Home > Inter-Tel > Communications System > Inter-Tel Imx/Gmx 256 Installation And Field Maintenance Manual

Inter-Tel Imx/Gmx 256 Installation And Field Maintenance Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Inter-Tel Imx/Gmx 256 Installation And Field Maintenance Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 31 Inter-Tel manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    Page
    of 624
    							INTEB-TELPBACTICESIMX/GMX 256 INS~TION & MAINTENANCEINSTALLATION
    Issue 1, November 1994
    4.7Since the IMX 256 System utilizes digital voice
    and data transmission between the digital keysets and
    the equipment cabinet, there are some additional digital
    keyset-only cabling requirements:l Do not use shielded cable, and do not use cable
    smaller than 24AWG.l
    Do not parallel cables (i.e., do not “double up on the
    COppX”).
    0Do not “bridge” or “Y” off the cable to another loca-
    tion.l Unlike analog 
    keysets, the digital keysets do not
    need to be routed in separate multi-pair cable runs.
    For example, if using 
    25pair cable runs to multiple
    station locations, it is acceptable to include 
    single-
    line sets, auxiliary equipment, and trunks in a cable
    being used for digital 
    keysets.
    B.TEBMINATING THE CABLES AT
    S’l%I’ION LOCATIONS
    Digital 
    Keys&
    4.8Terminate the digital keyset station cables on four-
    or six-conductor modular jack assemblies at the station
    lOC&iOIlS.
    4.9Do not mount the assemblies on the wall at this
    time; they will be wall mounted later when the station
    instruments are installed. Refer to Figure 3-l below for
    a wiring diagram.
    CAUTIONIf the tip and ring is reversed when installing a
    digital keyset, the keyset will not function.
    FIGURE 3-l.
    DIGITAL KEYSET MODULAR JACK ASSEMBLY WIRING
    RING
    I
    FOR DIGITAL KEYSETS
    USING FOUR-CONDUCTOR JACKSRING
    I
    TIP
    FOR DIGITAL KEYSETS
    USING SIX-CONDUCTOR JACKS
    Page 3-7 
    						
    							IlWTALUTIONIssue 1, November 1994INTER-TELlPRACTICESlMX/GMX 256 INSTALLATION & MAINTENANCE
    Analog Station Instruments
    4.10Terminate the analog 
    keyset, analog DSS/BLF
    Unit, Attendant Computer Console, single-line set, and
    playback device station cables on six-conductor modu-
    lar jack assemblies at the station locations. (For excep-
    tions to this, refer to the NOTE following section A on
    the previous page.)
    4.I.lDo not mount the assemblies on the wall at this
    time; they will be wall mounted later when the station
    instruments are installed. Refer to Figure 3-2 below for
    a wiring diagram.CAUTION
    If the power pair (W/BL, BL/W) is reversed, in-stalling a 
    keyset, Attendant Computer Console,
    or DSS/BLF Unit will open the fuse or associated
    thermistor on the 
    Keyset Card. If the card has a
    fuse, this affects operation of all station instru-
    ments connected to that card. If tip and ring 
    (W/
    BL, 
    BL/W) is reversed for DC-ringing single-line
    sets, the instrument may ring continuously.
    FIGURE 3-2.ANALOG SlATION MODULAR JACK ASSEMBLY WIRING
    I
    WlBLI
    w/oWIG
    BLMfWI0
    WIGFOR ANALOG 
    KEYSETS,
    FOR SINGLE-LINE SETS
    ATTENDANT COMPUTER CONSOLES,AND
    AND ANALOG 
    DSS/BLF UNITSPLAYBACK DEVICES
    NOTE: The W/BL and BL/W conductors for the two types of stations are reversed. If the type of station
    instrument is changed, the modular jack must be rewired.
    Page 3-g 
    						
    							INTER-TELPRACTIcEsIMX/GMX 256 INSTALLATION & MAINTENANCEINSTALLATIONIssue 1. November 1994
    5.ASSEMBLING THE MAIN
    DISTRIBUTION 
    FRAME (MDF’)
    BACKBOARD
    5.1The main distribution frame (IUDF) is the point at
    which the station instruments, trunks, and auxiliary sys-
    tem equipment are connected to terminal blocks (or, in
    the case of 
    Tl spans and optional Tl equipment, modu-lar jack assemblies are used instead). These terminal
    blocks (or modular jacks) are then connected to the 256
    System. It is extremely important that the connections
    be made 
    careffilly and accurately.
    NOTE: To simplify the MDF installation instructions,
    this manual outlines basic one block to one card installa-
    tion using bridging clips. However, it is quite accept-able, and in some situations more 
    functional, to use
    additional blocks and then moss connect between them.
    5.2Assemble the MDF as follows:
    (1)Mount at least a 4 
    x 8-foot (1.2 x 2.4meter),g-inch plywood backboard at the MDF loca-
    tion. (Depending on the number of stations and
    trunks to 
    lx installed, a larger backboard may be
    necessary.)
    (2)Attach the 66Ml-Xl-type terminal blocks to the
    plywood backboard. Refer to Figure 3-3 on the
    next page for a sample MDF block layout and
    cable assignments. Blocks include:l
    Up to 15 blocks for connecting CO trunks and
    the 
    25pair cables for the Loop/Ground StartCards 
    (LGCs) and/or the Loop Start Cards
    (Lscs)-
    Up to 15 blocks for connecting DID trunks
    and the 
    25pair cables for the Inward Dialing
    ~~0.
    Up to 16 blocks for connecting station cables
    and the 
    25pair cables for the station cards -Digital 
    Keyset Cards (DKSCs) for digital
    keysets; Keyset Cards (KSCs or KSC-Ds) for
    analog 
    keysets, analog DSWBLF Units, and
    Attendant Computer Consoles; Single-LineCards 
    (SLCs) for single-line sets and play-
    back devices; and Inward Dialing Cards
    (ID&) for off-premises extensions and/or
    on-premises single-line sets and playback
    devices.
    NOTE: If, as recommended, three-pair cable
    is used for wiring single-line sets and play-
    back devices, extra terminal blocks and the
    use of cross-connect wiring techniques are
    required.One block for connecting the RCPU Card
    cable and cables for music sources, paging
    equipment relay control, power failure trans-fer equipment, night transfer equipment,
    general signaling devices, etc.
    (3)If any Tl spans or any optional Tl alarm signal-
    ing devices are to be installed, attach eight-con-
    ductor modular jack assemblies to the MDF as
    required. (For complete information on install-
    ing 
    Tl spans, refer to page 3-17.)
    Page 3-9 
    						
    							lN!3TALLATIONIssue 1, November 1994INTER-TELPRACTICESIMX/GMX 256 INS-TION & MAINTENANCE
    FIGURE 3-3.SAMPLE MDF BLOCK LAYOUT AND CABLE ASSIGNMENTS->*.z-1ITO CENTRAL
    OFFICE
    + TO STATIONS LGC OR LSC
    CO TRUNKSl-8 -
    1
    SLCSLC-
    i
    fEL
    :
    -tKSC
    21
    nl28
    -
    -13.1
    I3.lC-LGC OR LSC
    CO TRUNKS
    9-16SLC
    14.1
    IIt14.16EMC
    E&M TRUNKS
    1-4
    KSC
    3.1I
    3.8
    SLC
    m
    7.1
    K7.8i
    6.1
    ol8.8
    -
    -
    -11.1
    ll.lE-
    DCDID TRUNKS
    l-8KSCRCPU CARDTO EXTERNAL
    EQUIPMENT
    CABLESbTO 256
    Page 3-10 
    						
    							INTER-TELPRACTICESIMX/GMX 256 INSTALLATlON & MAINTENANCE
    INS-TIONIssue 1, November 1994
    A.CONNECTING THE TRUNK CABLES TO
    TEEMDFco 
    lhmks
    5.3Connect the CO trunks and Loop/Ground Start
    Card (LGC) and/or Loop Start Card (LX) cables as out-
    lined below. Note that step 2 mentions two installation
    methods. Although the first method is more flexible, the
    second method can be used to minimize the number of
    terminal blocks that are used. Refer also to Figures 3-5
    and 3-6 on the following pages.
    (1)
    (2)
    (3)
    Cross connect the CO trunks from the telephone
    company RJ-type blocks to the 
    righz side of the
    LGC/LSC blocks.
    NOTE: For additional lightning protection, see
    paragraph 5.6 on the next page.
    Mefhod A: Using enough 25-pair cable to run
    from the LGC/LSC blocks to the cards, make the
    termination cables. Attach a 
    %)-pin female am-
    phenol-type connector to one end of each 
    LGC/
    LSC cable. Label each connector and cable end
    with the appropriate slot number (for example,
    SLOT-15). These 
    oo~ectors will be attached to
    the cards after they are installed in the equipment
    cabinet.
    Method B: Using enough 25pair cable to run
    from the LGC/LSC blocks to the cards, make thespecial termination cables. Attach up to three
    %-pin female amphenol-type connectors to one
    end of each 
    LGC/LSC cable as shown in Figure
    3-6. Connect CO trunks l-8 to one connector,
    trunks 9-16 to another connector, trunks 17-24
    to a third connector, and so on for each cable.
    Label each connector with the appropriate slot
    number (for example, SLOT-E). These connec-
    tors will be attached to the cards after they are in-
    stalled in the equipment cabinet.
    Using standard electrical tape, tape two ferrite
    split beads around each 
    25-pair cable just below
    the amphenol-type connector (as shown in Fig-
    ure 
    3-4 on the next page).NOTE: Ferrite beads must be installed to meet
    Part 15 of FCC regulations. Refer to REPLACE-
    MENT PARTS for the part number.
    (4)Terminate the other end of each 
    25-pair cable onthe left side of the corresponding 
    LGCZSC
    block.
    (5)
    Install bridging clips to complete the connec-
    ti0I.B.
    DID ‘D-u&
    5.4Connect the Direct Inward Dialing (DID) trunks
    and Inward Dialing Card 
    (RX!) cables as follows. Referto 
    Figure 3-7 on page 3-15 and Figure 3-19 on page
    3-28.
    NOTE: Resides DID trunks, IDCs can also be used toinstall single-line sets, playback devices, and 
    off-
    premises stations. Any combination using the eight cir-
    cuits on the card is possible. Refer to pages 3-21 to 3-28
    for station installation instructions.
    (1)
    (2)
    (3)
    (4)
    Q
    Cross connect the DID trunks from the telephone
    company RJ-type blocks to the right side of the
    IlX blocks.
    NOTE: For additional lightning protection, see
    paragraph 5.6 on the next page.
    Using enough 
    25-pair cable to run from the IDC
    blocks to the Inward Dialing Cards, make the ter-
    mination cables. Attach a 
    50-pin female amphe-
    nol-type connector to one end of each IDC cable.
    Label each connector and cable end with the 
    ap
    propriate slot number (for example, SLOT-16).
    These connectors will be attached to the Inward
    Dialing Cards after the circuit cards are installed
    in the equipment cabinet.
    Using standard electrical tape, tape two ferrite
    split beads around each 
    25-pair cable just below
    the amphenol-type connector (as shown in Fig-
    ure 3-4 on the following page).
    Terminate the other end of each 
    25-pair cable on
    the 
    Zej? side of the corresponding IDC block.Install bridging clips to complete the connec-
    tiOIlS.
    Page 3-11 
    						
    							INS~TIONIssue 1, November 1994INTER-TELPRACTICESIMWGMX 256 INSTALLATION & MAINTENANCE
    E&M’Ih&s5.5 Connect E&M trunks and E&M Card 
    @MC)
    cables as follows. Refer to Figure 3-g on page 3-16.
    (1)Cross 
    comtect the E&M trunks from the tele-
    phone company RJ-type blocks to the right side
    of the 
    RMC blocks.
    NOTE: For additional lightning protection, see
    paragraph 5.6.(2) 
    UsingenoughpaircabletorunfromtheEMC
    blocks-to the EZ&M Cards, make the terminationcables. Attach a 
    50-pin female amphenol-type
    connector to one end of each EMC cable. Label
    each connector and cable end with the appropri-
    ate slot number (for example, 
    SLQT-16). These
    connectors will be attached to the 
    -E&M Cards
    after the telecommunication cards ‘are installed
    in the equipment cabinet.
    (3)Using standard electrical tape, tape two ferrite
    split beads around each 
    25pair cable just below
    the amphenol-type connector (as shown in Fig-
    ure 3-4 below).(4)Terminate the other end of each 
    25-pair cable on:‘!,the ZejI side of the corresponding EMC block.::,
    (5)Install bridging clips to complete the connec-
    tiOIiS.
    Lightning Protection
    5.6For additional lightning protection, install gas dis-charge tubes with silicon avalanche suppressors to
    ground (grounding rod or copper, cold water pipe) on
    each CO, DID, E&M, and 
    OPXtrunk. This must be done
    external to the system. Each gas discharge tube is in-
    stalled directly between the telephone company RI-type
    block and the system’s 
    CO/DID/E&M/OPX input. This
    protection should give energy absorption and filter 
    low-
    level surge potentials. (For installation instructions and
    specific recommendations, contact Customer Support.)
    5.7Also, in areas with 
    frequent occurrences of light-
    ning, it is recommended that the cable between the tele-
    phone company RJ-type blocks and the gas discharge
    tubes be at least 75 feet long (the cable may be coiled up
    if desired).
    FIGURE 3-4.EXAMPLE OF FERRITE BEAD INSTALLATION
    AMPHENOL-TYPE
    CONNECTORS
    25-PAIR CABLES
    TO THE 
    MDF
    FERRITE
    BEADS
    Page 3-12 
    						
    							INTER-TELPRAcTICE!3IMX/GMX 256 INSTALLATION & MAINTENANCEINSTALIATIONIssue 1, November 1994
    FIGURE 3-5.LGC/LSC BLOCK CABLE TERMJNATIONS (METHOD A)
    LOOP/GROUND
    START CARD OR
    LOOP START
    CARD
    r
    LGC/LSC
    1.1 1,-RIUG-----
    TIP-
    121r-12----
    RING -
    AMPHENOL-
    TYPE
    CONNECTOR
    66Ml-SO-TYPE
    BLOCK
    (PART OF 
    MDF)
    3 TEE0
    RJ
    Page 3-13 
    						
    							INS-TIONIssue 1, November 1994
    lNTER.TEJaPRAcTIcEs
    IMX/GMX 256 DKIXLLATION 2% MAINTENANCE
    FIGURE 3-6.LGC/LSC BLOCK CABLE TERMINATIONS (METHOD B)
    FEMALE AMPHENOL-TYPE CONNECTORS
    LGWLSC
    66Ml-50-TYPE BLOCK
    (PART OF 
    MDF)
    ------
    TRUNK6 17-24
    n--------
    l-2WraL-oRR
    25-PAIRCABLE TO 
    -
    MDF
    6-16
    Rm-aw
    17-24f&WV
    Page 3-14 
    						
    							INTER-TELPRACTICESIMX/GMX 256 INSTALLATION & MAINTENANCEINS-mONIssue 1, November 1994
    FIGURE 3-7.IDC BLOCK CABLE TERMINATIONS
    IDC
    np-r 1.1 -RING ---
    np -1.2 1I- 1.2 -RINB-
    INWARD
    DIALING
    CARD
    np1.8--1.8-RING--
    RIONoTusED--
    .
    R/BR--BRlR.
    Fm--I
    ~~-
    SIR--BKBLAC ENABLEBL%K.1.111.1--
    AMPHENOL-
    TYPE
    CONNECTOR
    66Ml-%-TYPE
    BLOCK
    (PART OF 
    MDF)TO
    b TELCO
    RJ
    NOTE: The AC Enable terminations shown above are used only when installing single-lines sets and play-
    back devices, not DID trunks. For information on their use, refer to the following pages.
    Page 3-15 
    						
    							IN-TIONIssue 1, November 1994INTER-TELPRACTICESIMX/GMX 256 INSTALLATION & MAINTENANCE
    FIGURE 3-8.EMC BLOCK CABLE TERMINATIONS
    E&M
    CARD
    r
    EMCH
    ,--Id IU
    l-
    AMPHENOL-TYPE
    CONNECTOR66Ml-50-TYPE
    BLOCK
    (PART OF 
    MDF)TO
    TELCO
    RJ
    TO
    TELCO
    RJ
    NOTE: Depending on the area of the country and/or the specific type of E&M trunk ordered, one or more of
    the cable pairs shown above may not always be needed. For each E&M trunk to be installed, terminate all
    cable pairs provided by the telephone company, as shown in the 
    pinout above.
    .
    Page 3-16 
    						
    All Inter-Tel manuals Comments (0)

    Related Manuals for Inter-Tel Imx/Gmx 256 Installation And Field Maintenance Manual