    Have a look at the manual Lucent Technologies DEFINITY Enterprise Communications Server Release 8.2 Installation And Test For Single-Carrier Cabinets Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 413 Lucent Technologies manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							DEFINITY Enterprise Communication Server Release 8.2
    Installation and Test for Single-Carrier Cabinets  555-233-120  Issue 1
    April 2000
    Connector and Cable Diagrams 
    C-7  
    C
    Figure C-6. Sample Cable Pinouts
    1
    2
    15
    3
    4
    17
    5
    18
    6
    20
    8
    22
    24
    7
    21- shield
    25-pin D-subFS 17H600-210 cable37-pin D-sub
    1
    4
    5
    6
    7
    8
    9
    10
    11
    12
    13
    15
    17
    19
    37
    35
    33
    31
    30
    29
    27
    26
    24
    23
    22
    Strapped
    wire leads
    Strapped
    wire leadsStrapped
    wire leads
    FS 19ED1E434-11,G175
    1
    2
    15
    3
    17
    5
    20
    8
    24
    4
    7
    25-pin D-sub37-pin D-sub
    1
    4
    5
    6
    7
    8
    9
    12
    13
    17
    18
    19
    31
    27
    26
    24
    23
    Resistor
    1
    3
    15
    2
    4
    17
    5
    18
    6
    20
    8
    22
    24
    7
    21- shield
    25-pin D-subFS 18H600-362 cable37-pin D-sub
    4
    5
    6
    7
    8
    9
    10
    11
    12
    13
    15
    17
    19
    37
    35
    33
    31
    30
    29
    27
    26
    24
    23
    22
    r975bb5 MMR 051396 
    						
    							DEFINITY Enterprise Communication Server Release 8.2
    Installation and Test for Single-Carrier Cabinets  555-233-120  Issue 1
    April 2000
    Connector and Cable Diagrams 
    C-8  
    C
    Figure C-7. STRATUM 3 Clock Connector Pinout
    01
    26
    02
    27
    32
    07
    34
    09
    29
    04
    31
    06
    33
    08
    28
    03
    10
    35
    11
    36
    12
    37
    13
    38
    14
    39
    15
    40
    16
    41
    17
    42
    30
    05NC
    NC
    NC
    NC
    NC
    NC
    NC
    NC
    NC
    NC
    NC
    NC
    NC
    NC TREF1
    RREF1
    TREF2
    RREF2
    BCLKRTN
    BCLKLST
    BPWRRTN
    BPWRLST
    REF2RTN
    REF2LST
    SCLKRTN
    SCLKLST
    SPWRRTN
    SPWRLST
    REF1RTN
    REF1LST
    CCA01T
    CCA01R
    CCB01T
    CCB01R
    CCA02T
    CCA02R
    CCB02T
    CCB02R
    CCA03T
    CCA03R
    CCB03T
    CCB03R
    CCA04T
    CCA04R
    CCB04T
    CCB04R
    BREFRTN
    BREFLST
    STRATUM 3 clock connector
    Duplicated synchronization clock,
    simplex system, dual input referencesFS 20STRATUM 3 clock connector
    To H600-274 primary source
    (See FS 22)
    To H600-274 secondary source
    (See FS 22)
    48
    23
    36
    11
    34
    09
    31
    06
    41
    16
    29
    04
    46
    21
    43
    18 ALRM5B
    ALRM5A
    ALRM4B
    ALRM4A
    ALRM3B
    ALRM3A
    ALRM2B
    ALRM2A
    ALRM1B
    ALRM1A
    ALRM0B
    ALRM0A
    EXTSYN0T
    EXTSYN0R
    EXTSYN1T
    EXTSYN1R
    A carrier TN780
    25 pair pin conn.
    r975bb6 MMR 051396 
    						
    							DEFINITY Enterprise Communication Server Release 8.2
    Installation and Test for Single-Carrier Cabinets  555-233-120  Issue 1
    April 2000
    Connector and Cable Diagrams 
    C-9  
    C
    Figure C-8. STRATUM 3 Clock Connector
    01
    26
    02
    27
    32
    07
    34
    09
    29
    04
    31
    06
    33
    08
    28
    03
    10
    35
    11
    36
    12
    37
    13
    38
    14
    39
    15
    40
    16
    41
    17
    42
    30
    05NC
    NC
    NC
    NC
    NC
    NC
    NC
    NC
    NC
    NC TREF1
    RREF1
    TREF2
    RREF2
    BCLKRTN
    BCLKLST
    BPWRRTN
    BPWRLST
    REF2RTN
    REF2LST
    SCLKRTN
    SCLKLST
    SPWRRTN
    SPWRLST
    REF1RTN
    REF1LST
    CCA01T
    CCA01R
    CCB01T
    CCB01R
    CCA02T
    CCA02R
    CCB02T
    CCB02R
    CCA03T
    CCA03R
    CCB03T
    CCB03R
    CCA04T
    CCA04R
    CCB04T
    CCB04R
    BREFRTN
    BREFLST
    STRATUM 3 clock connectorDuplicated synchronization clock,
    duplicated system, dual input referencesFS 21STRATUM 3 clock connector
    To H600-274 primary source
    (See FS 22)
    To H600-274 secondary source
    (See FS 22)
    48
    23
    36
    11
    34
    09
    31
    06
    41
    16
    29
    04
    46
    21
    43
    18 ALRM5B
    ALRM5A
    ALRM4B
    ALRM4A
    ALRM3B
    ALRM3A
    ALRM2B
    ALRM2A
    ALRM1B
    ALRM1A
    ALRM0B
    ALRM0A
    EXTSYN0T
    EXTSYN0R
    EXTSYN1T
    EXTSYN1R
    48
    23
    36
    11
    34
    09
    31
    06
    41
    16
    29
    04
    46
    21
    43
    18 ALRM5B
    ALRM5A
    ALRM4B
    ALRM4A
    ALRM3B
    ALRM3A
    ALRM2B
    ALRM2A
    ALRM1B
    ALRM1A
    ALRM0B
    ALRM0A
    EXTSYN0T
    EXTSYN0R
    EXTSYN1T
    EXTSYN1R
    A carrier TN780
    25 pair pin conn.
    B carrier TN780
    25 pair pin conn.
    r975bb7 MMR 051396 
    						
    							DEFINITY Enterprise Communication Server Release 8.2
    Installation and Test for Single-Carrier Cabinets  555-233-120  Issue 1
    April 2000
    Connector and Cable Diagrams 
    C-10  
    C
    Figure C-9. Sample H600-274 Cable
    FS 22H600-274
    1
    2
    3
    4
    5
    6
    7
    8
    9
    10
    11
    12
    13
    14
    15 Pin
    numberPin
    number
    Pin
    number
    1
    22
    4
    23
    26
    47
    5
    48
    26
    47
    1
    22
    50-pin clock
    connector 50-pin system
    connector 15-pin D-sub
    to CSU
    422
    422
    r975bb8 MMR 051396 
    						
    							Access Security Gateway 
    D-1  
    D
    DEFINITY Enterprise Communication Server Release 8.2
    Installation and Test for Single-Carrier Cabinets  555-233-120  Issue 1
    April 2000
    D
    Access Security Gateway
    This ap p end ix provid es information on how to ad minister and use Ac c ess 
    Sec urity Gateway (ASG). ASG employs a c halleng e/resp onse p rotoc ol to c onfirm 
    the valid ity of a user and  red uc e the op portunity for unauthorized  ac c ess. ASG 
    authentic ation will b e imp osed  for Luc ent servic es log ins as ind ic ated  below: 
    ninit - all types of ac c ess req uire ASG authentic ation
    ninad s - all typ es of ac c ess require ASG authentic ation
    nc raft - if ac c essing  remotely, ASG authentic ation is req uired .
    NOTE:
    Craft login sessions c ontinue to rely on p assword  authentic ation. 
    						
    							DEFINITY Enterprise Communication Server Release 8.2
    Installation and Test for Single-Carrier Cabinets  555-233-120  Issue 1
    April 2000
    Access Security Gateway 
    D-2 Using the ASG Mobile 
    D
    Using the ASG Mobile
    1. Double c lic k on the ASG Mob ile V1.1 on your d esktop  and  an ASG Mob ile 
    V1.1 Log in wind ow ap p ears.
    2. In the Tech ID
     field , type your log in ID, whic h is the name of the attac hed  
    file (without the “ .asg” ). Your log in ID is the same as your Luc ent log in (or 
    an ab b reviated  p art of it).
    3. Typ e the p assword  twic e. Note that the p assword  is c ase-sensitive.
    NOTE:
    Your new p assword  will b e sent to you in a sep arate email. 
    4. Click OK
     and  an ASG Mob ile V1.1 Authentic ation wind ow ap p ears.
    5. Use your c ommunic ations p ac kag e (for examp le, DSA, DNA, or 
    ProComm) to d ial the switc h you need  to c ontac t.
    6. Log  into your c ommunic ations p ac kag e wind ow as either init
    , inads
    , or 
    craft
    . Instead  of a password  p romp t, a seven-d ig it (c halleng e) numb er 
    ap p ears in the wind ow of your c ommunic ations p ac kag e.
    7. Move to the ASG Mob ile V1.1 Authentic ation wind ow.
    8. Typ e the 10-d ig it Prod uc t ID in the Equipment ID
     field . The d efault ID is 
    10 zeros (0000000000).
    9. Type init
    , inads
    , or craft 
    in the Equipment Login
     field . The c raft login ID 
    is the d efault.
    10. Typ e the c halleng e numb er (from your c ommunic ations p ac kag e wind ow) 
    into the Challenge
     field . Do not use the “ -”  c harac ter.
    11. Typ e the troub le tic ket numb er in the Ticket Number
     field . If there is no 
    tic ket numb er, you c an use this field  as a one-word  c omment field  or leave 
    it blank.
    12. Clic k Start
    . The Activity Status
     field  d isp lays “ Started ”  and  the 
    Response
     field displays a new 7-digit number. 
    13. Move to your c ommunic ations pac kag e wind ow.
    14. Typ e the new 7-d ig it (resp onse) numb er in the Response
     field . Do not use 
    the “ -”  c harac ter.
    DEFINITY ECS verifies the resp onse. If c orrec t, DEFINITY log s you on. If 
    the resp onse is inc orrec t, return to step  1. If this is the third  rejec tion, see 
    the maintenanc e b ook for your system. 
    						
    							UPS Installation for SCC EPN A-Carrier Cabinet 
    E-1  
    E
    DEFINITY Enterprise Communication Server Release 8.2
    Installation and Test for Single-Carrier Cabinets  555-233-120  Issue 1
    April 2000
    E
    UPS Installation for SCC EPN
    A-Carrier Cabinet 
    This ap p end ix desc rib es the p roc ed ure for c onnec ting  the Luc ent Series 1 
    On-Line Uninterrup tib le Power System (UPS) to a DEFINITY® SCC EPN c ab inet. 
    The UPS p rovid es information on wiring , ad ministering , and  d oc umenting  alarms, 
    whic h allows remote monitoring  of p ower and  UPS p rob lems. It also maintains 
    c ritic al A-c arrier p orts for ab out 14 minutes d uring  a p ower outage. 
    There are two c onfig urations for c onnec ting  a UPS to an SCC c ab inet: 
    nUPS c onnec tion for fib er-remoted SCC EPN
    nUPS c onnec tion for DS1-remoted  SCC EPN and  assoc iated  Channel 
    Service Unit (CSU). 
    The installation p roc edure follows this g eneral p roc ess:
    1. Connect the UPS
    2. Wire the 700A8 plug
    3. Make the remaining  c onnec tions
    4. Ad minister the external d evic e alarm
    5. Load -test and  verify alarms 
    						
    							DEFINITY Enterprise Communication Server Release 8.2
    Installation and Test for Single-Carrier Cabinets  555-233-120  Issue 1
    April 2000
    UPS Installation for SCC EPN A-Carrier Cabinet 
    E-2 Parts List 
    E
    Parts List
    NOTE:
    This p roc ed ure requires a c ross-c onnec t p unc hd own tool.
    Connect the UPS
    1. Notify the c ustomer of an EPN outag e d uring  this proc edure.
    2. Turn off the SCC c irc uit b reaker.
    3. Unp lug  the SCC from the c ommerc ial p ower sourc e.
    4. Plug  the SCC p ower c ord  into the UPS.
    5. Turn on the SCC c irc uit b reaker.
    6. Plug  the UPS into a 120 VAC NEMA 5-15R rec ep tac le.
    7. Press and  hold  the OUTPUT ON b utton on the UPS until you hear a b eep . 
    The INPUT ON and  OUTPUT ON LEDs lig ht up .
    8. Prog ram the UPS c ommunic ation interfac e p ort for AS400 mod e. Refer to 
    t h e  U PS Site Prep aration, Installation and  Op erator’s Manual, 
    167-405-120.
    Table E-1. Required Hardware
    Comcode Description
    407662733 (800VA)
    407662741 (1000VA)800-VA UPS for 1 CSU and 1 SCC
    1000-VA UPS for 2 to 4 CSUs and  1 
    SC C
    407691401 Z3A2 UPS alarm ad ap ter with 700A8 
    p lug  inc lud ed
    Continued on next page 
    						
    							DEFINITY Enterprise Communication Server Release 8.2
    Installation and Test for Single-Carrier Cabinets  555-233-120  Issue 1
    April 2000
    UPS Installation for SCC EPN A-Carrier Cabinet 
    E-3 Wire the 700A8 Plug 
    E
    Wire the 700A8 Plug
    1. Cut a p iec e of 24AWG (2 twisted  p airs) wire long  enoug h to reac h from the 
    rear of the UPS to the 110 c ross-c onnec t field .
    2. Hold  the c lear c over for the 700A8 p lug  in your hand  with the p unc h d own 
    g rooves away from you. The g roove on the left sid e is p in 1. See Figure 
    E-1.
    NOTE:
    If the wire p airs are not in the c orrec t p ositions, then the alarm 
    verific ation test may not work.
    3. Route the wires through the c over, p lac ing  the utility fail p air in positions 1 
    and  2 and the UPS pair in p ositions 5 and 6. Positions 3, 4, 7, and  8 are 
    not used .
    4. Press the plug  onto the c over. This forc es the wires into the p lug  c ontac ts.
    Figure E-1. Wiring the 700A8 Plug  Figure Notes
    1. 700A8 p lug
    2. Clear c over for 700A8 p lug3. Utility fail wire p air
    4. UPS fail wire p air
    1
    3
    5 2
    4
    6
    7
    8
    1
    2
    pldf700a KLC 092899
    3
    4 
    						
    							DEFINITY Enterprise Communication Server Release 8.2
    Installation and Test for Single-Carrier Cabinets  555-233-120  Issue 1
    April 2000
    UPS Installation for SCC EPN A-Carrier Cabinet 
    E-4 Make the Remaining Connections 
    E
    Make the Remaining Connections
    For a fib er-remoted  SCC EPN, refer to Figure E-2. For a DS1-remoted  SCC EPN 
    and  assoc iated  CSUs, refer to Figure E-3
    .
    1. Plug  the 700A8 p lug  into the Z3A2 UPS alarm ad ap ter.
    2. Connec t the alarm ad ap ter to the UPS DB25 RS-232 serial p ort c onnec tor.
    3. Connec t the wires from the p lug  to the 110 c ross-c onnec t field  for the AUX 
    connec tor (see Table E-2
     and Figure E-4).
    If c onnec ting  a UPS for a DS1-remoted  SCC EPN:
    4. Plug  the CSU(s) used  in the A-level DS1 c onverter into the UPS.
    Table E-2. Wire Connections
    700A8 PlugDEFINITY AUX Connector 110 
    Field
    UPS Alarm 
    Name Pins Pins External Alarm Name
    Pa ir  1 :
    Utility Fail Alarm1
    Connects to1
    1M
    Major Alarm Pair
    22
    Pa ir  3 :
    U PS Fa i l Al a r m53
    1m Minor Alarm Pair
    64
    Continued on next page 
    						