Have a look at the manual Lucent Technologies DEFINITY Enterprise Communication Server Release 8.2 Installation And Test For Multi-Carrier Cabinets Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 413 Lucent Technologies manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
DEFINITY ECS Release 8.2 Installation and Test for Multi-Carrier Cabinets 555-233-114 Issue 1 April 2000 Install Telecommunications Cabling 2-35 Station Circuit Distribution from Equipment Room 2 The 4-p air station c ab les c an b e run d irec tly from the eq uip ment room to the information outlets if 4-p air terminal b loc ks are used in the d istrib ution field . See Figure 2-20 . The station c ables must b e field -terminated on the 110-typ e terminal blocks. Figure 2-20. 4-Pair Run to Equipment Room or Satellite Location Figure Notes: 1. Station Sid e of MDF or Satellite Loc ation 2. 4-Pair Circ uit3. Blue Field 4. DIW Station Cab le (D-Insid e Wire) 5. Information Outlet 3 4 15 2 2 r764798a CJL 030796
DEFINITY ECS Release 8.2 Installation and Test for Multi-Carrier Cabinets 555-233-114 Issue 1 April 2000 Install Telecommunications Cabling 2-36 Station Circuit Distribution from Equipment Room 2 If 110-type terminal b loc ks are used with a mod ular p lug -end ed station c ab le, an ad ap ter c an be c onnec ted d irec tly to the 110-typ e terminal b loc k c onnec tors. See Fig ure 2-21 . Figure 2-21. 4-Pair Run to Equipment Room or Satellite Location Figure Notes: 1. Part of MDF 2. 3-Pair Connec ting Bloc ks 3. 4-Pair Connec ting Bloc ks 4. Purple Field 5. Patc h Cord or Cross-Connec t Jump ers 6. Blue Field7. To System Cab inet (3 pair mod ularity) 8. A25D Cab le 9. 258A or BR2580A Ad ap ter 10. Information Outlet 11. 4-Pair Circ uit (DIW station cab le (D-Inside Wire)) 8 7 19 10 11 r758532a CJL 031196 2 4 3 6 5
DEFINITY ECS Release 8.2 Installation and Test for Multi-Carrier Cabinets 555-233-114 Issue 1 April 2000 Install Telecommunications Cabling 2-37 Station Circuit Distribution from Equipment Room 2 3-Pair to 4-Pair Station Circuit Distribution Fi g u re 2 - 2 2 shows the 3-p air c irc uit distrib ution from an eq uipment room MDF to a satellite loc ation using 110-typ e hard ware. Four-p air c irc uits are d istrib uted from the satellite loc ation to the information outlets. Figure 2-22. 3-Pair to 4-Pair Satellite Location Connectivity Figure Notes: 1. Part of MDF 2. 3-Pair Connec ting Bloc ks 3. Purple Field 4. White Field 5. Patc h Cord or Cross-Connec t Jump ers 6. To System Cab inet (3 Pair Mod ularity) 7. A25D Cab le (3-Pair Circ uits) 8. B25A Cable9. Connec torized (stag g ered fing er) Multip le 25-Pair Cable 10. 4-Pair Connec ting Bloc ks 11. Blue Field 12. 258A or BR2580A Ad ap ter 13. Information Outlet 14. 4-Pair Circ uit [ DIW Station Cab le (D-Insid e Wire)] 15. Part of Satellite Loc ation 16. 4-Pair Circ uits (B25A Cab le) 2 2 3 8 8 4 4 9 10 3 11 7 6 1 12 16 15 14 13
DEFINITY ECS Release 8.2 Installation and Test for Multi-Carrier Cabinets 555-233-114 Issue 1 April 2000 Install Telecommunications Cabling 2-38 Station Circuit Distribution from Equipment Room 2 Three-p air c irc uits c an also b e run direc tly from the eq uip ment room MDF to a 356A ad ap ter as shown in Fig ure 2-23 . Four-p air station c ab les c onnec t the ad ap ter to the information outlets. Four-p air station c ables c an b e run d irec tly from a satellite loc ation to the information outlets as p reviously d esc rib ed . Figure 2-23. 3-Pair to 4-Pair Circuit Distribution and Connectivity NOTE: Brid g ed tap s are not allowed on any p art of the station wiring . Figure Notes: 1. Part of Main Distrib ution Frame (MDF) 2. 3-Pair Connec ting Bloc ks 3. Purple Field 4. Blue Field 5. Patc h Cord or Cross-Connec t Jump ers 6. To System Cab inet (3-Pair Mod ularity)7. B25A Cable 8. 3-Pair Circuits 9. 356A Ad ap ter 10. Information Outlet 11. 3-Pair Circ uit in 4-Pair Wire 12. DIW Station Cab le (D-Insid e Wire ) 8 7 1 9 10 11 12 r758533a CJL 031196 22 43 6 5
DEFINITY ECS Release 8.2 Installation and Test for Multi-Carrier Cabinets 555-233-114 Issue 1 April 2000 Install Telecommunications Cabling 2-39 Layout 2 Layout Locate Information Outlets The customer or marketing representative must provide floor plans showing the information outlet loc ations and typ es (flush- or surfac e-mounted ) req uired . The floor plans must also show a c omplete overview of all c onduit and cabling fac ilities in the b uild ing. Locate Satellites and Sites Use the following information when determining site, satellite, or adap ter loc ations. a. Keep the numb er of loc ations to a minimum. b . To minimize the station wiring d istanc es, c entrally loc ate the sites/satellites, or ad ap ters among the information outlets. c . Site/satellite loc ations must b e easily ac c essib le and c ontain AC-p owered rec ep tac les. Adapter Requirements One 258A/BR2580A ad ap ter is req uired for eac h 25-pair station c ab le c ontaining 4-p air station c irc uits. One 356A ad ap ter is req uired for eac h 25-p air station c ab le c ontaining 3-p air station c irc uits. Hardware Requirements Hard ware req uirements are the same as for the eq uip ment room. Sizing 4-Pair Station Cables Use the sc ale of the floor p lan to d etermine the ap p roximate leng th of the station c ab les req uired p er the stand ard SYSTIMAX wiring c onc epts.
DEFINITY ECS Release 8.2 Installation and Test for Multi-Carrier Cabinets 555-233-114 Issue 1 April 2000 Install Telecommunications Cabling 2-40 Layout 2 Sizing 25-Pair and Multiple 25-Pair Station Cables Use the sc ale of the floor p lan to d etermine the ap p roximate leng th of eac h 25-p air station c ab le. The c ables must b e selec ted and p rop erly sized to make maximum use of the hard ware at the equip ment room or satellite loc ation. Use 25-p air B25A c ab les to c onnec t ad ap ters d irec tly to the MDF or satellite loc ation. Stag g ered -fing er c ab les, eq uip ped with fac tory-installed 25-pair c onnec tors at b oth end s, should b e used when multip le 25-p air c ab les are used b etween the eq uip ment room or satellite loc ation and the ad ap ters. B25A c ab les are req uired at the eq uip ment room or satellite loc ation to c onnec t the stag g ered-fing er c ab les to the 110-typ e terminal bloc ks. Use the following information to d etermine the c ab le size (c ab le p airs) req uired for either 3-p air or 4-p air c irc uits. Note the leng th and size on the floor p lan to aid in the ord ering and installation of the station c ab les. 3-Pair Station Cable Circuits To d etermine the size of station c ab les c ontaining 3-p air c irc uits, multip ly the numb er of 3-pair c irc uits req uired at the satellite loc ation b y 3.5. Then, using the minimum size c ab le req uirement, round up the c ab le size req uirement to the next highest available c ab le b und le size. This will p rovid e add itional p airs for g rowth and c omp ensate for every twenty-fifth p air in a c ab le that is not used . 4-Pair Station Cable Circuits To d etermine the size of station c ab les c ontaining 4-p air c irc uits, find out how many information outlets are served b y the eq uip ment room MDF or satellite loc ation MDF. Multiply the numb er of information outlets by 4. Then, using the minimum size c ab le req uirement, round up the c ab le size req uirement to the next highest available c ab le b und le size. NOTE: This formula may not c omp ensate for the unused twenty-fifth p air in all c ases. If not, it must b e allowed for.
DEFINITY ECS Release 8.2 Installation and Test for Multi-Carrier Cabinets 555-233-114 Issue 1 April 2000 Install Telecommunications Cabling 2-41 Voice and Data Terminals 2 Voice and Data Terminals The system c an c onnec t to all DTE terminals and have RS-232 (or EIA-232) or DCP interfac es. Ta b l e 2 - 4 lists some of the terminals that c an c onnec t to the system. Contac t your Luc ent Tec hnolog ies rep resentative for more information. Table 2-4. Voice and Data Terminals Station Type Type Analog sets: 500, 2500, 7101A, 7103A, 7104A, 8110, DS1SA, and DS1FDAnalog voic e Other Analog Ports 1, Wired Sp are Ports, and Non-wired Sp are PortsAnalog voic e 10MET set — 10 b uttons 20MET set — 20 b uttons 30MET set — 30 b uttonsVo i c e Terminal — 510 BCT Terminal — 515 BCTData 602A1 Callmaster I 603A1 Callmaster II 603D1 Callmaster III 603E1 Callmaster III 606A1 Callmaster IVData and voic e Dig ital set — 6402 Dig ital set — 6408 Dig ital set — 6408D Dig ital set — 6408D+ Dig ital set — 6416D+ Dig ital set — 6416D+ w/XM24B exp ansion mod ule Dig ital set — 6424D+ Dig ital set — 6424D+ w/XM24B exp ansion mod uleDig ital voic e Voic e/d ata — 6538 Data and voic e Hybrid set — 7303S Hybrid set — 7305S Hybrid set — 7309H Hybrid set — 7313H Hybrid set — 7314H Hybrid set — 7315H Hybrid set — 7316H Hybrid set — 7317HHyb rid voic e Continued on next page
DEFINITY ECS Release 8.2 Installation and Test for Multi-Carrier Cabinets 555-233-114 Issue 1 April 2000 Install Telecommunications Cabling 2-42 Voice and Data Terminals 2 Dig ital set — 7401D/7401+ Dig ital set — 7403D Dig ital set — 7404D Dig ital set — 7404D w/d isp lay Dig ital set — 7405D Dig ital set — 7405D w/d isp lay Dig ital set — 7405D w/c ov Dig ital set — 7406D Dig ital set — 7406D w/d isp lay Dig ital set — 7406+ Dig ital set — 7406+ w/d isp lay Dig ital set — 7407D Dig ital set — 7407+ Dig ital set — 7410D Dig ital set — 7410+ Dig ital set — 7434D Dig ital set — 7434D w/d isp lay Dig ital set — 7434D w/c all c overag e mod ule Dig ital set — 7444DDig ital voic e Dig ital set — 8403B Dig ital set — 8405B/B+ Dig ital set — 8405D/D+ Dig ital set — 8410B Dig ital set — 8410D Dig ital set — 8411B Dig ital set — 8411D Dig ital set — 8434 D Dig ital set — 8434 with XM24B Exp ansion Mod ule Dig ital set — 9403B Dig ital set — 9410D Dig ital set — 9434DDig ital voic e Basic attend ant c onsole (302A, 302B) Enhanc ed attend ant c onsole (302C) Attend ant selec tor c onsole (26B1)Data and voic e ISDN-BRI — 7505D — 7506D — 7507D — 8503D — 8510T w/d isp lay — 8520T w/d isp layBRI voice Wireless 9601A 2Vo i c e Table 2-4. Voice and Data Terminals — Continued Station Type Type Continued on next page
DEFINITY ECS Release 8.2 Installation and Test for Multi-Carrier Cabinets 555-233-114 Issue 1 April 2000 Install Telecommunications Cabling 2-43 Voice and Data Terminals 2 The following notes ap p ly to the b utton and d ata mod ule rec ord s in Ta b l e 2 - 4: nAny DCP p hone (exc ep t 6400- and 8400-series) c an ad d a 7400B, req uiring 1 d ata module rec ord . nA d ata mod ule c an b e ad d ed to a 7403D or 7405D, req uiring 1 d ata mod ule rec ord . nA d ata mod ule (ADM-T) c an b e ad ded to a 7505D, 7506D, or 7507D, req uiring 1 d ata module rec ord . nAn ISDN-BRI end p oint rec ord is req uired for eac h d istinc t ISDN-BRI end p oint. Thus eac h voic e-only, d ata-only, or voic e-d ata end p oint uses 1 of these rec ord s. ADJLK 3 ADX8D ADX16A ADX16D ASAI CP9530 DIG800 K2500 MDC9000 MDW9000 PCVo i c e VM I 4 VM I FD4 VM I SA4 VRU5 VRU FD VRU SA WC B RI 105TLVo i c e 1. Includ es music -on-hold , rec ord ed announc ement, and loud sp eaker p ag ing . 2. The rad io c ontroller sup p orts 24 simultaneous calls and 2 wireless fixed b ases. 3.Need s ASAI interfac e and ASAI p rop ad junct links turned on in “ system-p arameters c ustomer op tions.” 4. Turn on mod e c od e in ” system-p arameters customer op tions.” 5. Need s DTMF turned on in “ system-p arameters customer op tions.” Table 2-4. Voice and Data Terminals — Continued Station Type Type Continued on next page
DEFINITY ECS Release 8.2 Installation and Test for Multi-Carrier Cabinets 555-233-114 Issue 1 April 2000 Install Telecommunications Cabling 2-44 Label the Main Distribution Frame 2 Administration Terminals Tab le 2-5 lists the ad ministration terminals that c an b e c onnec ted to the system. NOTE: The 715 BCS (406803148 and 406803155), has a 6-p in mini-DIN keyb oard c onnec tor. The 2900/715 BCS (4073113881 and 407313899), has a 6-p in RJ-11 keyb oard jac k loc ated on the sid e of the terminal. Label the Main Distribution Frame Fi g u re 2 - 2 4 shows the g rap hic symb ols used on labels for the system, c ross-c onnec tions, information outlets, and c ab les. The lab els are c olor-c od ed to id entify system wiring : nGreen — To Central Offic e (CO) nPu r p le — To system p orts nYe l l o w — To auxiliary eq uip ment and misc ellaneous system lead s nBlue — To information outlets nWh i t e — From Main Distrib ution Frame to satellite loc ations (3-p air) Table 2-5. Administration Terminals Administration Terminal Application 510D Remote ad ministration 610D, 513, 610, 615, 715 1 BCT, 4410, 4425, and VT220 1. The keyb oard s and terminals are interc hangeable when an ad ap ter c able is used . Manag ement Terminal: ad ministration and g eneral p urp ose 515 Business Communic ations Terminal (BCT)Remote ad ministration, g eneral p urp ose 615 Manag ement Terminal Manag ement Terminal system ad ministration and maintenanc e terminal 715 BCS, 2900/715 BCS, and 715 BCS-2 Management TerminalManag ement Terminal system ad ministration and maintenanc e terminal