Home > NEC > Communications System > NEC Neax 2400 Imx System Operations And Maintenance Manual

NEC Neax 2400 Imx System Operations And Maintenance Manual

    Download as PDF Print this page Share this page

    Have a look at the manual NEC Neax 2400 Imx System Operations And Maintenance Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 1168 NEC manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    Page
    of 647
    							CHAPTER 5 NDA-24238
    Page 354
    Revision 3.0
    FAULT REPAIR PROCEDURES
    5.4Speech Path System Fault - STBY Side Has Become Faulty
    Faulty Situation:
     A fault occurred in the STBY side of the dual configuration system.
    [1-B] TSW Failure (Permanent)
    [1-D] TSW Write Failure
    [1-F] TSW Clock Failure
    [4-D] TSW Ready Failure
    Check to see if the TSW circuit card is mak-
    ing poor contact.Set the TSW MBR switch of the TSW circuit
    card UP.
    Set the MB switch of the TSW circuit card UP
    and extract the circuit card from its mounting
    slot.
    Extract the TSW circuit card from its mounting
    slot and clean the contact portion.
    If cleaning cannot be done, repeat insertion and
    extraction of the circuit card two or three times.
    Set the TSW MBR and MB switches of the
    TSW circuit card UP and insert the circuit card
    into its mounting slot.
    Set the MB switch of the TSW circuit card
    DOWN.
    Set the TSW MBR switch DOWN.
    Check if a station-to-station connection can be
    set up.
    Check PCM cables. Check the PCM cables. See Figure 5-8.
    Initialize the system by pressing the START
    button on the TOPU and see if a station-to-sta-
    tion connection can be set up.
    ATTENTIONContents
    Static Sensitive
    Handling
    Precautions Required
    START
    A 
    						
    							NDA-24238 CHAPTER 5
    Page 355
    Revision 3.0
    FAULT REPAIR PROCEDURES
    Faulty Situation:
     Fault related to speech such as noise, one-way speech, no-speed, etc. occurs.
     Even if dialing started, Dial Tone (DT) does not stop.
    [1-C] Both TSW Write Failure
    [1-D] TSW Write Failure
    Check to see if fault occurs by extracting
    TSW circuit cards one by one.Replace the TSW circuit card referring to Sec-
    tion 2.3.2, TSW Card Replacement Procedure
    in Chapter 4.
    Set the TSW circuit card into ACT mode by
    flipping the MBR key on the active GT (PH-
    GT09) card. Refer to Section 12.1.6, Manual
    System Changeover of Speech Path System, in
    Chapter 6.
    Initialize the system by pressing the START
    button on the TOPU.
    Check to see if a station-to-station connection
    can be set up to identify a TSW circuit card re-
    sponsible for the fault.
    Perform the above check by extracting the TSW
    circuit cards individually.
    Check to see if the fault occurs by
    extracting MUX circuit cards one by one.Replace the MUX circuit card referring to Sec-
    tion 3.3.2, MUX Card Replacement Procedure,
    in Chapter 4.
    Set the MUX circuit card into ACT mode by
    flipping the MBR key on the active GT (PH-
    GT09) card. Refer to Section 12.1.6, Manual
    System Changeover of Speech Path System, in
    Chapter 6.
    Check to see if a station-to-station connection
    can be set up and identify a TSW circuit card re-
    sponsible for the fault.
    Perform the above check by extracting the
    MUX circuit cards individually.
    ATTENTIONContents
    Static Sensitive
    Handling
    Precautions Required
    A
    END 
    						
    							CHAPTER 5 NDA-24238
    Page 356
    Revision 3.0
    FAULT REPAIR PROCEDURES
    6. CONTROL SYSTEM FAULT
    This section explains the fault repair procedure for the control system listed in Table 5-8.
    6.1 Check Point
    When repairing the control system, check the status of the following lamps:
    CPR
    GT
     TSW
    MUX
     EMA circuit cards
    Figure 5-9 shows a block diagram of the CPU controlling block, where CPU #0 is active.
    Table 5-8  Control System Fault Situation
    FAULTY SITUATION REFERENCE SECTION
    Fault occurs occasionally at the STBY side.Section 6.2, Control System Fault - Fault Occurs Intermittently
    STBY side is faulty.Section 6.3, Control System Fault - STBY Side Is Faulty 
    						
    							NDA-24238 CHAPTER 5
    Page 357
    Revision 3.0
    FAULT REPAIR PROCEDURES
    Figure 5-9   CPU Controlling Block Diagram
    LPM
    EMAIOC /
    MISC
    ISAGT 0
    LANI
    PWR
    PWR
    CPU 0
    MEMORY
    PCI BUSISA BUS
    CPU board CPR
    CPU clock
       CPR
    (ST-BY)
    Reset Signal
    MISC BUS
    MISC BUS
    ISAGT 1 T
    MT
    LC/TRK
    MUX
    MUX
    LC/TRK
    PM BUS
    PM BUS
    LC/TRK
    MUX
    MUX
    LC/TRK
    PM BUS
    PM BUS
    LC/TRK
    MUX
    MUX
    LC/TRK
    PM BUS
    PM BUS
    LC/TRK
    MUX
    MUX
    LC/TRK
    PM BUS
    PM BUS
    IMG0
    PIM 3
    PIM 2
    PIM 1
    PIM 0
    LC/TRK
    MUX
    MUX
    LC/TRK
    PM BUS
    PM BUS
    LC/TRK
    MUX
    MUX
    LC/TRK
    PM BUS
    PM BUS
    LC/TRK
    MUX
    MUX
    LC/TRK
    PM BUS
    PM BUS
    LC/TRK
    MUX
    MUX
    LC/TRK
    PM BUS
    PM BUS
    IMG1
    PIM 3
    PIM 2
    PIM 1
    PIM 0
    Note 1:  The circuit cards, drawn by dotted lines, indicate they are in STBY state. These cards (TSW, MUX and
                   DLKC) are totally  changed over to the ACT mode, when the MBR key of the active GT (PH-GT09) card is 
                   once flipped. However, PLO (PH-CK16/17/16-A/17-A) is independent and not affected by the development.
    Symbols
              :  Controlling Routes of CPU                         :  Cable
              :  Circuit card (active)                  :  Circuit card (STBY)
                :  External Cable                  :  Clock Oscillator
                :  Signral
    EMA:      PH-PC40                      ISAGT:     PZ-GT13
    LANI:      PZ-PC19                      GT:           PH-GT09
    IOC:        PH-IO24                       TSW:        PH-SW12
    DLKC:    PH-PC20                      PLO:        PH-CK16/17/16-A/17-A
    MUX:      PH-PC36 
    TSWM  
    TSW 00TSW 10TSW 11TSW 01
    PLO 0PLO 1
    DLKC 1DLKC 0DLKC 1
    GT 1
    GT 0
    MISC BUS
    MISC BUS
    MISC BUS
    MISC BUSMISC BUS MISC BUS
    TSW
        02TSW 
        03TSW
        13TSW
        12
    To IMG 2To IMG 3To IMG 3 To IMG 2
    IOP1
    IOP0
    TSW/INT TSW/INT TSW/INTTSW/INT
    M
    U
    X003
    M
    U
    X002
    M
    U
    X001
    M
    U
    X000
    M
    U
    X013
    M
    U
    X012
    M
    U
    X011
    M
    U
    X010
    M
    U
    X100
    M
    U
    X101
    M
    U
    X102
    M
    U
    X103
    M
    U
    X110
    M
    U
    X111
    M
    U
    X112
    M
    U
    X113
      TSW
       /INT  TSW
       /INT  TSW
       /INT   TSW
       /INT
    Note 1
    Note 3
    Note 2
    Note 2:  If the ACT/STBY of CPU is once changed over, the system of GT (in TSWM) also changes over.
    Note 3:  Though an external cable is physically connected between ISAGT0 and GT1, the actual control signal is
    sent/received only between ISAGT0 and GT0. This is because GT0 and GT1 are having a multiple connection
    
                   on the backboard side. (Refer to Chapter 6, Section 12.)
    BUS
    TSW I/O BUSTSW I/O  
    						
    							CHAPTER 5 NDA-24238
    Page 358
    Revision 3.0
    FAULT REPAIR PROCEDURES
    Figure 5-9  CPU Controlling Block Diagram (Continued)
    LPM
    EMAIOC /
    MISC
    ISAGT 0
    LANI
    PWR
    PWR
    CPU 0
    MEMORY
    PCI BUSISA BUS
    CPU board CPR
    CPU clock
       CPR
    (ST-BY)
    Reset Signal
    MISC BUS
    MISC BUS
    ISAGT 1 T
    MT
    LC/TRK
    MUX
    MUX
    LC/TRK
    PM BUS
    PM BUS
    LC/TRK
    MUX
    MUX
    LC/TRK
    PM BUS
    PM BUS
    LC/TRK
    MUX
    MUX
    LC/TRK
    PM BUS
    PM BUS
    LC/TRK
    MUX
    MUX
    LC/TRK
    PM BUS
    PM BUS
    IMG2
    PIM 3
    PIM 2
    PIM 1
    PIM 0
    LC/TRK
    MUX
    MUX
    LC/TRK
    PM BUS
    PM BUS
    LC/TRK
    MUX
    MUX
    LC/TRK
    PM BUS
    PM BUS
    LC/TRK
    MUX
    MUX
    LC/TRK
    PM BUS
    PM BUS
    LC/TRK
    MUX
    MUX
    LC/TRK
    PM BUS
    PM BUS
    IMG3
    PIM 3
    PIM 2
    PIM 1
    PIM 0
    Note 1:  The circuit cards, drawn by dotted lines, indicate they are in STBY state. These cards (TSW, MUX and
                   DLKC) are totally  changed over to the ACT mode, when the MBR key of the active GT (PH-GT09) card is 
                   once flipped. However, PLO (PH-CK16/17/16-A/17-A) is independent and not affected by the development.
    Symbols
              :  Controlling Routes of CPU                    :  Cable
              :  Circuit card (active)              :  Circuit card (STBY)
                :  External Cable                  :  Clock Oscillator
                :  Signral
    EMA:      PH-PC40                      ISAGT:     PZ-GT13
    LANI:      PZ-PC19                      GT:           PH-GT09
    IOC:        PH-IO24                       TSW:        PH-SW12
    DLKC:     PH-PC20                      PLO:        PH-CK16/17/16-A/17-A 
    MUX:      PH-PC36 
    TSWM  
    TSW 02TSW 12TSW 13TSW 03
    PLO 0PLO 1
    DLKC 1DLKC 0DLKC 1
    GT 1
    GT 0
    MISC BUS
    MISC BUS
    MISC BUS
    MISC BUSMISC BUS MISC BUSTSW I/O TSW I/O 
    TSW
        00TSW 
        01TSW
        11TSW
        10
    To IMG 0To IMG 1To IMG 1 To IMG 0
    IOP1
    IOP0
    TSW/INT TSW/INT TSW/INTTSW/INT
    M
    U
    X023
    M
    U
    X022
    M
    U
    X021
    M
    U
    X020
    M
    U
    X033
    M
    U
    X032
    M
    U
    X031
    M
    U
    X030
    M
    U
    X120
    M
    U
    X121
    M
    U
    X122
    M
    U
    X123
    M
    U
    X130
    M
    U
    X131
    M
    U
    X132
    M
    U
    X133
      TSW
       /INT  TSW
       /INT  TSW
       /INT   TSW
       /INT
    Note 1
    Note 3
    Note 2
    Note 2:  If the ACT/STBY of CPU is once changed over, the system of GT (in TSWM) also changes over.
    Note 3:  Though an external cable is physically connected between ISAGT0 and GT1, the actual control signal is
    sent/received only between ISAGT0 and GT0. This is because GT0 and GT1 are having a multiple connection
    
                   on the backboard side. (Refer to Chapter 6, Section 12.)
    BUSBUS
    (ST-BY) 
    						
    							NDA-24238 CHAPTER 5
    Page 359
    Revision 3.0
    FAULT REPAIR PROCEDURES
    6.2 Control System Fault - Fault Occurs Intermittently
    Faulty Situation:
     Fault occurs intermittently at ACT side in the dual configuration system.
     Fault occurs intermittently in the single configuration system.
    [0-C] ~ [0-K] CPU Failure
    [1-C] Both TSW Write Failure
    [1-D] TSW Write Failure
    [3-D], [3-E] Lock-Up Failure (Permanent/Temporary)
    (1) For Dual Configuration
    Replace ACT-side related circuit card
    (CPU, GT, TSW, MUX, EMA) with a spare,
    and check.Replace the circuit cards (CPU, GT, TSW, MUX,
    EMA) individually referring to the following sec-
    tions in Chapter 4:
    Section 1.3.1, CPR Replacement Procedure
    Section 1.3.2, EMA Card Replacement
    Procedure 
    Section 2.3.1, GT Card Replacement
    Procedure
    Section 2.3.2, TSW Card Replacement
    Procedure
    Section 3.3.2, MUX Card Replacement
    Procedure
    Place the circuit card (CPU, GT, TSW, MUX)
    into ACT mode individually by executing CPU or
    Speech Path System changeover. Refer to Section
    12.1.6, Manual System Changeover of Speech
    Path System, in Chapter 6.
    Check to see if a station-to-station connection can
    be set up and identify a circuit card responsible
    for the fault.
    After all the steps are complete, place the whole
    circuit card (CPU, GT, TSW, MUX examined
    above) to the ACT mode. Refer to Section 12.1.6,
    Manual System Changeover of Speech Path Sys-
    tem, in Chapter 6.
    When a fault is not indicated, set the
    faulty system to STBY mode. Refer
    to Section 12, System Control Pro-
    cedures, in Chapter 6.Check to see if a fault is indicated.
    ATTENTIONContents
    Static Sensitive
    Handling
    Precautions Required
    START
    A 
    						
    							CHAPTER 5 NDA-24238
    Page 360
    Revision 3.0
    FAULT REPAIR PROCEDURES
    (2) For Single Configuration
    Replace the related circuit card (CPU, GT,
    TSW, MUX, EMA) with a spare, and check.Replace the circuit card (CPU, GT, TSW, MUX, 
    EMA) individually by referring to the following 
    sections in Chapter 4:
    Section 1.3.1, CPR Replacement Procedure
    Section 1.3.2, EMA Card Replacement
    Procedure
    Section 2.3.1, GT Card Replacement
    Procedure
    Section 2.3.2, TSW Card Replacement
    Procedure
    Section 3.3.2, MUX Card Replacement
    Procedure
    Initialize the system by pressing the START
    button on the TOPU and check to see if a
    station-to-station connection can be set up and
    identify a circuit card responsible for the fault.
    AT T E N T I O NContents
    Static Sensitive
    Handling
    Precautions Required
    A
    END 
    						
    							NDA-24238 CHAPTER 5
    Page 361
    Revision 3.0
    FAULT REPAIR PROCEDURES
    6.3 Control System Fault - STBY Side Is Faulty
    Faulty Situation:
     Fault has occurred in the STBY side of dual configuration system.
    [0-I] STBY CPU Failure
     The ACT side has become faulty, and system changeover has executed.
    [0-C], [0-H], [0-J] Processor Failure (ACT side)
    Replace STBY side related circuit cards
    (CPU, GT, TSW, MUX, EMA) with a spare,
    and check.Replace the circuit cards (CPU, GT, TSW, 
    MUX, EMA) individually by referring to the 
    following paragraphs in Chapter 4:
    Section 1.3.1, CPR Replacement Procedure
    Section 1.3.2, EMA Card Replacement
    Procedure
    Section 2.3.1, GT Card Replacement
    Procedure
    Section 2.3.2, TSW Card Replacement
    Procedure
    Section 3.3.2, MUX Card Replacement
    Procedure
    Place the circuit cards (CPU, GT, TSW, MUX)
    into ACT mode by executing CPU changeover.
    Refer to Section 12.1.6, Manual System
    Changeover of Speech Path System, in Chapter
    6.
    Check to see if a station-to-station connection
    can be set up to identify the circuit card
    responsible for the fault.
    When a fault is not indicated, set 
    the faulty systems to STBY side in 
    advance by executing CPU 
    changeover. Refer to Section 12, 
    System Control Procedures, in 
    Chapter 6.
    ATTENTIONContents
    Static Sensitive
    Handling
    Precautions Required
    START
    END 
    						
    							CHAPTER 5 NDA-24238
    Page 362
    Revision 3.0
    FAULT REPAIR PROCEDURES
    Figure 5-10   Alarm Bus Cable Connections Diagram
    IMG 0
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 3
    ALMA
    ALMB
    DSPLTO P U
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 0
    ALMA
    ALMB
    LED3
    LED2
    LED1
    ALM3
    MUSIC
    ALM2
    ALM1EMA
    EMAFH
    ALM
    ALM
    DSP
    PA L M 1
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 1
    ALMA
    ALMB
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 2
    ALMA
    ALMB
    PZ-DK222
    IMG 1
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 3
    ALMA
    ALMB
    DSPMTOPU
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 0
    ALMA
    ALMB
    TSWM
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 1
    ALMA
    ALMB
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 2
    ALMA
    ALMB
    PZ-DK222
    EMA
    PA L MPWR1LANI 1GT 1
    PWR0LANI 0GT 0
    PZ-PW92
    PZ-PW92
    PA L M 0PA L M
    - Symbols -
               :  
    Alarm related connector                                     :Cable EMA:  PH-PC40                     MUX:  PH-PC36        
              :  Circuit card  :  External Cable              LANI:  PZ-PC19                     ISAGT:  PZ-GT13
    LPM (REAR VIEW) LPM (FRONT VIEW) REAR VIEW 
    						
    							NDA-24238 CHAPTER 5
    Page 363
    Revision 3.0
    FAULT REPAIR PROCEDURES
    Figure 5-10  Alarm Bus Cable Connections Diagram (Continued)
    IMG 2
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 3
    ALMA
    ALMB
    DSPM     TOPU
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 0
    ALMA
    ALMB
    LED3
    LED2
    LED1
    ALM3
    MUSIC
    ALM2
    ALM1
    DSP
    DSP
    PA L M 1
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 1
    ALMA
    ALMB
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 2
    ALMA
    ALMB
    PZ-DK222
    IMG 3
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 3
    ALMA
    ALMB
    DSPMTO P U
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 0
    ALMA
    ALMB
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 1
    ALMA
    ALMB
    MUX 0LC/TRKMUX 1PWR
    DPWR
    PIM 2
    ALMA
    ALMB
    PZ-DK222
    EMA
    PA L MPWR1LANI 1GT 1
    PWR0LANI 0GT 0
    PZ-PW92
    PZ-PW92
    PA L M 0PA L M
    LPM (REAR VIEW) LPM (FRONT VIEW)
    - Symbols -
             :  
    Alarm related connector                                     :Cable EMA:  PH-PC40                     MUX:  PH-PC36        
              :  Circuit card  :  External Cable              LANI:  PZ-PC19                     ISAGT:  PZ-GT13 
    						
    All NEC manuals Comments (0)

    Related Manuals for NEC Neax 2400 Imx System Operations And Maintenance Manual