Home > NEC > Communications System > NEC Neax 2400 Imx System Operations And Maintenance Manual

NEC Neax 2400 Imx System Operations And Maintenance Manual

    Download as PDF Print this page Share this page

    Have a look at the manual NEC Neax 2400 Imx System Operations And Maintenance Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 1168 NEC manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    Page
    of 647
    							CHAPTER 7 NDA-24238
    Page 504
    Revision 3.0
    ROUTINE MAINTENANCE PROCEDURE
    2.7 Alarm Tests
    An alarm is to be generated which will be displayed at the DESKCON/ATTCON. Be sure to inform 
    the attendant of the test in advance.
    Replace the –48V fuse in the FANU with a blown fuse.
    Confirm that an alarm is indicated on the TOPU.
    Replace the blown fuse with the original –48V fuse.
    Using the RALM command, reset all alarm indications.
    START
    END 
    						
    							NDA-24238 CHAPTER 7
    Page 505
    Revision 3.0
    ROUTINE MAINTENANCE PROCEDURE
    2.8 Main Power System Check
    Note:For a longer battery life, observe the following items:
    Place the batteries in a dark, cool place.
    Keep the room temperature within the range of 10°C to 35°C (40°F to 85°F).
    Floating voltage must be kept within the range of the battery specification at all times.
    After discharging, perform equalized charging as per the battery specification. Check the load voltage (DC –48V ±5 V) of the rectifier.
    Check the batteries. Check the forced-charge voltage and floating 
    voltage.
    Check the specific gravity, liquid level and 
    rated capacity of each battery.
    START
    END 
    						
    							CHAPTER 7 NDA-24238
    Page 506
    Revision 3.0
    ROUTINE MAINTENANCE PROCEDURE
    2.9 Trunk RGU Check
    Check alarm lamps on the line/trunk circuit cards.
    Check to see if a system message pertaining to a circuit card has been output.
    Check the speech path for each PIM and also check ringing signal.
    START
    END 
    						
    							NDA-24238 CHAPTER 7
    Page 507
    Revision 3.0
    ROUTINE MAINTENANCE PROCEDURE
    2.10 ATTCON/DESKCON Check
    (1) Attendant Console Check
    Note:Adjusting Time Method (see Figure 7-2.)
    If the Hour (H) button is pushed once, the time will advance one hour. (To push the button, use a thin
    object, such as a toothpick.)
    If the H button is held continuously, the time will advance one hour each second.
    If the Minute (M) button is pushed once, the time will advance one minute.
    If the M button is held continuously, the time will advance one minute each second.
    Figure 7-2   Adjusting Time on ATTCON
    Ask the operator at each ATTCON if the ATTCON is operating normally.
    Each operator presses the LCHK button on the ATTCON and confirms that all the lamps on the 
    control panel light up.
    When the ATTCON is equipped with a Time Indicator Section, the operator also checks the displayed 
    time.
    START
    END
    STATION/TRUNK NUMBER AM
    PM
    TIMEADJUST.
    HM 
    						
    							CHAPTER 7 NDA-24238
    Page 508
    Revision 3.0
    ROUTINE MAINTENANCE PROCEDURE
    (2) Desk Console Check
    Note 1:The lamp checks can be suspended any time when the * key on the control panel is pressed.
    Note 2:The DESKCON obtains time information only from the PBX side. Therefore, adjust the time and date
    using the MAT command.
    Figure 7-3   Desk Console
    Ask the operator at each DESKCON if the DESKCON is operating normally.
    On the DESKCON control panel, each operator presses the L3, SRC, and Release keys simultaneously 
    and confirms that all the lamps on the control panel light red.
    Operator presses the # key and confirms that all the lamps on the same transverse line between the 
    EMG and Mute lamps light green. Refer to Figure 7-3.
    Operator presses the # key and confirms that all the green lamps (in the step above) go OFF and the 
    LCD on the DESKCON displays black.
    Operator presses the # key and confirms the black LCD display is cleared and a ringing tone is heard.
    Operator presses the # key and confirms the provided ringing tone has suspended.
    Operator presses the keys on the DESKCON one by one and confirms that each lamp, corresponding 
    to the pressed key, emits a light and the name of the key displays on the LCD, respectively.
    Operator presses the * button and completes the lamp checks. 
    Note 1
    Operator checks the displayed time on the right part of LCD. Note 2
    START
    END
    HoldRelease
    L6L5L4L3L2L1
    
    0 896 3
    5 2
    1
    4
    7
    #
    SRCDESTTalk Cancel
    Answer
    BUSYLDN Alarm Position
    AvailablePosition
    BusyNightATNDNANSRECALLPAGETIE
    TRKSL EMG Call Park SC SVC StartREC
    Mute BV
    3:25 PM WED 1 
    						
    							NDA-24238 CHAPTER 7
    Page 509
    Revision 3.0
    ROUTINE MAINTENANCE PROCEDURE
    2.11 System Check
    Check the OPE lamps (green) on all circuit cards.
    Check whether a system message pertaining to the CPU/TSW has been output.
    Check speech conditions by establishing a station-to-station connection at each PIM.
    If the condition is abnormal, determine the nature of the problem (dial tone cannot be heard, 
    no speech can be established, etc.)
    Does the condition occur in No. 0 TSW or in No. 1 TSW?
    Does the condition occur in No. 0 CPU or in No. 1 CPU?
    Using MEM_HDD command, check the data memory.
    START
    END 
    						
    							CHAPTER 7 NDA-24238
    Page 510
    Revision 3.0
    ROUTINE MAINTENANCE PROCEDURE
    3. ROUTINE MAINTENANCE CHECK LISTS
    This section provides check lists (Maintenance Procedure Reports) to be used when performing routine main-
    tenance. The Routine Maintenance Check Lists consists of the following items:
     Maintenance Procedure Report
     C.O. Trunk/Tie Line
     Register/Sender Trunk (RST)
     Digital Conference Function
     Speech Path for each PIM, and Ringing Generator Unit
     Attendant/Desk Console 
    						
    							NDA-24238 CHAPTER 7
    Page 511
    Revision 3.0
    ROUTINE MAINTENANCE PROCEDURE
    USER NAMESIGNATURE OF 
    SUPERVISORWORK TIME
    (FROM -  )
    Name of User (Company) Date: Maintenance
    ClassificationRoutine/Non-
    routine
    Control No. Maintenance
    Company
    Name of Equipment Room Temperature - °C 
    °F & humidity %Name of Worker
    Reference 
    SectionItem Detail Check Reference 
    SectionItem Detail Check
    2.1Check of Ambient 
    Conditions in the 
    Switch RoomAmbient 
    Temperature2.9Trunk RGU Check SND Trunk
    Relative humidity DCF Function
    2.2Alarm Check TOPU Tone
    2.3MAT/Printer Check MAT MAT
    Printer2.10ATTCON Check Ringing Signal
    2.4Collection of 
    System MessagesRelated to Fault2.11System Check
    Result of Routine 
    DiagnosisCPU
    2.5Display of Locked- 
    out StationLocked out 
    StationsTSW
    2.6Fan Unit Check
    PM
    2.7Alarm Tests TOPU
    2.8Main Power 
    System CheckRectifier
    Battery
    2.9Trunk RGU Check C.O. Trunk
    Tie Trunk
    ORT
    IRT
    Condition And Cause
    Procedure and Parts Used 
    						
    							CHAPTER 7 NDA-24238
    Page 512
    Revision 3.0
    ROUTINE MAINTENANCE PROCEDURE
    C.O. Trunk/Tie Line
    TEST TYPE TEST ITEM CONNECTION DIAGRAM
    C.O. Trunk/Tie Line 
    Speech Path Test Set up a speech path test by
    seizing a trunk using the 
    Station or ATTCON/DESKCON 
    connection test diagrammed to
    the right. Connection Test-Station 
     Connection Test-ATTCON/DESKCON
    C.O. Trunk/Tie Line
    NAME OF TRUNK ROUTEACCESS 
    NUMBERROUTE 
    NUMBERTRUNK 
    NUMBERCHECK REMARKS
    LCTRK
    C.O./Tie
    Line
    ATITRK
    C.O./Tie
    Line
    ATTCON/
    DESKCON 
    						
    							NDA-24238 CHAPTER 7
    Page 513
    Revision 3.0
    ROUTINE MAINTENANCE PROCEDURE
    Register/Sender Trunk (RST)
    TEST TYPE TEST ITEM CONNECTION DIAGRAM
    ORT Function   Perform the test by specifying 
    an ORT using the Connection 
    Test-Station.
     Confirm that [6-I] system 
    message displays as a result of 
    the test.DP/PB
    SENDER Function   Perform the test by specifying 
    an ORT using the Connection 
    Test-Station. 
     Confirm that [6-I] system 
    message displays as a result of 
    the test.
    LC
    ORT
    LC~
    SND
    ORT 
    						
    All NEC manuals Comments (0)

    Related Manuals for NEC Neax 2400 Imx System Operations And Maintenance Manual