Home > Mitel > Communications System > Mitel Sx 200 Ml Pabx Lightware 16 Instructions Guide

Mitel Sx 200 Ml Pabx Lightware 16 Instructions Guide

    Download as PDF Print this page Share this page

    Have a look at the manual Mitel Sx 200 Ml Pabx Lightware 16 Instructions Guide online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 55 Mitel manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    Page
    of 626
    							Maintenance Log Messages 
    Table 7-4 Main Control Reset Log Reports 
    Reset Log Message 
    Main Control was reset due to power up 
    Main Control was reset due to pushbutton 
    Main Control was reset due to watch dog timer 
    Main Control was reset due to local bay cause 
    Main Control was reset due to msg link failure 
    Main Control was reset due to software error 
    Process 00 ANYTHING at address 012345 
    Main Control was reset due to software error 
    Main Control was reset due to software error 
    Process 00 has overflowed its stack 
    Main Control was reset due to software error 
    Exception = ANYTHING at address 012345 Action Required 
    Information only. Main Control Card II is reset at 
    power-up. 
    The RESETpushbutton on the Main Control Card 
    II was pushed. Investigate. 
    In all cases, check if Main Control Card II is 
    functioning; if not, go to Emergency 
    Troubleshooting procedures. 
    Table 7-5 Bay Reset Log Reports 
    Reset Log Message 
    Bay X was reset due to msg link failure 
    Bay X reported cause: scanner/power 
    Bay number X reported cause: parity failure 
    at address XXXXXX 
    Bay number X reported cause: power up Information only. Bay Control Card is reset at 
    at address XXXXXX power-up. 
    Bay number X reported cause: reset by MCC 
    at address XXXXXX Bay was reset because Main Control Card II was 
    reset. Investigate possible Main Control Card II 
    problem. 
    Bay number X reported cause: watchdog timer 
    at address XXXXXX 
    Bay number X reported cause: ** anything else** 
    at address XXXXXX Action Required 
    The main control was unable to communicate with 
    the bay, and therefore reset the bay. Bay may 
    have lost power; possibly faulty Scanner Card. 
    Failure of on-board DRAM. If persistent, replace 
    the Bay Control Card. 
    Software failure. Check if Main Control Card II is 
    functioning; if not, go to Emergency 
    Troubleshooting procedures. 
    Software failure. Check if Main Control Card II is 
    functioning; if not, go to Emergency 
    Troubleshooting procedures. 
    March 1997 Issue 1 Revision 0 7-l 7  
    						
    							Troubleshooting 
    Table 7-6 Miscellaneous Log Reports 
    Reset Log Message Action Required 
    System Configuration/System ID module 
    conflict. Change system configuration to clear 
    error. Check the installation of the System ID module. 
    Check Form 4 option selection. 
    Log(s) deleted by user A user logged in to the maintenance facility 
    (maintenance terminal or console) deleted one or 
    more log entries via the DELETE LOGS 
    command. 
    Involved in recovery is 01 04 04 04 ext 1100 
    01 03 03 03 Trk 001 
    Main Control trace back at address = XXXXXX 
    (anything) 
    CP Process recovered from software error # XX 
    (anything) In all cases, this indicates a software error. Refer 
    the problem to MITE1 Field Service. 
    7-18 Issue 1 Revision 0 March 1997  
    						
    							8 Troubleshooting Aids 
    Call Processing Information 
    Table 8-l Digital Bay to Digital Bay Call 
    Step Event 
    1. Caller in Bay 1 goes Off-Hook (the event). 
    2. The Bay Control Card (BCC) scans circuits on each card for events (hardware). 
    3. When an event occurs, the BCC assembles a message (in HDLC format) describing the 
    event, the associated PLID, and the device which caused the event. 
    4. The message is then sent via a dedicated message channel to the Main Control Card II (MCC 
    II). 
    5. The message is picked up by the message system and routed to the appropriate destination; 
    in this case, the Call Processor (CP) processes messages in a first in - first out manner. 
    6. CP, taking the message from its message queue, then accepts the message and looks up 
    the Device Work Area (DWA). This work area allows CP to determine the COS, COR, and 
    other features enabled for the device which caused the event. 
    7. CP checks for an available receiver and channel, and connects them to the device via the DX 
    matrix. 
    6. Once the Receiver is connected to the device, dial tone is sent from the Digital Signal Pro- 
    cessor (DSP) on the MCC Il. This also must be connected to the device via the DX matrix. 
    9. The caller then hears dial tone and begins dialing digits. 
    10. For ONS calls only, the Receiver decodes the first digit and passes it to the MCC Il. For 
    SUE~SE7telephones digits are sent to Call Processing (CP). 
    Il. The MCC II accepts the digit and turns off dial tone from the DSP; it then waits for further 
    digits. 
    12. While waiting for and receiving the digits, the MCC II checks validity of digits dialed against 
    database and against COS/COR limits for the device. 
    13. Once all digits are accepted, the MCC II uses the information received to find the destination 
    device and set up a channel to initiate the call. 
    14. Assuming the destination is idle, the MCC II sends the ringing message to the BCC to ring 
    the destination. The receiver is dropped during ringback. 
    15. The BCC then instructs the Bay Power Supply (BPS) to send ringing voltage via the back- 
    plane and dry contact relays on the line card to the destination. Ringing reference is supplied 
    by the DSP and cadenced by the BCC for a specified pattern such as l second ON, 3 sec- 
    onds OFF. SU/?EfEE~ telephones are sent a message to cause the set to begin warbling. 
    16. While the destination is being rung, ringback tone is sent to the calling party. This is supplied 
    by the DSP from the MCC Il. 
    17. Destination hears ringing and goes OFF-HOOK. 
    18. BCC detects off-hook while scanning all ports in its bay and sends the answer message to 
    the MCC Il. 
    Page 1 of 2 
    March 1997 Issue 1 Revision 0 8-l  
    						
    							Troubleshooting 
    Table 8-l Digital Bay to Digital Bay Call (continued) 
    I I 
    Step Event 
    19. MCC II accepts the answer message, instructs the BCC to turn off the ringing being sent to 
    the destination, turns off ringback tone being sent to the source, and then instructs the DX 
    matrix to connect the source to the destination. 
    This establishes the voice connection. 
    20. Conversation is carried out and completed. 
    21. One party hangs up. BCC detects and sends disconnect message to MCC Il. MCC II puts 
    other party in ‘suspended - xxxx hung up’ or ‘lockout - locked out’ until he also hangs up. 
    Then 
    the MCC II returns the set to idle. 
    Page 2 of 2 
    Troubleshooting Kit 
    The following is a recommended list of items required in the Field Service Engineering 
    Troubleshooting Kit: 
    . One of each circuit card as a spare,. including modules 
    . Butt set 
    . Digital multimeter 
    . Moving coil multimeter 
    . Static strap 
    . Ground mat 
    . Assorted screwdrivers, wrenches 
    . Long nose pliers 
    . Spare fuses 
    . Wire strippers 
    . Fan filter 
    . Breakout Box (for Data). 
    Loop Current Measurement 
    There are two methods available to measure loop current: 
    0 In-Line method 
    l Voltage conversion measurement 
    If it is not possible to break the loop (i.e., open the Tip or Ring lead) the second method 
    may be used; however, it is not as accurate. 
    In-Line Method. The procedure for the in-line method of measuring loop current is 
    shown in Figure 8-l and is described as follows: 
    I. 
    Open either the Tip or Ring lead of the trunk facility by removing one of the bridge 
    clips on the MDF. 
    8-2 Issue 1 Revision 0 March 1997  
    						
    							TroubleshooGng Aids 
    2. insert an ammeter where the clip was. 
    3. Take current readings at the instant the trunk is seized, and after the call has been 
    completed. Do this in both incoming and outgoing directions. 
    4. Release the trunk and repeat the measurements several times on the same 
    Central Office at peak and low traffic hours. 
    5. Repeat the above steps using different Central Office trunks. 
    Voltage Conversion Method. This method of loop current measurement should be 
    used only in such instances when it is not desirable to open the Tip or Ring leads. The 
    procedure is as follows: 
    1. With the trunk seized, use a voltmeter to measure the voltage between the Tip 
    and Ring of the trunk. 
    2. This voltage is then used to calculate the loop current (see below). 
    3. Release the trunk and repeat the measurement several times using the same 
    Central Office trunk at peak and low traffic hours. 
    4. Repeat the above measurements using different Central Office trunks. 
    5. Typical equivalent resistance seen between Tip and Ring, when the trunk is 
    seized, is approximately 250 ohms. 
    6. The following is a simple calculation used to obtain the loop current value: 
    Loop Current = measuredTiptoRingvoltage 
    2 250 
    MDF 
    BRIDGE CLIP 
    TRUNK 
    TRUNK FACILITY 
    Figure 8-l In-Line Current Measurement 
    March 1997 Issue 1 Revision 0 B-3  
    						
    							Troubleshooting 
    Loop Stat-t Versus Ground Start Check 
    The loop start versus ground start check should be performed as follows (also refer to 
    Figure 8-2): 
    1. Locate the PBX trunk circuit Tip and Ring on the connecting block at the MDF. 
    2. Remove the bridge clips on the Tip and Ring (i.e., disconnect the PBX trunk circuit 
    from the Central Office Tip and Ring). 
    3. Connect the butt set across the Central Office Tip and Ring. 
    4. Go off-hook with the butt set. If Central Office dial tone is returned, then the Central 
    Office trunk is loop start. 
    5. If no dial tone is returned, then momentarily ground the Ring lead with a butt set 
    off-hookacross Tip and Ring. If Central Office dial tone is returned, then the Central 
    Office is ground start. 
    6. If still no dial tone is returned, repeat the previous step and ground the Tip lead 
    instead. If Central Office dial tone is returned, the Central Office trunk is ground 
    start (however, the Tip and Ring are reversed). 
    7. If still no dial tone is returned in either of these cases, there is a problem (perhaps 
    Tip and Ring opened or shorted, or there is a large ground differential between 
    PABX ground and Central Office ground.) Check PABX ground. If PABX ground 
    is good, then report the problem to telephone company. 
    Note: In most cases with ground start trunks, dial tone may be returned by grounding either Tip or 
    Ring. If this should occur, repeat the 5th and 6th steps using the butt set in its “on-hook” or 
    “monitor” state. Hold the ground lead on for a few seconds; CO should return dial tone as long 
    as the ground lead is connected. 
    CONNECTING BLOCK 
    TO PABX 
    TRUNK 
    CIRCUIT 
    BUTT SET v 
    8-4 
    Figure 8-2 Loop Start Versus Ground Start Check 
    Issue 1 Revision 0 March 1997  
    						
    							Troubleshooting Aids 
    March 1997 
    NOTES 
    Issue 1 Revision 0  
    						
    							Troubleshooting 
    8-6 Issue 1 Revision 0 March 1997  
    						
    							SX-200@ ML PABX 
    RS-232 
    Maintenance 
    Terminal 
    TM, @I - Trademark of Mite1 Corporation. 
    @ Copvriaht 1997. Mite1 Corporation. 
    @ MITEL’  
    						
    							RS-232 Maintenance Terminal 
    NOTICE 
    The information contained in this document is believed to be accurate in all re- 
    spects but is not warranted by Mite1 Corporation (MlTEL@). The information is 
    subject to change without notice and should not be construed in any way as a 
    commitment by Mite1 or any of its affiliates or subsidiaries. Mite1 and its affiliates 
    and subsidiaries assume no responsibility for any errors or omissions in this doc- 
    ument. Revisions of this document or new editions of it may be issued to incor- 
    porate such changes. 
    SX-200, SUPERSET, SUPERSET 3, SUPERSET 4, SUPERSET 3DN, SUPERSET 4DN, 
    SUPERSET 401+, SUPERSET 410, SUPERSET 420, and SUPERSET 430 are trademarks 
    or registered trademarks of Mite1 Corporation. 
    VTIOOTM is a trademark of Digital Equipment Corp. 
    Issue 1 Revision 0 March 1997  
    						
    All Mitel manuals Comments (0)

    Related Manuals for Mitel Sx 200 Ml Pabx Lightware 16 Instructions Guide