Home > NEC > Communications System > NEC Neax 2400 Imx System Operations And Maintenance Manual

NEC Neax 2400 Imx System Operations And Maintenance Manual

    Download as PDF Print this page Share this page

    Have a look at the manual NEC Neax 2400 Imx System Operations And Maintenance Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 1168 NEC manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    Page
    of 647
    							CHAPTER 4 NDA-24238
    Page 304
    Revision 3.0
    UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE
    6. Fuse Replacement
    The system uses the fuses shown in Figure 4-28 as a protection against an overload resulting from a short cir-
    cuit.
    Figure 4-28   Fuses Used by System
    When excessive current is applied to a PWR circuit card, the related fuse is blown. The blown fuse after a fault
    can be confirmed as shown in Figure 4-29.
    Figure 4-29   Blown Fault Example
    The purpose of fuses is to let them blow before the components are damaged. If any fuse gets blown, replace
    it immediately with a new one using the following procedure:
    (1) Confirm the blown fuse via the system message [6-A] or MJ lamp on the top of IMG0.
    (2) Replace the fuse with a new one, referring to Figure 4-30 and Figure 4-31.
    (3) Determine the cause of the blown fault, referring to Figure 4-32 (case of RGU fuse) or Figure 4-33 (DC-
    48V fuse.)
    1.5A
    12.5V25A
    If a fuse is blown, 
    this area turns white.
    A normal fuse A blown fuse 
    						
    							NDA-24238 CHAPTER 4
    Page 305
    Revision 3.0
    UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE
    Figure 4-30 shows the location of fuses within the system. In Chapter 4-30, the fuses are indicated by   or  .
    Figure 4-30   Fuse Locations Within System
    NECNEAX 2400 IMS
    PZ-M377
    3.2A 5.0A
    PZ-M3695.0A
    ..... .....
    ..... .....
    PZ-PW92
    5.0A 25A
    25A
    5.0A0.5A
    PA-PW54
    PA-PW555.0A
    0.5A
    25A
    PBX [Front View] 
    						
    							CHAPTER 4 NDA-24238
    Page 306
    Revision 3.0
    UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE
    In the TSWM, the fuse shown in Figure 4-31 is used for the PWR SW (PH-PW14) card, which is housed in
    Slot No. 00 and/or 01.
    Figure 4-31   Fuse Location Within TSWM
     PH-PW14
    (PWR SW)
    FUSE:    15A
    TSWM
    PBX (IMG1)
    Front View
    
     
    						
    							NDA-24238 CHAPTER 4
    Page 307
    Revision 3.0
    UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE
    Perform the procedure in Figure 4-32 to confirm the cause of the RGU fuse blown fault.
    Figure 4-32   RGU Fuse Blown Fault Flowchart
    
    Start
    Visual check: No pin contacting
     or backboard melting?
    OPE  Lamp (green) of 
    each LC card  remains lit?
    Replace the blown fuse with a new
    one. The fuse is blown again?Yes
    Yes
    Yes
    Yes YesNo
    1.  Turn ON (UP) the MB key
         on the LC card.
    2.  Remove the card from the PIM.
    3.  Replace the fuse with a new one.
     Turn ON (UP) the MB
     keys on all LC cards,
    and  remove them from the
    PIM. (Only PWR cards are
    inside the PIM)
    Turn ON (UP) the MB
    keys on the whole LC cards,
    and  remove them from the
    PIM. (Only PWR cards are
    inside the PIM)
    The replaced fuse
     is blown again?
    
    Perform station-to-station 
    connections within the PIM.
    Is any fuse blown?
    
    Perform station-to-station 
    connections within the PIM.
    Is any fuse blown?No
    No No No No
    No
    Yes
    YesNo
    
    Fault in LC card that accompanied
    the fuse blowing.
    
    Fault of LC card that accompanied 
    the fuse blowing.
    
    Probable Cause: Not  confirmed.
    Needs further observation of the fault
    
    There is a short circuit
    on the backboard of the PIM.
    
    Fault in LC card that accompanied 
    the fuse blowing.
    
    Fault of PWR card.
    
    Perform system initialization
    after inserting all removed cards.
    
    Fault of LC card
    that was removed
    Replace the blown fuse
    with a new one.
    Replace the blown fuse
    with a new one.
    Replace the PWR card
    Yes
    Insert the removed cards
    one by one (into the PIM).
    Is any fuse blown?
    The replaced fuse is 
    blown again?
     Fuse is still blown? NoYes
    
     
    The replaced  fuse
     is blown again? 
    						
    							CHAPTER 4 NDA-24238
    Page 308
    Revision 3.0
    UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE
    Perform the procedure in Figure 4-33 to confirm the cause of the DC-48V fuse blown fault.
    Figure 4-33   DC -48V Fuse Blown Fault Flowchart
    Start
    Visual check: No pin contacting
     or backboard melting?
    OPE  Lamps (green) of 
    LC/TRK/NCU cards remain lit?
    Make sure in which module 
    the fuse has blownNo
    1.  Turn ON (UP) the MB key
         on the circuit card.
    2.  Remove the card from the PIM.
    3.  Replace the fuse with a new one.
    Turn ON (UP) the MB
    keys on the whole circuit
    cards, and remove them from
    the PIM. (Only PWR cards
    are inside the PIM)
    Turn ON (UP) the MB
    keys on the whole circuit 
    cards, and remove them from
    the PIM. (Only PWR cards 
    are inside the PIM)
    The replaced  fuse
     is blown again?No
    No
    No No
    
    Fault of  circuit card that
    accompanied the fuse blown.
    Perform system initialization
    after inserting all removed cards.
    
    Fault of circuit card
    that was removed
    Replace the blown fuse
    with a new one.
    Replace the blown fuse
    with a new one.Yes
    Yes
     Yes
    Insert the removed cards 
    one by one  (into the PIM).
    Is there any fuse blowing?
    The replaced  fuse
    is blown again?
    The fuse is still blown?
    
    
    There is a short circuit on the 
    backboard of the PIM.
    
    Fault of PWR card.
    Replace the PWR cardYes
    YesLPM / TSWM / PIM
    No
    
    Fault of circuit card that
    accompanied the fuse blown.
    
    Perform system initialization
    after inserting all removed cards. Yes
    Insert the removed cards 
    one by one  (into the PIM).
    Is any fuse blown?
    
     
    						
    							NDA-24238 CHAPTER 5
    Page 309
    Revision 3.0
    FAULT REPAIR PROCEDURES
    CHAPTER 5 FAULT REPAIR PROCEDURES
    This chapter provides information on how to repair the fault(s) within the system. If any of the components or
    equipment listed in Table 5-1 has a failure, move on to the repair procedure explained for each faulty condition.
    Table 5-1  Fault Repair Procedure Quick Reference
    FAULTY ITEM FAULTY SITUATION REFERENCE SECTION
    Line Fault DP/PB Telephone Dial tone is not heard.Section 1.3, Line Fault - When Dial 
    Tone (DT) Cannot Be Heard
    Dialing results in a wrong 
    connection.Section 1.4, Line Fault - When 
    Dialing Results in Wrong 
    Connection
    Bell does not ring.Section 1.5, Line Fault - When Bell 
    Does Not Ring
    Answer/speech cannot be 
    made.Section 1.6, When Call Cannot Be 
    Answered and Speech Cannot Be 
    Made
    D
    termDterm cannot be operated.
     Operations are abnormal.Section 1.7, Dterm Fault
    Trunk Fault  No connections can be set up.
     PB/DP signals are erroneously received or set out 
    from ORT/SND.
     No three-way calling can be made on CFT, or noise 
    gets in a established connection.
     A connection results in no speech.
     Noise gets in a established connection.Section 2.3, Trunk (ORT, SND, 
    CFT) Fault and Section 2.4, Trunk 
    (COT, TLT, DTI) Fault
    ATTCON/DESKCON  No speech can be made.
     No control operations can be made.Section 3.3, ATTCON/DESKCON 
    Fault
    Unit Fault Faults related to speech.Section 4.2, Unit Fault - Fault 
    Related to Speech
    Dial tone is not heard.Section 4.3, Unit Fault - When Dial 
    Tone (DT) Cannot Be Heard
    The ACT MUX card side has become faulty and system 
    changeover has been executed.Section 4.4, Unit Fault - ACT-Side 
    MUX Card Is Faulty and System 
    Has Changed Over 
    						
    							CHAPTER 5 NDA-24238
    Page 310
    Revision 3.0
    FAULT REPAIR PROCEDURES
    Speech System Fault Faults related to speech.Section 5.2, Speech Path System 
    Fault - Fault Related to Speech
    Dial tone is not heard.Section 5.3, Speech Path System 
    Fault - When Dial Tone (DT) 
    Cannot Be Heard
    STBY side is faulty.Section 5.4, Speech Path System 
    Fault - STBY Side Has Become 
    Faulty
    Control System Fault Fault occurs occasionally at the ACT side.Section 6.2, Control System Fault - 
    Fault Occurs Intermittently
    STBY side is faulty.Section 6.3, Control System Fault - 
    STBY Side Is Faulty
    Alarm Indication Fault No fault indication is made on the Alarm Indicator 
    Panel.Section 7.2, Fault of Alarm 
    Indicating Panel
    Fault is not detected.Section 7.3, Fault That Cannot Be 
    Detected
    Power Supply Fault Fuse for RGU/-48V has blown.Section 8.2, Fuse Blown Fault
    The circuit breaker of PWR supply is off.Section 8.3, Circuit Breaker OFF 
    Fault in PWR Supply
    Alarm lamp on the PWR supply is lit.Section 8.4, Fault of Alarm Lamps 
    on PWR Supply
    Fan  Unit  Fault  Fan are not activated even if the temperature has risen 
    higher than a predetermined degree.
     Fans are not activated even if the FAN START switch 
    is set to AUTO position.Section 9.2, Fan Unit Fault
    Tone Fault Tone is distorted.Section 10.2, Tone Fault
    System Down Fault Cause for the fault cannot be identified.Section 11.1, When Cause for Fault 
    Cannot Be Identified
    The faulty circuit card can be detected.Section 11.2, When Faulty Circuit 
    Cards Can Be Assumed From 
    System Message
    CCIS Line Fault  A Specific CCH/CCT card is faulty. When the signal 
    transmission line is a digital line, transmission/re-
    ceiving of control signals cannot be performed. 
     When the signal transmission line is an analog line, 
    transmission/receiving of control signals cannot be 
    performed.Section 12.3, Specific CCH/CCT 
    Card Is Faulty and
    Section 12.4, Fault of CCH, DTI 
    and Related Flat Cable Table 5-1  Fault Repair Procedure Quick Reference (Continued)
    FAULTY ITEM FAULTY SITUATION REFERENCE SECTION 
    						
    							NDA-24238 CHAPTER 5
    Page 311
    Revision 3.0
    FAULT REPAIR PROCEDURES
    1. LINE FAULT
    This section explains the fault repair procedure in a case where only one specific station line is in any of the
    faulty conditions listed in Ta b l e  5 - 2.
    ISDN Line Fault  A specific DCH/PRT card is faulty.
     When the signal transmission line is a digital line, 
    transmission/receiving of control signals cannot be 
    performed.Section 13.3, Specific DCH/PRT 
    Card Is Faulty and
    Section 13.4, Fault of DCH, DTI, 
    and Related Flat Cable
    Hard Time Clock Fault EMA card is faulty.Section 14, Hard Time Clock Fault
    Table 5-2  Line Fault Situation
    FAULTY SITUATION REFERENCE SECTION
    When Dial Tone cannot be heardSection 1.3, Line Fault - When Dial Tone (DT) Cannot Be Heard
    When dialing results in a wrong connectionSection 1.4, Line Fault - When Dialing Results in Wrong 
    Connection
    When the bell does not ringSection 1.5, Line Fault - When Bell Does Not Ring
    When call cannot be answered and speech cannot be 
    madeSection 1.6, When Call Cannot Be Answered and Speech 
    Cannot Be Made
    D
    term FaultSection 1.7, Dterm Fault Table 5-1  Fault Repair Procedure Quick Reference (Continued)
    FAULTY ITEM FAULTY SITUATION REFERENCE SECTION 
    						
    							CHAPTER 5 NDA-24238
    Page 312
    Revision 3.0
    FAULT REPAIR PROCEDURES
    1.1 Check Point
    When repairing a line fault, consider the following items:
    (1) Check alarm lamps on line circuit cards.
    (2) When an outgoing call cannot be originated to a specific line/trunk or when an incoming call cannot be
    terminated from a specific line/trunk, check Tenant Restriction Data (assigned via ATNR command) and
    Route Restriction Data (assigned via ARSC command).
    1.2 Line Control
    Each line in a specific Line circuit (LC/ELC) card is controlled by the PM in that line circuit card. The
    line circuit cards are controlled from the CPU via the MUX. Figure 5-1 shows the control route of line
    circuit cards.
    Figure 5-1   Controlling LC/ELC Circuit Cards and Speech Path
    LC
    MUX
    TDSW/INT
    GT
    ISAGT
    CPU
    CPRTSW
    MDF
    LT Cable
    LT Cable Control Signal
    Speech Path
    Control SignalLC/ELC
    Ordinary Telephone/ Ordinary Telephone/
    Symbols:
               :  Circuit Card                              :  Speech Path
              :  Control Signal
    TSW:  PH-SW12                     GT:  PH-GT09
    MUX:  PH-PC36                     ISAGT:  PZ-GT13
    LC
    PM
    MUXLCLT Cable
    LT Cable Control Signal
    Speech PathLC/ELC
    LC
    PM
    Dterm
    Dterm 
    						
    							NDA-24238 CHAPTER 5
    Page 313
    Revision 3.0
    FAULT REPAIR PROCEDURES
    1.3 Line Fault - When Dial Tone (DT) Cannot Be Heard
    Note:If a circuit card is replaced because only one line is
    faulty, no other lines in that circuit card can be used
    until the replacement is complete.
    When OPE lamp on the LC circuit card
    does not illuminateConfirm MB switch of the LC circuit card is in
    ON position (UP).
    Use ASDT command to confirm that station
    data in the LC circuit card is assigned.
    Replace the LC circuit card with a spare.
    When BL lamp for each line is flashing or
    illuminating on the LC circuit cardConfirm MB switch of the LC circuit card is in
    ON position (UP side).
    Use MBST command to confirm LC circuit
    card has not been placed into make-busy state.
    Use ASDT command to check the station data
    assignment.
    Replace the LC circuit card with a spare.
    ATTENTIONContents
    Static Sensitive
    Handling
    Precautions Required
    START
    A 
    						
    All NEC manuals Comments (0)

    Related Manuals for NEC Neax 2400 Imx System Operations And Maintenance Manual