NEC Neax 2400 Imx System Operations And Maintenance Manual
Have a look at the manual NEC Neax 2400 Imx System Operations And Maintenance Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 1168 NEC manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
CHAPTER 3 NDA-24238 Page 234 Revision 3.0 SYSTEM MESSAGES Repair Procedure Depending on the fault status shown in data ➁, perform necessary repair work: (1) Hardware Failure/Onboard Power Alarm SDT (PA-SDTA/B) card is faulty. Replace the card with a spare by referring to Chapter 4, Section 3.3.3, SDT Card Replacement Procedure. (2) Optical Line Failure Diagnosis: In addition to this alarm, is the “PCM Loss” alarm also indicated? YES→Optical line side is faulty. Verify that the SDT card in the distant node is not placed into make-busy state. Also, perform the light level check of the optical fiber cables. NO→SDT card is faulty. Replace the SDT card with a spare by referring to Chapter 4, Section 3.3.3, SDT Card Replace- ment Procedure. (3) Abnormal MB Key Operation This alarm is indicated when the MB key on the PA-SDTA card is turned ON, even though the MBR key has been on the OFF side. Place the MBR key UP (=ON) and then turn ON the MB key. (4) PCM Loss Abnormal state is detected on the optical line side. Verify that the SDT card in the distant node is not placed into make-busy state. Also, perform the light level check of the optical fiber cables. (5) 52M Interface Alarm - Frame Alignment Loss - Receiving Section Failure - Mistake Rate Degradation - Sending Section Failure - Mistake Detection Clock synchronization with the distant node might be lost, or a trouble might occur on the optical line side. Check the PLO cards first in both self-node and distant node. When no fault is found, proceed with the light level check of the optical fiber cables.
NDA-24238 CHAPTER 3 Page 235 Revision 3.0 SYSTEM MESSAGES (6) Receiving Path Failure/Receiving Path Error Abnormal state is detected in the process of multiplexing the “Receive” signals. To restore this, perform the following: STEP 1 Initialization of SDT card (distant node) Initialize the SDT card in the distant node, and observe the situation. If the fault is not restored, proceed with STEP 2. STEP 2 Initialization of SDT card (self-node) Initialize the SDT card in the self-node, and observe the situation. If the fault is not restored, proceed with STEP 3. STEP 3 Replacement of SDT card It cannot be confirmed which node side (self-node or distant node) is faulty. By referring to Chapter 4, Section 3.3.3, SDT Card Replacement Procedure, first replace the SDT card only in one of the nodes. When the fault does not recover, then also replace the SDT card in other side of the nodes. (7) Pointer Failure/Sending Path Failure/Sending Path Error Abnormal state is detected in the process of multiplexing the “Send” signals. To restore this, perform the following: STEP 1 Initialization of SDT card Initialize the SDT card in the self-node, and observe the situation. If the fault is not restored, proceed with STEP 2. STEP 2 Replacement of SDT card By referring to Chapter 4, Section 3.3.3, SDT Card Replacement Procedure, replace the SDT card in the self-node with a spare.
CHAPTER 3 NDA-24238 Page 236 Revision 3.0 SYSTEM MESSAGES This message displays when the SDT (PA-SDTA/B) card or optical fiber line, which was once detected as faulty, recovers. ➀ MG (Module Group) ➁ Details on the fault 1: X0XX 0000 0000 0000 2: 0000 0000 0000 0000 3: 0000 0000 0000 0000 ➀ ➁ 4: 0000 0000 0000 0000 5: 0000 0000 0000 0000 6: 0000 0000 0000 0000 7: 0000 0000 0000 0000 8: 0000 0000 0000 0000 9: 0000 0000 0000 0000 b7 b0 b7 b4 b3 b2 b1 b0 Default Alarm: NON33-DSDT Alarm RestoreDefault Grade: 1Grade Modified: Lamp Modified: b7: 0/1 = Even-number MG/Odd-number MG b4, b3 b2-b0 0 0 0 0 0 0 0 0 0 1 Hardware Failure 0 0 0 1 0 Optical Line Failure 0 0 0 1 1 Onboard Power Alarm 0 0 1 0 0 Abnormal MB Key Operation 0 1 0 0 0 0 1 0 0 1 PCM Loss 0 1 0 1 0 Frame Alignment Loss 0 1 0 1 1 Receiving Section Failure 0 1 1 0 0 Mistake Rate Degradation 0 1 1 0 1 Sending Section Failure 0 1 1 1 0 Mistake Detection 1 0 0 0 0 1 0 0 0 1 Receiving Path Failure 1 0 0 1 0 Pointer Failure 1 0 0 1 1 Sending Path Failure 1 0 1 0 0 Receiving Path Error 1 0 1 0 1 Sending Path Error b7: SDT Card Status 0/1=No. 0 System/No.1 System SDT Card Trouble 52M Interface Alarm VC-11 Path Trouble
NDA-24238 CHAPTER 3 Page 237 Revision 3.0 SYSTEM MESSAGES This message displays when the ACT/STBY of the SDT (PA-SDTA) card is changed over as a result of fault detection in the optical fiber line. When the ACT/STBY change cannot be performed, this message also indi- cates the cause for the changeover execution failure. ➀ MG (Module Group) ➁ Detailed information ➂ Cause for changeover execution failure Repair Procedure Once this message displays, be sure to check other messages, such as [33-C] SDT Alarm Trouble, and review the cause for the changeover. If any fault is implicated, repair the whole fault(s) according to the situation. 1: X0XX XX00 0000 0000 2: 0000 0000 0000 0000 3: 0000 0000 0000 0000 ➀ ➁ 4: 0000 0000 0000 0000 5: 0000 0000 0000 0000 6: 0000 0000 0000 0000 7: 0000 0000 0000 0000 8: 0000 0000 0000 0000 9: 0000 0000 0000 0000 b7 b0 b7 b6 b5 b4 b3 b2 b1 b0 b7 b6 b5 b4 b3 b2 b1 b0 Default Alarm: NON33-ESDT Interface Change NotifyDefault Grade: 2Grade Modified: Lamp Modified: b7: 0/1 = Even-number MG/Odd-number MG b0: Active SDT after Changeover 0/1=No.0 System/No.1 System b1: Operating Status of SDT 0/1=In service/Out of service b2, b3: Result of Changeover 0/1=Success/Failure b7-b4 Cause for Changeover 0001 SDT had a serious failure 0010 MB key on SDT card was turned ON 0H: (Changeover Success) 1H: Optical interface isn’t dual 2H: Optical interface has a serious failure in each No.0/No.1 system
CHAPTER 3 NDA-24238 Page 238 Revision 3.0 This page is for your notes.
NDA-24238 CHAPTER 4 Page 239 Revision 3.0 UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE CHAPTER 4 Unit/Circuit Card Replacement Procedure 1. LPM Accommodating Unit/Circuit Card Replacement Procedure This section explains how to replace unit/circuit cards mounted in the LPM. 1.1 Precaution Use this procedure to replace a faulty unit/circuit card with a spare or to check a spare card. There are functional switches (having set the default switch) on some of the circuit cards to be re- placed. As for switch setting on the circuit cards, confirm the circuit card mounting face layout for the LPM. When a circuit card with a default switch setting is replaced with a spare card, always make the switch setting on the new circuit card the same as on the replaced card. Otherwise, electronic compo- nents on the circuit card may be destroyed, or the circuit card itself may fail to function normally. When handling a circuit card, always use the field service kit for countermeasures against static elec- tricity. Touching a circuit card without using the field service kit may destroy the card due to static electricity on the human body. 1.2 Circuit Card Mounting Face Layout Figure 4-1 shows the face layout of circuit cards mounted in the LPM. The circuit cards marked with * are optional.
CHAPTER 4 NDA-24238 Page 240 Revision 3.0 UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE Figure 4-1 Circuit Card Mounting Face Layout of LPM Note: In place of PZ-IO27, the CPR may be equipped with PZ-IO28, which does not have the MB (Make-busy) key. 12 34 567 8 OFF 12 34 567 8 OFF 12 34 OFF MBR FDD ON OFF PALM ON OFF OUT PWR IN PWR5AHDD SW MB SYSTEM SELECT0 SENSE SYSTEM SELECT1 SYSTEM SELECT2 CPURST SLOT No. 0 1 2 3 4 5 6 STATUS IMG1 IMG2 IMG3 CPUOPE WDTIMG0 ON ON ON4C026AE 12 34 567 8 OFF 12 34 567 8 OFF 12 34 OFF MBR FDD ON OFF ON OFF OUT PWR IN PWR5AHDD SW MB SYSTEM SELECT0 SENSE SYSTEM SELECT1 SYSTEM SELECT2 CPURST SLOT No. 0 1 2 3 4 5 6 STATUS IMG1 IMG2 IMG3 CPUOPE WDTIMG0 ON ON ON4C026AE 00 01 02 03 04 MISC MISC/IOC IOC(PH-IO24) EMA(PH-PC40)MISC LPM FRONT VIEW CPR PZ-PW92 PZ-IO27LANI(PZ-PC19)GATE(PZ-GT16) PALM Note
NDA-24238 CHAPTER 4 Page 241 Revision 3.0 UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE 1.3 Operating Procedures The following paragraphs provide operating procedures to replace unit/circuit cards of the LPM. Perform the operations that correspond to each Reference Item specified in Table 4-1. Table 4-1 LPM Unit/Circuit Cards and Reference Items UNIT/CIRCUIT CARD REFERENCE ITEM REMARKS CPRSection 1.3.1, CPR Replacement ProcedureCPU, ISAGT, LANI EMA CardSection 1.3.2, EMA Card Replacement Procedure IOC CardSection 1.3.3, IOC Card Replacement Procedure PWR UnitSection 1.3.4, Power Supply Unit Replacement Procedure MISC CardSection 1.3.5, MISC Card Replacement Procedure Improper key operations may result in a system down. Operate the key using extreme care. During replacement of a circuit card, the system issues system messages and activates the related alarm. Reset the indicated alarm after completing the replacement procedure. If the indicated alarm is cleared via the RALM command, the system also clears the contents of the system message. Before using the RALM command, print the messages using the DFTD command. Use the ALM RST button only to reset the alarm lamps.WA RN I NG
CHAPTER 4 NDA-24238 Page 242 Revision 3.0 UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE 1.3.1 CPR Replacement Procedure This section explains how to replace the Control Processor Rack (CPR). Before starting the procedures, make a backup copy of the main data, such as office data, Call Forwarding (CF) data and Speed Calling (SPD) data, on to the hard disk of the HFC. Figure 4-2 shows the front view of the CPR. Operate the related keys and con- nectors to replace the CPU with a new one. Using a Phillips screwdriver, remove the four screws and extract the CPR with care, as shown in Figure 4-3. Figure 4-2 CPR Face Layout AT T E N T I O NContents Static SensitiveHandling Precautions Required 12 34 567 8 OFF 12 34 567 8 OFF 12 34 OFF MBR FDD ON OFF ON OFF OUT PWR PALM IN PWR5AHDD SW MB SYSTEM SELECT0 SENSE SYSTEM SELECT1 SYSTEM SELECT2 CPURST SLOT No. 0 1 2 3 4 5 6 STATUS IMG1 IMG2 IMG3 CPUOPE WDTIMG0 ON ON ON 4C026AE PZ-IO27 PZ-PW92Note Note:In place of PZ-IO27, the CPR may be equipped with PZ-IO28, which does not have the MB (Make-Busy) key.
NDA-24238 CHAPTER 4 Page 243 Revision 3.0 UNIT/CIRCUIT CARD REPLACEMENT PROCEDURE Figure 4-3 How to Replace the CPU ..... ..... 12 34 567 812 34 567 812 345A SLOT No. 0 1 2 3 45 6 26E ..... ..... 12 34 567 812 34 567 8 12 345A SLOT No. 0 1 2 3 4 5 6 26E CPR LPM PBX