Home > NEC > Communications System > NEC Neax 2400 Ipx System Operations And Maintenance Manual

NEC Neax 2400 Ipx System Operations And Maintenance Manual

    Download as PDF Print this page Share this page

    Have a look at the manual NEC Neax 2400 Ipx System Operations And Maintenance Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 1168 NEC manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    Page
    of 724
    							NDA-24307 CHAPTER 5
    Page 413
    Issue 1
    FAULT REPAIR PROCEDURES
    7. CONTROL SYSTEM FAULT
    This section explains the fault repair procedure for the control system listed in Table 5-9.
    7.1 Check Point
    When repairing the control system, check the status of the following lamps:
    LN
    CPR
    GT
    TSW
    MUX
    EMA
    ISW
    CPR
    IOGT
    TSW
    HSW
    EMA
    Figure 5-1 and Figure 5-2 shows a block diagram of the control system.
    Table 5-9  Control System Fault Situation
    FAULTY SITUATION REFERENCE SECTION
    Fault occurs occasionally at the ACT side.Section 7.2, Control System Fault - Fault Occurs Intermittently
    STBY side is faulty.Section 7.3, Control System Fault - STBY Side is Faulty 
    						
    							CHAPTER 5 NDA-24307
    Page 414
    Issue 1
    FAULT REPAIR PROCEDURES
    7.2 Control System Fault - Fault Occurs Intermittently
    Faulty Situation:
    Fault occurs intermittently at ACT side in the dual configuration system.
    Fault occurs intermittently in the single configuration system.
    [0-C] ~ [0-K] CPU Failure
    [1-C] Both TSW Write Failure
    [1-D] TSW Write Failure
    [3-D], [3-E] Lock-Up Failure (Permanent/Temporary)
    (1) For Dual Configuration
    Replace ACT-side related circuit card with
    a spare, and check.
    Replace the circuit cards individually referring to the
    following sections in Chapter 4:
    LN
    Section 1.3.1, CPR Replacement Procedure
    Section 1.3.2, EMA Card Replacement
    Procedure 
    Section 2.3.1, GT Card Replacement Procedure
    Section 2.3.2, TSW Card Replacement
    Procedure
    Section 3.3.2, MUX Card Replacement
    Procedure
    ISW
    Section 1.3.1, CPR Replacement Procedure
    Section 1.3.2, EMA Card Replacement
    Procedure 
    Section 4.3.1, IOGT Card Replacement
    Procedure
    Section 4.3.2, TSW Card Replacement
    Procedure
    Section 4.3.3, HSW Card Replacement
    Procedure
    Place the replaced circuit card into ACT mode
    individually by executing CPU or Speech Path System
    changeover. Refer to 
    Section 12, Chapter 6.
    Check to see if a station-to-station connection can be
    set up and identify a circuit card responsible for the
    fault.
    After all the steps are complete, place the whole circuit
    card examined above to the ACT mode. Refer to
    Section 12, Chapter 6.
    When a fault is not indicated, set the
    faulty system to STBY mode. Refer
    to Section 12, Chapter 6.Check to see if a fault is indicated.
    ATTENTIONContents
    Static Sensitive
    Handling
    Precautions Required
    START
    A 
    						
    							NDA-24307 CHAPTER 5
    Page 415
    Issue 1
    FAULT REPAIR PROCEDURES
    (2) For Single Configuration
    Replace the related circuit card with a spare,
    and check.Replace the circuit cards individually by 
    referring to the following sections in Chapter 4:
    LN
    Section 1.3.1, CPR Replacement Procedure
    Section 1.3.2, EMA Card Replacement
    Procedure 
    Section 2.3.1, GT Card Replacement Procedure
    Section 2.3.2, TSW Card Replacement
    Procedure
    Section 3.3.2, MUX Card Replacement
    Procedure
    ISW
    Section 1.3.1, CPR Replacement Procedure
    Section 1.3.2, EMA Card Replacement
    Procedure 
    Section 4.3.1, IOGT Card Replacement
    Procedure
    Section 4.3.2, TSW Card Replacement
    Procedure
    Section 4.3.3, HSW Card Replacement
    Procedure
    Initialize the system by pressing the START
    button on the TOPU and check to see if a
    station-to-station connection can be set up and
    identify a circuit card responsible for the fault.
    AT T E N T I O NContents
    Static Sensitive
    Handling
    Precautions Required
    A
    END 
    						
    							CHAPTER 5 NDA-24307
    Page 416
    Issue 1
    FAULT REPAIR PROCEDURES
    7.3 Control System Fault - STBY Side is Faulty
    Faulty Situation:
    Fault has occurred in the STBY side of dual configuration system.
    [0-I] STBY CPU Failure
    The ACT side has become faulty, and system changeover has executed.
    [0-C], [0-H], [0-J] Processor Failure (ACT side)
    Replace STBY side related circuit cards
    with a spare, and check.Replace the circuit cards individually by 
    referring to the following paragraphs in Chapter 
    4:
    LN
    Section 1.3.1, CPR Replacement Procedure
    Section 1.3.2, EMA Card Replacement
    Procedure 
    Section 2.3.1, GT Card Replacement Procedure
    Section 2.3.2, TSW Card Replacement
    Procedure
    Section 3.3.2, MUX Card Replacement
    Procedure
    ISW
    Section 1.3.1, CPR Replacement Procedure
    Section 1.3.2, EMA Card Replacement
    Procedure 
    Section 4.3.1, IOGT Card Replacement
    Procedure
    Section 4.3.2, TSW Card Replacement
    Procedure
    Section 4.3.3, HSW Card Replacement
    Procedure
    Place the circuit cards into ACT mode by
    executing CPU changeover. Refer to Section 12,
    Chapter 6.
    Check to see if a station-to-station connection
    can be set up to identify the circuit card
    responsible for the fault.
    When a fault is not indicated, set 
    the faulty systems to STBYmode. 
    Refer to Section 12, Chapter 6.
    ATTENTIONContents
    Static Sensitive
    Handling
    Precautions Required
    START
    END 
    						
    							NDA-24307 CHAPTER 5
    Page 417
    Issue 1
    FAULT REPAIR PROCEDURES
    8. ALARM INDICATION FAULT
    This section explains the fault repair procedure where any of the faults shown in Table 5-10 occur.
    8.1 Check Point
    When repairing an alarm indication fault, check the alarm cable route shown in Figure 5-10 and Figure 5-
    11.
    8.2 Fault of Alarm Indicating Panel
    Table 5-10  Alarm Indication Fault Situation
    FAULTY SITUATION REFERENCE SECTION
    A fault is indicated on the TOPU, but it is not indicated on the Alarm Indicating Panel 
    (External Alarm Indicating Panel).Section 8.2, Fault of Alarm 
    Indicating Panel
    A system message is indicated, but no alarm indication is made on the TOPU.
    An alarm lamp on the circuit card is lighting, but no alarm indication is made on the MAT 
    or on the TOPU.Section 8.3, Fault That 
    Cannot Be Detected
    ATTENTIONContents
    Static Sensitive
    Handling
    Precautions Required
    Confirm lamps and power supply circuit of the Alarm Indicating Panel.
    Confirm cross connections on the MDF.
    Confirm that the connector of 16 PH EXMISC CA is firmly plugged in the MISC 0A connector on
    the backplane of LPM. START
    END 
    						
    							CHAPTER 5 NDA-24307
    Page 418
    Issue 1
    FAULT REPAIR PROCEDURES
    Figure 5-10   Cable Routing for Alarm Indications
    Alarm
    Indicating
    Panel
    KEYDSP
    DSPLKEY
    ALMA
    ALMB
    MISC0B
    MISC0A
    EXALM
    ALM1
    CN3CN2CN1CN0
    KEY
    (00) (04) Alarm Lamps
    TOPU
    ISWMTOPU
    ISWM
    LPM LPM
    00 0403 02 01
        MMC
    PH-M22
    To CN0 connector of LN0 To CN0 connector of LN1 To CN0 connector of LN2 To CN0 connector of LN3
    MDF68PH EXMISC CA Cable
    A
    ISW (FRONT VIEW) ISW (REAR VIEW)
    :  CHAMP connector-ended cable:  Internal alarm bus cable
    :  Connector:  Circuit CardA:  To alarm information of PWRSW, HSW, TSW, etc. - Symbols =
    EMA (PH-PC40) 
    						
    							NDA-24307 CHAPTER 5
    Page 419
    Issue 1
    FAULT REPAIR PROCEDURES
    Figure 5-11   Cabling Related to Alarm Indicating Panel
    Table 5-11  PIN Location of External Alarm
    126
    2MPALM 27
    328
    4 EXTAA 29
    530
    6 BELAA 31
    732
    8MNAA 33MNBA
    9 SUPAA 34 SUPBA
    10 MJAA 35 MJBA
    11 36
    12 37
       Alarm  
    Indicating  
        Panel
    LPM
    Backplane
    MISC0A
    BELAA
    MNAA
    SUPAA
    MJAA
    BELBA
    MNBA
    SUPBA
    MJBA
    RPT1(G)
    RPT0(-48V)
    Fuse
    -48V
    G
    MJ / MN / BELL ISW
    CHAMP Connector Cable
    MDF 68PH EXMISC CA Cable
    Power Receiving Terminal 
    						
    							CHAPTER 5 NDA-24307
    Page 420
    Issue 1
    FAULT REPAIR PROCEDURES
    Figure 5-12   Distribution/Collection of Key/Alarm Information within the System
    PZ-DK222
           (TOP KEY)
    PH-PC40 PH-M22
    EMA
    RELAY
    RECEIVER
    PZ-DK222
           (TOP KEY)
    PH-PC40 PH-M22
    EMA
    RELAY
    RECEIVER
    PZ-DK227
           (TOP KEY)
    PH-PC40 PH-M22
    EMA SEL
    RELAY
    RECEIVER
    ISEL ISW
    LN LN
    AUDIBLE
    AND
    VISUAL
    ALARM
    INDICATING
    PANEL
    KEY INFORMATION
    ALM INFORMATION
    This figure shows the flow of alarm and key information between ISW and each LN. 
    						
    							NDA-24307 CHAPTER 5
    Page 421
    Issue 1
    FAULT REPAIR PROCEDURES
    Figure 5-13   Alarm Bus Cable Connections Diagram (1/2)
    To MMC (       ) of LN3 To MMC (       ) of LN2 To MMC (       ) of LN1
    ISWM
    HSW0/1TSW0/1IOGT0/1PLO0/1PWRSW
              0/1
    ISWM
    ALMA
    ALMB
    DSPLTOPUPZ-DK227
    This figure shows the alarm bus cable connections diagram.
    IMG0 (LN0)
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 3
    ALMA
    ALMB
    DSPLKEY
    KEY
    TOPU
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 0
    ALMA
    ALMB
    EMAFHALMEMA
    CN0
    CN0
    CN0
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 1
    ALMA
    ALMB
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 2
    ALMA
    ALMB
    PZ-DK222
    IMG1 (LN0)
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 3
    ALMA
    ALMB
    DSPMTOPU
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 0
    ALMA
    ALMB
    TSWM0 (REAR VIEW)
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 1
    ALMA
    ALMB
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 2
    ALMA
    ALMB
    PZ-DK222
    PALMPWR1LANI 1ISAGT-1A
    PWR0LANI 0ISAGT-0A
    ISAGT-1B
    ISAGT-0B
    PZ-PW92
    PZ-PW92
    PALM
    00 01 02 03 04
    CN0
    KEY
    MMC
    LPM (FRONT VIEW)
    PALMPWR1LANI 1ISAGT1
    PWR0LANI 0ISAGT0
    PZ-PW92
    PZ-PW92
    PALM
    00 01 02 03 04CN3CN2CN1CN0
    KEY
    MMC
    LPM (FRONT VIEW)
    LED3
    LED2
    LED1
    ALM3
    MUSIC
    ALM2
    ALM1
    EXALMDSP
    ALMKEY
    PALM1
    MISC0B
    PALM0
    LPM (REAR VIEW)Slot 00 Slot 04LED3
    LED2
    LED1
    ALM3
    MUSIC
    ALM2
    ALM1
    EXALMDSP
    ALMKEY
    PALM1
    MISC0B
    PALM0
    LPM (REAR VIEW)Slot 00 Slot 04
                          To 
             of IMG2
    :  Alarm-related connector:  Circuit Card:  External Cable
    < ISW:  Inter-node Switch >
    MMC :  PH-M22           EMA:  PH-PC40               PWRSW:  PH-PW14           HSW:  PU-SW01           TSW:  PU-SW00           LANI:  PZ-PC19          
    ISAGT:  PZ-GT13         IOGT:  PH-GT10            PLO:  PH-CK16-A/PH-CK17-A
    < LN:  Local Node > 
    MMC:  PH-M22           EMA:  PH-PC40           ISAGT-A:  PZ-GT13           ISAGT-B:  PZ-GT20              MUX:  PH-PC36           LANI:  PZ-PC19
    EMAEMA
    EMAEMAEMA 
    						
    							CHAPTER 5 NDA-24307
    Page 422
    Issue 1
    FAULT REPAIR PROCEDURES
    Figure 5-13  Alarm Bus Cable Connections Diagram (2/2)
    LED3
    LED2
    LED1
    ALM3
    MUSIC
    ALM2
    ALM1
    EXALMDSP
    ALMKEY
    PALM1
    MISC0B
    PALM0
    LPM of LN0 (REAR VIEW)Slot 00 Slot 04
    EMA
    This figure shows the alarm bus cable connections diagram.
    :  Alarm-related connector:  Circuit Card:  External Cable
    EMA:  PH-PC40           MUX:  PH-PC36
    IMG2 (LN0)
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 3
    ALMA
    ALMB
    DSPMTOPU
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 0
    ALMA
    ALMB
    TSWM1 (REAR VIEW)
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 1
    ALMA
    ALMB
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 2
    ALMA
    ALMB
    PZ-DK222
               To  
               of IMG1
    IMG3 (LN0)
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 3
    ALMA
    ALMB
    DSPMTOPU
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 0
    ALMA
    ALMB
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 1
    ALMA
    ALMB
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 2
    ALMA
    ALMB
    PZ-DK222
    ALMEMA
    EMA 
    						
    All NEC manuals Comments (0)

    Related Manuals for NEC Neax 2400 Ipx System Operations And Maintenance Manual