Home > Inter-Tel > Communications System > Inter-Tel Imx/Gmx 416/832 Installation Manual

Inter-Tel Imx/Gmx 416/832 Installation Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Inter-Tel Imx/Gmx 416/832 Installation Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 31 Inter-Tel manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    Page
    of 702
    							TROUBLESHOOTING 
    Issue 1, November 1994 INTER-TELPRA(zTKxs lMX/GMX 416/832 INSTALLATION & MAINTENANCE 
    FIGURE 6-3. CO TRUNK TROUBLESHOOTING CHART _ . 
    .: 
    // 
    SYMPTOM 
    ZO trnnk inoperative 
    hroughout the system 
    SYMPTOM 
    Cannot obtain CO dial tone 
    PROBABLE CAUSE 
    Defective CO trunk from 
    central office 
    Iiunk is dedicated to a sec- 
    ondary carrier requiring an 
    access code 
    Defective cabling or mis- 
    wired amphenol connector 
    on the trunk card 
    Programming error 
    Trunk has been taken out of 
    service by the attendant 
    Defective trunk card 
    Defective MXC or EXP 
    Card 
    PROBABLE CAUSE 
    CORRECTIVE ACTION 
    If 
    reorder tone is heard, pro- 
    gramming error Ensure that the keyset has outgoing access. Refer 
    to page 5-34 in PROGRAMMING. 
    Check to see if the keyset is programmed for LCR 
    only. Refer to page 5-42 PROGRAMMING. If so, 
    check LCR programming, page 5-98 in PRO- 
    GRAMMING. 
    If progress tone is heard, 
    user error 
    Defective trunk card 
    Defective MXC or EXP 
    Card 
    CORRECTWE ACTION 
    At the 
    associated Co block, remove the bridging 
    clips for the trunk. On the telco side of the block, 
    use a test set to verify the CO trunk connection. 
    Also, move the CO trunk to a known good CG 
    circuit. If the problem follows the trunk, contact 
    the telephone company. 
    Verify the type of CO trunk. Instruct users to dial 
    access code if required. 
    Using a test set, ensure presence and correct loca- 
    tion of the CO trunk at the associated CO block. 
    Ensure that the trunk is assigned to the correct 
    trunk group and stations have been given access to 
    it. See page 5-109 in PROGRAMMING. 
    Place the trunk back in service. Refer to PEA- 
    ‘PURRS, page 4-113, or page 5-149 in PRO- 
    GRAMMING. 
    Replace the associated trunk card. 
    Refer to page 3-103 to test the system voltages. 
    Replace the card(s) if faulty. 
    Ensure trunk is assigned to the correct trunk group. 
    Refer to page 5-109 in PRGGRAAMING. 
    System is programmed to expect a forced account 
    code. Refer to PROGMMMIN G, page 5-32. 
    Replace the associated trunk card. 
    Refer to page 3-103 to test the system voltages. 
    Replace the card(s) if faulty. 
    Page 6-18  
    						
    							INTER-TELPRACTICES TROUBLE!SHOOTING 
    lMX/GMX 416/832 INSTALLAl’ION & MAINTENANCE Issue 1, November 1994 
    FIGURE 6-3. CO TRUNK TROUBLESHOOTING CHART (CONT’D) 
    SYMPTOM 
    Low volume on all CO 
    runks; cannot break CO dial 
    :one 
    PROBABLE CAUSE 
    Defective trunk card 
    Defective CO trunk from 
    central office 
    Open or loose connection in 
    the cable between the power 
    supply and cardfile 
    Defective power supply 
    module(s) 
    Hybrid balance mismatch 
    NOTE: See also keyset problems on page 6-32. 
    Defective CO trunk from 
    central office 
    Timer error 
    I 1 Card 
    CORRECTIVE ACTION 
    Measure -12VlX at the MXC or EXP Card test 
    points. (See page 3-103.) If it is not within toler- 
    ance, remove all trunk cards and check voltage 
    again. If the voltage returns to normal; replace the 
    cards one at a time until the defective card is iso- 
    lated and replaced. 
    At the CO block, remove the bridging clips for the 
    trunk. On the telco side of the block, use a test set 
    to verify the CO trunk connection. Also, move the 
    CO trunk to a known good CO circuit. If the prob- 
    lem follows the trunk, contact the telephone com- 
    Pay. 
    If, with all trunk cards removed, the -12VDC is 
    still not within tolerance, turn off the system and 
    check the cable and connector with an ohmmeter. 
    Replace or repair the faulty cable. 
    With all trunk cards removed, measure -12VDC at 
    the power supply connector(s). If not within toler- 
    ance, replace the power supply module(s). 
    Select the balance network - ideal, loaded, or 
    unloaded -that best matches the trunk’s imped- 
    ance. See PROGRAMMIN G, page 5-148. 
    CORRECTlVE ACTION 
    Ensure that CO trunk and CO circuit use same 
    type signaling (MMP or dial pulse). See PRO- 
    GRAMMING, page 5-103. 
    At the CO block, remove the bridging clips for the 
    trunk. On the telco side of the block, use a test set 
    to verify the CO trunk connection. Also, move the 
    CO trunk to a known good CO circuit. If the prob- 
    lem follows the trunk, contact the telephone com- 
    PanY. 
    If trunk is IXMP, the IYfMP Digit Duration/Pause 
    timer setting may not be compatible with the 
    trunk. See PROGRAMMIN G, page 5-77. 
    Replace the associated trunk card. 
    Refer to page 3-103 to test the system voltages. 
    Replace the card(s) if faulty. 
    NOTE: See also keyset problems on page 6-32. 
    Page 6-19  
    						
    							TR~U~~L~HOOTING INTER-TELPRACTICES 
    Issue 1, November 1994 IMX/GMX 416/832 INSTALLATION & MAINTENANCE 
    FIGURE 6-3. CO TRUNK TROUBLESHOOTING CHART (CONT’D) 
    SYMPTOM PROBABLE CAUSE CORRECTIVE ACTION 
    Zannot place an outgoing programming error Check station class of service (SCOS). See PRO- 
    x11; CO dial tone is present; GRAMMING, page 5-42. Check that equal access 
    ntercom works and absorbed digit programming for the trunk 
    group are correct. See PRGGRAh4MING, page 
    5-113. If using LCR, check LCR programming on 
    page 5-98 in PROGRAMMING. 
    Defective CG trunk from 
    At the CO block, remove the bridging clips for the 
    central office trunk. On the t&o side of the block, use a test set 
    to verify the CO trunk connection. Also, move the 
    CO trunk to a known good CG circuit. If the prob- 
    lem follows the trunk, contact the telephone com- 
    pany. 
    Defective station instrument Replace the station instrument and/or perform the 
    keyset self-test as outlined in INSTALLKfION, 
    pages 3-107,3-116, or 3-128. 
    Defective trunk card 
    Replace the associated trunk card. 
    Defective MXC or Exp 
    Refer to page 3-103 to test the system voltages. 
    Card 
    Replace the card(s) if faulty. 
    SYMPTOM 
    PROBABLE CAUSE 
    CORRECTIVE ACTION 
    Xher station conversations Defective CO trunk(s) 
    zan be heard on the CO Isolate the trunk(s) with crosstalk by removing the 
    runk (crosstalk) bridging clips from the CO block. On the telco 
    side of the block, attach a test set to each trunk 
    and check for crosstalk. If present, contact the 
    telephone company. 
    Defective cabling or mis- 
    Using a test set, ensure presence and correct loca- 
    wired amphenol connector 
    tion of the CO trunk at the associated CO block. 
    on the trunk card 
    Defective station card 
    Defective trunk card 
    Defective h4XC or EXP 
    Card Replace the associated station card. 
    Replace the associated trunk card. 
    Refer to page 3-103 to test the system voltages. 
    Replace the card(s) if faulty. 
    Page 6-20  
    						
    							INTER-TELPFtACTICES TROUBLESHOOTING 
    IMX/GMX 416/832 INSTALIATION % MAINTENANCE Issue 1, November 1994 
    FIGURE 6-3. CO TRUNK TROUBLESHOOTING CHART (CONT’D) 
    SYMPTOM 
    Mside calls dropped during 
    conversation or upon an- 
    lwering CO trunk 
    SYMPTOM 
    CO trunk cannot be reseized 
    PROBABLE CAUSE 
    CORRECTIVE ACTION 
    User error (trunk key being 
    Instruct users not to press the trunk key while on a 
    pressed after initial connec- 
    call. Or, if necessary, set the CO Reseize timer to a 
    tion is made) 
    higher value. Default value is 3 seconds. See page 
    5-77 in PROGRAMMIN G. Or, program the sta- 
    tion to disallow CO reseize. See PROGRAM- 
    MING, page 5-30. 
    Defective CO trunk from At the CO block, remove the bridging clips for the 
    central office trunk. On the telco side of the block, use a test set 
    to verify the CO trunk connection. Also, move the 
    CO trunk to a known good CO circuit. If the prob- 
    lem follows the trunk, contact the telephone com- 
    pany. 
    Insufficient loop current 
    Central office must supply 20mA minimum loop 
    supplied by central office 
    current. 
    ICC0 Disconnect timer 
    Ensure timer value is long enough to ignore nor- 
    value is set too short 
    ma1 interruptions in CO loop current. Default val- 
    ue is 0.6 seconds. See page 5-77 in PROGRAM- 
    MING. 
    Inter-Ring Silence timer val- Ensure timer value is set longer than the central 
    ue is set too short 
    office ring signal is “off.” Refer to PROGWM- 
    MING, page 5-77. 
    Defective station instrument Replace the station instrument and/or perform the 
    keyset self-test as outlined in INST~ON, 
    pages 3-107,3-116, or 3-128. 
    Defective trunk or station 
    Replace the associated card. 
    card 
    Defective h4XC or EXP 
    Card Refer to page 3-103 to test the system voltages. 
    Replace the card(s) if faulty. 
    PROBABLE CAUSE 
    CORRECTWE ACTION 
    CO Reseize feature is dis- 
    Check station programming as described on page 
    abled 
    5-30 in PROGRAMMlN G. If the CO reseize op 
    tion has been disabled, the user cannot reseize a 
    trunk until it has been disconnected by hanging up 
    or pressing another trunk key. 
    CO Reseize timer is set too 
    Set the timer to a lower timer value. Default value 
    high 
    is 3 seconds. See page 5-77 in PROGIWMMING. 
    Page 6-21  
    						
    							‘I’ROUBLESHOOTING INTER-TELPRACTICES 
    Issue 1, November 1994 IMX/GMX 416/832 INSTALLATION & MAINTEWANCE 
    FIGURE 6-3. CO TRUNK TROUBLESHOOTING CHART (CONT’D) 
    SYMPTOM I PROBABLE CAUSE 
    I CORRECTIVE ACTION 
    Noise on CO trunk at all sta- Defective CO trunk At the CO block, remove the bridging clips for the 
    tions 
    trunk. On the tclco side of the block, use a test set 
    to verify the CO trunk connection. Also, move the 
    CO trunk to a known good CO circuit; If the prob- 
    lem follows the trunk, contact the telephone com- 
    pany 
    Defective trunk card Replace the associated trunk card. 
    Defective power supply Refer to INSTALLATION, page 3-55, to perform 
    module(s) 
    the power supply electrical test. Replace the power 
    supply module(s) if faulty. 
    Defective MXC or EXP Refer to page 3-103 to test the system voltages. 
    Card Redace the card(s) if faultv. 
    SYMPTOM PROBABLE CAUSE 
    CORRECTIVE ACTION 
    ZO trunk remains seized af- Characteristic of some ES 
    Central office must provide disconnect signal. Or, 
    :er a call has been ended 
    central offices 
    install a trunk release module available from most 
    supply houses. 
    ICC0 or CO-CO Discon- Central office disconnect signal was not detected 
    nect timer value set too long by ICC0 or CO-CO Disconnect timer. Default 
    value of the ICC0 timer is 0.6 seconds; the CO- 
    CO timer is 0.35 seconds. See page 5-77 in PRO- 
    GRAMMING. 
    Defective CO trunk 
    At the CO block, remove the bridging clips for the 
    trunk. On the telco side of the block, use a test set 
    to verify the CO trunk connection. Also, move the 
    CO trunk to a known good CO circuit. If the prob- 
    lem follows the trunk, contact the telephone com- 
    pany. 
    Defective station instrument Replace the station instrument and/or perform the 
    keyset self-test as outlined in INSTALLAfION, 
    pages 3-107,3-116, or 3-128. 
    Defective trunk card 
    Replace the associated trunk card. 
    Defective MXC or EXP 
    Refer to page 3-103 to test the system voltages. 
    Card 
    Replace the card(s) if faulty. 
    Page 6-22  
    						
    							lNT.ER-TELPRAcTIcEs TROUBLESHOOTING 
    IMX/GMX 416/832 INS’LALLATION & MAINTENANCE Issue 1. November 1994 
    FIGURE 6-3. CO TRUNK TROUBLESHOOTING CHART (CONT’D) 
    SYMPTOM 
    3ound start trunks not 
    5mctioning properly 
    PROBABLE CAUSE 
    System not properly 
    grounded 
    LGC jumper straps not set 
    correct1 y 
    Tip and ring are reversed 
    Programming error 
    6Ol-l~ AC power is getting 
    onto the trunks 
    CORRECTIVE ACTION 
    Verify that the system AC circuit is isolated and 
    dedicated (see page 34 in INSTALLATION) and 
    check for proper grounding (see page 3-54 in IN- 
    !XALLAl-ION). 
    For each ground start circuit, both corresponding 
    LGC jumper straps must be set in the GS position. 
    If the strap settings are mixed, or if one or both of 
    the straps is missing, the circuit will not function 
    properly. Also, when setting the straps, note the 
    unique ordering of the LGC circuits as shown in 
    INSTALLATION on page 3-97. 
    At the CO block, check to make sure that tip and 
    ring are not reversed. See INSIWLAPION, page 
    3-14. Unlike loop start trunks, ground start trunks 
    are polarity sensitive. 
    Ensure that the trunks are identified correctly as 
    ground start trunks. Refer to PROGRAMMING, 
    page 5-103. 
    Use a voltmeter to check the AC voltage between 
    tip and earth ground while the trunks are con- 
    nected to an LGC. If more than 5V (RMS) are 
    measured, there is AC power contamination (e.g., 
    due to faulty wiring insulation). Locate and re- 
    move the source of 
    AC power contamination. 
    Page 6-23  
    						
    							TROUBLESHOOTING INTER-TELPRACTICES Issue 1, November 1994 IMX/GMX 416/832 INSTALLATION & MAINTENANCE 
    FIGURE 6-4. FEATURE TROUBLESHOOTING CHART -. 
    ‘ 
    ,/ 
    SYMPTOM PROBABLE CAUSE CORRECTIVE ACTION 
    Feature does not work prop User error Refer to PEMURES for procedures. Also, ensnre 
    trly that the feature is available on the software pack- 
    age installed. 
    Programming error Check feature code programming. 
    Refer to PRO- 
    GRAMMING, page 5-58. Also, check user-pro- 
    grammable feature key programming. Refer to 
    PEAWRFS, page 4-51, and PRGGRAMMlNG, 
    page 5-44. 
    Defective station instrument Replace the station instrument and/or perform the 
    keyset self-test as described in INSTAJLAI’ION, 
    pages 3-107,3-116, or 3-128. 
    Defective station card Replace the associated station card. 
    Defective MXC or FXP Refer to page 3-103 to test the system voltages. 
    Card Replace the card(s) if faulty. 
    SYMPTOM 
    PROBABLE CAUSE CORRECTIVE ACTION 
    Cannot transfer CO or inter- User error (e.g., wrong fea- Refer to IZALWES, page 4-70, for procedures. 
    corn calls to other stations 
    ture code) 
    Called station is in do-not- A station in do-notdisturb cannot receive trans- 
    disturb 
    ferred calls. 
    Call transferred to an illegal Use only valid intercom numbers. 
    intercom number 
    Called station is in a differ- 
    To allow such transfers (if desired), place the two 
    ent tenant group and cross- stations in the same tenant group or allow cross-te- 
    tenant traffic is denied nant traffic. See PROGRAMMIN G, page 5-67. 
    Defective station instrument Replace the station instrument and/or perform the 
    keyset self-test as described in INSTALLATION, 
    pages 3-107,3-116, or 3-128. 
    Defective MXC or EXP Refer to page 3-103 to test the system voltages. 
    Card Replace the card(s) if faulty. 
    I SYMPTOM I PROBABLE CAUSE 
    I CORRECTWE ACTION 
    I 
    Cannot transfer calls to out- 
    User error (e.g., wrong fea- Refer to PEMURES, page 4-70, for procedures. 
    side numbers ture code) 
    Programming error Check trunk access and toll restriction. 
    I 
    Defective MXC or EXP 
    I 
    Refer to page 3-103 to test the system voltages. 
    Card Replace the card(s) if faulty. 
    I I I . _ 
    1 
    Page 6-24  
    						
    							INTER-TELPRACTICES TROUBLESHOOTING 
    IkD4GM.X 416,‘832 INSTALLATION & MAINTENANCE Issue 1, November 1994 
    -FIGURE 6-4. FEATURE TROUBLESHOOTING CHART (CONT’D) 
    SYMPTOM 
    Cannot transfer incoming 
    CO calls or place them on 
    hold 
    PROBABLE CAUSE 
    User error 
    CORRECTIVE ACTION 
    Refer to FEHURES, page 4-70, for procedures. 
    Inter-Ring Silence timer is Ensure timer value is set longer than the central 
    set too short office ring signal is “off.” Refer to PROGRAM- 
    MING, page 5-77. 
    User error (trunk key being Set the CO Reseize timer to a higher value. 
    pressed after initial comrec- Default value is 3 seconds. See. page 5-77 in PRO- 
    tion is made) GRAMMING. Or, program the station to disallow 
    CO reseize. See PROGRAh4MIN G, page 5-30. 
    Programming error Check user-programmable feature key program- 
    ming. Refer to EATUREB, page 4-51, and PRO- 
    GRAMMING, page 5-44. 
    PROBABLE CAUSE 
    User error 
    CORRECTIVE ACTION 
    Refer to FEHURES, page 4-76, for correct pro- 
    cedures. 
    System capacity exceeded Refer to the maximum system capacities on page 
    l-g in OVERVIEW. 
    Defective station instrument 
    Replace the station instrument and/or perform the 
    keyset self-test as described in INSTALLKfION, 
    pages 3-107,3-116, or 3-128. 
    I 
    Defective station card 
    ~ Defective MXC or EXP 
    ~ Card Replace the associated station card. 
    Refer to page 3-103 to test the system voltages. 
    Replace the card(s) if faulty. 
    I SYMPTOM I PROBABLE CAUSE 
    I CORRECTIVE ACTION 
    I 
    Last Number Redial feature 
    inoperative User error 
    System speed-dial number 
    identified as non-display 
    Defective station instrument 
    Defective MXC or EXP 
    Card Refer to m, page 4-93, for procedures. 
    Keyset may be programmed for Last Number 
    Saved. 
    A system speed-dial number identified as nondis- 
    play camtot be redialed. 
    Replace the station instrument and/or perform the 
    keyset self-test as described in INSTALLH’ION, 
    pages 3-107,3-116, or 3-128. 
    Refer to page 3-103 to test the system voltages. 
    Replace the card(s) if faulty. 
    Page 6-25  
    						
    							TROUBLESHOOTING 
    Issue 1, November 1994 INTER-TELPRACTICES 
    IMX/GMX 416/832 INSTALLATION & MAINTENANCE 
    FIGURE 6-4. FEATURE TROUBLESHOOTING CHART (CONT’D) ._ 
    .I 
    1 
    SYMPTOM 
    Zannot initiate an internal 
    PROBABLE CAUSE 
    User error 
    CORRECTIVE ACTION 
    Refer to PEMURES, page 4-94, for correct pro- 
    cedures. 
    All stations in the paging 
    zone are busy, or a voice 
    channel is not available 
    All stations in the paging 
    zone are in do-not-disturb Reorder tone is heard. Wait several seconds and 
    then attempt to place the page again. Paging re- 
    quires a voice channel. 
    Reorder tone is heard if all stations in the zone are 
    in do-not-disturb and if external paging for the 
    zone is disabled. 
    No stations are programmed Reorder tone is heard. Check paging assignment. 
    to receive pages 
    Refer to page 5-70 in PROGRAMMING. 
    Defective station instrument Replace the station instrument and/or perform the 
    keyset self-test as described in INSTALLApION, 
    pages 3-107,3-116, or 3-128. 
    Defective MXC or EXP 
    Refer to page 3-103 to test the system voltages. 
    Card 
    Replace the card(s) if faulty. 
    SYMPTOM 
    Cannot initiate an external 
    page 
    PROBABLE CAUSE 
    User error 
    CORRECTIVE ACTION 
    Refer to EXPIRES, page 4-94, for correct pro- 
    cedures. 
    Another external zone page Reorder tone is heard. Wait several seconds and 
    is being made or a voice 
    then attempt to place the page again. only one 
    channel is not available 
    external zone page can be made at a time. Paging 
    requires a voice channel. 
    Defective station instrument Replace the station instrument and/or perform the 
    keyset self-test as described in INST~LATION, 
    pages 3-107,3-116, or 3-128. 
    Defective MXC or EXP 
    Card Refer to page 3-103 to test the system voltages. 
    Replace the card(s) if faulty. 
    SYMPTOM PROBABLE CAUSE 
    I CORRECTIVE ACTION 
    House phone is not working 
    properly or is inoperative User error 
    Programming error (data- 
    base) Incoming calls take precedence over outgoing 
    calls. Refer to E&lURES, page 4-92. 
    Ensure that the station is designated as a house 
    phone. Refer to page 5-38 in PROGRAMMING. 
    Also, make sure the station has been assigned the 
    proper SCOS and trunk access. See page 5-42 in 
    PROGRAhMING. 
    Programming error (data- 
    base or speed-dial) Ensure that the correct numbers are in appropriate 
    day number and night number (speeddial) loca- 
    tions. Refer to page 4-92 in PMTUREB. 
    Page 6-26  
    						
    							INTER-TELPRACTICES TROUBLESHOOTING 
    IMX/GMX 416/832 INSTALLATION & -ANCE Issue 1, November 1994 
    FIGURE 6-4. FEATURE TROUBLESHOOTING CHART (CONT’D) 
    SYMPTOM 
    Zamrot initiate a call 
    Torward 
    PROBABLE CAUSE 
    CORRECTIVE ACTION 
    User error 
    Refer to m, page 4-82, for correct pro- 
    cedures. 
    User attempting illegal for- Stations are not allowed to set call forward if it 
    ward 
    forms an unconditional loop, the receiving station 
    is in do-not-disturb, or an invalid intercom number 
    is dialed. SCOS and outgoing access are checked 
    when a call is forwarded to an outside telephone 
    number. Also, LCR cannot be used to forward to 
    an outside number. 
    Defective station instrument Replace the station instrument and/or perform the 
    keyset self-test as described in INSTALLAI’ION, 
    pages 3-107,3-116, or 3-128. 
    Defective MXC or EXP 
    Refer to page 3-103 to test the system voltages. 
    Card 
    Replace the card if faulty. 
    SYMPTOM 
    Calls will not forward 
    PROBABLE CAUSE 
    User error 
    Illegal forward 
    CORRECTIVE ACTION 
    Refer to lWWURJ%, page 4-82, for procedures. 
    Conditional forwards (i.e., if busy, if unanswered) 
    may form an undetected loop. If a call forward 
    request forms a conditional loop, the call returns to 
    the first station. 
    Defective station card 
    Defective IvlXC or EXP 
    Card Replace the associated station card. 
    Refer to page 3-103 to test the system voltages. 
    Replace the card(s) if faulty. 
    SYMPTOM I PROBABLE CAUSE 
    I CORRECTIVE ACTION 
    I 
    Station not receiving hunt 
    group calls User error 
    Hunt group calls may have been halted using the 
    Hunt Group Remove feature code (see page 4-19 
    in PEXURES). Or, the station may be in do-not- 
    disturb. 
    Programming error 
    Check hunt group programming. Refer to page 
    5-61 in PROGRAMMING. 
    I 
    SYMPTOM 1 PROBABLE CAUSE 
    I CORRECTIVE ACTION 
    I 
    Station is not receiving 
    pages User error 
    Programming error Pages may have been halted using the Page Re- 
    move feature code (see page 4-94 in m). 
    Or, the station may be in do-not-disturb. 
    Check page zone programming for the station. See 
    PROGRAMMING, page 5-70. 
    Page 6-27  
    						
    All Inter-Tel manuals Comments (0)

    Related Manuals for Inter-Tel Imx/Gmx 416/832 Installation Manual