Home > NEC > Communications System > NEC Neax 2400 Imx System Operations And Maintenance Manual

NEC Neax 2400 Imx System Operations And Maintenance Manual

    Download as PDF Print this page Share this page

    Have a look at the manual NEC Neax 2400 Imx System Operations And Maintenance Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 1168 NEC manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    Page
    of 647
    							CHAPTER 3 NDA-24238
    Page 234
    Revision 3.0
    SYSTEM MESSAGES
    Repair Procedure
    Depending on the fault status shown in data 
    ➁, perform necessary repair work:
    (1) Hardware Failure/Onboard Power Alarm
    SDT (PA-SDTA/B) card is faulty. Replace the card with a spare by referring to Chapter 4, Section 3.3.3,
    SDT Card Replacement Procedure.
    (2) Optical Line Failure
    Diagnosis: In addition to this alarm, is the “PCM Loss” alarm also indicated?
    YES→Optical line side is faulty.
    Verify that the SDT card in the distant node is not placed into make-busy state. Also, perform the
    light level check of the optical fiber cables.
    NO→SDT card is faulty.
    Replace the SDT card with a spare by referring to Chapter 4, Section 3.3.3, SDT Card Replace-
    ment Procedure.
    (3) Abnormal MB Key Operation
    This alarm is indicated when the MB key on the PA-SDTA card is turned ON, even though the MBR key
    has been on the OFF side. Place the MBR key UP (=ON) and then turn ON the MB key.
    (4) PCM Loss
    Abnormal state is detected on the optical line side. Verify that the SDT card in the distant node is not
    placed into make-busy state. Also, perform the light level check of the optical fiber cables.
    (5) 52M Interface Alarm
    - Frame Alignment Loss
    - Receiving Section Failure
    - Mistake Rate Degradation
    - Sending Section Failure
    - Mistake Detection
    Clock synchronization with the distant node might be lost, or a trouble might occur on the optical line
    side. Check the PLO cards first in both self-node and distant node. When no fault is found, proceed with
    the light level check of the optical fiber cables. 
    						
    							NDA-24238 CHAPTER 3
    Page 235
    Revision 3.0
    SYSTEM MESSAGES
    (6) Receiving Path Failure/Receiving Path Error
    Abnormal state is detected in the process of multiplexing the “Receive” signals. To restore this, perform
    the following:
    STEP 1 Initialization of SDT card (distant node)
    Initialize the SDT card in the distant node, and observe the situation. If the fault is not restored,
    proceed with STEP 2.
    STEP 2 Initialization of SDT card (self-node)
    Initialize the SDT card in the self-node, and observe the situation. If the fault is not restored,
    proceed with STEP 3.
    STEP 3 Replacement of SDT card
    It cannot be confirmed which node side (self-node or distant node) is faulty. By referring to
    Chapter 4, Section 3.3.3, SDT Card Replacement Procedure, first replace the SDT card only in
    one of the nodes. When the fault does not recover, then also replace the SDT card in other side
    of the nodes. 
    (7) Pointer Failure/Sending Path Failure/Sending Path Error
    Abnormal state is detected in the process of multiplexing the “Send” signals. To restore this, perform the
    following:
    STEP 1 Initialization of SDT card
    Initialize the SDT card in the self-node, and observe the situation. If the fault is not restored,
    proceed with STEP 2.
    STEP 2 Replacement of SDT card
    By referring to Chapter 4, Section 3.3.3, SDT Card Replacement Procedure, replace the SDT
    card in the self-node with a spare. 
    						
    							CHAPTER 3 NDA-24238
    Page 236
    Revision 3.0
    SYSTEM MESSAGES
    This message displays when the SDT (PA-SDTA/B) card or optical fiber line, which was once detected as
    faulty, recovers.
    ➀ MG (Module Group)
    ➁ Details on the fault
    1: X0XX 0000 0000 0000 2: 0000 0000 0000 0000 3: 0000 0000 0000 0000
    ➀ ➁
    4: 0000 0000 0000 0000 5: 0000 0000 0000 0000 6: 0000 0000 0000 0000
    7: 0000 0000 0000 0000 8: 0000 0000 0000 0000 9: 0000 0000 0000 0000
    b7 b0
    b7 b4 b3 b2 b1 b0
    Default Alarm:
    NON33-DSDT Alarm RestoreDefault Grade:
    1Grade Modified: Lamp Modified:
    b7: 0/1 = Even-number MG/Odd-number MG
    b4, b3 b2-b0
    0 0 0 0 0
    0 0 0 0 1 Hardware Failure
    0 0 0 1 0 Optical Line Failure
    0 0 0 1 1 Onboard Power Alarm
    0 0 1 0 0 Abnormal MB Key Operation
    0 1 0 0 0
    0 1 0 0 1 PCM Loss
    0 1 0 1 0 Frame Alignment Loss
    0 1 0 1 1 Receiving Section Failure
    0 1 1 0 0 Mistake Rate Degradation
    0 1 1 0 1 Sending Section Failure
    0 1 1 1 0 Mistake Detection
    1 0 0 0 0
    1 0 0 0 1 Receiving Path Failure
    1 0 0 1 0 Pointer Failure
    1 0 0 1 1 Sending Path Failure
    1 0 1 0 0 Receiving Path Error
    1 0 1 0 1 Sending Path Error
    b7: SDT Card Status
    0/1=No. 0 System/No.1 System
    SDT Card
    Trouble
    52M Interface
    Alarm
    VC-11 Path
    Trouble 
    						
    							NDA-24238 CHAPTER 3
    Page 237
    Revision 3.0
    SYSTEM MESSAGES
    This message displays when the ACT/STBY of the SDT (PA-SDTA) card is changed over as a result of fault
    detection in the optical fiber line. When the ACT/STBY change cannot be performed, this message also indi-
    cates the cause for the changeover execution failure.
    ➀ MG (Module Group)
    ➁ Detailed information
    ➂ Cause for changeover execution failure
    Repair Procedure
    Once this message displays, be sure to check other messages, such as [33-C] SDT Alarm Trouble, and review
    the cause for the changeover. If any fault is implicated, repair the whole fault(s) according to the situation.
    1: X0XX XX00 0000 0000 2: 0000 0000 0000 0000 3: 0000 0000 0000 0000
    ➀ ➁
    4: 0000 0000 0000 0000 5: 0000 0000 0000 0000 6: 0000 0000 0000 0000
    7: 0000 0000 0000 0000 8: 0000 0000 0000 0000 9: 0000 0000 0000 0000
    b7 b0
    b7 b6 b5 b4 b3 b2 b1 b0
    b7 b6 b5 b4 b3 b2 b1 b0
    Default Alarm:
    NON33-ESDT Interface Change NotifyDefault Grade:
    2Grade Modified: Lamp Modified:
    b7: 0/1 = Even-number MG/Odd-number MG
    b0: Active SDT after Changeover
    0/1=No.0 System/No.1 System
    b1: Operating Status of SDT
    0/1=In service/Out of service 
    b2, b3: Result of Changeover
    0/1=Success/Failure
    b7-b4
    Cause for Changeover
    0001 SDT had a serious failure
    0010 MB key on SDT card was turned ON
    0H: (Changeover Success)
    1H: Optical interface isn’t dual
    2H: Optical interface has a serious failure in each No.0/No.1 system 
    						
    							CHAPTER 3 NDA-24238
    Page 238
    Revision 3.0
    This page is for your notes. 
    						
    							NDA-24238 CHAPTER 4
    Page 239
    Revision 3.0
    UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE
    CHAPTER 4 Unit/Circuit Card Replacement Procedure
    1. LPM Accommodating Unit/Circuit Card Replacement Procedure
    This section explains how to replace unit/circuit cards mounted in the LPM.
    1.1 Precaution
     Use this procedure to replace a faulty unit/circuit card with a spare or to check a spare card.
     There are functional switches (having set the default switch) on some of the circuit cards to be re-
    placed. As for switch setting on the circuit cards, confirm the circuit card mounting face layout for the
    LPM. When a circuit card with a default switch setting is replaced with a spare card, always make the
    switch setting on the new circuit card the same as on the replaced card. Otherwise, electronic compo-
    nents on the circuit card may be destroyed, or the circuit card itself may fail to function normally.
     When handling a circuit card, always use the field service kit for countermeasures against static elec-
    tricity. Touching a circuit card without using the field service kit may destroy the card due to static
    electricity on the human body.
    1.2 Circuit Card Mounting Face Layout
    Figure 4-1 shows the face layout of circuit cards mounted in the LPM. The circuit cards marked with *
    are optional. 
    						
    							CHAPTER 4 NDA-24238
    Page 240
    Revision 3.0
    UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE
    Figure 4-1   Circuit Card Mounting Face Layout of LPM Note:
    In place of PZ-IO27, the CPR may be equipped with PZ-IO28, which does not have the MB
    (Make-busy) key.
    12
    34
    567
    8
    OFF
    12
    34
    567
    8
    OFF
    12
    34
    OFF
    MBR
    FDD ON
    OFF
    PALM
    ON
    OFF OUT PWR
    IN PWR5AHDD SW
    MB
    SYSTEM SELECT0
    SENSE SYSTEM SELECT1
    SYSTEM SELECT2
    CPURST
    SLOT No.    0 1 2 3 4 5 6 STATUS IMG1 IMG2 IMG3 CPUOPE
    WDTIMG0
    ON
    ON
    ON4C026AE
    12
    34
    567
    8
    OFF
    12
    34
    567
    8
    OFF
    12
    34
    OFF
    MBR
    FDD ON
    OFF
    ON
    OFF OUT PWR
    IN PWR5AHDD SW
    MB
    SYSTEM SELECT0
    SENSE SYSTEM SELECT1
    SYSTEM SELECT2
    CPURST
    SLOT No.    0 1 2 3 4 5 6 STATUS IMG1 IMG2 IMG3 CPUOPE
    WDTIMG0
    ON
    ON
    ON4C026AE
    00 01 02 03 04
    MISC MISC/IOC IOC(PH-IO24) EMA(PH-PC40)MISC
    LPM
    FRONT VIEW
    CPR PZ-PW92
    PZ-IO27LANI(PZ-PC19)GATE(PZ-GT16)
    PALM
    Note 
    						
    							NDA-24238 CHAPTER 4
    Page 241
    Revision 3.0
    UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE
    1.3 Operating Procedures
    The following paragraphs provide operating procedures to replace unit/circuit cards of the LPM. Perform
    the operations that correspond to each Reference Item specified in Table 4-1.
    Table 4-1  LPM Unit/Circuit Cards and Reference Items
    UNIT/CIRCUIT CARD REFERENCE ITEM REMARKS
    CPRSection 1.3.1, CPR Replacement ProcedureCPU, ISAGT, 
    LANI
    EMA CardSection 1.3.2, EMA Card Replacement Procedure
    IOC CardSection 1.3.3, IOC Card Replacement Procedure
    PWR UnitSection 1.3.4, Power Supply Unit Replacement Procedure
    MISC CardSection 1.3.5, MISC Card Replacement Procedure
    Improper key operations may result in a system down. Operate the key using extreme care.
    During replacement of a circuit card, the system issues system messages and activates the related
    alarm. Reset the indicated alarm after completing the replacement procedure.
    If the indicated alarm is cleared via the RALM command, the system also clears the contents of the system
    message. Before using the RALM command, print the messages using the DFTD command.
    Use the ALM RST button only to reset the alarm lamps.WA RN I NG 
    						
    							CHAPTER 4 NDA-24238
    Page 242
    Revision 3.0
    UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE
    1.3.1 CPR Replacement Procedure
    This section explains how to replace the Control Processor Rack (CPR). Before
    starting the procedures, make a backup copy of the main data, such as office data,
    Call Forwarding (CF) data and Speed Calling (SPD) data, on to the hard disk of the
    HFC. Figure 4-2 shows the front view of the CPR. Operate the related keys and con-
    nectors to replace the CPU with a new one. Using a Phillips screwdriver, remove the four screws and
    extract the CPR with care, as shown in Figure 4-3.
    Figure 4-2   CPR Face Layout
    AT T E N T I O NContents
    Static SensitiveHandling
    Precautions Required
    12
    34
    567
    8
    OFF
    12
    34
    567
    8
    OFF
    12
    34
    OFF
    MBR
    FDD ON
    OFF
    ON
    OFF OUT PWR
    PALM
    IN PWR5AHDD SW
    MB
    SYSTEM SELECT0
    SENSE SYSTEM SELECT1
    SYSTEM SELECT2
    CPURST
    SLOT No.    0 1 2 3 4 5 6 STATUS IMG1 IMG2 IMG3 CPUOPE
    WDTIMG0
    ON
    ON
    ON
    4C026AE
    PZ-IO27
    PZ-PW92Note
    Note:In place of PZ-IO27, the CPR may be equipped with PZ-IO28, which does not have the MB
    (Make-Busy) key. 
    						
    							NDA-24238 CHAPTER 4
    Page 243
    Revision 3.0
    UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE
    Figure 4-3   How to Replace the CPU
    ..... .....
    12
    34
    567
    812
    34
    567
    812
    345A
    SLOT No.    0 1 2 3
    45 6
    26E
    ..... .....
    12
    34
    567
    812
    34
    567
    8
    12
    345A
    SLOT No.   
    0
    1
    2
    3
    4
    5
    6
    26E
    CPR
    LPM
    PBX 
    						
    All NEC manuals Comments (0)

    Related Manuals for NEC Neax 2400 Imx System Operations And Maintenance Manual