Home > Inter-Tel > Communications System > Inter-Tel Imx/Gmx 256 Installation And Field Maintenance Manual

Inter-Tel Imx/Gmx 256 Installation And Field Maintenance Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Inter-Tel Imx/Gmx 256 Installation And Field Maintenance Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 31 Inter-Tel manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    Page
    of 624
    							lNTER-TELPRAc~cEsIMX/GMX 256 INSTALLATION & MAINTENANCE
    TROUBLE!SHOOTING
    Issue 1, November 1994
    FIGURE 6-2.SYSTEM TROUBLESHOOTING CHART (CONT’D)
    SYMPTOM
    DISA inoperativePROBABLE CAUSEUser errorCORRECTIVE ACTIONRefer to l%KWREB, page 4-39, for correct pro-
    cedures.
    Telephone not compatibleUser must dial in 
    from a DTMP telephone.
    Programming errorEnsure that the 
    trunk group is identified correctly
    as a day or night DISA trunk group. Refer to PRO-_ GRAMMING, page 
    5-111.
    Defective trunk cardReplace the associated card.
    Defective RCPU CardRefer to pages 6-l and 6-2 to test the system
    voltages. Replace the card if faulty.
    NOTE: Due to the natural characteristics of the CO trunk, the volume level of 
    DIMP tones transmitted over the trunk
    may be substantially reduced before reaching the 256 System. This natural degradation in tone volume may adversely
    affect the reliability of the DISA feature. Other factors which can affect 
    DISAperformance are CO trunk noise and the
    quality and strength of the 
    DTMP tones generated by the off-premises phone itself.SYMPTOM
    &table to interface with
    computer call-up device
    [banking machine, 
    answer-
    ng machine, auto dialer,
    SC.)PROBABLE CAUSE
    fgipgnt being called is
    DTMP digit duration/pause
    specifications of called
    equipment is incompatible
    with 
    256 System
    CO 
    trunk is designated fordial-pulse signaling
    Defective trunk card
    Defective RCPU Card
    CORRECTWE ACTION
    Ensure that the called equipment is functioning
    correctly.
    Check with the equipment manufacturer for
    MMP digit duration/pause specifications. Adjust
    IYIMP Digit Duration/Pause timer. (Refer to page5-77 in 
    PROGRAMMING.)Default value is 6/100
    second.
    CO trunk must be designated as 
    DTMF. Refer to
    page 5-103 in PROGRAMMING.
    Replace the associated trunk card.
    Refer to pages 6-l and 6-2 to test the system
    voltages. Replace the card if faulty.
    Page 6-15 
    						
    							TROUBLESHOOTINGIssue 1, November 1994INTER-TELPRACTICESIMX/GMX 256 INSTALLATION & MAINTENANCE
    FIGURE 6-2.SYSTEM TROUBLESHOOTING CHART (CONT’D)
    ,
    SYMPTOM
    No music-on-hold/back-
    ground music (external mu-
    sic source connected)
    SYMPTOM
    XFI/EMI present over con-
    rersations
    PROBABLE CAUSE
    External music source
    turned off or inoperative
    CORRECTWE ACTION
    Check the external music source for proper opera-tion. Optimal input level is 
    .775VRMS (OdB). Re-
    fer to INSTALLAI’ION, page 3-99.
    RCPU Card MOH jumperMove the music-on-hold jumper strap(s) on the
    strap(s) not in proper 
    posi-RCPU Card to the ON position.
    tion (no MOH, but back-
    -
    ground music is operative)
    Defective cable betweenRepair or replace the cable. Check to see that the
    music source and RCPUproper 
    connector was used. Refer to SPECIFICA-
    CardTIONS, page 2-10.
    Defective RCPU CardReplace the RCPU Card.
    PROBABLE CAUSE
    AC power source or ground-
    ing 
    incmrect
    Grounding point is source of
    AC power source is causing
    CORRECTIVE ACTION
    Verify that the AC circuit is isolated and dedicated
    (see page 3-3 in 
    INST&LAIION) and check for
    proper grounding (see page 3-41 in INSTALLA-
    TION).
    While the system is
    running on AC power, tempo-
    rarily remove the grounding wire to determine if it
    is the source of the 
    RFI/EMI. See page 3-41 in
    INSALmON for proper grounding require-
    ments.
    If an external battery back-up power source is in-
    stalled, switch system operation to battery back-up
    power by unplugging the power source’s AC pow-
    er cord (with grounding wire connected to equip-
    ment cabinet). If 
    RFI/EMI stops, the AC power
    source is the cause. Install an 
    RFI/EMI filter or
    equivalent on the AC outlet.,
    NOTE: For further RFI/EMI troubleshooting assistance while ou site, certified technicians should contact Technical
    Service with the following information:1. Modulation
    - AM, FM, or other
    2.Frequency of the interfering station (in Hz)3. Broadcast power
    4.Distance between equipment cabinet and broadcast antenna5. Who hears 
    RFkl Outside call
    - inside party only?l Outside call
    - outside party only?
    0Outside call - both parties?
    0 Intercom call- one or both parties?
    m 6.Type of instrument(s) on which RFI is heard-Standard Digital Keyset, Executive Digital Keyset, IMX 24-line
    keyset, IMX 24-line AIM keyset, IMX 12&e keyset, IMX 12-line Al&I keyset, lMX g-line keyset, IMX g-line
    AIM keyset, Inter-Tel/DVK 24&e keyset, Inter-Tel/DVK la-line keyset, Inter-Tel/DVX g-line keyset, GMX
    24&e keyset, GMX 12-line keyset, GX 24line keyset, ESLS, SLI, or single-line DTMF set
    Page 6-16 
    						
    							INTER-TELPRACTICESIMWGMX 256 INSTALLATION % MAINTENANCETROUBLESHOOTINGIssue 1, November 1994
    FIGURE 6-2.SYSTEM TROUBLESHOOTING CHART (CONT’D)
    SYMPTOM
    PROBABLE CAUSECORRECTWE ACTION
    Faulty DID numbers dis-
    User error (after dialing theOnly valid DID “start” digits can be properly pro-
    played at attendant stationscorrect 3- or 4digit “base”cased by the system.
    number, the user entered in-
    correct or incomplete “start”
    digits)
    Rogmnming errorEnsure that all valid DID numbers have been pro-
    -gmnmed to ring in to the appropriate locations.
    (See page 5-107 in PROGRAMMING.)
    Defective DID trunk 
    fromAt the DC block, remove the bridging clips for
    central office (the system isthe trunk. On the system side of the block, use a
    receiving incomplete or mu-
    test set to verify the DID trunk connection and the
    tilated DID “start” digits)system’s ability to accept and process valid digits.
    Also, move the trunk to a known good 
    IDC circuit.
    If the problem follows the trunk, contact the tele-
    phone company.
    Defective 
    IDC CardReplace the associated IDC Card.
    Page 6-17 
    						
    							~O~LESEOOTINGSue 1, November 1994INTER-TELPRACTICESIMX/GMX 256 INSTALLATION & MAINTENANCE
    FIGURE 6-3.CO TRW TROUBLESHOOTING CHART.-:._;;SYMPTOM
    20 trunk inoperative
    hroughout the systemPROBABLE CAUSECORRECTIVE ACTIONDefective CO trunk fromAl the associated CO block, remove the bridging
    central officeclips for the trunk. On the 
    telco side of the block,
    use a test set to verify the CO trunk connection.
    Also, move the CO trunk to a known good CO
    circuit. If the problem follows the trunk, contact
    the telephone company.
    Trunk is dedicated to a 
    set- -Verify the type of CO trunk. Instruct users to dial
    ondary carrier requiring anaccess code if required.
    awess code
    Defective cabling or 
    mis-
    wired 
    amphenol connectorUsing a test set, ensure presence and correct 
    loca-
    tion of the CO trunk at the associated CO block.
    on the trunk card
    Programming errorEnsure that the trunk is assigned to the correct
    trunk group and stations have been given access to
    it. 
    See page S-109 in PROGRAMMING.
    Trunk has been taken out ofPlace the trunk back in service. Refer to PEA-
    service by the attendant
    TURES, page 4-113, or page 5-148 in PRO-
    GRAMMING.
    Defective trunk card
    Replace the associated trunk card.
    Defective RCPU CardRefer to pages 6-1 and 6-2 to test the system
    voltages. Replace the card if faulty.
    WMPTOMPROBABLE CAUSECORRECTIVE ACTION
    Cannot obtain CO dial toneIf reorder tone is heard, pro-
    Ensure that keyset has outgoing access. Refer to
    gramming error
    page 5-34 in PROGRAMMING.
    Check to see if the 
    keyset is programmed for LCR
    only. Refer to page 5-42 PROGRAMMING. If so,
    check LCR programming, page 5-98 in PRO-
    GRAMMING.
    If progress tone is heard,
    user error
    Defective trunk card
    Defective RCPU CardEnsure trunk is assigned to the correct trunk group.
    Refer to page 5-109 in PROGRAMMING.
    System is programmed to expect a forced 
    accOunt
    code. Refer to
    PROGRAMMING, page 5-55.
    Replace the associated trunk card.
    Refer to pages 6-l and 6-2 to test the system
    voltages. Replace the card if faulty.
    Page 6-18 
    						
    							yl&sT&&MmCTICEs!STALIATION & MAINTENANCETROUBLESHOOTINGIssue 1, November 1994
    FIGURE 6-3.CO TRUNK TROUBLESHOOTING CHART (CONT’D)SYMPTOM
    fiw volume on all CO
    runks, cannot break CO dial
    onePROBABLE CAUSE
    Defective trunk card
    Defective CO trunk from
    central office
    Open or loose connection in
    the cable between the power
    supply and 
    cardfile
    Defective power supply
    module(s)
    Hybrid balance mismatch
    NOTE: See also 
    keyset problems on page 6-32.SYMPTOM
    Zamtot break CO dial tonePROBABLE CAUSECO circuit is programmed
    for wrong signaling type
    Defective CO trunk 
    from
    central office
    Timer error
    Defective trunk card
    Defective RCPU CardCORRECTIVE ACTION
    Measure -12VDC at the RCPU Card test points.
    (See page 3-61.) If it is not within tolerance, re-
    move all trunk cards and check voltage again. If
    the voltage returns to normal, replace the cards
    one at a time until the defective card is isolated
    and replaced.
    At the CO block, remove the bridging clips for the
    trunk. On the telco side of the block, use a test set
    to verify the CO trunk connection. 
    Also, move the
    CO trunk to a known good CO circuit. If the prob-
    lem follows the trunk, contact the telephone 
    com-
    PanY.
    If, with all trunk cards removed, the -12VDC is
    s&l1 not within tolerance, turn off the system and
    check the cable and 
    comtector with an ohmmeter.
    Replace or repair the faulty cable.
    With all trunk cards removed, measure -12VDC at
    the power supply connector(s). If not within toler-
    ance, replace the power supply module(s).
    Select the balance network 
    - ideal, loaded, or
    unloaded
    - that best matches the trunk’s imped-
    ance. See 
    PROGRAMhIING, page 5-147.CORRECTIVE ACTION
    Ensure that CO trunk and CO circuit use same
    type signaling 
    (DTMP or dial pulse). gee PRO-
    GlLAMMING, page 5-103.
    At the CO block, remove the bridging clips for the
    trunk. On the telco side of the block, use a test set
    to verify the CO trunk connection. Also, move the
    CO trunk to a known good CO circuit. If the prob-
    lem follows the 
    trnnk, contact the telephone com-
    PanYe
    If trunk is DTMF, the DTMP Digit Duration/Pause
    timer setting may not be compatible with the
    trunk. See 
    PROGRAMMING, page S-77.
    Replace the associated trunk card.
    Refer to pages 6-l and 6-2 to test the system
    voltages. Replace the card if faulty.
    NOTE: See also keyset problems on page 6-32.
    Page 6-19 
    						
    							TROUBLESHOOTINGIssue 1, November 1994lNTzR-TELPRAcTrcEsIMX/GMX 256INSTALLATION & MAINTENANCE
    FIGURE 6-3.CO TRUNK TROUBLESHOOTING CHART (CONT’D)
    SYMPTOMPROBABLE CAUSECORRECTIVE ACTION
    hnot place an outgoingPrognmming errorCheck station class of service (SCOS). See PRO-
    gll; CO dial tone is present;GRAMMING, page 5-42. Check that equal access
    ntercom worksand absorbed digit programmirq~ for the trunk
    group are correct. See PROGRAMMING, page
    5-113. If using 
    LCR, check LCR programming on
    page 5-98 in PROGRAMMING.
    -Defective CO trunk fromAt the CO block, remove the bridging clips for the
    central officetrunk. On the telco side of the block, use a test set
    to verify the CO trunk connection. Also, move the
    CO trunk to a known good CO circuit. If the prob-
    lem follows the trunk, contact the telephone com-
    pany.
    Defective station instrumentReplace the station instrument and/or perform the
    keyset self-test as outlined in INS’IAL~ON,
    pages 3-64,3-73, or 3-85.
    Defective trunk cardReplace the associated trunk card.
    Defective RCPU CardRefer to pages 6-l and 6-2 to test the system
    voltages. Replace the card if faulty.
    SYMPTOMPROBABLE CAUSECORRECTIVE ACTION
    other station conversationsDefective CO trunk(s)Isolate the trunk(s) with crosstalk by removing the
    can be heard on the CObridging clips from the CO block. On the telco
    trunk (crosstalk)side of the block, attach a test set to each trunk
    and check for crosstalk. If present, contact the
    telephone company.
    Defective cabling or 
    mis-Using a test set, ensure presence and correct loca-
    wired 
    amphenol connectortion of the CO trunk at the associated CO block.
    on the trunk card
    Defective station card
    Defective trunk card
    Defective RCPU CardReplace the associated station card.
    Replace the associated trunk card.
    Refer to pages 6-l and 6-2 to test the system
    voltages. Replace the card if faulty.
    Page 6-20 
    						
    							mTER-TELPRAcTIcEsWGMX 256 INSTALLATION & MAINTENANCETROUT3LJBHOOTlNGIssue 1, November 1994
    FIGURE 6-3.CO TRUNK TROUBLESHOOTING CHART (CONT’D)SYMPTOM
    Outside calls dropped during
    conversation or upon an-
    swering CO trunkSYMPTOM
    CO trunk cannot be reseized
    1PROBABLE CAUSECORRECTIVE ACTION
    User error (trunk key beingInstruct users not to press the trunk key while on a
    pressed after initial 
    connec-
    tion is made)call. Or, if necessary, set the CO Reseize timer to a
    higher value. Default value is 3 seconds. See page5-77 in 
    PROGRAMMlNG.Or, program the sta-
    tion to disallow CO reseize. See PROGRAM-
    MING, page 5-30.
    Defective CO trunk from
    -
    central officeAt the CO block, remove the bridging clips for the
    trunk. On the telco side of the block, use a test set
    to verify the CO trunk connection. Also, move the
    CO trunk to a known good CO circuit. If the prob-
    lem follows the trunk, contact the telephone com-
    pany.
    Insufficient loop current
    supplied by central officeCentral office must supply 20mA minimum loop
    current.
    ICC0 Disconnect timer
    value is set too shortEnsure timer value is long enough to ignore nor-
    ma1 interruptions in CO loop current. Default val-
    ue is 0.6 seconds. See page 5-77 in 
    PROGRAM-
    MlNG.
    Inter-Ring Silence timer val-
    ue is set too shortEnsure timer value is set longer than the central
    office ring signal is “off.” Refer to PROGRAM-
    MING, page S-77.
    Defective station instrumentReplace the station instrument and/or perform the
    keyset self-test as outlined in INSTALLKI’ION,
    pages 
    3-64,3-73, or 3-85.
    Defective trunk or station
    Replace the associated card.
    card
    Defective RCPU CardRefer to pages 6-l and 6-2 to test the system
    voltages. Replace the card if faulty.PROBABLE CAUSE
    CORRECTWE ACTION
    CO Reseize feature is dis-
    abledCheck station programming as described on page5-30 in PROGRAMMING.If the CO reseize op
    tion has been disabled, the user cannot reseize a
    trunk until it has been disconnected by hanging up
    or pressing another trunk key.
    CO Reseize timer is set tooSet the timer to a lower timer value. Default valuehigh
    is 3 seconds. See page 5-77 in PROGRAMMING.
    Page 6-21 
    						
    							TROUBLESHOOTINGIssue 1, November 1994INTEX-TELPRACTICESIMWGMX 256 INS~TION & MAINTENANCE
    FIGURE 6-3.CO TRUNK TROUBLESHOOTING CHART (CONT’D)SYMPTOM
    Noise on CO tank at all sta-
    tiOllSSYMPTOM
    20 trunk remains seized af-
    ier a call has been ended
    IPROBABLE CAUSE
    Defective CO trunk
    Defective trunk card
    Defective power supply
    module(s)
    Defective RCPU CardCORRECTIVE 
    ACTtON
    At the CO block, remove the bridging clips for the
    trunk. On the telco side of the block, use a test set
    to verify the CO trunk 
    connection. Also, move the
    CO trunk to a known good CO circuit. If the prob-
    lem follows the trunk, contact the telephone 
    com-
    P”Y*
    -Replace the associated trunk card.
    Refer to 
    INSTALIAI’ION, page 3-42, to perform
    the power supply electrical test. Replace the power
    supply module(s) if faulty.
    Refer to pages 6-l and 6-2 to test the system
    voltages. Replace the card if faulty.PROBABLE CAUSE
    Characteristic of some ESS
    x&al offices
    [C-CO or CO-CO Discon-
    nect timer value set too long
    Defective CO trunk
    Defective station instrument
    Defective trunk card
    Defective RCPU CardCORRECTIVE ACTION
    Central office must provide disconnect signal. Or,
    install a trunk release module available from most
    supply houses.
    Central office disconnect signal was not detected
    by 
    ICC0 or CO-CO Disconnect timer. Default
    value of the 
    ICC0 timer is 0.6 second, the CO-
    CO timer is 0.35 seconds. See page 5-77 in PRO-
    GRAMMING.
    At the CO block, remove the bridging clips for the
    trunk. 
    On the telco side of the block, use a test set
    to verify the CO trunk connection. Also, move the
    CO trunk to a known good CO circuit. If the prob-
    lem follows the trunk, contact the telephone 
    com-
    PanY.
    Replace the station instrument and/or perform the
    keyset self-test as outlined in INSTALLM’ION,
    pages 
    3-64,3-73, or 3-85.
    Replace the associated trunk card.
    Refer to pages 6-l and 6-2 to test the system
    voltages. Replace the card if faulty.Page 6-22 
    						
    							INTER-TELPRACTICESIMx/GMx 256 INSTALLATION & MAINTENANCETROUBLESHOOTINGIssue 1, November 1994
    FIGURE 6-3.CO TRUNK TROUBLESHOOTING CHART (CONT’D)
    SYUPTOM
    Ground start trunks not
    hmctioning properly
    PROBABLE CAUSE
    System not properly
    grounded
    CORRECTIVE ACTION
    Verify that the system AC circuit is isolated and
    dedicated (see page 3-3 in 
    INSTZLATION) and
    check for proper grounding (see page 3-41 in IN-
    STALLATION).
    LGC jumper straps not set
    correctly
    Tip and riug are reversed
    Programmiug error
    6OHz AC power is getting
    onto the trunksFor each ground start circuit, both corresponding
    LGC jumper straps must be set in the GS position.
    lf the strap settings are mixed, or if one or both of
    the straps is missing, the circuit will not function
    properly. Also, when setting the straps, note the
    unique ordering of the LGC circuits as shown in
    INSTi4LLN’lON on page 3-55.
    At the CO block, check to make sure that tip and
    ring are not reversed. See 
    INSTALLATLON, page
    3-13. Unlike loop start trunks, ground start trunks
    are polarity sensitive.
    Ensure that the trunks are identified correctly as
    ground start trunks. Refer to 
    PRGGRAMMING,
    page 5-103.
    Use a voltmeter to check the AC voltage between
    tip and earth ground while the trunks are con-
    nected to an LGC. If more than 5V 
    (Rh4S) are
    measured, there is AC power comamination (e.g.,
    due to faulty wiriug insulation). Locate and re-
    move the source of AC power contamination.
    Page 6-23 
    						
    							TROUBLESHOOTINGIssue 1, November 1994INTER-TELPRACTIcEslMX/GMX 256 INSTALLATION & MAINTENANCE
    FIGURE 6-4.FEATURE TROUBLESHOOTING CHARTSYMPTOM
    ?eature does not work prop
    :rlySYMPTOM
    Zannot transfer CO or inter-
    zom calls to other stationsPROBABLE CAUSECORRECTIVE ACTION
    User errorRefer to PRMURES for procedures. Also, ensure
    that the feature is available on the software pack-
    age installed.
    Programming errorCheck feature code programming. Refer to 
    PRO-
    G-G, page 5-58. Also, check user-pro-
    grammable feature key programming. Refer to
    - PEAlWE& page 4-51, and PROGRAMMING,
    page 5-44.
    Defective station 
    instrumentReplace the station instrument and/or perform the
    keyset self-test as described in INSTALLATION,
    pages 
    3-64,3-73, or 3-85.
    Defective station card
    Replace the associated station card.
    Defective RCPU CardRefer to pages 6-l and 6-2 to test the system
    voltages. Replace the card if faulty.PROBABLE CAUSECORRECTIVE ACTION
    User error (e.g., wrong fea-Refer to PEXWRES, page 4-70, for procedures.
    lure code)
    Called station is 
    iu do-not-A station in do-notdisturb cannot receive trans-
    disturbferred calls.
    Call transferred to an illegalUse only valid intercom numbers.
    intercom number
    Called station is in a 
    differ-To allow such transfers (if desired), place the two
    ent tenant group and 
    cross-stations in the same tenant group or allow cross-te-
    tenant traffic is deniednant traffic. See 
    PROGRAMh4lNG,page 5-67.
    Defective station instrumentReplace the station instrument and/or perform the
    keyset self-test as described in INSTALLATION,
    pages 
    3-64,3-73, or 3-85.
    Defective RCPU Card
    Refer to pages 6-l and 6-2 to test the system
    voltages. Replace the card if faulty.SYMPTOMPROBABLE CAUSE
    CORRECTWE ACTION
    Cannot transfer calls to out-User error (e.g., wrong fea-Refer to m, page 4-70, for procedures.
    side numbersture code)
    Programming errorCheck trunk access and toll restriction.
    Defective RCPU CardRefer to pages 6-l and 6-2 to test the system
    voltages. Replace the card if faulty.
    Page 6-24 
    						
    All Inter-Tel manuals Comments (0)

    Related Manuals for Inter-Tel Imx/Gmx 256 Installation And Field Maintenance Manual