a digit grabber. Verify that the messaging system can access the line and connect to the remote site. · If the switch requires a suffix code to access an outside line, add the suffix code to the SET_UP.CFG A-69 bucket. · Note that OctelNet does not work if the greeting by port feature is used. Class of Service dialog box: · Verify that the Networking Options are set to access the appropriate nodes. · Verify that Dispatch Options are not set to Not Allowed. System Setup parameters: · Verify that the Outbound parameter on the Networking tab is enabled. Operator or subscriber gets blank messages Resolution Possibilities: · Verify that the method the switch uses for a disconnect and verify that the appropriate parameters are configured properly. For more information, see the topic, Determining a Switch’s Disconnect Signal, later in this section. · If the blank messages are recorded noise, check the phone system for the following problems: - Noisy phone lines. - RF interference. - Ground problems. - Cross talk/wiring problems. - Tip and ring reversed.
24. Testing and Troubleshooting the System Implementation and Service Manual System Troubleshooting Table24-42 System Setup parameters: · Verify that the Minimum Message Length parameter on the Message Timing tab is set to the recommended setting, 2 seconds. Note that any message shorter in length than two seconds is automatically deleted. · If setting the Minimum Message Length parameter on the Message Timing tab to 2 seconds does not correct the problem, set the parameter to 4 seconds and set the Maximum Silence parameter on the Hangup Detection tab to 350. PC is locked up Resolution Possibilities: · Press and hold them down for a few seconds. OS/2 may indicate that an executable file is not responding and prompt you to end it. End the file. If this does not work the first time, hold down again for a longer period of time. · Press . The PC will restart, and you can restart the messaging system. · If the previous two procedures do not work, the last resort is to turn off power to the PC. If you must turn off the PC, use the following procedure: 1. Turn off the power to the PC. W ait 30 seconds, then turn power back on. 2. After the messaging system has restarted, view the PLUS.LOG file for an error that might have caused the lockup. Report this error to a technical support representative. For more information on viewing the log file, see the topic, Viewing the PLUS.LOG File, later in this chapter. 3. Log in as a Level 2 or Level 3 supervisor and select Exit from the File menu. 4. Run the Quick Assist utility using the Verify option. 5. If Quick Assist does not report any errors, restart the messaging system. If Quick Assist detects errors, it instructs you on which recovery options to run. Contact a technical support representative if Quick Assist recommends you use the Update All or Rebuild All options.