NEC Neax 2400 Imx System Operations And Maintenance Manual
Have a look at the manual NEC Neax 2400 Imx System Operations And Maintenance Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 1168 NEC manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
CHAPTER 4 NDA-24238 Page 304 Revision 3.0 UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE 6. Fuse Replacement The system uses the fuses shown in Figure 4-28 as a protection against an overload resulting from a short cir- cuit. Figure 4-28 Fuses Used by System When excessive current is applied to a PWR circuit card, the related fuse is blown. The blown fuse after a fault can be confirmed as shown in Figure 4-29. Figure 4-29 Blown Fault Example The purpose of fuses is to let them blow before the components are damaged. If any fuse gets blown, replace it immediately with a new one using the following procedure: (1) Confirm the blown fuse via the system message [6-A] or MJ lamp on the top of IMG0. (2) Replace the fuse with a new one, referring to Figure 4-30 and Figure 4-31. (3) Determine the cause of the blown fault, referring to Figure 4-32 (case of RGU fuse) or Figure 4-33 (DC- 48V fuse.) 1.5A 12.5V25A If a fuse is blown, this area turns white. A normal fuse A blown fuse
NDA-24238 CHAPTER 4 Page 305 Revision 3.0 UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE Figure 4-30 shows the location of fuses within the system. In Chapter 4-30, the fuses are indicated by or . Figure 4-30 Fuse Locations Within System NECNEAX 2400 IMS PZ-M377 3.2A 5.0A PZ-M3695.0A ..... ..... ..... ..... PZ-PW92 5.0A 25A 25A 5.0A0.5A PA-PW54 PA-PW555.0A 0.5A 25A PBX [Front View]
CHAPTER 4 NDA-24238 Page 306 Revision 3.0 UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE In the TSWM, the fuse shown in Figure 4-31 is used for the PWR SW (PH-PW14) card, which is housed in Slot No. 00 and/or 01. Figure 4-31 Fuse Location Within TSWM PH-PW14 (PWR SW) FUSE: 15A TSWM PBX (IMG1) Front View
NDA-24238 CHAPTER 4 Page 307 Revision 3.0 UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE Perform the procedure in Figure 4-32 to confirm the cause of the RGU fuse blown fault. Figure 4-32 RGU Fuse Blown Fault Flowchart Start Visual check: No pin contacting or backboard melting? OPE Lamp (green) of each LC card remains lit? Replace the blown fuse with a new one. The fuse is blown again?Yes Yes Yes Yes YesNo 1. Turn ON (UP) the MB key on the LC card. 2. Remove the card from the PIM. 3. Replace the fuse with a new one. Turn ON (UP) the MB keys on all LC cards, and remove them from the PIM. (Only PWR cards are inside the PIM) Turn ON (UP) the MB keys on the whole LC cards, and remove them from the PIM. (Only PWR cards are inside the PIM) The replaced fuse is blown again? Perform station-to-station connections within the PIM. Is any fuse blown? Perform station-to-station connections within the PIM. Is any fuse blown?No No No No No No Yes YesNo Fault in LC card that accompanied the fuse blowing. Fault of LC card that accompanied the fuse blowing. Probable Cause: Not confirmed. Needs further observation of the fault There is a short circuit on the backboard of the PIM. Fault in LC card that accompanied the fuse blowing. Fault of PWR card. Perform system initialization after inserting all removed cards. Fault of LC card that was removed Replace the blown fuse with a new one. Replace the blown fuse with a new one. Replace the PWR card Yes Insert the removed cards one by one (into the PIM). Is any fuse blown? The replaced fuse is blown again? Fuse is still blown? NoYes The replaced fuse is blown again?
CHAPTER 4 NDA-24238 Page 308 Revision 3.0 UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE Perform the procedure in Figure 4-33 to confirm the cause of the DC-48V fuse blown fault. Figure 4-33 DC -48V Fuse Blown Fault Flowchart Start Visual check: No pin contacting or backboard melting? OPE Lamps (green) of LC/TRK/NCU cards remain lit? Make sure in which module the fuse has blownNo 1. Turn ON (UP) the MB key on the circuit card. 2. Remove the card from the PIM. 3. Replace the fuse with a new one. Turn ON (UP) the MB keys on the whole circuit cards, and remove them from the PIM. (Only PWR cards are inside the PIM) Turn ON (UP) the MB keys on the whole circuit cards, and remove them from the PIM. (Only PWR cards are inside the PIM) The replaced fuse is blown again?No No No No Fault of circuit card that accompanied the fuse blown. Perform system initialization after inserting all removed cards. Fault of circuit card that was removed Replace the blown fuse with a new one. Replace the blown fuse with a new one.Yes Yes Yes Insert the removed cards one by one (into the PIM). Is there any fuse blowing? The replaced fuse is blown again? The fuse is still blown? There is a short circuit on the backboard of the PIM. Fault of PWR card. Replace the PWR cardYes YesLPM / TSWM / PIM No Fault of circuit card that accompanied the fuse blown. Perform system initialization after inserting all removed cards. Yes Insert the removed cards one by one (into the PIM). Is any fuse blown?
NDA-24238 CHAPTER 5 Page 309 Revision 3.0 FAULT REPAIR PROCEDURES CHAPTER 5 FAULT REPAIR PROCEDURES This chapter provides information on how to repair the fault(s) within the system. If any of the components or equipment listed in Table 5-1 has a failure, move on to the repair procedure explained for each faulty condition. Table 5-1 Fault Repair Procedure Quick Reference FAULTY ITEM FAULTY SITUATION REFERENCE SECTION Line Fault DP/PB Telephone Dial tone is not heard.Section 1.3, Line Fault - When Dial Tone (DT) Cannot Be Heard Dialing results in a wrong connection.Section 1.4, Line Fault - When Dialing Results in Wrong Connection Bell does not ring.Section 1.5, Line Fault - When Bell Does Not Ring Answer/speech cannot be made.Section 1.6, When Call Cannot Be Answered and Speech Cannot Be Made D termDterm cannot be operated. Operations are abnormal.Section 1.7, Dterm Fault Trunk Fault No connections can be set up. PB/DP signals are erroneously received or set out from ORT/SND. No three-way calling can be made on CFT, or noise gets in a established connection. A connection results in no speech. Noise gets in a established connection.Section 2.3, Trunk (ORT, SND, CFT) Fault and Section 2.4, Trunk (COT, TLT, DTI) Fault ATTCON/DESKCON No speech can be made. No control operations can be made.Section 3.3, ATTCON/DESKCON Fault Unit Fault Faults related to speech.Section 4.2, Unit Fault - Fault Related to Speech Dial tone is not heard.Section 4.3, Unit Fault - When Dial Tone (DT) Cannot Be Heard The ACT MUX card side has become faulty and system changeover has been executed.Section 4.4, Unit Fault - ACT-Side MUX Card Is Faulty and System Has Changed Over
CHAPTER 5 NDA-24238 Page 310 Revision 3.0 FAULT REPAIR PROCEDURES Speech System Fault Faults related to speech.Section 5.2, Speech Path System Fault - Fault Related to Speech Dial tone is not heard.Section 5.3, Speech Path System Fault - When Dial Tone (DT) Cannot Be Heard STBY side is faulty.Section 5.4, Speech Path System Fault - STBY Side Has Become Faulty Control System Fault Fault occurs occasionally at the ACT side.Section 6.2, Control System Fault - Fault Occurs Intermittently STBY side is faulty.Section 6.3, Control System Fault - STBY Side Is Faulty Alarm Indication Fault No fault indication is made on the Alarm Indicator Panel.Section 7.2, Fault of Alarm Indicating Panel Fault is not detected.Section 7.3, Fault That Cannot Be Detected Power Supply Fault Fuse for RGU/-48V has blown.Section 8.2, Fuse Blown Fault The circuit breaker of PWR supply is off.Section 8.3, Circuit Breaker OFF Fault in PWR Supply Alarm lamp on the PWR supply is lit.Section 8.4, Fault of Alarm Lamps on PWR Supply Fan Unit Fault Fan are not activated even if the temperature has risen higher than a predetermined degree. Fans are not activated even if the FAN START switch is set to AUTO position.Section 9.2, Fan Unit Fault Tone Fault Tone is distorted.Section 10.2, Tone Fault System Down Fault Cause for the fault cannot be identified.Section 11.1, When Cause for Fault Cannot Be Identified The faulty circuit card can be detected.Section 11.2, When Faulty Circuit Cards Can Be Assumed From System Message CCIS Line Fault A Specific CCH/CCT card is faulty. When the signal transmission line is a digital line, transmission/re- ceiving of control signals cannot be performed. When the signal transmission line is an analog line, transmission/receiving of control signals cannot be performed.Section 12.3, Specific CCH/CCT Card Is Faulty and Section 12.4, Fault of CCH, DTI and Related Flat Cable Table 5-1 Fault Repair Procedure Quick Reference (Continued) FAULTY ITEM FAULTY SITUATION REFERENCE SECTION
NDA-24238 CHAPTER 5 Page 311 Revision 3.0 FAULT REPAIR PROCEDURES 1. LINE FAULT This section explains the fault repair procedure in a case where only one specific station line is in any of the faulty conditions listed in Ta b l e 5 - 2. ISDN Line Fault A specific DCH/PRT card is faulty. When the signal transmission line is a digital line, transmission/receiving of control signals cannot be performed.Section 13.3, Specific DCH/PRT Card Is Faulty and Section 13.4, Fault of DCH, DTI, and Related Flat Cable Hard Time Clock Fault EMA card is faulty.Section 14, Hard Time Clock Fault Table 5-2 Line Fault Situation FAULTY SITUATION REFERENCE SECTION When Dial Tone cannot be heardSection 1.3, Line Fault - When Dial Tone (DT) Cannot Be Heard When dialing results in a wrong connectionSection 1.4, Line Fault - When Dialing Results in Wrong Connection When the bell does not ringSection 1.5, Line Fault - When Bell Does Not Ring When call cannot be answered and speech cannot be madeSection 1.6, When Call Cannot Be Answered and Speech Cannot Be Made D term FaultSection 1.7, Dterm Fault Table 5-1 Fault Repair Procedure Quick Reference (Continued) FAULTY ITEM FAULTY SITUATION REFERENCE SECTION
CHAPTER 5 NDA-24238 Page 312 Revision 3.0 FAULT REPAIR PROCEDURES 1.1 Check Point When repairing a line fault, consider the following items: (1) Check alarm lamps on line circuit cards. (2) When an outgoing call cannot be originated to a specific line/trunk or when an incoming call cannot be terminated from a specific line/trunk, check Tenant Restriction Data (assigned via ATNR command) and Route Restriction Data (assigned via ARSC command). 1.2 Line Control Each line in a specific Line circuit (LC/ELC) card is controlled by the PM in that line circuit card. The line circuit cards are controlled from the CPU via the MUX. Figure 5-1 shows the control route of line circuit cards. Figure 5-1 Controlling LC/ELC Circuit Cards and Speech Path LC MUX TDSW/INT GT ISAGT CPU CPRTSW MDF LT Cable LT Cable Control Signal Speech Path Control SignalLC/ELC Ordinary Telephone/ Ordinary Telephone/ Symbols: : Circuit Card : Speech Path : Control Signal TSW: PH-SW12 GT: PH-GT09 MUX: PH-PC36 ISAGT: PZ-GT13 LC PM MUXLCLT Cable LT Cable Control Signal Speech PathLC/ELC LC PM Dterm Dterm
NDA-24238 CHAPTER 5 Page 313 Revision 3.0 FAULT REPAIR PROCEDURES 1.3 Line Fault - When Dial Tone (DT) Cannot Be Heard Note:If a circuit card is replaced because only one line is faulty, no other lines in that circuit card can be used until the replacement is complete. When OPE lamp on the LC circuit card does not illuminateConfirm MB switch of the LC circuit card is in ON position (UP). Use ASDT command to confirm that station data in the LC circuit card is assigned. Replace the LC circuit card with a spare. When BL lamp for each line is flashing or illuminating on the LC circuit cardConfirm MB switch of the LC circuit card is in ON position (UP side). Use MBST command to confirm LC circuit card has not been placed into make-busy state. Use ASDT command to check the station data assignment. Replace the LC circuit card with a spare. ATTENTIONContents Static Sensitive Handling Precautions Required START A