Home > NEC > Communications System > NEC Neax 2400 Ipx System Operations And Maintenance Manual

NEC Neax 2400 Ipx System Operations And Maintenance Manual

    Download as PDF Print this page Share this page

    Have a look at the manual NEC Neax 2400 Ipx System Operations And Maintenance Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 1168 NEC manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    Page
    of 724
    							NDA-24307 CHAPTER 5
    Page 403
    Issue 1
    FAULT REPAIR PROCEDURES
    (2) For Single Configuration
    Check to see if the fault occurs by
    replacing TSW circuit cards one by one.Replace the TSW circuit card referring to
    Section 2.3.2, TSW Card Replacement
    Procedure, Chapter 4.
    Check to see if a station-to-station connection
    can be set up and identify a TSW circuit card
    responsible for the fault.
    Perform the above check by extracting the TSW
    circuit cards individually.
    Check to see if the fault occurs by
    replacing MUX circuit cards one by one.Replace the MUX circuit card referring to
    Section 3.3.2, MUX Card Replacement
    Procedure, Chapter 4.
    Initialize the system by pressing the START
    button on the TOPU.
    Check to see if a station-to-station connection
    can be set up and identify a TSW circuit card
    responsible for the fault.
    Perform the above check by extracting the TSW
    circuit cards individually.
    ATTENTIONContents
    Static Sensitive
    Handling
    Precautions Required
    START
    A 
    						
    							CHAPTER 5 NDA-24307
    Page 404
    Issue 1
    FAULT REPAIR PROCEDURES
    When the PLO (PH-CK16-A/17-A)/CLK
    (PH-CK18) circuit card is mounted for
    digital interface, replace the PLO circuit
    card with a spare and check it.Set MB switch of the PLO/CLK circuit card
    to UP side.
    Confirm OPE lamp on the PLO/CLK circuit
    card goes out.
    Extract PLO/CLK circuit card from its
    mounting slot.
    Set MB switch UP and insert the new PLO/
    CLK circuit card into its mounting slot.
    Set MB switch DOWN.
    Confirm the OPE lamp on the new PLO/CLK
    circuit card illuminates.
    Confirm that speech can be carried out
    normally by a station-to-station call.
    ATTENTIONContents
    Static Sensitive
    Handling
    Precautions Required
    A
    END 
    						
    							NDA-24307 CHAPTER 5
    Page 405
    Issue 1
    FAULT REPAIR PROCEDURES
    5.3 Speech Path System Fault - When Dial Tone (DT) Cannot Be Heard
    Faulty Situation:
    Dial Tone (DT) cannot be heard.
    [1-A] Both TSW Failure (Permanent)
    [1-E] Both TSW Clock Failure
    [4-C] Both TSW Ready Failure
    [23-Y] MUX Clock Failure
    Note:For dual system configuration, if a system message indicates that both systems are faulty, first repair
    the fault in the indicated system and then proceed to repair the PIM in the other system.
    Check to see if the TSW circuit card is
    making poor contact.Set TSW circuit card into STBY mode. Refer to
    Section 12, Chapter 6.
    Set TSW MBR switch on the TSW card UP.
    Set MB switch of the TSW circuit card UP.
    Extract the TSW circuit card from its mounting
    slot and clean the contact portion.
    If cleaning cannot be done, repeat insertion and
    extraction of the circuit card two or three times.
    Set TSW MBR and MB switches on the TSW
    circuit card UP and insert the circuit card into
    its mounting slot.
    Set MB switch of the TSW circuit card DOWN.
    Set TSW MBR switch DOWN.
    Check if a station-to-station connection can be
    set up.
    Check PCM cables. Check the PCM cables. (See Figure 5-8).
    Initialize the system by pressing the START
    button on the TOPU and see if a station-to-sta-
    tion connection can be set up.
    ATTENTIONContents
    Static Sensitive
    Handling
    Precautions Required
    START
    END 
    						
    							CHAPTER 5 NDA-24307
    Page 406
    Issue 1
    FAULT REPAIR PROCEDURES
    5.4 Speech Path System Fault (LN) - STBY Side Has Become Faulty
    Faulty Situation:
    A fault occurred in the STBY side of the dual configuration system.
    [1-B] TSW Failure (Permanent)
    [1-D] TSW Write Failure
    [1-F] TSW Clock Failure
    [4-D] TSW Ready Failure
    Check to see if the TSW circuit card
    (STBY) is making poor contact.Set the TSW MBR switch of the TSW circuit
    card UP.
    Set the MB switch of the TSW circuit card UP
    and extract the circuit card from its mounting
    slot.
    Extract the TSW circuit card from its mounting
    slot and clean the contact portion.
    If cleaning cannot be done, repeat insertion and
    extraction of the circuit card two or three times.
    Set the TSW MBR and MB switches of the
    TSW circuit card UP and insert the circuit card
    into its mounting slot.
    Set the MB switch of the TSW circuit card
    DOWN.
    Set the TSW MBR switch DOWN.
    Check if a station-to-station connection can be
    set up.
    Check PCM cables. Check the PCM cables. See Figure 5-8.
    Initialize the system by pressing the START
    button on the TOPU and see if a station-to-
    station connection can be set up.
    ATTENTIONContents
    Static Sensitive
    Handling
    Precautions Required
    START
    A 
    						
    							NDA-24307 CHAPTER 5
    Page 407
    Issue 1
    FAULT REPAIR PROCEDURES
    Faulty Situation:
    Fault related to speech such as noise, one-way speech, no-speed, etc. occurs.
    Even if dialing started, Dial Tone (DT) does not stop.
    [1-C] Both TSW Write Failure
    [1-D] TSW Write Failure
    Check to see if fault occurs by extracting
    TSW circuit cards one by one.Replace the TSW circuit card referring to
    Section 2.3.2, TSW Card Replacement
    Procedure, Chapter 4.
    Set the TSW circuit card into ACT mode. Refer
    to Section 12, Chapter 6.
    Check to see if a station-to-station connection
    can be set up to identify a TSW circuit card re-
    sponsible for the fault.
    Perform the above check by extracting the TSW
    circuit cards individually.
    Check to see if the fault occurs by
    extracting MUX circuit cards one by one.Replace the MUX circuit card referring to
    Section 3.3.2, MUX Card Replacement
    Procedure, Chapter 4.
    Set the MUX circuit card into ACT mode. Refer
    to Perform the above check by extracting the
    TSW circuit cards individually.
    Check to see if a station-to-station connection
    can be set up and identify a TSW circuit card
    responsible for the fault.
    Perform the above check by extracting the
    MUX circuit cards individually.
    ATTENTIONContents
    Static Sensitive
    Handling
    Precautions Required
    A
    END 
    						
    							CHAPTER 5 NDA-24307
    Page 408
    Issue 1
    FAULT REPAIR PROCEDURES
    6. SPEECH PATH SYSTEM FAULT (WHOLE SYSTEM/ISW)
    This section explains the fault repair procedure when any of the fault shown in Table 5-8 has occurred in a
    whole system.
    6.1 Check Point
    System messages pertaining to whole system fault are shown in Figure 5-9. Check the system messages.
    Figure 5-9   System Messages Related to Speech Path System Fault (Whole System/ISW)Table 5-8  Speech Path (TSW) System Fault Situation (LN)
    FAULTY SITUATION REFERENCE SECTION
    Noise, one-way speech, no tone
    Even after dialing a digit, dial tone is still heard.
    Dial tone cannot be heard.Section 6.2, Speech Path System Fault (Whole 
    System/ISW) - Fault Related to Speech
    The system message that indicates a fault occurrence to the active 
    Speech Path System (Whole System /ISW) is intermittently printed 
    out.
    The alarm lamp on the circuit card of the active Speech Path System 
    (Whole System /ISW) lights up intermittently.Section 6.3, Speech Path System Fault (Whole 
    System/ISW) - ACT side becomes Faulty 
    Intermittently
    The system message that indicates a fault occurrence to the STBY 
    Speech Path System (Whole System /ISW) is intermittently printed 
    out.
    The alarm lamp on the circuit card of the STBY Speech Path 
    System (Whole System /ISW) lights up intermittently.Section 6.4, Speech Path System Fault (Whole 
    System/ISW) - STBY side becomes Faulty 
    Intermittently
    Clock (CALK, PLOT) is faulty.
    CPUTSW
    PLO/CLK
    HSW
    “1-G” ~ “1-J”HSW Write Failure
    “1-K” ~ “1-L”HSW Clock Failure
    “4-E” ~ “4-F”HSW Ready Failure
    “1-A” ~ “1-D”TSW Write Failure
    “1-E” ~ “1-F”TSW Clock Failure
    “4-C” ~ “4-D”TSW Ready Failure
    “1-O” ~ “1-P”PLO Clock Failure 
    						
    							NDA-24307 CHAPTER 5
    Page 409
    Issue 1
    FAULT REPAIR PROCEDURES
    6.2 Speech Path System Fault (Whole System/ISW) - Fault Related to Speech
    Replace the TSW card mounted in the 
    ISWM with a spare.Replace the TSW card by referring to Section 
    4.3.2, TSW Card Replacement Procedure, 
    Chapter 4.
    Place the TSW circuit card on the ACT mode.
    Refer to Section 12, Chapter 6.
    After replacement of the TSW card, 
    make a station to station call and 
    check and see if a fault occurs.
    When a fault occurs in the whole system, 
    replace the HSW card with a spare.Replace the HSW card by referring to Section 
    4.3.3, HSW Card Replacement Procedure, 
    Chapter 4.
    Place the HSW card on the ACT mode. 
    Refer to Section 12, Chapter 6.
    After replacement of the HSW card, 
    make a station to station call, and 
    check and see if a fault occurs.
    AT T E N T I O NContents
    Static Sensitive
    Handling
    Precautions Required
    START
    END 
    						
    							CHAPTER 5 NDA-24307
    Page 410
    Issue 1
    FAULT REPAIR PROCEDURES
    6.3 Speech Path System Fault (Whole System/ISW) - ACT side becomes Faulty 
    Intermittently
    Check by replacing related circuit cards of 
    the ACT mode with a spare.Related circuit cards: 
    IOGT (Section 4.3.1, Chapter 4)
    TSW (Section 4.3.2, Chapter 4)
    HSW (Section 4.3.3, Chapter 4)
    Set the faulty system on the STBY mode.
    Refer to Section 12, Chapter 6.
    On the circuit card, set its MB switch UP and 
    extract the circuit card out of its mounting slot.
    Make switch setting on the new circuit card.
    On the new circuit card, set its MB switch UP 
    and insert the circuit card into its mounting slot.
    Set MB switch DOWN.
    If a fault occurs, set the faulty system on the 
    STBY mode. Refer to Section 12, Chapter 
    6.Set the faulty system on the ACT mode.
    Refer to Section 12, Chapter 6.
    Check and see if a fault indication is made. Faulty Situation:
    ACT-side Speech Path System becomes faulty intermittently in ISW/Whole System.
    [1-I] HSW Write Temporary Failure (Both Systems)
    [1-J] HSW Write Temporary Failure (One System)
    ATTENTIONContents
    Static Sensitive
    Handling
    Precautions Required
    START
    END 
    						
    							NDA-24307 CHAPTER 5
    Page 411
    Issue 1
    FAULT REPAIR PROCEDURES
    6.4 Speech Path System Fault (Whole System/ISW) - STBY side becomes Faulty 
    Intermittently
    Check by replacing related circuit cards of 
    the STBYmode with a spare.Related circuit cards: 
    IOGT (Section 4.3.1, Chapter 4)
    TSW (Section 4.3.2, Chapter 4)
    HSW (Section 4.3.3, Chapter 4)
    Set the faulty system on the STBY mode.
    Refer to Section 12, Chapter 6.
    On the circuit card, set its MB switch UP and 
    extract the circuit card out of its mounting slot.
    Make switch setting on the new circuit card.
    On the new circuit card, set its MB switch UP 
    and insert the circuit card into its mounting slot.
    Set MB switch DOWN.
    If a fault occurs, set the faulty system on the 
    STBY mode. Refer to Section 12, Chapter 
    6.Set the faulty system on the ACT mode.
    Refer to Section 12, Chapter 6.
    Check and see if a fault indication is made. Faulty Situation:
    STBY-side Speech Path System becomes faulty intermittently in ISW/Whole System.
    [1-I] HSW Write Temporary Failure (Both Systems)
    ATTENTIONContents
    Static Sensitive
    Handling
    Precautions Required
    START
    END 
    						
    							CHAPTER 5 NDA-24307
    Page 412
    Issue 1
    FAULT REPAIR PROCEDURES
    6.5 PLO Fault
    Replace the faulty PLO circuit card with a 
    spare.Set MB switch of the PLO circuit card UP and 
    extract the circuit card from its mounting slot.
    Make necessary switch settings on the new PLO 
    circuit card.
    Set MB switch UP and insert the circuit card 
    into its mounting slot.
    Set MB switch DOWN.
    Confirm that no noise generates in a station- 
    to-station connection.If the system has been operated by the STBY 
    side, set MB switch on the ACT-side PLO 
    circuit card UP and execute system changeover.
    Refer to Section 12, Chapter 6.
    OPE lamp (Green) illuminates on the PLO 
    circuit card.
    Confirm that digital interface connection can 
    be set up. Faulty Situation:
    Both PLOs have become faulty, and the system is in operation by clocks from the
    HSW.
    One of the two PLOs has become faulty and the other PLO has been set on the ACT
    mode.
    [1-O], [1-P] PLO Clock Failure
    [1-K], [1-L] HSW Clock Failure
    ATTENTIONContents
    Static Sensitive
    Handling
    Precautions Required
    START
    END 
    						
    All NEC manuals Comments (0)

    Related Manuals for NEC Neax 2400 Ipx System Operations And Maintenance Manual