Home > GTE > Communications System > GTE Omni Si Database Technical Practices Manual

GTE Omni Si Database Technical Practices Manual

    Download as PDF Print this page Share this page

    Have a look at the manual GTE Omni Si Database Technical Practices Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 3 GTE manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    Page
    of 950
    							5210TL-130200-1001
    START
    i-’IF THE PROBLEM IS NOT SOLVED,
    REINSERT THE ORIGINAL TRUNK
    CARD(S) AND REPLACE THE
    ASSOCIATED 
    MPB85 CARD.
    (SEE NOTE).
    (END)
    NOTE: See paragraph 
    l&5.
    Figure 5.9Trunk Operation Troubleshooting Flowchart
    8187M-175 
    						
    							TL-130200-1001Tl -Type Trunk5.4 The Tl-Type Supervisory and Alarm Cards
    Maintenance(FB-20718-1A) have buffers which retain the status of the
    sense and control points (see Table 5.5). With the maintenance
    TTY, maintenance personnel can read or write into the digital
    trunk address in the same manner as with the analog trunks.
    Refer to Table 5.6 for trunk addresses. Be advised that analog
    trunk card locations are preempted from use when 
    Tl is
    implemented.
    When referring to Table 5.5, note that the channel A and B
    signaling used with FX trunks does not provide for returning
    reverse battery from the CO. Therefore, the RB bit (bit 4 of the
    FX sense word) is an inactive bit and always appears as a 0 to
    the CPU.
    Bit 5 of the FX trunk work, the CF (Current Flow) bit, is a 
    logic-gated sense point. The Tl-Type Supervisory Card gates the
    loop closure instruction forwarded to the far end with the
    detection of the IS (Incoming Seizure) sense bit to create the CF
    bit.
    BIT 7GD
    GS
    Table 5.5Sense and Control Words for Digital Trunks
    BIT 6BIT 5BIT 4BIT 3BIT 2
    BIT 1BIT 0IS
    CFRBFX TRUNK
    SENSE
    WORD
    ISE&M
    TRUNK
    SENSE
    WORD
    LPFX TRUNK
    CONTROL
    WORD
    LPE&M
    TRUNK
    CONTROL
    WORD
    GD = Ground Detected
    GS = Ground Start
    IS =Incoming Sequence
    CF= Current Flow
    RB =Reverse Battery
    LP =Close Loop
    81875210 
    						
    							5210TL-130200-1001
    Channel Unit Removal
    5.5 The Tl-tvoe interface cards do not detect removal of a
    loopstart 
    chainel unit at the CO and use should be avoided.
    Table 5.6Trunk to Digital Span: Channel Correlation
    ANALOG TRUNK
    CARD LOCATION
    HARDWAREDIGITAL SPAN
    FILESLOTUNIV. POS
    ADDRESSCHANNEL
    IDENTIFICATIONIDENTIFICATION
    _.
    19Cl051821X
    051922051A
    23
    051 B24
    17c20528
    17X0529
    18
    052A190528
    20
    055B8
    0568
    1x
    9C605692056A
    3056B
    4
    8187M-l 77 
    						
    							--TL-130200-1001
    Removal of a ground-start channel unit at the CC causes the
    GD (Ground-Detected) sense point, bit 7, in the FX trunk sense
    word Table (5.5) to become true, making the associated trunk
    busy to the system.
    Removal of an E 
    & M or incoming loop dial channel unit at the far
    end causes an incoming seizure to the system. If the system
    data base is configured for the trunk circuit as a 
    ringdown to the
    attendant, the removal of the far-end channel unit causes an
    incoming call to the attendant’s loop.
    If a channel unit at the CO channel bank is equipped with a busy
    key, operation of the busy key is equivalent to removing the
    channel unit from service.
    NOTE:The FX channel unit, when configured as a loopstart
    channel unit, is not detected as removed from service when the
    busy key is operated.
    Alarms5.6 The SYS LED on the Tl-Type Supervisory card 
    (FB-
    20718-1A) is activated when any one of the following occurs:
    0 A local alarm
    * A remote alarm
    0 A RPR ( remote power failure alarm)
    e When the digital trunks are in a loop test mode
    l When alarms above are off, but bit 2 (inhibit) is still being
    forwarded to the other end during the alarm 
    restoral sequence.
    An alarm signal to the Tl-type Supervisory Card will be
    forwarded when the Frame, Detector card (FB-15278-A)
    determines that the frame sequence from the CO has been lost
    81875210 
    						
    							TL-130200-1001
    System alarms are associated with the system’s status as a
    slave. If the FB-20922-A Network Clock card should lose
    frequency synchronization with the SINX input for more that 2
    seconds, a fault code 15 will be generated. When the
    FB-20922-A Card regains frequency synchronization on the
    SINX input, a response code is generated.
    When the RPF and SYS 
    LEDs light (Tl-Type Supervisory card),
    a power failure has occurred in the CO terminating equipment. A
    power failure occurs when a normally operated device, such as a
    relay, restores and closes a 
    Tl PF Tl (Power Failure) circuit
    grounding input lead in the Tl-Type Supervisory Card. When
    the power failure is detected, the RFP LED lights. If the power
    failure exists for longer than the local alarm (strapping option)
    threshold on the Tl-Type Supervisory Card, the local alarm is
    activated. If a common power source feeds the office
    terminating repeaters, only two or more power sources are used,
    wire one 
    Tl PF and Tl PFG pair per power source.
    Testing5.7 The loop test determines if the Tl-Type interface can
    achieve frame synchronization.Before any loop test is initiated,
    all trunks must be in the maintenance busy state to avoid
    disconnection a customer from an established connection.
    To perform the loop test, set the 
    AC0 (Alarm Cutoff) switch on the
    Tl-Type Supervisory card to the UP position, then set the LPT
    (loop) switch to the UP position. During the loop test, the
    incoming bipolar stream is terminated into a 
    loo-ohm resistor.
    An all one (1) logic value is transmitted to the distant end. The
    outgoing unipolar transmit signal is looped back to the receiver
    side. The framing synchronization during the loop test is such
    that the incoming bipolar stream is offset one channel from the
    outgoing unipolar stream.
    If framing synchronization is achieved during the loop test, the
    SYS, ACO, and LOOP 
    LEDs remain on. If framing
    synchronization is achieved in the system, but not with the far
    end, the span interface card may be defective. In most
    instances, if the loop test framing synchronization is achieved, it
    will also be achieved with the distant end barring any external
    wiring or repeater problems.
    If an alarm condition exists before a loop test, or if an alarm
    condition appears after the system is placed in loop test, the
    alarm state will persist for approximately 13.5 seconds. If the
    alarm condition persists longer than 13.5 
    + or - 3 seconds, a
    failure has occurred in one or more of the cards.
    5210
    8l87M-l 79 
    						
    							-!-L-l 30200-l 001
    --To test the network clock synchronization, ensure that the 
    Tl-type card group is frame-synchronized to the far end. Once this
    has been determined and the coaxial cables are properly
    connected between the Span Interface card and the Network
    Clock card, the SINX input can be cabled. If the 
    SINX input
    cabled to a span interface card in an active Tl-type group
    cannot be selected, then that cable or span interface card is
    faulty. This testing can be done with the system off-line. The
    Tl-Type Supervisory Card must not be in the loop test mode. If
    more than one LED on the Network Clock card handle is on, the
    system is not frequency-synchronizing to a master clock.
    Tl Trunk Trouble5.8 Verify the the failure is not system related before starting any
    troubleshooting procedure on the digital trunk interface cards.
    Check the system fault log for codes 
    15 and 17. Trouble-
    shooting flowcharts for Tl are shown in Figures 6-25 through
    6-28.The following failures have been categorized in four different
    modes on the digital trunk interface:
    1. Supervision failure is the full or partial loss of supervisory
    signaling capability between the system digital interface and
    the distant-end equipment when the span is synchronized.
    2. Transmission failure is the full or partial loss of voice (analog)
    signals over the digital span while the system is synchronized.
    3. Frame synchronization failure (misframing) occurs when the
    system cannot identify the start of a frame in the incoming
    span. Misframing results in loss of communication from the far
    end. In misframing errors, the clocks are assumed to be
    running synchronously, but the digital trunk interface cards
    cannot decode the incoming span data properly and locate the
    245channel frames.
    4. A clock synchronization (frequency synchronization) problem,
    or loss-of-slaving condition, results when the system clock
    is running at a frequency other than that of the bit frequency on
    the incoming Tl-type span. The system can maintain frame
    synchronization, but because of differences in clock
    frequencies, it will occasionally skip over a frame and never
    decode that frame of information. The system is slipping
    frames.
    M-l 80
    81875210 
    						
    							TL-130200-1001
    STARTciSYSTEM HAS LOST PARTIAL OR
    FULL SUPERVISION IN THE DIGITAL
    TRUNK INTERFACE.
    IARE
    ANY FAULT
    CODES PRINTED ONREFER TO SYSTEM FAULT TABLES
    THE MAINTENANCE
    INO
    clA
    Figure 5.10Tl-Type Trunk Loss of Supervision Troubleshooting Flowchart (Sheet 1 of 7)5210
    8h37 
    						
    							TL-130200-1001IS THESYSTEMbCOMMON TO THE
    SYNCHRONIZED?
    YESYESNO
    ;,PROBLEM STILL
    YES
    1NO
    (--Z---l
    1NO
    REMOVE AND REPLACE THE
    FOLLOWING DIGITAL TRUNK
    CARDS ONE AT A TIME. IF THE
    TROUBLE STILL EXISTS AFTER
    EACH REPLACEMENT, REINSTALL
    EACH ORIGINAL CARD.
    FB-17192-A 
    TlB2FB-17277-A OR 15277-1 SILFB-15280-A LCM.
    Figure 5.10Tl-Type Trunk Loss of Supervision Troubleshooting Flowchart (Sheet 2 of 7)
    M-l 82
    81875210 
    						
    							TL-130200-1001
    PROBLEM STILLYES
    Figure 5.10Tl-Type Trunk Loss of Supervision Troubleshooting Flowchart (Sheet 3 of 7)5210
    8A37M-183 
    						
    							TL-130200-1001D
    70
    B---CORRECT?
    YESTHE FB-20718-l
    NO
    IS THE PROBLEM
    RESOLVED?
    IS THE
    PROBLEMNO
    ‘IREPLACE 
    f MB CARD.
    Figure 5.10Tl-Type Trunk Loss of Supervision Troubleshooting Flowchart (Sheet 4 of 7)
    5210 
    						
    All GTE manuals Comments (0)

    Related Manuals for GTE Omni Si Database Technical Practices Manual