Have a look at the manual Lucent Technologies DEFINITY Enterprise Communications Server Release 8.2 Installation And Test For Single-Carrier Cabinets Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 413 Lucent Technologies manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-13 Connect AC Power 1 Connect AC Power Set the Ringer Frequency The d efault ring er freq uenc y setting on the 1217A p ower sup p ly for North Americ a is 20 Hz and the international setting c an b e either 20 Hz or 25 Hz. To set the ring er freq uenc y on the 1217A p ower sup p ly: !CAUTION: When add ing or rep lac ing any hard ware, b e sure to g round yourself against elec trostatic d isc harg e (ESD) b y wearing a g round ed wrist strap . 1. Power d own AUDIX and any other c irc uit p ac k that mig ht b e running an application. 2. Power d own the c ab inet. 3. Release b oth latc hes on the p ower supp ly and slid e the unit out of the c ab inet. 4. Observe the ring freq uenc y switc h lab el on the sid e of the p ower sup p ly and loc ate the switc h on the b ottom. 5. Set the ring frequenc y selec t switc h to the ap p rop riate freq uenc y setting . 6. Slid e the p ower sup p ly bac k into the slot and ensure that b oth latc hes snap c losed . Connect the Power Cord into the Power Receptacle 1. Provid e one rec ep tac le per Sing le-Carrier Cab inet. 2. Verify the c irc uit b reakers are OFF. 3. Plug the c ab inet AC p ower c ord into the AC p ower rec eptac le on the rear of eac h c ab inet. 4. Plug the op p osite end of eac h AC p ower c ord into the ap p ropriate AC p ower rec ep tac le in the eq uip ment room. NOTE: Loop the exc ess c ord and tie wrap it to the b ac k c over to p revent ac c idental unp lug g ing .
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-14 Connect DC Power 1 Connect DC Power The following proc ed ures app ly to b oth the Proc essor Port Networks (PPN) and Exp a n si o n Po r t N e t w o rk s (EPN ) . DC Power Connections A 30 foot (9 m) c able c onnec ts to eac h c ab inet. A sp ec ial c onnec tor on one end of the c ab le is p lug g ed into the c ab inet p ower c onnec tor. The c ab le must b e c ut to leng th and terminated insid e the J58890R DC Power Cab inet. Eac h rec tifier assemb ly c an supp ly up to 50 Amp s of DC c urrent. A minimum of two rec tifiers are installed in eac h DC Power Cabinet to sup p ly a total of 100 Amp s. A third rec tifier assemb ly c an b e installed and is used as a bac kup (N+ 1). Eac h Sing le-Carrier Cab inet c an p ull up to 18 Amp s. Up to three DC Power Cabinets can be stacked to supply power to Single-Carrier Cabinet stacks. Fi g u re 1 - 6 shows a typ ic al p ower and g round layout for a DC-powered system without a J58890CG DC Power Distrib ution Unit. The J58890CG is req uired if the d istanc e b etween the DC Power Cab inet(s) is g reater than 30 feet (9 m). Fi g u re 1-7 shows a typical power and ground layout for a DC-powered system containing a DC power distribution unit. Connect AC Power to DC Power Cabinet 1. Ensure the assoc iated c irc uit breakers at the AC p ower p anel are OFF. 2. Have an elec tric ian c onnec t AC p ower lead s to the rec tifiers using the instruc tions p rovid ed with the rec tifiers in the DC Power Cab inet. Eac h rec tifier should have its own b ranc h c irc uit. Terminate lead s on the AC INPUT terminal b loc k of eac h rec tifier. !CAUTION: Power is p resent in the c ab inet even if the AC p ower c ab le is unp lug g ed . Turn off the main c irc uit b reaker on the front of the c ab inet when proc ed ures require ALL p ower to b e removed from the c ab inet.
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-15 Connect DC Power 1 DC Power Connections Figure 1-6. Typical DC Power Connections Figure Notes 1. System Cab inet Stac k 2. DC Power Cabinet 3. White Wires 4. Green Ground Wires and Blac k Wires Connec t to the -48 VDC Return Bus 5. -48 VDC Bus 6. Connec t White Wires to Circ uit Breakers 7. DC Power Cab le (H600-436, G1) to Power Connec tor on Eac h Cab inet. Cut to Leng th and Crimp a Ring Terminal Onto Eac h Wire 8. 30 Feet (9 m) Maximum 9. Route Cab les Throug h Slid ing Door 10. Circ uit Breaker 11. Sup plied #10-32 Sc rew, #10 Star Washer, and #10-32 Hex Nut 12. Inset Showing DC Power Connec tor (Male)
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-16 Connect DC Power 1 DC Power Connections with DC Distribution Unit A 10 foot (3 meter) p ower c ord is eq uip p ed with the ap prop riate c onnec tors. In the configuration shown in Fi g u re 1 - 7 , eac h c ab inet stac k has a DC Power Distribution Unit assoc iated with it. Figure 1-7. Connections Using DC Power Distribution Unit Figure Notes 1. System Cab inet Stac k 2. DC Power Cabinet 3. DC Power Distrib ution Unit (Position to the Rig ht of the Cab inet Stac k) 4. White Wire (Connec t to Circ uit Breaker). See Inset. 5. Green Ground Wire and Blac k Wire Connec t to the -48 VDC Return Bus 6. -48 VDC Bus 7. Inset 8. 12 Inc hes (30.5 c m) From Floor to DC Power Distrib ution Unit9. DC Power Cab le to Power Connec tor on Eac h Cabinet 10. DC Power Distrib ution Unit Power Cord (Route to Rear of DC Power Cab inet) 11. Route Power Cord Throug h Slid ing Door 12. Circ uit Breaker 13. Supp lied #10-32 Sc rew, #10 Star Washer, and #10-32 Hex Nut 14. Inset Showing DC Power Connec tor (Male)
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-17 Connect DC Power 1 Stacking DC Power Cabinets Up to three DC Power Cab inets c an be stac ked to sup p ly p ower to Sing le-Carrier Cab inet stac ks. See Fig ure 1-8 . Figure 1-8. DC Power Cabinet Stack — Rear Figure Notes 1. DC Power Cabinet Stac k 2. DC Power Cables Daisy Chained Between DC Power Cab inets 3. Connec t to -48 VDC Bus4. Connec t to -48 VDC Return Bus 5. Inset Ap plies to -48 VDC and -48 VDC Return Buses in All Three DC Power Cab inets pwrdist4 RBP 052896
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-18 Connect Battery Cabinet 1 Connect Battery Cabinet Fi g u re 1 - 9 shows typ ic al c onnec tions from the DC Battery Cab inet to the DC Power Cab inet. Figure 1-9. DC Battery to DC Power Cabinet Connections !CAUTION: Power is present in the c ab inet even if the AC p ower c ab le is unp lug g ed . Turn off the main c irc uit b reaker on the front of the c abinet when proc ed ures req uire ALL p ower to b e removed from the c abinet. Figure Notes 1. DC Power Cabinet 2. Connec t Red DC Power Cab le to -48 VDC Return Bus 3. Connec t Blac k DC Power Cab le to -48 VDC Bus4. Inset Ap p lies to -48 VDC Buses and -48 VDC Return Buses 5. Battery Cab inet 6. DC Power Cab les (Red and Blac k) pwrdist5 RBP 052896
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-19 Connect Optional Battery Leads 1 Connect Optional Battery Leads To p revent the internal b atteries from d isc harg ing , the Control Cab inet is ship p ed with the b attery lead s disc onnec ted . Figure 1-10. Control Cabinet Battery Location — Right Side 1. Set the c irc uit b reakers OFF. See Fig ure 1-10 . 2. Connec t the b attery lead s. The battery is near the top of the c arrier toward the front-rig ht. The battery leads are loc ated next to the b attery and are ac c essib le from the front of the c ab inet. Figure Notes 1. Battery 2. Battery Lead Connec tor3. Circ uit Breakers (Loc ated Between Plates) 4. Cab inet Sing le-Point Ground Bloc k 3 4 1 2 4_3 LJK 031096
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-20 Connect AC Power to Stratum 3 Clock Cabinet 1 Connect AC Power to Stratum 3 Clock Cabinet The c loc k c ab inet requires a 120 VAC, 15 Amp rec ep tac le. The g reen wire g round p rovid ed b y the rec ep tac le is suffic ient. The c loc k c ab inet d oes not req uire a g round c onnec tion bac k to the sing le-p oint ground . Check and Connect Commercial AC Power Before p owering up the system, c hec k the AC p ower using a KS-20599 d ig ital voltmeter (DVM) (or eq uivalent). 1. Set the DVM to the 250 volt range. 2. Carefully measure the voltage b etween the hot and neutral sid e of the rec ep tac le. The neutral wire is white, the hot wire is b lac k. 3. Verify the meter read s 106 to 128 VAC. If not, have a q ualified elec tric ian c orrec t the p rob lem. 4. Measure the voltag e b etween the neutral and ground sid e of the rec ep tac le. The g round wire is green. 5. Verify the meter reads 0 VAC. If not, have a q ualified elec tric ian c orrec t the problem. 6. Set all c ab inet p ower mod ules OFF. Plug the AC p ower c ab le into the rec ep tac le. Connect DC Power and Ground to Stratum 3 Clock Cabinet The c loc k c ab inet should b e p owered from the same DC p ower p lant as the DEFINITY System. The c loc k c ab inet must b e g rounded to the DC p ower p lant. Connect Clock Cabinet Grounding 1. Measure and cut a 6 AWG (#40) (4 mm2) wire long enoug h to reac h from the c loc k c abinet to the g round disc harg e bar in the DC p ower p lant. 2. Insert one end of the wire into the g round lug on the c loc k c ab inet and tig hten the sc rew. 3. Attac h the lug to the rec ep tac le c over. Be sure the lug and c ab inet g round wires c onnec t to sep arate sc rews on the rec ep tac le c over. 4. Route the ground wire to the DC p ower p lant and c onnec t to DISCH GRD in the c ab inet.
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-21 Connect Time Division Multiplexing Bus Cables 1 Connect Stratum 3 Clock DC Power 1. Set the c loc k c ab inet c irc uit b reaker at the DC p ower p lant OFF. 2. At the c loc k c ab inet, c onnec t a 6 AWG (#40) (4 mm 2) g round wire to the -48V terminal on the terminal strip. 3. At the c loc k c ab inet, c onnec t a 6 AWG (#40) (4 mm 2) wire to the -48VRTN terminal on the terminal strip . 4. Route the wires out of the c abinet and to the DC power p lant. 5. At the DC p ower plant, c onnec t the -48V wire to the DC OUTPUT c irc uit breaker. 6. At the DC p ower plant, c onnec t the -48VRTN wire to the DISCH GRD b ar. Connect Time Division Multiplexing Bus Cables If the c ab inet stac k c ontains only one Sing le-Carrier Cab inet, skip this sec tion and p roc eed to ‘‘Verify Port Cabinet Address Plugs’’ on page 1-26 . Loc ate the white fabric -c overed Time Division Multip lexing (TDM) b us c ab le on the rear of the c ab inets. Standard Reliability Processor Port Network One c ab inet stac k: 1. Remove the Time Division Multiplexing (TDM) Bus Terminator (AHF110) from Slot 18 of the Control Cab inet (Proc essor Port Network (PPN)) and move it to Slot 17 on the top Port Cab inet. See Fig ure 1-11 . 2. Connect the supplied Time Division Multiplexing (TDM) Bus Cables (WP-91716 L3) as shown in Fig ure 1-11 .
DEFINITY Enterprise Communication Server Release 8.2 Installation and Test for Single-Carrier Cabinets 555-233-120 Issue 1 April 2000 Install and Connect the Cabinets 1-22 Connect Time Division Multiplexing Bus Cables 1 High or Critical Reliability Processor Port Network Two cabinet stacks: 1. Remove the Time Division Multip lexing (TDM) Bus Terminator from Slot 18 of Control Cab inet A (Proc essor Port Network (PPN)) and move it to Slot 18 of Control Cab inet B. See Fi g u re 1 - 1 2 . 2. Connect the supplied Time Division Multiplexing (TDM) Bus Cables (WP-91716 L3) from Cab inet A to Cab inet B as shown. High or Critical Reliability Processor Port Network Three c ab inet stac ks: 1. Remove the Time Division Multip lexing (TDM) Bus Terminator from Slot 18 of Control Cab inet A (Proc essor Port Network (PPN)) and move it to Slot 17 on the top p ort c ab inet. See Figure 1-13 . 2. Connec t the sup plied TDM Bus Cab les (WP-91716 L3) as shown. Expansion Port Network (All Reliability Options) 1. Remove the TDM Bus Terminator from Slot 18 of Control Cab inet A (PPN) and move it to Slot 17 on the top p ort c ab inet. See Fig ure 1-12 . 2. Connec t the sup plied TDM Bus Cab les (WP-91716 L3) as shown.