    Have a look at the manual Lucent Technologies DEFINITY Enterprise Communications Server Release 8.2 Installation And Test For Single-Carrier Cabinets Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 413 Lucent Technologies manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							DEFINITY Enterprise Communication Server Release 8.2
    Installation and Test for Single-Carrier Cabinets  555-233-120  Issue 1
    April 2000
    Install and Connect the Cabinets 
    1-33 Connect System Cables 
    1
    Recommended Cable Routing
    1. Route the fib er optic  c ab le up  toward the top  of the c ab inet. The exc ess 
    c ab le should  b e loop ed  and  d rap ed  from the B25A c able c lamp  on the 
    top  g round  p late in the stac k. See Figure 1-18
    .
    2. Dress the c ab le b y tie wrap p ing  it to the outsid e of the B25A c able c lamp .
    !CAUTION:
    Do not route fib er op tic  c ab les and the B25A c ab les tog ether.
    Figure 1-18. Single-Carrier Cabinet Fiber Routing Figure Notes
    1. Supplied B25A Cables
    2. Loop  and  Drap e Exc ess Fib er 
    Op tic  Cab le3. Fib er Op tic  Cab le Sheath
    4. Port Cabinet
    5. Control Cab inet
    3
    44
    44
    44
    55
    1
    2 
    						
    							DEFINITY Enterprise Communication Server Release 8.2
    Installation and Test for Single-Carrier Cabinets  555-233-120  Issue 1
    April 2000
    Install and Connect the Cabinets 
    1-34 Connect System Cables 
    1
    Standard Reliability Fiber Connections
    Connec t and  route the fib er op tic  c able as shown in the c ab le running  list. See 
    Fi g u re  1 - 1 9
     for a samp le c ab le routing.
    Figure 1-19. Connections to Standard Reliability SystemsFigure Notes
    1. Control Cab inet
    2. Port Cab inet
    3. Exp ansion Control Cab inet4. Cab inet Stac k 1
    5. Cab inet Stac k 2
    6. Cab inet Stac k 3
    18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 118 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
    3
    18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 118 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 118 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
    18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
    18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
    18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 118 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
    18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 118 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
    2
    16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1Terminal
    stndard LJK 032896 
    						
    							DEFINITY Enterprise Communication Server Release 8.2
    Installation and Test for Single-Carrier Cabinets  555-233-120  Issue 1
    April 2000
    Install and Connect the Cabinets 
    1-35 Connect System Cables 
    1
    High Reliability Fiber Connections
    Connec t and  route the fib er op tic  c able as shown in the c ab le running  list. See 
    Fi g u re  1 - 2 0
     for a samp le c ab le routing.
    Figure 1-20. Connections to High Reliability SystemsFigure Notes
    1. Control Cab inet
    2. Duplic ate Control Cab inet
    3. Port Cab inet
    4. Exp ansion Control Cab inet5. Cab inet Stac k 1
    6. Cab inet Stac k 2
    7. Cab inet Stac k 3
    18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 118 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
    18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 118 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 118 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
    18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 118 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 118 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
    18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 118 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 116 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1Te r m i n a l
    16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1Te r m i n a l
    high LJK 032896 
    						
    							DEFINITY Enterprise Communication Server Release 8.2
    Installation and Test for Single-Carrier Cabinets  555-233-120  Issue 1
    April 2000
    Install and Connect the Cabinets 
    1-36 Connect System Cables 
    1
    Critical Reliability Fiber Connections
    Connec t and  route the fib er op tic  c able as shown in the c ab le running  list. See 
    Fi g u re  1 - 2 1
     for a samp le c ab le routing.
    Figure 1-21. Connections to Critical Reliability SystemsFigure Notes
    1. Control Cab inet
    2. Duplic ate Control Cab inet
    3. Port Cab inet
    4. Exp ansion Control Cab inet5. Cab inet Stac k 1
    6. Cab inet Stac k 2
    7. Cab inet Stac k 3
    18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 118 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
    18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 118 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 118 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
    18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 118 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 118 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
    18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 118 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 116 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1Te r m i n a l
    16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1Te r m i n a l
    critical LJK 032896 
    						
    							DEFINITY Enterprise Communication Server Release 8.2
    Installation and Test for Single-Carrier Cabinets  555-233-120  Issue 1
    April 2000
    Install and Connect the Cabinets 
    1-37 Install Earthquake Protection 
    1
    Install Earthquake Protection
    Earthq uake p rotec tion only installs on Sing le-Carrier Cab inets. 
    Figure 1-22. Front Mounting Angle Location
    1. Position the Control Cab inet (J58890L) in the p osition it is to oc c up y when 
    the installation is c omp lete. Be sure the c ab inet is level.
    2. Using  a p enc il or marker and  using  the Front Mounting  Ang le as a 
    temp late, mark the loc ations of the two floor mounting  holes.
    3. Move the c ab inet out of the way and  d rill a hole 0.5-inc h (1.3 c m) in 
    d iameter and  1.5 inc hes (3.8 c m) d eep  at the loc ations marked  in Step  2.
    4. Insert a c onc rete floor anc hor (STARR p art numb er 3425) into eac h hole. Figure Notes
    1. #12-24x1/2-inc h Thread Forming  
    Sc re w
    2. Control Cab inet
    3. Front Mounting  Ang le4. Hex Head  Bolt
    5. Nylon Insulating  Washer
    6. Conc rete Floor 
    7. Conc rete Floor Anc hor
    4
    1
    3
    2
    5
    6
    7
    r781854a CJL 030896 
    						
    							DEFINITY Enterprise Communication Server Release 8.2
    Installation and Test for Single-Carrier Cabinets  555-233-120  Issue 1
    April 2000
    Install and Connect the Cabinets 
    1-38 Install Earthquake Protection 
    1
    5. Sec ure the Front Mounting  Ang le to the floor using  the short hex head  
    bolts provided.
    6. Move the c ab inet b ac k into p lac e.
    7. At the rear of the c ab inet, remove the two hole plug s from the b ottom of 
    the c ab inet. See Fig ure 1-2 3
    .
    8. Insert a p enc il or marker throug h the holes in the b ottom of the c ab inet 
    and  mark the floor d irec tly b eneath eac h hole. 
    9. Move the c ab inet out of the way and  d rill a hole 0.5-inc h (1.27 c m) in 
    d iameter and  1.5 inc hes (3.8 c m) d eep  at the loc ations marked  in Step  8.
    10. Insert a c onc rete floor anc hor (STARR p art numb er 3425) into eac h hole.
    11. Move the c ab inet b ac k into p lac e and  alig n with the Front Mounting Ang le.
    12. Attac h the c ab inet to the Front Mounting  Ang le using  the four sup p lied  
    #12-24 x 1/2-inc h (1.27 c m) thread -forming  sc rews. See Fi g u re  1 - 2 2
    . 
    						
    							DEFINITY Enterprise Communication Server Release 8.2
    Installation and Test for Single-Carrier Cabinets  555-233-120  Issue 1
    April 2000
    Install and Connect the Cabinets 
    1-39 Install Earthquake Protection 
    1
    Figure 1-23. Cabinet Earthquake Mounting — Rear View
    13. Lay the sup p lied  Stiffener on the bottom rear of the c ab inet and  alig n with 
    the holes in the b ottom of the c ab inet. See Fig ure 1-2 3
    .
    14. Slid e a nylon washer onto eac h of the two sup p lied  long  hex head  b olts.
    15. Insert the b olts throug h the Stiffener and  thread  into the c onc rete floor 
    anc hor. Tig hten sec urely.
    NOTE:
    If c ritic al reliab ility is installed, the Exp ansion Control Cab inet sets on 
    the floor, next to Control Cab inet A. Rep eat the ab ove proc edures. Figure Notes
    1. Cabinet
    2. Nylon Insulating  Washer (2 Req uired )
    3. Long  Hex Head  Bolt (2 Req uired )
    4. Stiffener5. Cabinet Foot
    6. Floor Plugs (Remove)
    7. Conc rete Floor Anc hor
    8. Conc rete Floor
    34
    5
    1
    8
    2
    7
    On
    OffOn
    Off
    6
    r781851a CJL 030796 
    						
    							DEFINITY Enterprise Communication Server Release 8.2
    Installation and Test for Single-Carrier Cabinets  555-233-120  Issue 1
    April 2000
    Install and Connect the Cabinets 
    1-40 Install Earthquake Protection 
    1 
    						
    							Install Telecommunications Cabling 
    2-1 Equipment Room Hardware 
    2
    DEFINITY Enterprise Communication Server Release 8.2
    Installation and Test for Single-Carrier Cabinets  555-233-120  Issue 1
    April 2000
    2
    Install Telecommunications Cabling
    Equipment Room Hardware
    SYSTIMAX 110-typ e hardware is used  for the Main Distrib ution Frame (MDF). 
    110-typ e hard ware is availab le in two b asic  types: the 110A and  110P. The 110A 
    req uires less wall sp ac e than the 110P. The 110P inc lud es horizontal and  vertic al 
    c ab le troug hs for manag ing c ross-c onnec t c ab les. The system is c onnec ted to 
    the MDF with the sup p lied  B25A male to female 25-pair c ab les. The c ab les are 
    p rovid ed in 10-foot (3 m) and  15-foot (4.5 m) lengths.
    Refer to 
    DEFINITY Communic ations System Generic  1 and  Generic  3 Main 
    Distribution Field Design
     for more information.
    Fi g u re  2 - 1
     shows a d etailed examp le of Sing le-Carrier Cab inet c ab les 
    c onnec ting system c ab inets and  satellite c losets to the MDF. The fig ure shows 
    the c ross-c onnec tions for one example station c irc uit. 
    						
    							DEFINITY Enterprise Communication Server Release 8.2
    Installation and Test for Single-Carrier Cabinets  555-233-120  Issue 1
    April 2000
    Install Telecommunications Cabling 
    2-2 Equipment Room Hardware 
    2
    Figure 2-1. Example MDF ConnectionsFigure Notes
    1. Rear of Port Cab inet
    2. Main Distrib ution Frame (MDF)
    3. Port Distribution Field  (Purp le Field )
    4. Station Distribution Field  (White Field)
    5. Trunk/Auxiliary Field
    6. Purp le Field
    7. Yellow Field
    8. Green Field9. Satellite Closet
    10. Auxiliary Cab inet (Yellow Field )
    11. White Field
    12. Blue Field
    13. Cross-Connec t Jumpers
    14. 103A or Mod ular Wall Jac k
    15. 4-Pair Line Cord
    16. To Line Circ uit Pac k 
    0016_0 RBP 052396
    16 17 18 19 15 14 13 12 11 10 09 08 07 06 05 04 03 02 01AUX
    25-Pair
    Cable25-Pair
    Cable
    25-Pair
    Cable
    25-Pair
    Cable
    Trunk Circuit Pack
    Line Circuit Pack 25-Pair
    Cable To
    Network
    Intrface
    Yellow Field 
    						