Home > NEC > Communications System > NEC Neax 2400 Imx System Operations And Maintenance Manual

NEC Neax 2400 Imx System Operations And Maintenance Manual

    Download as PDF Print this page Share this page

    Have a look at the manual NEC Neax 2400 Imx System Operations And Maintenance Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 1168 NEC manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    Page
    of 647
    							CHAPTER 5 NDA-24238
    Page 374
    Revision 3.0
    FAULT REPAIR PROCEDURES
    9. FAN UNIT FAULT
    This section explains the fault repair procedure where a fan in the Fan Unit (FANU) does not operate.
    9.1 Check Point
    (1) When repairing a FANU fault, exercise care about the following conditions. The fans (a total of 3) are
    activated by operating the PWR SW key located on the PZ-M369. The conditions for starting the fan are
    as follows:
     With PWR SW key for the fan set to ON position: Always operating
     With PWR SW key for the fan set to AUTO position: Starts  operating  if  the  in-frame  tempera-
    ture is higher than 40°C (104°F); stops op-
    erating at temperatures lower than 32°C
    (90°F). See Figure 5-19.
    (2) When replacing the FANU with a spare, refer to Section 4., Fan Unit Replacement, in Chapter 4.
    Figure 5-19   Circuit Diagram of Fan Unit and Thermal Unit
    FAN 0FAN 1FAN 2
    Power
    Filter Fan Unit
    FC0 FC1 FC2
    POW
    RLFUSE ALM
    -48V
    G
    FEFUSE
    FAN1
    3
    4
    2 To PIM
    ON
    OFF
    AUTO
    rl
    F
    FAN START Switch
    Thermal Unit
    Thermal
    Relay
    32
    o C
    89o F
    Thermal
    Relay
    40
    o  C
    104o F
     
    Thermal
    Relay
    70
    o  C
    158o F
    Thermal
    Relay
    60
    o  C
    140o F
    RL rl
    GFEFA
    LM
    FAN
    N P
    -48V
    EMNMJ
    rl
    To PIM To Display
    Section
    of TOPU 
    						
    							NDA-24238 CHAPTER 5
    Page 375
    Revision 3.0
    FAULT REPAIR PROCEDURES
    9.2 Fan Unit Fault
    Set the PWR SW key on the PZ-M369 to the ON position.
    When the fan spins
    Set PWR SW key to AUTO position, and short the thermal relay of the thermal
    unit.
    If the fan does not
    operateCheck the connector cable between
    the FANU and the thermal unit.
    If the fan operates Replace thermal relay with a spare.
    Disconnect the fan
    connector of the cable for
    the thermal unit.
    Replace thermal relay with
    a spare.
    Connect the fan connector.
    If the fan does not operate
    Check the voltage (DC -48 V) at connectors FC0 through FC2.
    If the voltage is less
    than -48 VCheck the connector cable (fan con-
    nector) between the FANU and the
    PIM.
    If the voltage is -48 V Replace the fan with a spare. Refer to
    Section 4., Fan Unit Replacement, in
    Chapter 4.
    After the fault is corrected, set PWR SW key to the AUTO position. If the fans are to continue operating
    constantly, set PWR SW key to the ON position. START
    END 
    						
    							CHAPTER 5 NDA-24238
    Page 376
    Revision 3.0
    FAULT REPAIR PROCEDURES
    10. TONE FAULT
    This section explains the fault repair procedure when any of the various tones cannot be heard in the whole
    system.
    10.1 Check Point
    When repairing a tone fault, consider that the tone generator circuit is equipped in the TSW circuit card
    and supplies tone.
    Figure 5-20 shows an example of the related trunking for dial tone connection.
    Figure 5-20   Dial Tone Connection
    TSW
    DT
    LC
    Dial
    Tone
    ORT 
    						
    							NDA-24238 CHAPTER 5
    Page 377
    Revision 3.0
    FAULT REPAIR PROCEDURES
    10.2 Tone Fault
    Replace the TSW circuit card with a spare
    and check.
    When only Hold Tone is faulty
    If External Hold Tone source is in
    useCheck the external equipment which sends out
    hold tone.
    Check cross connections on the MDF. Figure 5-
    21 shows a block diagram of external hold tone
    supply (optional).
    Replace the EMA/PLO circuit
    card with a spare.
    Note:When system is 1-IMG
    configuration, replace
    EMA card. Otherwise,
    replace PLO card.Set the MB switch of the EMA/PLO circuit
    card to UP side and extract the circuit card from
    its mounting slot.
    If the EMA card is removed
    from the system while the
    system is in operation under
    the control of the CPU #1, the
    system will reset and stop all
    call processing. Refer to
    Section 1.3.2, EMA Card
    Replacement Procedure, in
    Chapter 4, for detailed
    instructions.Make necessary switch settings on the new
    circuit card, referring to the card extracted.
    Set the MB switch of the new circuit card UP
    and insert the circuit card into its mounting slot.
    Set the MB switch DOWN.
    Initialize the system and confirm the tone.
    ATTENTIONContents
    Static Sensitive
    Handling
    Precautions Required
    START
    END
    WA R N I N G 
    						
    							CHAPTER 5 NDA-24238
    Page 378
    Revision 3.0
    FAULT REPAIR PROCEDURES
    Figure 5-21   External Hold Tone Supply Block Diagram Note:
    If PH-CK16-A/PH-CK17-A is used, multiple connections are made between PLO#0 and PLO#1.
    Refer to the description of PH-CK16-A or PH-CK17-A in the Circuit Card Manual.
    PLO 1
    External    Tone
     Source
    (Option)
    To Music 
    Connector
    for EMA
    Card (IMG0)
    MDF TSWM PIM 0 PIM 2 PIM 3
    IMG1
    PIM 1
    Symbols
    :  Circuit Card
    :  Connector
    Note
    TSW 10
    TSW 00
    TSW 11
    TSW 01
    TSW 12
    TSW 02
    TSW 13
    TSW 03Melody
    ICPLO 0EMAFH
    EMA :  PH-PC40 PLO :  PH-CK16/17/16-A/17-A TSW :  PH-SW12 : External Cable 
    						
    							NDA-24238 CHAPTER 5
    Page 379
    Revision 3.0
    FAULT REPAIR PROCEDURES
    11. SYSTEM DOWN FAULT
    This section explains the fault repair procedure when both the CPU and TSW systems are faulty. Figure 5-22
    shows the sequence of repair for system down fault.
    Figure 5-22   System Down Fault Repair Sequence
    When cause for the fault cannot be identified:
    Section 11.1When faulty circuit cards can be assumed from
    system message: Section 11.2
    Check power supply.
    Minimize system configuration.
    Execute system initialization and see if the mode becomes ON-LINE.Replace doubtful circuit card with a spare. 
    						
    							CHAPTER 5 NDA-24238
    Page 380
    Revision 3.0
    FAULT REPAIR PROCEDURES
    11.1 When Cause for Fault Cannot Be Identified
    Check power supply circuits. Check voltage (DC: -48V, ±5V) at LOAD side 
    of the rectifier.
    Confirm that NFB (circuit breaker) on all PWR 
    supplies is at ON position (UP side).
    Check to see if there is any PWR supply to 
    which the alarm lamp illuminates.
    System Initialization by loading office data
    and program data from the hard disk (Refer
    to Chapter 6.)
    Service connections such as 
    station-to-station connection 
    cannot be set up.See “Check by Minimizing the System 
    Configuration” on the next page.
    Service connections such as 
    station-to-station connection can 
    be set up.Data in the memory is temporarily destroyed. 
    Observe the situation for a while. START
    A 
    						
    							NDA-24238 CHAPTER 5
    Page 381
    Revision 3.0
    FAULT REPAIR PROCEDURES
    (1) Check by minimizing the system configuration
    Mount only the basic circuit cards in CPU 
    No. 0 system and initialize.Remove all circuit cards from CPU No. 0
    system except the basic circuit cards.
    Circuit cards to be mounted are as follows:
    CPU, EMA, TSW, MUX
    (EMA: PH-PC40, TSW: PH-SW12, MUX:
    PH-PC36)
    On the CPU Display Panel (DSP), set its SENSE
    switch to “1.”
    Press Reset (RST) button on the DSP.
    CPU OPE lamp should be illuminated on the
    DSP.
    Initialization cannot be made. Check by replacing the basic circuit cards indi-
    vidually.
    Set MB switch of the circuit card UP and
    extract the circuit card from its mounting
    slot.
    Make necessary switch settings on the new
    circuit card.
    Set MB switch of the new circuit card UP
    and insert the circuit card into its mounting
    slot.
    Set MB switch DOWN.
    On the DSP (CPU), set SENSE switch to “1.”
    Press RST button on the DSP.
    CPU OPE lamp should illuminate on the DSP.
    If CPU OPE lamp of the DSP does not
    illuminate, replace next circuit card and check it.
    (Repeat the above steps for all basic circuit
    cards.)
    END 
    						
    							CHAPTER 5 NDA-24238
    Page 382
    Revision 3.0
    FAULT REPAIR PROCEDURES
    11.2 When Faulty Circuit Cards Can Be Assumed From System Message
    Faulty Situation:
    When the system is down with message [0-C] ~ [0-J] indicated, faulty circuit cards can be assumed from
    the message detail data. Replace circuit cards with spares.
    Replace  faulty  circuit  card  with  a  spare. Set MB switch UP and extract the circuit card
    from its mounting slot.
    Make necessary switch settings on the new
    circuit card.
    Set the MB switch UP and insert the circuit
    card into its mounting slot.
    Set the MB switch DOWN.
    Initialize the system by loading the office data
    and program data from the hard disk.
    Confirm that service connections such as
    station-to-station connection can be set up. START
    END 
    						
    							NDA-24238 CHAPTER 5
    Page 383
    Revision 3.0
    FAULT REPAIR PROCEDURES
    12. COMMON CHANNEL INTEROFFICE SIGNALING (CCIS) LINE FAULT
    This section explains the fault repair procedure when any of the faults shown in Table 5-11 occur to a specific
    CCIS line.
    12.1 Check Point
    When repairing a CCIS Line fault, consider the following items:
    (1) Check alarm lamps on the CCH or CCT circuit card.
    (2) Refer to Figure 5-23, and check the cable connection.
    12.2 CCIS Line Control
    The CCH/CCT circuit card controls the signal link (digital) of the interoffice common channel signaling
    system and transmitting/receiving call processing information. The signal link controls permit normal
    transmission and reception of call processing information.
    A break in signal links is detected, then restored to establish signal links. The call processing information
    is converted into No. 7 signal format for channel 1 (any channel) of the DTI before being transmitted to a
    distant office. Figure 5-23 shows the CCIS line control route.
    Figure 5-23   Controlling CCIS Line Table 5-11  CCIS Line Fault Situation
    FAULTY SITUATION REFERENCE SECTION
    A specific CCH/CCT card is faulty.Section 12.3, Specific CCH/CCT Card Is Faulty
    When the signal transmission line is a digital line, transmitting/
    receiving of control signals cannot be performed.Section 12.4, Fault of CCH, DTI and Related Flat 
    Cable
    CPUTSW
    MUX
    CCH
    CCT
    DTI
    LT Cable Front
    CableMDF
    To CCIS Line LT Cable 
    						
    All NEC manuals Comments (0)

    Related Manuals for NEC Neax 2400 Imx System Operations And Maintenance Manual