Home > Mitel > Communications System > Mitel SMART L CALL CONTROLLER Hardware Installation Manual

Mitel SMART L CALL CONTROLLER Hardware Installation Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Mitel SMART L CALL CONTROLLER Hardware Installation Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 55 Mitel manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    Page
    of 458
    							SECTION MlTL8350-048-l OO-NA 
    PROGRAMMING ROUTING PARAMETERS 
    7.112 
    The factory installed defaults are sufficient to place all callbacks 
    on the DDD route. The routing parameters require no further 
    programming if the use of the DDD route is sufficient. 
    7.113 A ‘Route’ is defined as the instructions to the Controller with 
    respect to the sequences to follow in performing automatic or 
    user-entered callbacks. These parameters control dialtone detection, 
    the order of digits that are dialed out, Centrex dialing if required, and 
    the procedures to follow in the event of call failure. Other route 
    information is also programmable, such as the route name to be used 
    in the Call Detail Record, etc. 
    7.114 The defaults that are resident in the routes are usually sufficient 
    to detect dialtone and dial out the automatic or user-entered 
    callback number. If ‘Other Common Carrier (OCC)’ is used, these pa- 
    rameters would also include the telephone number of the OCC, the 
    authorization code for the OCC, and the detection of that particular 
    carrier’s dialtones and manipulation of the dialout digit order required. 
    7.115 In the parameters to follow, ‘r’ is 1 through 8 to designate 
    routes ‘1’ through ‘8’. 
    The routes to be used are chosen within 
    the Search Tables upon a successful match of digits within the Search 
    Tables. As each callback number is passed through the search tables, a 
    particular route will be chosen after which control is passed to these 
    route parameters. 
    6r5 Access Route, Access Control Sequences 
    7.116 
    The Access Control Sequences instruct the Controller on the 
    specific actions to perform for the dialout of digits. The route 
    Access Control Sequences are a series of digits that indicate actions. 
    These sequences may be repeated or combined in any order required, 
    as long as the total number of characters in the command is less than 
    34. 
    7.117 The 6r5 route is reached as a result of an action digit in the 801 
    to 815 Search Tables. A search table action of ‘Force Route 1’ 
    for a Search Table template will send control to parameter 615 (r=l). 
    Table 7-12 below lists the 6r5 parameter codes with descriptions. 
    Table 7-12, 6r5 Parameter Codes 
    ) CODE 
    1 DESCRIPTION 
    0 Dial the digit ‘0’. 
    1 Dial the digit ‘1’. 
    BOA Dial the DTMF digit ‘jc’. 
    800 Dial the DTMF digit I#‘. 
    BOI Dial a DTMF ‘#’ if the last digit dialed was not a ‘#‘. 
    2 Dial the Callback Number 
    Page 67  
    						
    							SECTION MITL8350-048-l OO-NA 
    Table 7-12 (Cont’d), 6r5 Parameter Codes 
    CODE DESCRIPTION 
    3 
    Dial the OCC Telephone Number in parameter 6rl. 
    4 Dial the OCC Authorization Number in parameter 6r2. 
    6 Dial the Trunk number of the Controller processing 
    this call. 
    7 Cut through - done. This 
    MUST be the last command 
    in the Route Access Control Sequence to instruct the 
    SAC to connect the lines together (after split). If this 
    command is not present, the Controller will wait for 
    the expiration of the Inter-digit Timer before accom- 
    plishing cut through. 
    a Change to DTMF dialing. Normally used with OCC 
    programming. This command would be inserted into 
    the Access Control Sequence when the Central Office 
    being used by the Controller is Rotary only and the 
    OCC requiring DTMF dialing only (parameter x00 
    would be set to 0 or 1). The code could then change 
    the dialout from rotary to DTMF after dialing out the 
    6rl OCC telephone number. 
    9 Dial the Centrex Access Code stored in 6r4. 
    7.118 Table 7-13 below lists the Dialtone Detector codes to be used 
    when coding parameter 6r5. Descriptions of each code is in- 
    cluded. ‘a’ in the code selects the minimum tone duration as listed in 
    Table 7-14. ‘b’ in the code selects the time out for tones not received 
    and are listed in Table 7-15. 
    Table 7-13, Dialtone Detector Codes 
    CODE 
    B25b 
    B3ab 
    B4ab 
    B5ab 
    B6ab 
    B7ab 
    B6ab 
    B9ab 
    BDab 
    BB 
    DESCRIPTION 
    Pause for ‘b’ seconds. 
    Search for ‘a’ milliseconds of high tone (570-680 
    Hz) for ‘b’ seconds. 
    Search for ‘a’ milliseconds of 440 Hz for ‘b’ seconds. 
    Search for ‘a’ milliseconds of 460 Hz Ringback tone 
    for ‘b’ seconds. 
    Search for ‘a’ milliseconds of 400 Hz for ‘b’ seconds. 
    Search for ‘a’ milliseconds of energy (350 to 620 Hz) 
    for ‘b’ seconds. 
    Search for ‘a’ milliseconds of precise dialtone 
    (350+440 Hz) for ‘b’ seconds. 
    Search for ‘a’ milliseconds of ‘Not On Network 
    (NON) tone (an OCC function) for ‘b’ seconds. 
    Search for ‘a’ milliseconds for any DTMF tones for 
    ‘b’ seconds. 
    Entry terminator 
    Page 68  
    						
    							SECTION MITL8350-048-l OO-NA 
    - 
    a 
    = 
    0 
    1 
    2 
    3 
    4 
    5 
    6 
    7 
    8 
    9 
    - 
    Table 7-14, ‘a’ Codes Table 7-15, ‘b’ Codes 
    TONE 
    IURATION ACTION IF b TIMEOUT/TONE NOT RCVD. 
    NOT RECEIVED 
    Minimum Redial per r58 or r78 
    200m.s Redial per r58 or r78 
    400ms Redial per r58 or r78 
    1 .os Redial per r58 or r78 
    2.55s Redial per r58 or r78 
    Minimum Then continue Dialout 
    200ms Then continue Dialout 
    400ms Then continue Dialout 
    1.0s Then continue Dialout 
    2.55s Then continue Dialout 
    0 0 Seconds 
    1 2 Seconds 
    2 4 Seconds 
    3 6 Seconds 
    4 8 Seconds 
    5 10 Seconds 
    6 12 Seconds 
    7 14 Seconds 
    8 16 Seconds 
    9 18 Seconds 
    * 20 Seconds 
    7.119 The default programming entry for all 6r5 Route Access Control 
    Sequences is: 
    874427 
    Where ‘B7’ indicates that the Controller should search for ‘a’ millisec- 
    onds of wideband dialtone (350+620 Hz) for ‘b’ seconds. In this case, ‘a’ 
    equals 2.55s tone duration, then fail to parameter r58. ‘b’ equals 8 
    seconds (i.e., the Controller will look for a minimum length of dialtone 
    for 8 seconds). If the tone is detected, then ‘2’ indicates that the 
    Controller should dial the callback (Speed Call) or user entered callback 
    number, and ‘7’ indicates that the dialing is finished. The ‘7’ also 
    indicates that the Controller should cut through (reconnect the lines). 
    Programming Examples 
    7.120 Programming the 6r5 Route Access Control Sequences consists 
    of entering the 6r5 parameter after the terminal prompt > 
    where ‘r’ selects the route number. This parameter is followed by a 
    data string for the Access Control Sequence as selected from the 
    previous tables. The entry is completed by typing the data terminator 
    ‘BB’. 
    Example 1 
    > [6158854347BBl 
    7.121 
    Example 1 shows that this is the Route 1 Access Control Se- 
    quence (615). The ‘88’ along with the ‘5’ and ‘4’ indicates that 
    the Controller is to wait for a minimum duration of precise dialtone for 
    up to 8 seconds. ‘3’ indicates that if dialtone is detected, the Controller 
    then dials the OCC telephone number that is listed in parameter 6rl. ‘4’ 
    indicates that the Controller should dial the OCC Authorization Number 
    listed in 6r2 if ‘3’ completes. ‘7’ indicates cut through and completion 
    after finishing with ‘4’. ‘BB’ terminates the string entry. 
    Page 69  
    						
    							SECTION MlTL8350-048-IOO-NA 
    7.122 
    Example 1 may not be a valid entry for the SAC, but does 
    illustrate the manner in selecting and entering the 6r5 param- 
    eters. 
    7.123 Table 7-16 below lists some additional Route Parameters that 
    may be programmed to desired operation. Entry is similar to 
    the 6r5 parameter described above for the 6xx parameters. For the r50t 
    through r58t and the r70t through r78t parameters, entry consists of 
    selecting a route number for ‘r’ and a parameter descriptor for ‘t’. 
    These descriptors are listed in the table under the applicable param- 
    eter. The descriptor may be an action to be performed or a description 
    of a format or register. 
    Note: r50t through r58t indicate primary routes (l-4) while r70t 
    through r78t indicate alternate routes (l-4). 
    Table 7-l 6, Additional Route Parameters 
    ENTER 
    6r4 (Number) BB DESCRIPTION (r = l-8) 
    Centrex Number (Default = 9). Can be up to 33 digits in length for 
    ‘number’. 
    6r2 ( Number) BB OCC Authorization Number. ‘number’ can be up to 33 digits in 
    length. 
    6rl( Number) BB OCC Telephone Number. ‘number’ can be up to 33 digits in length. 
    ENTER DEFAULT DESCRIPTION (r = l-4) 
    r50t 
    r70t 0 
    0 
    Automatic or User Entered Callback Number Format, where t 
    equals: 
    0 = Any number of digits. 
    1 = Add Area Code stored in 601 to 7 digits. If 10 digits, do 
    not add Area Code. 
    2 = Add l+Area Code stored in 601 to 7 digits or l+ to 10 
    digits. 
    4 = Dial ‘1’ before 7 or 10 digits (do not add Area Code). 
    8 = 7 or 10 digits only. 
    r58t 
    r78t 5 
    5 Action upon Call Failure. This entry is the action that is initiated 
    upon call failure indicated by the ‘a’ code of parameter 6r5 if ‘a’ 
    is less than ‘5’, where ‘t’ equals: 
    0 = Redial on Route 1 (or 5) 
    1 = Redial on Route 2 (or 6) 
    2 = Redial on Route 3 (or 7) 
    3 = Redial on Route 4 (or 8) 
    4 = Drop call (Deny) 
    5 = Redial on same route once, then drop 
    6 = Redial on same route twice, then drop 
    7 = Redial on same route three times, then drop 
    8 = Redial on same route once, then on Route 1 (or 5) 
    9 = Redial on same route twice, then on Route 1 (or 5) 
    A = Redial on same route three times, then on Route 1 (or 5) 
    Page 70  
    						
    							SECTION MITL8350-048-l OO-NA 
    CALL DETAIL RECORD (CDR) PROGRAMMING 
    7.124 
    The Call Detail Record (CDR) output of the RS-232 Computer 
    Port is governed by parameters 006 (Baud Rate), 007 (Nulls after 
    Carriage Return), 009 (Print Format), 010 (Route to Monitor), 602 
    (Machine Identifier), 6rO (Route Name), and 821 through 835 (print or 
    no print action digit for password). In addition, the CDR responds to 
    the control characters  and  (stop and start commands). 
    The control-S command will suspend the CDR output, while the 
    control-Q will restart the output. These commands are entered by 
    pressing the  and ‘S’ or ‘Q’ keys at the same time. 
    CDR Description 
    7.125 
    The incoming call record will indicate the date, time, and dura- 
    tion of the access attempt. It will also indicate ‘INWARD’ on a 
    callback access. It will print the ‘INVALID’ password of an unsuccessful 
    access. In addition, it will indicate ‘C-THRU’ if the action was not a 
    callback, and will print the successful password used if the password 
    action digit was so programmed. It will not indicate a user entered 
    callback number. The user entered callback number will be printed in 
    the outgoing call record, instead. 
    7.126 The outgoing call record will indicate the date, time and dura- 
    tion of the outgoing call along with printing the successful 
    password used if the password action digit was so programmed. It will 
    print the callback Speed Call ‘bin’ number (‘nnn’ of parameter ‘7nnn’). It 
    will also print the user entered callback number if the password action 
    digit indicates that it should do so. 
    Call Detail Record Format 
    SMarT-1 Format (009t = 2, Default) 
    a 
    4 
    5 
    6 7 
    MM/DD_HH:MM__ DH:DM:DS_nnnnnnnnnnnnnnnnnnnn 
    I I I ___TSTn_######_eeeaasaaaea~aaaaaa_SAC 
    1 uu-II 
    A B 
    c D 
    E F 
    Where: 
    A) is the Date and Call Duration. 
    B) is the Speed Call Bin Number or Callback Number on outgoing 
    calls. Nothing is printed in this field on incoming calls. 
    C) is T for denied on outgoing attempt (space if otherwise), S for 
    Speed Call (space if otherwise), and Tn is the Trunk Number. 
    D) is the Route Name programmed in ASCII for outgoing calls. 
    ‘C-THRU’ in this field on an incoming call indicates that the 
    caller gained access to the Modem by virtue of the 
    Page 71  
    						
    							SECTION MITL8350-048-l OO-NA 
    ‘cut-through’ action digit associated with the printed password 
    in that call record. ‘THRU’ in an outgoing call indicates that no 
    route was dialed. The dial immediate function has either been 
    used on the Speed Call dialout or the SAC is programmed to 
    the ‘cut-through’ mode and is asleep. ‘DENIED’ in this field will 
    indicate an unsuccessful password entry and failure to access 
    the host system. :. ...-, 
    . . . . : 
    E) is the Password digits if enabled by the password action digit, 
    or any invalid password received. 
    F) is the Machine Identifier from programming in parameter 602. 
    Examples 
    7.127 Figure 7-5 below is an example of the SMarT-1 Call Detail 
    Record printout for incoming calls. There are 8 lines in the 
    Figure and these are considered for discussion purposes to be exam- 
    ples 
    1 through 8, respectively, in the paragraphs that follow. The 
    examples also assume that the ‘print password’ action digit has been 
    used for each of the passwords. If it was not used, the password 
    section of the printout would be blank. 
    00/99 00.09 0o:oo: 15 Tl DENIED 
    SAC 
    11/02 10: 55 00:00:26 Tl DENIED 
    SAC 
    11/02 11:25 00:01:06 Tl INWARD 76276663 SAC 
    11/02 11:53 01:13:49 Tl C-THRU 
    623346 SAC 
    1 l/O2 13:31 00:01:57 T2 INWARD 
    22552225 SAC 
    11/0’3 21:50 00:01:22 Tl DENIED 
    10000000 SAC 
    11103 21:22 00:01:22 Tl DENIED 
    10000001 SAC 
    11/03 22:Ol 00:01:30 T3 INWARD 76276664 SAC 
    Figure 7-5, Incoming Call Detail Record Examples 
    . 
    7.128 Line 1 of Figure 7-5 indicates that a test call was made to the 
    unit. Note the ‘.’ versus the ‘:’ 
    in the time field. The time is 
    incorrect (not programmed into the unit or the unit has momentarily 
    been powered down). Access was denied by virtue of the unit not 
    having been programmed. 
    7.129 Line 2 of Figure 7-5 indicates that the unit has been pro- 
    grammed and that the first call was made into the unit without 
    entering any password. 
    7.130 Line 3 of Figure 7-5 indicates that an incoming call was re- 
    ceived with a successful password. Speed Call action digits are 
    associated with the password. In Figure 7-6 (Outgoing Calls), Line 1 
    would be a printout for returning the call. 
    ’ 
    _: 
    7.131 Line 4 of Figure 7-5 shows that an incoming call was received 
    with a ‘cut-through’ action digit for the password. In this case, 
    there is no corresponding outgoing call record. 
    Page 72  
    						
    							SECTION MITL8350-048-1 OO-NA 
    7.132 Line 5 of Figure 7-5 shows that an incoming call was received 
    with a a successful password. A request for a callback number 
    action digit happens to have been used. Note that the incoming record 
    shows only the successful password. In Figure 7-6, Line 2 shows the 
    outgoing call record associated with the incoming call. It displays the 
    user entered callback number along with the password. 
    7.133 Lines 6 and 7 of Figure 7-5 are access denials. The Call Detail 
    Record shows the password attempt. 
    7.134 Line 8 of Figure 7-5 shows an incoming record with a success- 
    ful password. Line 3 of Figure 7-6 shows the associated out- 
    going record. The call listed in the outgoing record was denied (T), 
    possibly because the programmer denied calls to the 818 area code 
    for some particular reason. 
    11/02 11:27 01:27:33 663 ST1 AT&T 76278663 SAC 
    11/02 ?3: 33 00:32:45 3153931212 Tl OCC 22662225 SAC 
    11/03 22:03 00:00:05 8185451958 T T3 OCC 76279664 SAC 
    Figure 7-6, Outgoing Call Detail Record Examples 
    MITEL Format 
    7.135 Since this format was developed for use in PABX applications, 
    there are fields that only pertain to transferred calls. The 
    SMarT-1’” unit has no use for this information and, as a result, these 
    fields are left blank. Otherwise, the format is very similar to the call 
    record produced by MITEL PABXs. 
    7.136 Several call costing machines can process the original MITEL 
    Format. For more information on tested systems, call MITEL 
    DATACOM. 
    The record is 86 characters long with the following fields: 
    0 
    0 M - Month/Day 
    B - Start time (BB.BB means that the clock is wrong) 
    (Note the period instead of a colon) 
    C - Call duration 
    Ill1 - Incoming line 
    D - User dialed digits 
    T - Denied 
    S - Speed dialed 
    L - Line number 
    R - Route (8 = Internal in Centrex mode) 
    A - Account code 
    N - System identification 
    Page 73  
    						
    							SECTION MITL8350-048-IOO-NA 
    The named fields on the previous page are printed in a line as illus- 
    trated by the line description below: 
    MITEL Format (009t = 1) 
    0 
    1 2 3 
    4 5 6 7 8 
    1234567890123456789012345676SJ 1234567690123456789012345676901234567890123456789912345678 
    _MM/DD_BB:BB__ CC:CC:CC_IIII______DDDDDDDDDDDDDDDDDDDDDDD___TSLLR~_______AAAAAAAAAAAA_NNN 
    where the fields are as described in Table 7-17. 
    7.137 Each line is ended with a CARRIAGE RETURN (ASCII 13) and 
    LINE FEED (ASCII 10) and a programmable number of NULLS 
    (ASCII 0). All alphabetic fields are in upper case. The dialed number and 
    the dialed account code fields will be numbers 0 through 9, x and #. 
    Table 7-17, MITEL Call Record Format Fields 
    FIELD COLUMN NR’ 
    CHARS. FORMAT MEANING 
    1 ? 
    “SPAeE” 
    M 2-6 5 MONTH; “/“; DATE 
    7 
    1 “SPACE” 
    B 8-12 
    5 HOURS; “:“; MINUTES (This is the time 
    of the start of call rounded out to 
    nearest minute) See note 1. 
    13-14 2 “SPACES” 
    C 15-22 8 HOURS; “:“; MINUTES; ‘Y’; SECONDS 
    (Call duration) 
    23 1 “SPACE” 
    I 24-27 4 
    “TnOO” (Printed on incoming calls only; 
    blank on outgoing calls. n is the Line 
    Number [l-4]) 
    28-33 6 “SPACES” 
    D 34-56 
    23 This is the number that was dialed as 
    the “destination”. See note 2. 
    57-59 3 “SPACES” 
    T 
    60 1 “T” = 
    Denied outgoing callback. “D” = 
    Denied incoming access. “C” = Incom- 
    ing cut through access. “SPACE” = 
    Otherwise. 
    S 61 1 
    “S” if the call was speed called; 
    “SPACE“ otherwise. 
    L,R 62-65 4 
    “TnOr” (Printed on outgoing calls only; 
    blank on incoming calls. n is the Line 
    Number [l-41. r is the route chosen 18 
    = no route] where r0 - r7 equals 
    Route 1 - 8.) 
    66-72 7 “SPACES” 
    A 73-84 12 Dialed account code. See note 3. 
    85 1 “SPACE” 
    N 86-88 3 System Identification (first three char- 
    acters of parameter 602). 
    Page 74  
    						
    							SECTION MlTL8350-048-l OO-NA 
    NOTE 1 
    NOTE 2 
    NOTE 3 Time Display Field: If the separating character in the start of 
    call field is a period (.), the time has not been programmed 
    into the Dialer. Use parameter 980 to program the time. When 
    a Dialer is powered on, it will continue to use the last time 
    that was programmed (time at power down) but will mark the 
    call record with a period (,). If the loss of power is only a few 
    seconds, it will not significantly affect the timekeeping. 
    Dialed Number Field: This field is the Speed Call Bin Number 
    or Callback Number on outgoing calls. Nothing is printed in 
    this field on incoming calls. 
    If there is further dialing, these digits may be collected in the 
    “account code”. If Centrex mode is being used, the user- 
    dialed Centrex Access Code (usually a “9”) is not printed. The 
    way to tell internal calls from external calls is to look at the 
    route character (O-7 means a route was used, which probably 
    dialed another “9” for the user; 8 means that the call was not 
    routed, and the Dialer only forwarded the digits as displayed). 
    If an automatic callback is accessed, the speed call ‘bin’ num- 
    ber will appear in this field. 
    Password Digits: This field displays the password digits that 
    were entered by the user, provided that the password action 
    digit allows ‘print password’ for a valid password. All invalid 
    passwords are printed in this field. Only the first 12 digits are 
    displayed, even though the SMarT-1’” unit can handle 23 digit 
    passwords. 
    7.138 This completes the description of programming for the Control- 
    ler. All of the parameters described in the preceding paragraphs 
    have been included in a handy reference table showing the default 
    settings in Appendix C. This table is to be used for those programmers 
    who have read and understood all of the descriptions, but wish to have 
    a quick reference guide to the parameter numbers. The table also 
    includes references to paragraphs that cover the particular parameter, 
    if needed. 
    CONTROLLER MEMORY CAPACITY 
    7.139 The SAC useable memory consists of an 8K X 8 bit battery 
    backed up Random Access Memory (RAM) chip that is capable 
    df holding approximately 14,500 characters. This memory area is avail- 
    able for the storage of parameters and data at programming time. The 
    rest of the available space is used for program execution overhead. 
    7.140 It is unlikely that a programmer will completely fill the RAM 
    area with data. In the event that memory space becomes a 
    matter of concern, the ground rules for estimating memory usage are 
    discussed in the paragraphs to follow starting with paragraph 7.143. 
    7.141 If a programmer runs out of space while programming the 
    Controller, none of the previously programmed data will be lost. 
    Page 75  
    						
    							SECTION MITL8350-048-l OO-NA 
    The controller simply refuses any more programming after complete 
    memory usage by displaying a question mark (?) on the terminal 
    screen at the termination of each data entry on the keyboard. if it is 
    suspected that RAM space has been completely used up, contact the 
    distributor or the MITEL DATACOM Field Service Office. Once con- 
    tacted, these personnel can verify that all RAM space has been used, 
    and can possibly recommend more efficient programming techniques 
    that can remedy the situation. As previously mentioned, the program- 
    mer should almost never run out of RAM space for parameters and 
    data. 
    7.142 Estimates of the memory space required versus the available 
    memory space are possible. The programmer can, therefore, 
    estimate the memory space required before programming and can 
    determine if the available space is insufficient. 
    Memory Space Estimating Method 
    7.143 
    The simplest way to determine if the the intended data base 
    will fit into available memory is to calculate the space required 
    by the data. This space is then compared to the space available 
    according to the following rules: 
    1) 
    2) 
    3) 
    4) There are approximately 14,500 available data spaces in a 
    freshly initialized SAC. These spaces are used to store pro- 
    grammed data. All data to be programmed into the SAC will use 
    this space with the exception of default settings. If a default 
    setting is used, it will not decrease the available space. Space is 
    mainly consumed by the parameters which are defined as 
    ‘string’ entries and require the ‘BB’ terminator for entry. Entries 
    that do not require the ‘BB’ terminator may be ignored in cal- 
    culations. 
    A Search Table entry (parameters 801 through 815) occupies a 
    number of spaces equal to the length of the template plus the 
    action digits. For example, an 804 Search Table entry such as 
    ‘804 1315 0 BB’ is four digits plus one action digit for a total of 
    five memory spaces. The ‘804’ and ‘BB’ entries are not counted. 
    An entry of ‘803 B9B9B9B2’ is six digits plus two action digits 
    for a total of eight memory spaces. 
    A password entry (parameters 821 through 835) occupies the 
    number of spaces equal to the length of the template 
    (password) plus the action digits. The password ‘12345’ with a 
    speed call callback action and 24 hour access action would be 
    programmed as ‘825 12345 20 BB’ and would require seven 
    spaces. The ‘825’ and ‘BB’ entries are not counted. 
    A callback (Speed Call) entry occupies a number of spaces 
    equal to the length of the Speed Call plus six (an internal 
    Controller requirement) spaces. This number must be rounded 
    off to the next larger even number if the result is odd. For 
    example, a Speed Call programmed as ‘7nnn 8 139311212 BB’ 
    requires 14 spaces in memory. The eight digits of the telephone 
    number plus six additional for the Controller equals 14. The 
    Page 76  
    						
    All Mitel manuals Comments (0)

    Related Manuals for Mitel SMART L CALL CONTROLLER Hardware Installation Manual