NEC Neax 2400 Ipx System Operations And Maintenance Manual
Have a look at the manual NEC Neax 2400 Ipx System Operations And Maintenance Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 1168 NEC manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

NDA-24307 CHAPTER 5 Page 413 Issue 1 FAULT REPAIR PROCEDURES 7. CONTROL SYSTEM FAULT This section explains the fault repair procedure for the control system listed in Table 5-9. 7.1 Check Point When repairing the control system, check the status of the following lamps: LN CPR GT TSW MUX EMA ISW CPR IOGT TSW HSW EMA Figure 5-1 and Figure 5-2 shows a block diagram of the control system. Table 5-9 Control System Fault Situation FAULTY SITUATION REFERENCE SECTION Fault occurs occasionally at the ACT side.Section 7.2, Control System Fault - Fault Occurs Intermittently STBY side is faulty.Section 7.3, Control System Fault - STBY Side is Faulty

CHAPTER 5 NDA-24307 Page 414 Issue 1 FAULT REPAIR PROCEDURES 7.2 Control System Fault - Fault Occurs Intermittently Faulty Situation: Fault occurs intermittently at ACT side in the dual configuration system. Fault occurs intermittently in the single configuration system. [0-C] ~ [0-K] CPU Failure [1-C] Both TSW Write Failure [1-D] TSW Write Failure [3-D], [3-E] Lock-Up Failure (Permanent/Temporary) (1) For Dual Configuration Replace ACT-side related circuit card with a spare, and check. Replace the circuit cards individually referring to the following sections in Chapter 4: LN Section 1.3.1, CPR Replacement Procedure Section 1.3.2, EMA Card Replacement Procedure Section 2.3.1, GT Card Replacement Procedure Section 2.3.2, TSW Card Replacement Procedure Section 3.3.2, MUX Card Replacement Procedure ISW Section 1.3.1, CPR Replacement Procedure Section 1.3.2, EMA Card Replacement Procedure Section 4.3.1, IOGT Card Replacement Procedure Section 4.3.2, TSW Card Replacement Procedure Section 4.3.3, HSW Card Replacement Procedure Place the replaced circuit card into ACT mode individually by executing CPU or Speech Path System changeover. Refer to Section 12, Chapter 6. Check to see if a station-to-station connection can be set up and identify a circuit card responsible for the fault. After all the steps are complete, place the whole circuit card examined above to the ACT mode. Refer to Section 12, Chapter 6. When a fault is not indicated, set the faulty system to STBY mode. Refer to Section 12, Chapter 6.Check to see if a fault is indicated. ATTENTIONContents Static Sensitive Handling Precautions Required START A

NDA-24307 CHAPTER 5 Page 415 Issue 1 FAULT REPAIR PROCEDURES (2) For Single Configuration Replace the related circuit card with a spare, and check.Replace the circuit cards individually by referring to the following sections in Chapter 4: LN Section 1.3.1, CPR Replacement Procedure Section 1.3.2, EMA Card Replacement Procedure Section 2.3.1, GT Card Replacement Procedure Section 2.3.2, TSW Card Replacement Procedure Section 3.3.2, MUX Card Replacement Procedure ISW Section 1.3.1, CPR Replacement Procedure Section 1.3.2, EMA Card Replacement Procedure Section 4.3.1, IOGT Card Replacement Procedure Section 4.3.2, TSW Card Replacement Procedure Section 4.3.3, HSW Card Replacement Procedure Initialize the system by pressing the START button on the TOPU and check to see if a station-to-station connection can be set up and identify a circuit card responsible for the fault. AT T E N T I O NContents Static Sensitive Handling Precautions Required A END

CHAPTER 5 NDA-24307 Page 416 Issue 1 FAULT REPAIR PROCEDURES 7.3 Control System Fault - STBY Side is Faulty Faulty Situation: Fault has occurred in the STBY side of dual configuration system. [0-I] STBY CPU Failure The ACT side has become faulty, and system changeover has executed. [0-C], [0-H], [0-J] Processor Failure (ACT side) Replace STBY side related circuit cards with a spare, and check.Replace the circuit cards individually by referring to the following paragraphs in Chapter 4: LN Section 1.3.1, CPR Replacement Procedure Section 1.3.2, EMA Card Replacement Procedure Section 2.3.1, GT Card Replacement Procedure Section 2.3.2, TSW Card Replacement Procedure Section 3.3.2, MUX Card Replacement Procedure ISW Section 1.3.1, CPR Replacement Procedure Section 1.3.2, EMA Card Replacement Procedure Section 4.3.1, IOGT Card Replacement Procedure Section 4.3.2, TSW Card Replacement Procedure Section 4.3.3, HSW Card Replacement Procedure Place the circuit cards into ACT mode by executing CPU changeover. Refer to Section 12, Chapter 6. Check to see if a station-to-station connection can be set up to identify the circuit card responsible for the fault. When a fault is not indicated, set the faulty systems to STBYmode. Refer to Section 12, Chapter 6. ATTENTIONContents Static Sensitive Handling Precautions Required START END

NDA-24307 CHAPTER 5 Page 417 Issue 1 FAULT REPAIR PROCEDURES 8. ALARM INDICATION FAULT This section explains the fault repair procedure where any of the faults shown in Table 5-10 occur. 8.1 Check Point When repairing an alarm indication fault, check the alarm cable route shown in Figure 5-10 and Figure 5- 11. 8.2 Fault of Alarm Indicating Panel Table 5-10 Alarm Indication Fault Situation FAULTY SITUATION REFERENCE SECTION A fault is indicated on the TOPU, but it is not indicated on the Alarm Indicating Panel (External Alarm Indicating Panel).Section 8.2, Fault of Alarm Indicating Panel A system message is indicated, but no alarm indication is made on the TOPU. An alarm lamp on the circuit card is lighting, but no alarm indication is made on the MAT or on the TOPU.Section 8.3, Fault That Cannot Be Detected ATTENTIONContents Static Sensitive Handling Precautions Required Confirm lamps and power supply circuit of the Alarm Indicating Panel. Confirm cross connections on the MDF. Confirm that the connector of 16 PH EXMISC CA is firmly plugged in the MISC 0A connector on the backplane of LPM. START END

CHAPTER 5 NDA-24307 Page 418 Issue 1 FAULT REPAIR PROCEDURES Figure 5-10 Cable Routing for Alarm Indications Alarm Indicating Panel KEYDSP DSPLKEY ALMA ALMB MISC0B MISC0A EXALM ALM1 CN3CN2CN1CN0 KEY (00) (04) Alarm Lamps TOPU ISWMTOPU ISWM LPM LPM 00 0403 02 01 MMC PH-M22 To CN0 connector of LN0 To CN0 connector of LN1 To CN0 connector of LN2 To CN0 connector of LN3 MDF68PH EXMISC CA Cable A ISW (FRONT VIEW) ISW (REAR VIEW) : CHAMP connector-ended cable: Internal alarm bus cable : Connector: Circuit CardA: To alarm information of PWRSW, HSW, TSW, etc. - Symbols = EMA (PH-PC40)

NDA-24307 CHAPTER 5 Page 419 Issue 1 FAULT REPAIR PROCEDURES Figure 5-11 Cabling Related to Alarm Indicating Panel Table 5-11 PIN Location of External Alarm 126 2MPALM 27 328 4 EXTAA 29 530 6 BELAA 31 732 8MNAA 33MNBA 9 SUPAA 34 SUPBA 10 MJAA 35 MJBA 11 36 12 37 Alarm Indicating Panel LPM Backplane MISC0A BELAA MNAA SUPAA MJAA BELBA MNBA SUPBA MJBA RPT1(G) RPT0(-48V) Fuse -48V G MJ / MN / BELL ISW CHAMP Connector Cable MDF 68PH EXMISC CA Cable Power Receiving Terminal

CHAPTER 5 NDA-24307 Page 420 Issue 1 FAULT REPAIR PROCEDURES Figure 5-12 Distribution/Collection of Key/Alarm Information within the System PZ-DK222 (TOP KEY) PH-PC40 PH-M22 EMA RELAY RECEIVER PZ-DK222 (TOP KEY) PH-PC40 PH-M22 EMA RELAY RECEIVER PZ-DK227 (TOP KEY) PH-PC40 PH-M22 EMA SEL RELAY RECEIVER ISEL ISW LN LN AUDIBLE AND VISUAL ALARM INDICATING PANEL KEY INFORMATION ALM INFORMATION This figure shows the flow of alarm and key information between ISW and each LN.

NDA-24307 CHAPTER 5 Page 421 Issue 1 FAULT REPAIR PROCEDURES Figure 5-13 Alarm Bus Cable Connections Diagram (1/2) To MMC ( ) of LN3 To MMC ( ) of LN2 To MMC ( ) of LN1 ISWM HSW0/1TSW0/1IOGT0/1PLO0/1PWRSW 0/1 ISWM ALMA ALMB DSPLTOPUPZ-DK227 This figure shows the alarm bus cable connections diagram. IMG0 (LN0) MUX 0LC/TRKMUX 1PWR DPWR PIM 3 ALMA ALMB DSPLKEY KEY TOPU MUX 0LC/TRKMUX 1PWR DPWR PIM 0 ALMA ALMB EMAFHALMEMA CN0 CN0 CN0 MUX 0LC/TRKMUX 1PWR DPWR PIM 1 ALMA ALMB MUX 0LC/TRKMUX 1PWR DPWR PIM 2 ALMA ALMB PZ-DK222 IMG1 (LN0) MUX 0LC/TRKMUX 1PWR DPWR PIM 3 ALMA ALMB DSPMTOPU MUX 0LC/TRKMUX 1PWR DPWR PIM 0 ALMA ALMB TSWM0 (REAR VIEW) MUX 0LC/TRKMUX 1PWR DPWR PIM 1 ALMA ALMB MUX 0LC/TRKMUX 1PWR DPWR PIM 2 ALMA ALMB PZ-DK222 PALMPWR1LANI 1ISAGT-1A PWR0LANI 0ISAGT-0A ISAGT-1B ISAGT-0B PZ-PW92 PZ-PW92 PALM 00 01 02 03 04 CN0 KEY MMC LPM (FRONT VIEW) PALMPWR1LANI 1ISAGT1 PWR0LANI 0ISAGT0 PZ-PW92 PZ-PW92 PALM 00 01 02 03 04CN3CN2CN1CN0 KEY MMC LPM (FRONT VIEW) LED3 LED2 LED1 ALM3 MUSIC ALM2 ALM1 EXALMDSP ALMKEY PALM1 MISC0B PALM0 LPM (REAR VIEW)Slot 00 Slot 04LED3 LED2 LED1 ALM3 MUSIC ALM2 ALM1 EXALMDSP ALMKEY PALM1 MISC0B PALM0 LPM (REAR VIEW)Slot 00 Slot 04 To of IMG2 : Alarm-related connector: Circuit Card: External Cable < ISW: Inter-node Switch > MMC : PH-M22 EMA: PH-PC40 PWRSW: PH-PW14 HSW: PU-SW01 TSW: PU-SW00 LANI: PZ-PC19 ISAGT: PZ-GT13 IOGT: PH-GT10 PLO: PH-CK16-A/PH-CK17-A < LN: Local Node > MMC: PH-M22 EMA: PH-PC40 ISAGT-A: PZ-GT13 ISAGT-B: PZ-GT20 MUX: PH-PC36 LANI: PZ-PC19 EMAEMA EMAEMAEMA

CHAPTER 5 NDA-24307 Page 422 Issue 1 FAULT REPAIR PROCEDURES Figure 5-13 Alarm Bus Cable Connections Diagram (2/2) LED3 LED2 LED1 ALM3 MUSIC ALM2 ALM1 EXALMDSP ALMKEY PALM1 MISC0B PALM0 LPM of LN0 (REAR VIEW)Slot 00 Slot 04 EMA This figure shows the alarm bus cable connections diagram. : Alarm-related connector: Circuit Card: External Cable EMA: PH-PC40 MUX: PH-PC36 IMG2 (LN0) MUX 0LC/TRKMUX 1PWR DPWR PIM 3 ALMA ALMB DSPMTOPU MUX 0LC/TRKMUX 1PWR DPWR PIM 0 ALMA ALMB TSWM1 (REAR VIEW) MUX 0LC/TRKMUX 1PWR DPWR PIM 1 ALMA ALMB MUX 0LC/TRKMUX 1PWR DPWR PIM 2 ALMA ALMB PZ-DK222 To of IMG1 IMG3 (LN0) MUX 0LC/TRKMUX 1PWR DPWR PIM 3 ALMA ALMB DSPMTOPU MUX 0LC/TRKMUX 1PWR DPWR PIM 0 ALMA ALMB MUX 0LC/TRKMUX 1PWR DPWR PIM 1 ALMA ALMB MUX 0LC/TRKMUX 1PWR DPWR PIM 2 ALMA ALMB PZ-DK222 ALMEMA EMA