Home > Lucent Technologies > Communications System > Lucent Technologies Octel 100 Implementation And Service Manual

Lucent Technologies Octel 100 Implementation And Service Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Lucent Technologies Octel 100 Implementation And Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 413 Lucent Technologies manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    Page
    of 690
    							13. Setting Up the System
    Implementation and Service Manual  System Setup Parameters List13-83
     
     If Set Too Low Hang-up strings may be ignored if the switch cannot send the digits fast
    enough to meet this value. This may cause excessive off hook times between
    calls.
     
     Min
     0
     Max
     30000
     Default
     0
     Requires Restart
     Yes
     Switch-Dependent
     Yes
     Set by Integrator
     Yes
     
      Hangup Detection Parameters
     
    Minimum
    Duration for
    Drop in Loop
    Current
    (LCDTIME)  This parameter specifies the amount of time, in 10 millisecond units,
    necessary to recognize a drop in loop current, when detecting a disconnect.
     When/How to Use This parameter is set when the Integrator utility is run.
     Adjust this parameter only when instructed to do so by a  technical support
    representative.
     A setting of 0 disables this parameter.
     
     Related Parameters/Features None.
     
     If Set Too High If the switch sends a loop current drop for a shorter time than the time set for
    LCDTIME, the system does not identify the disconnect. This may cause
    excessive off hook times between calls.
     
     If Set Too Low If this parameter is set too low, noise spikes on the line could cause
    disconnect. Set this parameter to 0 to disable it.
     A low setting can also cause call ghosting on the ports.
     
     Min
     0
     Max
     30000
     Default
     30
     Requires Restart
     Yes
     Switch-Dependent
     Yes
     Set by Integrator
     Yes
     
      Hangup Detection Parameters
     
    Maximum
    Silence Before
    Hanging Up
    (MAXSIL)  This parameter specifies the amount of time, in 10 millisecond units, during
    message recording that the system records silence before it determines the
    caller has hung up and drops the line. MAXSIL prevents the system from
    recording silence when a caller has hung up during a record session.
     
     When/How to Use This parameter is used for switches that do not use positive disconnects or
    dial tones to indicate disconnects.
     For most systems, the default value should be sufficient.
     
     Related Parameters/Features Set this parameter to a value less than 1000 if using AMIS messaging.
     Set this parameter to a value greater than 0 if using HANGUPSTR. 
    						
    							13. Setting Up the System
    Implementation and Service Manual  System Setup Parameters List13-84
     
     If Set Too High If this parameter is set too high, the system records silence. Also, switches
    could detect a port as available and mistakenly pass incoming calls to a port
    on which the system is recording silence (missed disconnect). In this case, a
    new caller would append to the previous recording.
     
     If Set Too Low If this parameter is set too low, callers could be cut off during recording due
    to natural pauses when they speak.
     
     Min
     0
     Max
     30000
     Default
     2000
     Requires Restart
     No
     Switch-Dependent
     Yes
     Set by Integrator
     No
     Port Parameters (Page 23 of 26)
      The Port parameters control the answering mode and ring count and define the types of ev ents allowed
    for each messaging system port.
      The ports displayed on the Port Parameters tab are determined by the number of ports allowed by the
    messaging system sentinel. For example, on a four-port system, you can only v iew ports 1 through 4. If
    the messaging system supports more than eight ports, you can access the remaining ports by clicking on
    the buttons on the bottom of the screen.  For example, to view the settings for ports 17 through 24, click
    on the Ports 17 - 24 button.
      If you run System Setup from the Installation Setup utility during messaging system installation, the
    system maximum number of ports is accessible on the Port Parameters tab. After installation is complete
    and you restart the messaging system, the number of ports displayed reflects the maximum allowed by
    the sentinel.
      You must set each Port parameter for each messaging system port.
     
      Port Parameters
     
    Init Mode  Init Mode reflects the method of answering for each port. The messaging
    system supports the following modes:
    C  Serial integration.
    D  Inband signaling, off hook waiting for inband signaling digits.
    N  Normal, on hook waiting for rings.
    P  Pulse inband signaling, off hook waiting for inband signaling
    digits.
    T  Tone inband signaling, off hook waiting for inband signaling digits.
    W  W ink start.
     
     When/How to Use Enter the letter in the field that represents the answering mode required by the
    switch.
     If the switch uses the COM port to indicate calls and hang-ups or to execute
    message indicators, set Init Mode to C 
    for each messaging system port
    using serial integration.
     
     Related Parameters/Features None.
     
     If Set Too High Not applicable.
     
     If Set Too Low Not applicable. 
    						
    							13. Setting Up the System
    Implementation and Service Manual  System Setup Parameters List13-85
     
     Min
     —
     Max
     —
     Default
     No
     Requires Restart
     Yes
     Switch-Dependent
     Yes
     Set by Integrator
     No
     
      Port Parameters
     
    Ring Count  This parameter specifies the number of rings each port must hear before it
    answers an incoming call. For example, if Ring Count is set to 2, a port must
    ring twice before it comes off hook to answer an incoming call.
     
     When/How to Use Enter the Ring Count in the corresponding field for each port. The default
    should be acceptable for most phone systems.
     On some phone systems, especially those without true hunt groups, Ring
    Count should be set to consecutive numbers to prevent multiple lines from
    being answered at the same time.
     
     Related Parameters/Features This parameter should not be confused with the Maximum Rings Before No
    Answer (RINGS) parameter on the Outbound Dialing tab in System Setup or
    the Max Rings parameter on the Class of Service dialog box.
     
     If Set Too High The higher you set this parameter, the longer the delay before the port
    answers the call.
     
     If Set Too Low The minimum of 1 should be sufficient for most systems.
     
     Min
     1
     Max
     9
     Default
     1
     Requires Restart
     Yes
     Switch-Dependent
     Yes
     Set by Integrator
     No
     
      Port Parameters
     
    Inbound  This parameter determines whether each port is allowed to accept incoming
    calls.
     
     When/How to Use Enable Inbound for each port that should be allowed to accept incoming calls.
    If you want to dedicate the port to outbound calls, disable Inbound.
     
     Related Parameters/Features If both Inbound and Outbound are enabled for a port, use SCHDW AIT to
    prevent the loss of outbound events due to call collision. Call collision occurs
    when an inbound call reaches a port at the same time as the port comes off
    hook to perform an outbound event.
     
     If Set Too High Not applicable.
     
     If Set Too Low Not applicable.
     
     Min
     —
     Max
     —
     Default
     Yes
     Requires Restart
     No
     Switch-Dependent
     No
     Set by Integrator
     No
      
    						
    							13. Setting Up the System
    Implementation and Service Manual  System Setup Parameters List13-86
      Port Parameters
     
    Outbound  This parameter determines whether each port is allowed to perform outbound
    events: message indicators, message notification, AMIS, fax, V-Edit, Visual
    Mailbox, future delivery, auto forward, and wake-up calls.
     
     When/How to Use Enable Outbound for each port that should be allowed to perform outbound
    events. If you want to dedicate the port to receive outbound calls, disable
    Inbound.
     If you dedicate a port to outbound events, remove it from the hunt group to
    prevent call collisions and subsequent loss of outbound events.
     W hen you dedicate a port to outbound events, the events are scheduled one
    after another. The system does not pause between events to determine if
    there is an incoming call to the port. This can greatly facilitate the
    performance of outbound events, especially message indicator events.
     W hen you enable Outbound for a port, you may enable and disable individual
    outbound events for that port by using the Outbound Usage Permitted
    parameters.
     If you disable all ports for Outbound, the system displays a warning when you
    save System Setup (“No ports have been designated for outbound calling.
    Outbound events, including Future Delivery and Auto Forward, cannot be
    supported.”)
     You may disable a port’s Outbound setting at any time. W hen you disable a
    port for Outbound, the system schedules no new events for that port. Events
    already scheduled at the time you disable Outbound, however, are still
    performed from that port.
     
     Related Parameters/Features The Outbound Usage Permitted parameters determine which outbound
    events are allowed for each port. W hen multiple ports are enabled for the
    same outbound events, the events go out on the highest numbered port
    enabled for that event at the time it is scheduled.
     Auto forwarding and wake-up calls are general outbound events that go out
    on the highest numbered port available for Outbound.
     If both Inbound and Outbound are enabled for a port, use SCHDW AIT to
    prevent the loss of outbound events due to call collision. Call collision occurs
    when an inbound call reaches a port at the same time as the port comes off
    hook to perform an outbound event.
     
     If Set Too High Not applicable.
     
     If Set Too Low Not applicable.
     
     Min
     —
     Max
     —
     Default
     Yes
     Requires Restart
     Yes
     Switch-Dependent
     No
     Set by Integrator
     No
      
    						
    							13. Setting Up the System
    Implementation and Service Manual  System Setup Parameters List13-87
      Port Parameters
     
    Outbound Usage
    Permitted/Msg
    Delivery  This parameter determines whether each port is allowed to perform message
    delivery events—message notification and future delivery. To use message
    notification and future delivery, you must enable at least one port for Msg
    Delivery.
     Msg Delivery is dimmed if Outbound is disabled.
     
     When/How to Use Enable Msg Delivery for each port that should be allowed to perform message
    notification or future delivery. If you want to dedicate the port to message
    notification and future delivery events, disable Inbound as well as all
    Outbound Usage Permitted options except Msg Delivery.
     If you experience delayed message notification and future delivery events,
    increase the number of ports enabled for Msg Delivery.
     You may disable a port for Msg Delivery at any time. W hen you disable a port
    previously enabled for Msg Delivery, the system schedules no new message
    notification or future delivery events for that port. Events already scheduled at
    the time you disable Msg Delivery, however, are still performed from that port.
     If you disable the port entered in the Line 1 field on the Subscriber Settings
    dialog box for Msg Delivery, message notification events do not occur, and
    the system writes an error to the PLUS.LOG file.
     
     Related Parameters/Features You must enable message notification in the subscribers’ Class of Service
    and configure it on the Subscriber Settings dialog box for message
    notification and future delivery to be available. In addition, if you set Delivery
    Options on the Class of Service dialog box to Not Allowed, you cannot use
    message notification.
     The parameters on the Message Delivery tab in System Setup must also be
    properly configured for the system for message notification to function.
     
     If Set Too High Not applicable.
     
     If Set Too Low Not applicable.
     
     Min
     —
     Max
     —
     Default
     Yes
     Requires Restart
     Yes
     Switch-Dependent
     No
     Set by Integrator
     No
     
      Port Parameters
     
    Outbound Usage
    Permitted/Msg
    Indicator  This parameter determines whether each port is allowed to perform message
    indicator events. To use message indicators, you must enable at least one
    port for Msg Indicator.
     Msg Indicator is dimmed if Outbound is disabled. 
    						
    							13. Setting Up the System
    Implementation and Service Manual  System Setup Parameters List13-88
     
     When/How to Use Enable Msg Indicator for each port that should be allowed to perform
    message indicator events. If you want to dedicate the port to message
    indicator events, disable Inbound as well as all Outbound Usage Permitted
    options except Msg Indicator.
     If you experience delayed indicator events, increase the number of ports
    enabled for Msg Indicator.
     If you disable a port for Msg Indicator that was used to turn a message
    indicator on, the system still allows the message indicator off event to go
    through that port. The system allows this because some switches require
    message indicators to be turned off through the same port that turned it on.
     
     Related Parameters/Features You must enable Msg Indicator in the subscribers’ Class of Service for Msg
    Indicators to be available.
     The parameters on the Msg Indicator tab in System Setup must be properly
    configured for message indicators to function.
     
     If Set Too High Not applicable.
     
     If Set Too Low Not applicable.
     
     Min
     —
     Max
     —
     Default
     Yes
     Requires Restart
     Yes
     Switch-Dependent
     No
     Set by Integrator
     No
     
      Port Parameters
     
    Outbound Usage
    Permitted/
    OctelNet/AMIS  This parameter determines whether each port is allowed to perform outbound
    OctelNet and AMIS events, including network messages, follow-me-forward
    messages, and delivery of group distribution list messages to remote sites.
    To perform outbound network events, you must enable at least one port for
    OctelNet/AMIS.
     OctelNet/AMIS is dimmed if Outbound is disabled.
     
     When/How to Use Enable OctelNet/AMIS for each port that should be allowed to send network
    messages. If you want to dedicate the port to outbound network events,
    disable Inbound as well as all Outbound Usage Permitted options except
    OctelNet/AMIS.
     If you experience delayed outbound network events, increase the number of
    ports enabled for OctelNet/AMIS.
     If you disable a port previously enabled for OctelNet/AMIS, the system
    schedules no new events. Any events already scheduled for the port at the
    time you disabled it, however, are executed from that port.
     If no ports are enabled for OctelNet/AMIS, subscribers can still address
    messages to network destinations. The system will, however, be unable to
    locate a port from which to schedule them, and the messages will be placed
    in the sending subscribers’ local mailboxes. 
    						
    							13. Setting Up the System
    Implementation and Service Manual  System Setup Parameters List13-89
     
     Related Parameters/Features If the sentinel does not support OctelNet and AMIS, the OctelNet/AMIS
    checkbox is disabled for all ports.
     You must enable an outbound network option (Casual AMIS, Administered
    AMIS, OctelNet) in the subscribers’ Class of Service for outbound network
    messaging to be available.
     You must enable Permit Outbound and enter the system location information
    on the Networking tab in System Setup for outbound network messaging to
    function properly.
     
     If Set Too High Not applicable.
     
     If Set Too Low Not applicable.
     
     Min
     —
     Max
     —
     Default
     Yes
     Requires Restart
     Yes
     Switch-Dependent
     No
     Set by Integrator
     No
     
      Port Parameters
     
    Outbound Usage
    Permitted/Fax  This parameter determines whether each port is allowed to perform outbound
    fax events, including delivery of fax retrieval documents, and sending or auto
    printing to local fax machines or primary fax destinations. To perform
    outbound fax events you must enable at least one port for Fax.
     Fax is dimmed if Outbound is disabled.
     
     When/How to Use Enable Fax for each port that should be allowed to support fax retrieval or
    auto printing and subscriber retrieval of fax mail documents to local fax
    machines or primary fax destinations. If you want to dedicate the port to
    outbound fax events, disable Inbound as well as all Outbound Usage
    Permitted options except Fax.
     If you experience delayed fax events, increase the number of ports enabled
    for Fax.
     If you disable a port previously enabled for Fax, the system schedules no new
    events. Any events already scheduled for the port at the time you disabled it,
    however, are executed from that port.
     If no ports are enabled for Fax, subscribers cannot retrieve fax messages and
    the fax retrieval feature cannot deliver fax documents.
     
     Related Parameters/Features Fax Options must be configured on the Class of Service dialog box. You must
    also configure the Fax parameters in System Setup.
     
     If Set Too High Not applicable.
     
     If Set Too Low Not applicable.
     
     Min
     —
     Max
     —
     Default
     Yes
     Requires Restart
     Yes
     Switch-Dependent
     No
     Set by Integrator
     No
      
    						
    							13. Setting Up the System
    Implementation and Service Manual  System Setup Parameters List13-90
      Port Parameters
     
    Outbound Usage
    Permitted/
    Application  This parameter determines whether each port is allowed to support external
    applications (Visual Mailbox, V-Edit). To support one or both of these external
    applications, you must enable at least one port for Applications.
     Applications is dimmed if Outbound is disabled.
     
     When/How to Use Enable Applications for each port that should be allowed to support V-Edit or
    Visual Mailbox. If you want to dedicate the port to outbound V-Edit or visual
    mailbox events, disable Inbound as well as all Outbound Usage Permitted
    options, except Applications.
     If subscribers have trouble connecting to Visual Mailbox or system managers
    have trouble connecting to V-Edit due to a lack of available ports, increase
    the number of ports enabled for Applications.
     If no ports are enabled for Applications, subscribers cannot connect to Visual
    Mailbox and system managers will not be able to connect to V-Edit.
     
     Related Parameters/Features W hile V-Edit is available on all messaging systems, Visual Mailbox is a
    sentinel-controlled feature.
     
     If Set Too High Not applicable.
     
     If Set Too Low Not applicable.
     
     Min
     —
     Max
     —
     Default
     Yes
     Requires Restart
     Yes
     Switch-Dependent
     No
     Set by Integrator
     No
     Voice System Parameters (Page 24 of 26)
      The Voice System parameters prov ide information for the messaging system for interaction with the
    switch. 
      Voice System Parameters
     
    Go OFF Hook
    when Port
    Disabled
    (OFFHDIS)  This parameter determines whether the messaging system takes a port off
    hook when the port is disabled, so callers to that port hear a busy signal. A
    number of occurrences can temporarily disable a port, such as a power loss
    or a shutdown after daily maintenance.
     
     When/How to Use It is generally recommended that you enable this parameter so callers hear a
    busy signal instead of ringing when they call a disabled port.
     Some switches, such as those using digital integration, lock the disabled
    ports when they have been off hook for a long time. If your switch uses digital
    integration, you should disable OFFHDIS. Refer to the configuration note for
    your switch for information on setting this parameter.
     
     Related Parameters/Features None.
     
     If Set Too High Not applicable.
     
     If Set Too Low Not applicable. 
    						
    							13. Setting Up the System
    Implementation and Service Manual  System Setup Parameters List13-91
     
     Min
     
    —
     Max
     
    —
     Default
     
    Yes
     Requires Restart
     Yes
     Switch-Dependent
     Yes
     Set by Integrator
     No
     
      Voice System Parameters
     
    Maximum Call
    Duration
    (PROGTIME)  This parameter specifies the maximum amount of time, in minutes, the
    messaging system allows a call to occupy a port before it disconnects the call
    without warning.
     
     When/How to Use Use caution when setting this parameter. If callers are disconnected while
    performing mailbox functions, such as listening to messages or creating
    mailboxes, data corruption could occur. Set this parameter to 0 disable it.
     If you set PROGTIME to a value greater than 0, consider the following:
    ·  Set PROGTIME to a value high enough so calls delivering faxes and
    callers on hold are not disconnected.
    ·  PROGTIME overrides Message Time on the Class of Service dialog
    box. Set PROGTIME higher to prevent callers from being
    disconnected while recording messages. If this happens, data
    corruption could occur.
    Related Parameters/FeaturesIf PROGTIME is shorter than the Message Time setting on the Class of
    Service dialog box, callers may be disconnected before they finish recording
    long messages.
    If Set Too HighThe higher you set this parameter, the longer callers are allowed to remain in
    the system before being disconnected.
    If Set Too LowIf this parameter is set to low, callers recording messages, sending faxes, or
    waiting in call queues are disconnected without warning and data corruption
    could occur. Set this parameter to 0 to disable it.
    Min
    0Max
    999Default
    0Requires Restart
    NoSwitch-Dependent
    YesSet by Integrator
    No
    Voice System Parameters
    DTMF Length to
    Interrupt a
    Prompt
    (PLAYDTMF)This parameter specifies the length of a DTMF the voice board must receive
    to interrupt a prompt voiced by the system.
    This parameter is set in 10 millisecond units, and the range is from 0 to
    30000. The default is 5 (50 milliseconds).
    When/How to UseFor most systems, the default value is sufficient. If the system misinterprets
    voice data as DTMF tones during prompts, try increasing this setting.
    W hen setting this parameter, keep in mind that when systems send OctelNet
    messages, they send DTMFs to signal an incoming OctelNet message. If you
    set this parameter too high or too low, the main greeting will not be
    interrupted, and the system may miss incoming OctelNet messages. 
    						
    							13. Setting Up the System
    Implementation and Service Manual  System Setup Parameters List13-92
    Related Parameters/FeaturesW hen RECDTMF is set to a higher value than PLAYDTMF, the RECDTMF
    value is used for both.
    If Set Too HighIf this parameter is set too high, the system may not recognize DTMF tones
    and will not interrupt the prompt. If the DTMF is not recognized, OctelNet
    messages may be missed.
    If Set Too LowIf this parameter is set too low, the system may interpret voice data as DTMF.
    If the DTMF is not recognized, OctelNet messages may be missed.
    Min
    0Max
    30000Default
    5Requires Restart
    YesSwitch-Dependent
    YesSet by Integrator
    No
    Voice System Parameters
    DTMF Duration
    to Interrupt
    Record
    (RECDTMF)This parameter specifies the length of a DTMF a voice board must receive to
    interrupt recording on the system.
    This parameter is set in 10 millisecond units, and the range is from 0 to
    30000. The default is 5.
    When/How to UseIf the system misinterprets voice data as DTMF tones during recording, try
    increasing this setting.
    Related Parameters/FeaturesW hen RECDTMF is set to a higher value than PLAYDTMF, the RECDTMF
    value is used for both.
    If Set Too HighThe system does not interrupt the recording session when the callers enter
    DTMFs.
    If Set Too LowThe system may misinterpret voice data as DTMF and interrupt the recording.
    Min
    0Max
    30000Default
    5Requires Restart
    YesSwitch-Dependent
    YesSet by Integrator
    No
    Voice System Parameters
    Default Input
    Timeout
    (TIMEOUT)This parameter specifies the number of seconds the messaging system waits
    for the caller to respond with a keypress after hearing a prompt before the
    system voices, 
    “Are you still there,” and repeats the prompt.
    When/How to UseFor most systems, the default allows sufficient time for most callers to
    respond to prompts.
    Related Parameters/FeaturesThe Maxim um  Num ber of No Entries param eter specifies the m axim um
    number of times the system voices prompts without receiving input before it
    disconnects the caller.
    If Set Too HighIf this parameter is set too high, there may be long pauses when the system
    voices prompts and waits for input. Consequently, calls occupy ports for a
    long time. 
    						
    All Lucent Technologies manuals Comments (0)

    Related Manuals for Lucent Technologies Octel 100 Implementation And Service Manual