Have a look at the manual Lucent Technologies DEFINITY Enterprise Communication Server Release 8.2 Installation And Test For Multi-Carrier Cabinets Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 413 Lucent Technologies manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
DEFINITY ECS Release 8.2 Installation and Test for Multi-Carrier Cabinets 555-233-114 Issue 1 April 2000 Install and Connect Cabinets 1-31 Fiber Optic Interconnect Cabling 1 Figure 1-13. High-Reliability CSS-Connected with 1 Switch Node Critical Reliability Fi g u re 1 - 1 4 shows typ ic al fiber op tic c abling b etween c ab inets. The c ab le b etween p ort slots 1 and 2 on eac h switc h nod e is a metallic c ab le (H600-278). 1. Connec t the 2 g roup s of 1 to 15 c ab les b etween the PPN and eac h EPN in an alternating p ort slot ord er: 20, 3; 19, 4; 18, 5; and so forth. Figure Notes 1. Cabinet 1 (PPN with 1 Switc h Nod e) 2. Cabinet 2 throug h 15 (EPN)3. H600-278 Metallic Cab le 4. To other EPNs
DEFINITY ECS Release 8.2 Installation and Test for Multi-Carrier Cabinets 555-233-114 Issue 1 April 2000 Install and Connect Cabinets 1-32 Fiber Optic Interconnect Cabling 1 Figure 1-14. Critical-Reliability CSS-Connected with 1 Switch Node 2. Both c onnec tions from eac h EPN must go to the same slot numb er. For examp le: EPN c ab inet 2, 2A1 to 1E3 and c ab inet 2, 2B2 to 1D3. Figure Notes 1. Cabinet 1 (PPN with 1 Dup lex Switc h Node) 2. Cabinet 2 throug h 16 (EPN)3. H600-278 Metallic Cab le 4. To other EPNs
DEFINITY ECS Release 8.2 Installation and Test for Multi-Carrier Cabinets 555-233-114 Issue 1 April 2000 Install and Connect Cabinets 1-33 Earthquake Protection Installation 1 Earthquake Protection Installation Install Concrete Floor Mounting 1. Position the c ab inet in the exac t p osition it is to oc c up y when the installation is complete. 2. Insert a p enc il or marker throug h the holes p reviously oc c up ied by the c arriag e b olts (front and rear) in the b ottom of the c ab inet and mark the floor d irec tly b eneath eac h hole. 3. Roll the c ab inet out of the way and d rill four 1/2-in. (1.27 c m) d iameter holes ab out 1.5 in. (3.8 c m) d eep at the loc ations marked in Step 2. 4. Insert c onc rete floor anc hors (STARR p art numb er 3425) into the holes. 5. Roll the c ab inet b ac k into p lac e and alig n the c ab inet holes over the c onc rete floor anc hors. 6. Ad just the leveling leg s until the c ab inet is level. See Fi g u re 1 - 1 5 . NOTE: If the system is sup plied with c ab le duc twork, the c ab inets must b e level from front to rear and from sid e to side. They must b e sq uare with respec t to eac h other to within ± 1/8-in. (0.3 c m). 7. Sec ure the c ab inet to the floor with the 4 sup p lied 3/8-16 x 4.5-in. (11.4 c m) b olts and four 3/8-in. flat washers. 8. Rep eat this p roc ed ure for eac h c abinet to b e installed . Install Raised Computer Floor Mounting 1. Position the c ab inet in the exac t p osition it is to oc c up y when the installation is complete. 2. Insert a p enc il or marker throug h the holes p reviously oc c up ied by the c arriag e b olts (front and rear) in the b ottom of the c ab inets and mark the raised floor p anels direc tly b eneath eac h hole. 3. Roll the c ab inet out of the way and d rill 4 holes 5/8-in. (1.6 c m) in d iameter throug h the raised floor p anels marked in Step 2. !CAUTION: Take c are while drilling the holes throug h the raised floor that the drill b it d oes not p enetrate any c ab les b elow the floor that c ould c ause d amag e to the c ab le or injury to the installer. 4. Insert a long p unc h throug h the holes d rilled in Step 3 and mark the c onc rete floor b eneath the raised floor p anels.
DEFINITY ECS Release 8.2 Installation and Test for Multi-Carrier Cabinets 555-233-114 Issue 1 April 2000 Install and Connect Cabinets 1-34 Earthquake Protection Installation 1 5. Remove the raised floor p anels in whic h the holes were d rilled. 6. Using 1/2-in. (1.3 c m) anc hor b its, d rill a hole at eac h of the loc ations marked in Step 4. Stop drilling when the mark on the sid e of the b it reac hes the floor level. 7. Insert a c onc rete floor anc hor (STARR part number 3425) into the hole until the mark on the b it reac hes floor level ag ain. Snap the top of the anc hor bit off. Rep eat for the remaining holes. Figure 1-15. Earthquake Mounting — Raised Computer Floor 3/8 inch flat washer Nut welded to frame Leveling foot variable height 4inches (10.16 cm) concrete subfloor3/8 - 16 Concrete floor anchor 3/8 - 16 threaded rod raised floor cab_base CJL 052096
DEFINITY ECS Release 8.2 Installation and Test for Multi-Carrier Cabinets 555-233-114 Issue 1 April 2000 Install and Connect Cabinets 1-35 Earthquake Protection Installation 1 8. A 3/8-16 thread ed rod (p art numb er 845557073) is used to sec ure the c ab inet to eac h c onc rete floor anc hor. See Figure 1-15 . Measure the d istanc e from 1 of the anc hors to the b ottom of the c ab inet. Ad d 1/2-in. (1.3 c m) to this measurement to allow the rod to b e thread ed into the floor anc hor. Ad d an ad d itional 1/2-in. (1.3 c m) to allow the rod to p rotrud e up throug h the b ottom of the c ab inet. For examp le: if the d istanc e from the floor anc hor to the b ottom of the c ab inet is 10 in. (25 c m), c ut the thread ed rod 11 in. (27.9 c m) long . 9. When all 4 threaded rod s are c ut, replac e the raised floor panels removed in Step 5. 10. Position the c ab inet over the holes and ad just the leveling leg s until the c ab inet is level. NOTE: If the system is sup plied with c ab le duc twork, the c ab inets must b e level from front to rear and from sid e to side. They must b e sq uare with respec t to eac h other to within + -1/8-in. (0.3 c m). 11. Insert the thread ed rod s throug h the c ab inet b ottom and thread into the c onc rete floor anc hors. 12. Plac e a 3/8-in. flat washer onto eac h rod . Thread a 3/8-16 hex nut onto eac h rod and tig hten sec urely. 13. Rep eat this p roc ed ure for eac h c abinet to b e installed (inc lud ing the Auxiliary Cabinet and the Stratum 3 Cloc k Cabinet).
DEFINITY ECS Release 8.2 Installation and Test for Multi-Carrier Cabinets 555-233-114 Issue 1 April 2000 Install and Connect Cabinets 1-36 Earthquake Protection Installation 1
Install Telecommunications Cabling 2-1 Equipment Room Hardware 2 DEFINITY ECS Release 8.2 Installation and Test for Multi-Carrier Cabinets 555-233-114 Issue 1 April 2000 2 Install Telecommunications Cabling Equipment Room Hardware SYSTIMAX 110-typ e hardware is used for the Main Distrib ution Frame (MDF). 110-typ e hard ware is availab le in 2 basic typ es: the 110A and 110P. The 110A req uires less wall sp ac e than the 110P. The 110P inc lud es horizontal and vertic al c ab le troug hs for manag ing c ross-c onnec t c ab les. The system c onnec ts to the MDF with the sup p lied B25A 25-p air c ab les. Refer to DEFINITY Communic ations System Generic 1 and Generic 3 Main Distrib ution Field Desig n, 555-230-630, for more information. Fi g u re 2 - 1 shows the c ross-c onnec tions for c ommon c irc uit p ac ks. Refer to the fig ure when c ross-c onnec ting wire pairs to the MDF.
DEFINITY ECS Release 8.2 Installation and Test for Multi-Carrier Cabinets 555-233-114 Issue 1 April 2000 Install Telecommunications Cabling 2-2 Equipment Room Hardware 2 Figure 2-1. Example MDF Connections widfccf2 EWS 102798 4 1101941322 21120 51423 3122161524918 71625817 Port Tie Trunk Port MET Line 4 4 Port Tie Trunk w/ E&M Signaling Port Data Line 8 Port Digital 8 Port BRI 12Port Hybrid 8Port DID 8 Port Analog Port CO 8 8 110 19 413 22 21120 5 1423 3 12 21 615 24 918 716 25 8 17 Port Digital 2416 DS1Port Analog Port Analog 16 24Port Digital
DEFINITY ECS Release 8.2 Installation and Test for Multi-Carrier Cabinets 555-233-114 Issue 1 April 2000 Install Telecommunications Cabling 2-3 Equipment Room Hardware 2 Cross-Connect Fields Eac h MDF c ontains a trunk/auxiliary field and a d istribution field . The trunk/auxiliary field c ontains 3 c ross-c onnec t areas: 1. The green field terminates the network interface leads from the Central Offic e (CO) and p rovid es the terminals to c ross-c onnec t the leads to the p urp le or yellow field s as req uired . A sing le row of the 110-typ e terminal b loc k c an terminate twenty-four 1-p air, eig ht 3-p air, or twelve 2-p air trunks. 2. The p urp le field terminates the trunk c irc uits from the system with WP-90929, List 1 or 3 c onc entrator c ab les. Also, 25-pair c ab les c an b e used to terminate trunk c irc uits from the system with eac h trunk c irc uit p ac k c onnec ting to one 25-p air row of the 110-typ e terminal b loc k. Eac h terminal b loc k row c an terminate twenty-four 1-p air, eight 3-p air, or twelve 2-p air trunks. 3. The yellow field p rovid es c ross-c onnec t terminals for all misc ellaneous lead s from the system, suc h as alarm monitors, emerg enc y transfer relay p ower, and attend ant c onsole p ower. This field is used for emerg enc y transfer wiring , p ag ing eq uipment, music sourc es, and so forth. The distribution field c ontains 4 cross-connec t areas: 1. The purple field (port field) terminates 25-pair c ables from the system. Eac h line c irc uit p ac k c onnec ts to one 25-p air row of the 110-typ e terminal b loc k. One 25-p air c ab le is required for eac h line c irc uit p ac k. NOTE: This is the c ase exc ept for the 16 p ort analog c irc uit p ac k and the MET c irc uit p ac k. The 16-p ort analog line c irc uit p ac k req uires an ad ap ter c ab le to c onnec t from 1 c onnec tor on the system to 2 25-p air c onnec tors on a 110-typ e terminal b loc k. Two MET c irc uit p ac ks req uire a c onc entrator c ab le to c onnec t from 2 c onnec tors on the system to one 25-p air c onnec tor on a 110-type terminal b loc k. 2. The yellow field (auxiliary field ) terminates all 25-p air c ab les from the auxiliary c ab inet and ad junc t eq uip ment c ab inets. The yellow field is loc ated in the lower rig ht-hand c orner of the d istrib ution field . 3. The white field (station field ) terminates the station wiring . The white field indic ates 3-p air station c irc uits (8 c irc uits p er 25-p air c ab le) routed throug h a satellite c loset. 4. The b lue field (station field ) also terminates station wiring . The b lue field indic ates 3- and /or 4-p air station c irc uits (8 or 6 c irc uits, resp ec tively, p er 25-p air c ab le). The fourth p air, of the 4-p air station c irc uit p rovid es ad junc t p ower from the c ross-c onnec t field on an as-need ed b asis to terminals within 250 ft (76 m) (wire leng th) of the MDF.
DEFINITY ECS Release 8.2 Installation and Test for Multi-Carrier Cabinets 555-233-114 Issue 1 April 2000 Install Telecommunications Cabling 2-4 Main Distribution Frame 2 Main Distribution Frame The MDF is loc ated d irec tly b ehind the system c abinet. Fi g u re 2 - 2 shows a typic al installation using 900-p air 110P-typ e terminal b loc ks. Figure 2-2. Typical 110A-Type Terminal BlocksFigure Notes 1. Multicarrier Cab inet 2. Z113A Cab le Slac k Manag er 3. 25-Pair Cab le to System Cab inet 4. Station Cab les5. Station Distrib ution Field 6. Port Distribution Field 7. Trunk/Auxiliary Field mccmdf KLC 060596