Mitel Sx 200 Ml Pabx Lightware 16 Instructions Guide
Have a look at the manual Mitel Sx 200 Ml Pabx Lightware 16 Instructions Guide online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 55 Mitel manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
2 Troubleshooting - General Emergency Procedures 2.1 When any switching machine is totally inoperative, the prime requirement is the restoration of service to the system or the part that has been affected. Table 2-i shows how to achieve this in the shortest possible time. Once service has been restored, the other procedures (see Table of Contents) may be used to determine the cause of the failure. Step 1. 2. 3. 4. 5 6. 7. Table 2-l Emergency Troubleshooting Procedures Action At the control cabinet, check if the green ACTIVEindicator on the Main Control Card II front panel is flashing. Press the RESET pushbutton on the front panel of the Main Control Card Il. Check if the POWER O/Vindicator on the Bay Power Supply is on. Turn the Cabinet power supply off, reseat the Main Control Card II and Bay Control Card, and turn the power on again. Any indication on numeric display? Check power rails and continuity on the backplane. Power down the cabinet, remove the Main Control Card II, and check if System ID module is securely installed. Ensure Bay PowerSupply isfirmlyseated into the backplane. ispowercordfirmlyconnected to the rear of the BPS? Check for loose power cable connections in the Cabinet. Description / Follow-Up Yes: l Go to step 7. No: l Go to step 2. l If the Main Control Card II numeric displays are blank, go to step 3; otherwise go to step 9. Yes: l Go to step 4. No: l Go to step 7. Yes: . Go to step 9. No: 0 Go to step 5. l Verify that the required voltage signals actually are present at the Main Control Card II connector. l Once verified, go to step 6. Yes: l Possible System ID problem - replace MainControl Card Il. No: l Install System ID module properly and go back to step 2. No: l Plug in securely; go back to step 2. Yes: l If no wiring problems are found, refer to the Bay Power Supply procedures. Page 1 of 2 March 1997 Issue 1 Revision 0 2-l
Troubleshooting Table 2-l Emergency Troubleshooting Procedures (continued) Step Action Description / Follow-Up 8. Attempt a station-to-station call - is Call Yes: l Stop. Continue to monitor system. Processing functioning? No: l Press the RESET push- button on the Main Control Card II front panel, and go to step 9. 9. Check for error codes on the Main Control l Refer to Table 2-2. Card II numeric display. Page 2 of 2 Main Control Card II Power-Up Error Codes Table 2-2 shows the Main Control Card II numeric display error codes which may appear during start-up. Also shown are the most likely causes of the error condition. Table 2-2 Main Control Card II Error Code Summary Error Code (blank) 0 E. 8 Likely Cause(s) l Faulty power system - refer to that procedure. l Faulty Main Control Card Il. l Faulty Main Control Card Il. l Faulty System ID module. l Nothing - indicates successful software download. This display may be immediately changed to display post-boot-up codes (see note 1). Note: 1. A normal running system may show other codes (card diagnostics or errors). However, during start-up, only the codes in this table are possible. Any other code shown during start-up indicates a faulty Main Control Card Il. 2. Codes possible AFTER start-up include card diagnostics codes (last card location tested - top number indicates bay number, bottom number indicates card slot number). Maintenance logs give results of test, i.e., pass or fail with cause). Troubleshooting Methodology General 2.2 Troubleshooting a malfunction in any complex electronic system is accomplished in a series of logical steps. This Section assumes the following basic steps in the troubleshooting of a malfunction: 2-2 Issue 1 Revision 0 March 1997
Troubleshooting - General l GATHERING of information l CLARIFICATION of the problem l CONFIRMATION of the problem l ISOLATION of the problem l CORRECTION and DOCUMENTATION When investigating a problem, the troubleshooter should continually verify each step in the isolation process so as to ensure that the system and the symptoms of the malfunction are clearly understood. This will ensure that the malfunction is accurately categorized so that appropriate diagnostics, where applicable, may be invoked. Information Gathering and Problem Clarification Chart 2-l provides a list of the information which may be necessary in order to adequately categorize a fault. All relevant information should be gathered and entered into a site fault record. If the fault has resulted in total or partial shutdown of the system, much of this data will be unobtainable or irrelevant. In such cases, reference should be made to the EMERGENCY TROUBLESHOOTING PROCEDURES. Chart 2-l Information Gathering and Clarification Step Action Description Follow-up 1. Talk to station users. Obtain the following information: - frequency of occurrence - intermittent or continuous nature - time period during which the fault occurs - circumstances common to all occurrences. 2. Check Maintenance Alarm indications. - Check maintenance log for fault/ alarm reports (see Note 1). - Check system LED and numeric display indicators for error codes. 3. Collectdataconcerning environmental conditions. - Check if the system is located close to a heat source or a source of power radiation (see Note 2). - Note the temperature and humidity conditions and compare with specified operating parameters. - Check the susceptibility of the area with respect to static electricity generation. - The following can seriously affect the performance of the system: - power fluctuations - lightning storms - excessively high humidity - excessively high temperature - dust - rf interference. 4. Verify system programming. - Check the existing programming to ensure that the correct options and features have been enabled (see Note 3). - Verify the Class Of Service assignments, trunk descriptors, and feature access codes. Page 1 of 2 March 1997 Issue 1 Revision 0 2-3
Troubleshooting Chart 2-l Information Gathering and Clarification (continued) 1 Step 5. 6. 7. Action Description Follow-up Make special checks for new installations, additions or modifications. - Check that the procedures specified in the /n.sWa~~o~~ /nformafion Practice have been properly implemented. - Verify that any changes have been made in accordance with the appropriate practices, and to the prescribed standards. Make random miscellaneous checks. Check for minor alarm indications - these assist in isolating and categorizing faults. - Check for possible conflicts if features have been added or deleted, or if other programming changes have been made. - Ensure all circuit cards are properly seated. - Verify that the system fans are running. - Check the main distribution field for loose or damaged wiring, improperly seated connectors, orothersigns of trouble. - Record relevant data and note the affected area of the system. Page 2 of 2 Note: 1. Refer to the W-232 Maintenance Terminal Practice, for details on procedures. 2. Refer to the Engineering hformation Practice, for the specified operating parameters. 3. Refer to the Features Description Practice, and the Customer Data Entty Practice. Problem Confirmation Many faults, particularly intermittent faults, “disappear” before the troubleshooter is able to make a positive trace. Wherever possible, attempts should be made to force the problem to recur, such that the effects may be observed and hence the cause determined. The information gathered up to this point may be used to set up conditions relating as closely as possible to those under which the fault originally manifested itself. Problem Isolation The aids listed in Table 2-3 are useful in isolating fault conditions. Table 2-3 Troubleshooting Aids Troubleshooting Aid Maintenance Log Maintenance Terminal Description and Use - Provides a record of maintenance activities and causes of alarms (the primary source of troubleshooting information). - Primary access to the maintenance log. - Provides ability to query alarm status, along with a variety of status reports. - Allows testing of individual functional units, using directed diagnostics. Page 1 of 2 2-4 Issue 1 Revision 0 March 1997
Troubleshooting - General Table 2-3 Troubleshooting Aids (continued) Troubleshooting Aid Description and Use Circuit Card Numeric Displays - Allow system power-up testing and operation to be monitored. Status LEDs (on peripher- - Used to determine if circuit is in use, idle, or not functioning. al cards) Page 2 of 2 Correction and Documentation Once a problem is isolated, the table of contents of this document should be consulted, and the appropriate procedure referenced. Many procedures contain instructions requiring control circuit cards to be reset, removed, powered down or replaced; in these circumstances it should be noted that these actions will cause a partial or total loss of service. If possible, these procedures should be performed during periods of little or no traffic. All repairs or adjustments to the system should be recorded into a log book which is kept permanently at the site. Faulty equipment should be returned in the same packaging as the replacement part (FRU). For further information on FRU items, refer to the Fie/d-Rep/aceab/e Units Practice. March 1997 Issue 1 Revision 0 2-5
3 Peripheral Equipment Troubleshooting Procedures Peripheral Interface Circuit Cards ONS / OPS / Station Line Cards 3.1 This section covers the ONS Line Card (PN 9109-010) and the OPS Line Card (PN 9109-040). Table 3-l outlines the most likely items to cause malfunction. For ONS Line Card problems involving Voice Mail, see Voice Mail - ONS Port. Table 3-l ONS Line Card Troubleshooting Summary Step Possible Malfunction Source 1. Faulty connections between the telephone and the cross-connect field. 2. Faulty connections between the cross-connect field and the system. 3. Faulty CDE programming; likely forms: l COS Define l Stations / SUPERSETTM Telephones l Device Interconnection Table l System Configuration 4. Faulty telephone set. 5. Faulty line card. 6. Faulty backplane cable connections. 7. Problem with DSP receivers or DTMF Receiver modules (not enough for peak traffic load). Note: Useful maintenance commands: SHOW STATUS, TEST, SHOW ALARMS - see the US-232 Maintenance Terminal Practice. March 1997 Issue I Revision 0 3-l
Troubleshooting COV Line Cards This section covers the COV Line Card (PN 9109-020). Table 3-2 outlines the most likely items to cause malfunction. For COV Line Card problems involving Voice Mail, see COV Port - Voice Mail in Chapter 5. Table 3-2 COV Line Card Troubleshooting Summary Step Possible Malfunction Source Faulty connections between the SWH?SE~telephone and the cross-connect field. 1. 2. 3. Faulty connections between the cross-connect field and the SX-200 ML system. Faulty CDE programming; likely forms: l COS Define 4. 5. 6. 7. l Stations / SUPE/%flTelephones l Device Interconnection Table l System Configuration. Faulty SUPH?SE~ telephone set. Faulty line card. Faulty backplane cable connections. Problem with DTMF Receivers (not enough for peak traffic load). Note: Useful maintenance commands: SHOW STATUS, TEST, SHOW ALARMS, SHOW ERRORS SS3-SS4 - see the RS-232 Maintenance Commands Practice. Digital Line Card General Intermittent problems can be caused by improper bridge taps, or incorrect loop lengths. The following table lists the maximum loop lengths in meters with 24 or 26 AWG twisted pair wiring. Table 3-3 Digital Line Card Loop Lengths Peripheral Maximum Loop Length Device Without Bridge Tap With Bridge Tap * SUPERSET 401 +TM 1 OOOm not permitted SUPERSET 41 OTM 1 OOOm not permitted SUPERSET 420TM 1 OOOm 1 OOOm SUPERSET 430TM 1 OOOm 1 OOOm Dataset 1103 2000m 1 OOOm Page 1 of 2 3-2 Issue 1 Revision 0 March 1997
Peripheral Equipment Troubleshooting Procedures Table 3-3 Digital Line Card Loop Lengths (continued) Peripheral Maximum Loop Length Device Without Bridge Tap With Bridge Tap * Dataset 2103 2000m 1 OOOm MILINKTM Data Module 2000m 1 OOOm SUPERCONSOLE 1 OOOTM console 1 OOOm 1 OOOm SUPERSET 7000TM console 1 OOOm not permitted Page 2 of 2 Note: Peripheral devices can not use bridge taps if they are connected to Digital Line Cards with PN 9109-012-001 -NA or PN 9109-012-001 -NA. Digital Line Cards with PN 9109-012-000-SA may have bridge taps. SHOW ERRORS DATASET Command The SHOW ERRORS DATASET command can be a useful tool in the troubleshooting of both the Digital Line Card and the Dataset. The following table lists the possible causes of the error types. Error Type CFICERR RESETS LINK FAIL Table 3-4 SHOW ERRORS Command L Call Possible Cause State Dataset Cabling DX Chip Line Card DTE/DCE any w ws w yes no w yes w yes 9s yes Call setup/ Talk yes vs yes w no Additional Troubleshooting Digital Line Cards are used for many applications. For additional troubleshooting information, refer to procedures for the specific application; i.e.: l SUPERSET 401+ Telephones l SUPERSET 4 IO Telephones March 1997 Issue 1 Revision 0 3-3
Troubleshooting . SWERSE~ 4ZU Telephones l SW ERSET 430 Telephones l SUPERSET 7000 console l DATASET 1103 l DATASET 2103 l A&WWData Module l Programmable Key Module Trunk Cards - General The procedures detailed below cover the isolation and correction of faults with the various trunk cards. Supplementary procedures are provided for specific trunk types where required. Table 3-5 summarizes troubleshooting for trunk cards. Table 3-5 Trunk Card Troubleshooting Summary Step Possible Malfunction Source 1. Faulty connections between the external trunk equipment and the cross-connect field. See Note 3. 2. Faulty connections between the cross-connect field and the system. 3. Faulty CDE programming; likely forms: l COS Define l Trunk Circuit Descriptors l Non-Dial In Trunks l Dial In Trunks * Trunk Groups l Device Interconnection Table l System Configuration. 4. Faulty external trunk equipment (see Note 4). 5. Incorrect jumper settings (LWGS Trunk card only) - see Figure 3-l. 6. Incorrect switch settings (E&M Trunk Module). 7. Faulty Universal Card (E&M Trunk Module only). 8. Faulty LS/GS or DID Trunk Card (see Note 3). 9. Faulty backplane cable connections. 10. Problem with DTMF Receivers (not enough for peak traffic load, see Note 2). Note: 1. Useful maintenance commands: SHOW STATUS, TEST, SHOW ALARMS - see the f!S-232 Maintenance Terminal Practice. 2* Refer to the Engineering hformation Practice, for details on CO Busy Hour and receiver provisioning. 3-4 Issue 1 Revision 0 March 1997