Home
>
Lucent Technologies
>
Communications System
>
Lucent Technologies Octel 100 Implementation And Service Manual
Lucent Technologies Octel 100 Implementation And Service Manual
Have a look at the manual Lucent Technologies Octel 100 Implementation And Service Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 413 Lucent Technologies manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
10. Establishing a Serial Integration Implementation and Service Manual Supporting Multiple-Prefix Centrex Systems10-11 11. To exit the editor, click the icon in the upper-left corner of the window and select Close. 12. To close the OS/2 window, type EXIT and press . 13. To load the file, shut down OS/2 and restart the PC. Example SMDI.PFX File The following sample file illustrates how you can set up the SMDI.PFX for a system using a 10-digit Centrex application. In the sample, the system has three prefixes (709513, 709514, 709515). Prefix 709513 is associated with mailboxes 7000 through 7500; prefix 709514 is associated with mailbox 7501; and prefix 709515 is associated with mailboxes 7600 through 7650. The following SMDI.PFX file is used: 7000 7500 709513 7501 709514 7600 7650 709515 The second entry abov e can also be specified as: 7501 7501 709514 You can edit the SMDI.PFX file at any time. The system must, however, be restarted for the changes you make to be recognized.
10. Establishing a Serial Integration Implementation and Service Manual Supporting Multiple-Prefix Centrex Systems10-12 Notes:
Implementation and Service Manual Integrating with an Uninterruptible Power Supply11-1 CHAPTER 11 Integrating with an Uninterruptible Power Supply During a power failure, the messaging system files and the PC can be sev erely damaged. Attaching an Uninterruptible Power Supply (UPS) prov ides protection against failures of a relativ ely short duration. Note, howev er, if there is a major power failure that exceeds the life of the UPS’s battery, the PC can lose power and the messaging system and PC can be damaged. The UPS utility enables the messaging system to integrate with the UPS’s status and recognize a potential interruption in operation before it occurs. The UPS utility can shut down the messaging system to maintain system integrity, and then restart the messaging system when power returns. Procedures in this chapter will help you to: · Understand how the UPS utility works · Meet the requirements for running the UPS utility · Run the UPS utility · Run the UPS utility after system installation · Check the UPS’s current operating state
11. Integrating with an Uninterruptible Power Supply Implementation and Service Manual Understanding How UPS Integration W orks11-2 Understanding How UPS Integration Works Most UPSs hav e three states of operation: · Normal Operation – The UPS is receiving power from the local utilities company through the electrical outlet. · Power Out – The UPS is not receiving power from the local utilities company, and the UPS is supplying power to the PC. · Low Battery – The UPS is still supplying power to the PC, but the battery is low and the UPS may cease to supply power to the PC at any moment. W hen you run the UPS utility, the system learns how to recognize these three states of operation. After the UPS is integrated, if a power failure occurs, the UPS monitor recognizes that the UPS is supplying power to the system, and normal operation continues. If the power failure is lengthy and the UPS reaches a low-battery state, the messaging system immediately performs a shutdown. All idle and occupied ports are disabled immediately. This procedure prev ents a shutdown with open files, which can cause data corruption. Because the UPS monitor still runs after the messaging system is shut down, UPS.EXE also monitors for the restoration of power. After power returns to the PC and the UPS recognizes a normal operating state, UPS.EXE signals the RUNVM.CMD file to restart the messaging system. This minimizes system downtime. Meeting the Requirements for Running the UPS Integration Utility The following requirements must be met to run UPS integration: · The UPS you use must hav e a serial port connection. The UPS shipped with new messaging systems has the required serial port connection. · A serial port on the PC must be dedicated to the UPS. · For the UPS utility to monitor the UPS, it must run in the background, independent of the messaging system. During messaging system software installation, the prompt, “Do you want the UPS monitor to load automatically upon boot up?” displays. If you are going to run UPS integration during installation, answer Yes to load the UPS.EXE file upon bootup. W hen auto-loaded, UPS.EXE is executed and stays resident until the PC is restarted. · Some messaging systems use a serial integration to the phone system (for example, Voice Bridge, DMID). You cannot run the Serial Integration utility, howev er, while the UPS monitor is activ e, because there is a common executable file (COMM.DLL) shared by the utilities. If you run the UPS Integration utility and the messaging system is instructed to run UPS automatically upon bootup, the UPS constantly runs in the background. Consequently, if you attempt to run the Serial Integration utility after UPS integration, the necessary file is not accessible to run the Serial Integration utility.
11. Integrating with an Uninterruptible Power Supply Implementation and Service Manual Running the UPS Integrator Utility11-3 There are two ways to av oid this file-sharing problem: - Run the Serial Integration utility before running the UPS Integration utility. - If you need to run the Serial Integration utility after the UPS integration has been run, close the UPS Monitor before running the Serial Integration utility. To do this, click the UPS icon once and select Close. After Serial Integration installation is complete, perform a shutdown and restart the PC. The UPS automatically starts upon bootup. Running the UPS Integrator Utility Use the following procedure to integrate the UPS with the messaging system. By default, the UPS Integrator only learns the normal and power-out states and interprets any mask (an 8-digit binary image that represents the state of operation) that is not recognized as either a normal or power-out state as a low-battery state and handles it accordingly. You can change the default so that the system attempts to learn the UPS’s low-battery state. This ensures that the system performs an automatic shutdown only when a true low-battery state is reached. Howev er, you should only change the default if you know that the UPS has a consistent low-battery mask. Consult the manual that came with the UPS for more information. Also, the UPS may require a signal to indicate that the system is monitoring UPS operation. This signal can come from the DTR (data terminal ready) or RTS (request to send) pin on the PC’s serial port. You can configure the UPS Integrator utility to set the proper pin to signal the UPS. By default, the Request to Send pin is set to signal the UPS. If the UPS requires the DTR pin to signal the UPS, or if you do not want any signal sent, you can change the default. Before doing so, howev er, consult the UPS documentation to determine if you should enable one or both of these options.
11. Integrating with an Uninterruptible Power Supply Implementation and Service Manual Running the UPS Integrator Utility11-4 To run the UPS Integrator utility immediately following messaging system installation: 1. During messaging system installation, select UPS from the Installation Setup utility dialog box. The UPS Integrator dialog box displays. 2. From the Options menu, select Setup. The UPS Setup dialog box displays. If the Power out and Low batter fields match the entries on the following screen, the UPS utility has been preconfigured for you. Select Cancel to exit the UPS utility. 3. If you do not want the system to attempt to learn the UPS’s low-battery state and you do not want to change the pin-signaling default, proceed with step 4. If you do want the system to attempt to learn the UPS’s low-battery state or you do want to change the pin-signaling default, complete the following: a. Click Adv anced. The Adv anced Settings dialog box displays. b. If you want the UPS Integrator to attempt to learn the UPS’s low-battery mask, disable the Low Battery Default option (remov e the check from the checkbox). This enables the UPS Integrator to attempt to learn the UPS’s low-battery state. c. If you want to change the pin-signaling setting, change the Data Terminal Ready and Request to Send options as appropriate for the UPS. d. To sav e the settings, click OK. The UPS Setup dialog box displays. 4. In the Port field, select 1, unless you modified the system configuration to use another serial port. 5. If you know the Normal Operation, Power Out, and Low Battery masks of the UPS connected to the PC, you can manually enter them in their respectiv e fields under Masks on the UPS Setup dialog box, then proceed to step 9. See the UPS manual to determine if the masks are prov ided. (For APC UPSs, the Normal mask is 00000000, the Power out mask is 00010000, and the Low batter mask is 10010000.)
11. Integrating with an Uninterruptible Power Supply Implementation and Service Manual Running the UPS Integrator Utility11-5 If you do not know the masks for the UPS, click Learn to start the Learn mode, which enables the UPS monitor to establish the UPS signals. The system displays the message, “Begin Learn Mode.” You can select Cancel at any time to abort the Learn process. 6. The system displays a message prompting you to v erify that the cable from the UPS to the serial port is securely attached. Click OK. The system displays the message “Learn normal state” as it learns the mask for the UPS’s normal operating state. After the system learns the normal operating state, it displays the message “Disconnect power from the UPS.” This allows the system to emulate a power out condition. 7. Remov e the UPS power cord from the electrical outlet, then click OK. The system then learns the power out state. If you did not change the default low-battery setting in step 3, proceed to step 8. If the Low Battery Default option is disabled on the Adv anced Settings dialog box, after the system learns the mask for the power out state, it continues running off the UPS until the UPS reaches a low-battery state. There is a delay between learning the power out state and learning the low-battery state mask as the system waits for the power on the UPS to diminish. 8. After the system learns the necessary states, the message “Reconnect power to UPS” displays. Reconnect the UPS power cord to the electrical outlet, then click OK. A dialog box displays the message “End Learn Mode.” After Learn mode is complete or you manually enter the UPS’s masks, the system constantly monitors the current mask and compares it to the recognized masks for each state to determine the current state of UPS operation. 9. To close the dialog box, click OK. The UPS Setup dialog box displays. 10. To retain the setup v alues, click Sav e. 11. To close the UPS Setup dialog box, click OK. The UPS Integrator dialog box displays. 12. To close the UPS Integrator, select Exit from the File menu.
11. Integrating with an Uninterruptible Power Supply Implementation and Service Manual Running UPS Integration After Messaging System Installation11-6 Running UPS Integration After Messaging System Installation Although it is recommended that you run UPS Integration during messaging system installation, you can run it at any time. By default, the UPS Integrator only learns the normal and power out states and interprets any mask (an 8-digit binary image that represents the state of operation) that is not recognized as either a normal or power out state as a low-battery state and handles it accordingly. You can change the default so that the system attempts to learn the UPS’s low-battery state. This ensures that the system performs an automatic shutdown only when a true low-battery state is reached. You should only change the default, howev er, if you know that the UPS has a consistent low-battery mask. Consult the manual that came with the UPS for more information. Also, the UPS may require a signal to know that the system is monitoring UPS operation. This signal can come from the DTR (data terminal ready) or RTS (request to send) pin on the PC’s serial port. You can configure the UPS Integrator utility to set the proper pin to signal the UPS. By default, the Request to Send pin is set to signal the UPS. If the UPS requires the DTR pin to signal the UPS, or if you do not want any signal sent, you can change the default. Before doing so, howev er, consult the UPS documentation to determine if you should enable one or both of these options. To run the UPS Integrator utility after messaging system installation: 1. If the messaging system is running, select Exit from the File menu to shut it down. 2. Double-click the UPS Monitor icon in the program folder. The UPS Integrator dialog box displays. 3. From the Options menu, select Setup. The UPS Setup dialog box displays. If the Power out and Low batter fields match the entries on the following screen, the UPS utility has been preconfigured for you. Select Cancel to exit the UPS utility.
11. Integrating with an Uninterruptible Power Supply Implementation and Service Manual Running UPS Integration After Messaging System Installation11-7 4. If you do not want the system to attempt to learn the UPS’s low-battery state and you do not want to change the pin-signaling default, proceed with the step 5. If you do want the system to attempt to learn the UPS’s low-battery state or you do want to change the pin-signaling default, complete the following: a. Click Adv anced. The Adv anced Settings dialog box displays. b. If you want the UPS Integrator to attempt to learn the UPS’s low-battery mask, disable the Low Battery Default option (remov e the check from the checkbox). This enables the UPS Integrator to attempt to learn the UPS’s low-battery state. c. If you want to change the pin signaling setting, change the Data Terminal Ready and Request to Send options as appropriate for the UPS. d. To sav e the settings, click OK. The UPS Setup dialog box displays. 5. In the Port field, enter the serial port to which the UPS is connected. 6. If you know the Normal Operation, Power Out, and Low Battery masks of the UPS connected to the PC, you can manually enter them in their respectiv e fields under Masks on the UPS Setup dialog box, then proceed to step 10. See the UPS manual to determine if the masks are prov ided. (For APC UPSs, the Normal mask is 00000000, the Power out mask is 00010000, and the Low batter mask is 10010000.) If you do not know the masks for the UPS, click Learn to start the Learn mode, which enables the UPS monitor to establish the UPS signals. The system displays the message “Begin Learn Mode.” You may select Cancel at any time to abort the Learn process. 7. The system displays a message prompting you to v erify that the cable from the UPS to the serial port is securely attached. Click OK. The system displays the message “Learn normal state” as it learns the mask for the UPS’s normal operating state. A mask is an 8-digit binary image that represents the state of operation. After the system learns the normal operating state, it displays the message “Disconnect power from the UPS.” This allows the system to emulate a power out condition. 8. Remov e the UPS power cord from the electrical outlet, then click OK. The system then learns the power out state. If you did not change the default low-battery setting in step 4, proceed to step 9. If the Low Battery Default option is disabled on the Adv anced Settings dialog box, after the system learns the mask for the power out state, it continues running off the UPS until the UPS reaches a low-battery state. There is a delay between learning the power out state and learning the low-battery state mask as the system waits for the power on the UPS to diminish.
11. Integrating with an Uninterruptible Power Supply Implementation and Service Manual Running UPS Integration After Messaging System Installation11-8 9. After the system learns the necessary states, the message “Reconnect power to UPS” displays. Reconnect the UPS power cord to the electrical outlet, then click OK. A dialog box displays the message “End Learn Mode.” After Learn mode is complete or you manually enter the UPS’s masks, the system constantly monitors the current mask and compares it to the recognized masks for each state to determine the current state of UPS operation. 10. To close the dialog box, click OK. The UPS Setup dialog box displays. 11. To retain the setup v alues, click Sav e. 12. To close the UPS Setup dialog box, click OK. The UPS Integrator dialog box displays. 13. To close the UPS Integrator, select Exit from the File menu. 14. Open an OS/2 window. 15. From the C:\ prompt, type COPY “ C:\DESKTOP\OS!2 SYSTEM\STARTUP\STARTUP.CMD” BACKUP.CMD” and press . 16. From the C:\ prompt, type E “ C:\DESKTOP\OS!2 SYSTEM\STARTUP\STARTUP.CMD and press . The contents of the file are displayed in an OS/2 editor window. 17. Mov e the cursor to the line START /MIN RUNVM.CMD and press to mov e the cursor to the beginning of the line. 18. Press to insert a new line. 19. Place the cursor at the start of the blank line. 20. Type START /PM /MIN UPS.EXE . to load the UPS monitor each time the system boots. 21. Select Sav e from the File menu. 22. Type EXIT and press to close the OS/2 window. 23. Shut down the PC: a. Click the right mouse button on an empty area of the OS/2 desktop and select Shut down from the menu that displays. b. W hen you are prompted whether you want to close all windows and activ e programs, click OK. c. When prompted to shut down or reboot, press to reboot the PC.