Home > Mitel > Communications System > Mitel Sx 200 Ml Pabx Lightware 16 Instructions Guide

Mitel Sx 200 Ml Pabx Lightware 16 Instructions Guide

    Download as PDF Print this page Share this page

    Have a look at the manual Mitel Sx 200 Ml Pabx Lightware 16 Instructions Guide online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 55 Mitel manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    Page
    of 626
    							2 Troubleshooting - 
    General 
    Emergency Procedures 
    2.1 When any switching machine is totally inoperative, the prime requirement is the 
    restoration of service to the system or the part that has been affected. Table 2-i 
    shows how to achieve this in the shortest possible time. Once service has been 
    restored, the other procedures (see Table of Contents) may be used to determine the 
    cause of the failure. 
    Step 
    1. 
    2. 
    3. 
    4. 
    5 
    6. 
    7. Table 2-l Emergency Troubleshooting Procedures 
    Action 
    At the 
    control cabinet, check if the green 
    ACTIVEindicator on the Main Control Card II 
    front panel is flashing. 
    Press the RESET pushbutton on the front 
    panel of the Main Control Card Il. 
    Check if the POWER O/Vindicator on the Bay 
    Power Supply is on. 
    Turn the Cabinet power supply off, reseat the 
    Main Control Card II and Bay Control Card, 
    and turn the power on again. Any indication 
    on numeric display? 
    Check power rails and continuity on the 
    backplane. 
    Power down the cabinet, remove the Main 
    Control Card II, and check if System ID 
    module is securely installed. 
    Ensure Bay PowerSupply isfirmlyseated into 
    the backplane. ispowercordfirmlyconnected 
    to the rear of the BPS? 
    Check for loose power cable connections in 
    the Cabinet. Description / Follow-Up 
    Yes: l Go to step 7. 
    No: 
    l Go to step 2. 
    l If the Main Control Card II numeric 
    displays are blank, go to step 3; otherwise 
    go to step 9. 
    Yes: 
    l Go to step 4. 
    No: 
    l Go to step 7. 
    Yes: . Go to step 9. 
    No: 0 Go to step 5. 
    l Verify that the required voltage signals 
    actually are present at the Main Control 
    Card II connector. 
    l Once verified, go to step 6. 
    Yes: 
    l Possible System ID problem - 
    replace MainControl Card Il. 
    No: 
    l Install System ID module properly 
    and go back to step 2. 
    No: 
    l Plug in securely; go back to step 2. 
    Yes: 
    l If no wiring problems are found, 
    refer to the Bay Power Supply 
    procedures. 
    Page 1 of 2 
    March 1997 Issue 1 Revision 0 2-l  
    						
    							Troubleshooting 
    Table 2-l Emergency Troubleshooting Procedures (continued) 
    Step Action Description / Follow-Up 
    8. Attempt a station-to-station call - is Call Yes: 
    l Stop. Continue to monitor system. 
    Processing functioning? No: 
    l Press the RESET push- 
    button on the Main Control Card II 
    front panel, and go to step 9. 
    9. Check for error codes on the Main Control 
    l Refer to Table 2-2. 
    Card II numeric display. 
    Page 2 of 2 
    Main Control Card II Power-Up Error Codes 
    Table 2-2 shows the Main Control Card II numeric display error codes which may 
    appear during start-up. Also shown are the most likely causes of the error condition. 
    Table 2-2 Main Control Card II Error Code Summary 
    Error Code 
    (blank) 
    0 
    E. 
    8 
    Likely Cause(s) 
    l Faulty power system - refer to that procedure. 
    l Faulty Main Control Card Il. 
    l Faulty Main Control Card Il. 
    l Faulty System ID module. 
    l Nothing - indicates successful software 
    download. This display may be immediately 
    changed to display post-boot-up codes (see 
    note 1). 
    Note: 1. A normal running system may show other codes (card diagnostics or errors). However, during 
    start-up, only the codes in this table are possible. Any other code shown during start-up 
    indicates a faulty Main Control Card Il. 
    2. Codes possible AFTER start-up include card diagnostics codes (last card location tested - 
    top number indicates bay number, bottom number indicates card slot number). Maintenance 
    logs give results of test, i.e., pass or fail with cause). 
    Troubleshooting Methodology 
    General 
    2.2 Troubleshooting a malfunction in any complex electronic system is accomplished in a 
    series of logical steps. This Section assumes the following basic steps in the 
    troubleshooting of a malfunction: 
    2-2 
    Issue 1 Revision 0 March 1997  
    						
    							Troubleshooting - General 
    l GATHERING of information 
    l CLARIFICATION of the problem 
    l CONFIRMATION of the problem 
    l ISOLATION of the problem 
    l CORRECTION and DOCUMENTATION 
    When investigating a problem, the troubleshooter should continually verify each step 
    in the isolation process so as to ensure that the system and the symptoms of the 
    malfunction are clearly understood. This will ensure that the malfunction is accurately 
    categorized so that appropriate diagnostics, where applicable, may be invoked. 
    Information Gathering and Problem Clarification 
    Chart 2-l provides a list of the information which may be necessary in order to 
    adequately categorize a fault. All relevant information should be gathered and entered 
    into a site fault record. If the fault has resulted in total or partial shutdown of the system, 
    much of this data will be unobtainable or irrelevant. In such cases, reference should 
    be made to the EMERGENCY TROUBLESHOOTING PROCEDURES. 
    Chart 2-l Information Gathering and Clarification 
    Step Action Description Follow-up 
    1. Talk to station users. Obtain the following information: 
    - frequency of occurrence 
    - intermittent or continuous nature 
    - time period during which the fault occurs 
    - circumstances common to all occurrences. 
    2. Check Maintenance 
    Alarm indications. - Check maintenance log for fault/ alarm reports (see Note 1). 
    - Check system LED and numeric display indicators for error 
    codes. 
    3. Collectdataconcerning 
    environmental 
    conditions. - Check if the system is located close to a heat source or a 
    source of power radiation (see Note 2). 
    - Note the temperature and humidity conditions and 
    compare with specified operating parameters. 
    - Check the susceptibility of the area with respect to static 
    electricity generation. 
    - The following can seriously affect the performance of 
    the system: 
    - power fluctuations 
    - lightning storms 
    - excessively high humidity 
    - excessively high temperature 
    - dust 
    - rf interference. 
    4. Verify system 
    programming. - Check the existing programming to ensure that the correct 
    options and features have been enabled (see Note 3). 
    - Verify the Class Of Service assignments, trunk descriptors, 
    and feature access codes. 
    Page 1 of 2 
    March 1997 Issue 1 Revision 0 2-3  
    						
    							Troubleshooting 
    Chart 2-l Information Gathering and Clarification (continued) 
    1 
    Step 
    5. 
    6. 
    7. 
    Action Description Follow-up 
    Make special checks 
    for new installations, 
    additions or 
    modifications. - Check that the procedures specified in the /n.sWa~~o~~ 
    /nformafion Practice have been properly implemented. 
    - Verify that any changes have been made in accordance 
    with the appropriate practices, and to the prescribed 
    standards. 
    Make random 
    miscellaneous checks. 
    Check for minor alarm 
    indications - these 
    assist in isolating and 
    categorizing faults. - Check for possible conflicts if features have been added or 
    deleted, or if other programming changes have been made. 
    - Ensure all circuit cards are properly seated. 
    - Verify that the system fans are running. 
    - Check the main distribution field for loose or damaged 
    wiring, improperly seated connectors, orothersigns of trouble. 
    - Record relevant data and note the affected area of the system. 
    Page 2 of 2 
    Note: 1. Refer to the W-232 Maintenance Terminal Practice, for details on procedures. 
    2. Refer to the 
    Engineering hformation Practice, for the specified operating parameters. 
    3. Refer to the Features Description Practice, and the Customer Data Entty Practice. 
    Problem Confirmation 
    Many faults, particularly intermittent faults, “disappear” before the troubleshooter is 
    able to make a positive trace. Wherever possible, attempts should be made to force 
    the problem to recur, such that the effects may be observed and hence the cause 
    determined. The information gathered up to this point may be used to set up conditions 
    relating as closely as possible to those under which the fault originally manifested itself. 
    Problem Isolation 
    The aids listed in Table 2-3 are useful in isolating fault conditions. 
    Table 2-3 Troubleshooting Aids 
    Troubleshooting Aid 
    Maintenance Log 
    Maintenance Terminal Description and Use 
    - Provides a record of maintenance activities and causes of alarms 
    (the primary source of troubleshooting information). 
    - Primary access to the maintenance log. 
    - Provides ability to query alarm status, along with a variety of status 
    reports. 
    - Allows testing of individual functional units, using directed 
    diagnostics. 
    Page 1 of 2 
    2-4 Issue 1 Revision 0 March 1997  
    						
    							Troubleshooting - General 
    Table 2-3 Troubleshooting Aids (continued) 
    Troubleshooting Aid Description and Use 
    Circuit Card Numeric 
    Displays - Allow system power-up testing and operation to be monitored. 
    Status LEDs (on peripher- - Used to determine if circuit is in use, idle, or not functioning. 
    al cards) 
    Page 2 of 2 
    Correction and Documentation 
    Once a problem is isolated, the table of contents of this document should be consulted, 
    and the appropriate procedure referenced. Many procedures contain instructions 
    requiring control circuit cards to be reset, removed, powered down or replaced; in these 
    circumstances it should be noted that these actions will cause a partial or total loss of 
    service. If possible, these procedures should be performed during periods of little or 
    no traffic. 
    All repairs or adjustments to the system should be recorded into a log book which is 
    kept permanently at the site. Faulty equipment should be returned in the same 
    packaging as the replacement part (FRU). For further information on FRU items, refer 
    to the Fie/d-Rep/aceab/e Units Practice. 
    March 1997 Issue 1 Revision 0 2-5  
    						
    							Troubleshooting 
    2-6 Issue 1 
    Revision 0 March 1997  
    						
    							3 Peripheral Equipment 
    Troubleshooting 
    Procedures 
    Peripheral Interface Circuit Cards 
    ONS / OPS / Station Line Cards 
    3.1 This section covers the ONS Line Card (PN 9109-010) and the OPS Line Card 
    (PN 9109-040). Table 3-l outlines the most likely items to cause malfunction. For 
    ONS Line Card problems involving Voice Mail, see Voice Mail - ONS Port. 
    Table 3-l ONS Line Card Troubleshooting Summary 
    Step Possible Malfunction Source 
    1. Faulty connections between the telephone and the cross-connect field. 
    2. Faulty connections between the cross-connect field and the system. 
    3. Faulty CDE programming; likely forms: 
    l COS Define 
    l Stations / SUPERSETTM Telephones 
    l Device Interconnection Table 
    l System Configuration 
    4. Faulty telephone set. 
    5. Faulty line card. 
    6. Faulty backplane cable connections. 
    7. Problem with DSP receivers or DTMF Receiver modules (not enough for peak traffic load). 
    Note: Useful maintenance commands: SHOW STATUS, TEST, SHOW ALARMS - see the US-232 
    Maintenance Terminal Practice. 
    March 1997 Issue I Revision 0 3-l  
    						
    							Troubleshooting 
    COV Line Cards 
    This section covers the COV Line Card (PN 9109-020). Table 3-2 outlines the most 
    likely items to cause malfunction. For COV Line Card problems involving Voice Mail, 
    see COV Port - Voice Mail in Chapter 5. 
    Table 3-2 COV Line Card Troubleshooting Summary 
    Step Possible Malfunction Source 
    Faulty connections between the SWH?SE~telephone and the cross-connect field. 
    1. 
    2. 
    3. Faulty connections between the cross-connect field and the SX-200 ML system. 
    Faulty CDE programming; likely forms: 
    l COS Define 
    4. 
    5. 
    6. 
    7. 
    l Stations / SUPE/%flTelephones 
    l Device Interconnection Table 
    l System Configuration. 
    Faulty SUPH?SE~ telephone set. 
    Faulty line card. 
    Faulty backplane cable connections. 
    Problem with DTMF Receivers (not enough for peak traffic load). 
    Note: Useful maintenance commands: SHOW STATUS, TEST, SHOW ALARMS, SHOW ERRORS 
    SS3-SS4 - see the RS-232 Maintenance Commands Practice. 
    Digital Line Card 
    General 
    Intermittent problems can be caused by improper bridge taps, or incorrect loop lengths. 
    The following table lists the maximum loop lengths in meters with 24 or 26 AWG twisted 
    pair wiring. 
    Table 3-3 Digital Line Card Loop Lengths 
    Peripheral Maximum Loop Length 
    Device Without Bridge Tap With Bridge Tap * 
    SUPERSET 401 +TM 1 OOOm not permitted 
    SUPERSET 41 OTM 1 OOOm not permitted 
    SUPERSET 420TM 1 OOOm 1 OOOm 
    SUPERSET 430TM 1 OOOm 1 OOOm 
    Dataset 1103 2000m 1 OOOm 
    Page 1 of 2 
    3-2 Issue 1 Revision 0 March 1997  
    						
    							Peripheral Equipment Troubleshooting Procedures 
    Table 3-3 Digital Line Card Loop Lengths (continued) 
    Peripheral Maximum Loop Length 
    Device Without Bridge Tap 
    With Bridge Tap * 
    Dataset 2103 2000m 1 OOOm 
    MILINKTM Data Module 2000m 1 OOOm 
    SUPERCONSOLE 1 OOOTM console 1 OOOm 1 OOOm 
    SUPERSET 7000TM console 1 OOOm not permitted 
    Page 2 of 2 
    Note: 
    Peripheral devices can not use bridge taps if they are connected to Digital Line Cards with PN 
    9109-012-001 -NA or PN 9109-012-001 -NA. Digital Line Cards with PN 9109-012-000-SA may 
    have bridge taps. 
    SHOW ERRORS DATASET Command 
    The SHOW ERRORS DATASET command can be a useful tool in the troubleshooting 
    of both the Digital Line Card and the Dataset. The following table lists the possible 
    causes of the error types. 
    Error 
    Type 
    CFICERR 
    RESETS 
    LINK FAIL Table 3-4 SHOW ERRORS Command 
    L 
    Call Possible Cause 
    State Dataset Cabling DX Chip Line Card DTE/DCE 
    any w ws 
    w yes no 
    w yes w yes 9s yes 
    Call setup/ Talk 
    yes vs yes w no 
    Additional Troubleshooting 
    Digital Line Cards are used for many applications. For additional troubleshooting 
    information, refer to procedures for the specific application; i.e.: 
    l SUPERSET 401+ Telephones 
    l SUPERSET 4 IO Telephones 
    March 1997 Issue 1 Revision 0 3-3  
    						
    							Troubleshooting 
    . SWERSE~ 4ZU Telephones 
    l SW ERSET 430 Telephones 
    l SUPERSET 7000 console 
    l DATASET 1103 
    l DATASET 2103 
    l A&WWData Module 
    l Programmable Key Module 
    Trunk Cards - General 
    The procedures detailed below cover the isolation and correction of faults with the 
    various trunk cards. Supplementary procedures are provided for specific trunk types 
    where required. Table 3-5 summarizes troubleshooting for trunk cards. 
    Table 3-5 Trunk Card Troubleshooting Summary 
    Step Possible Malfunction Source 
    1. Faulty connections between the external trunk equipment and the cross-connect field. 
    See Note 3. 
    2. Faulty connections between the cross-connect field and the system. 
    3. Faulty CDE programming; likely forms: 
    l COS Define 
    l Trunk Circuit Descriptors 
    l Non-Dial In Trunks 
    l Dial In Trunks 
    * Trunk Groups 
    l Device Interconnection Table 
    l System Configuration. 
    4. 
    Faulty external trunk equipment (see Note 4). 
    5. 
    Incorrect jumper settings (LWGS Trunk card only) - see Figure 3-l. 
    6. Incorrect switch settings (E&M Trunk Module). 
    7. Faulty Universal Card (E&M Trunk Module only). 
    8. 
    Faulty LS/GS or DID Trunk Card (see Note 3). 
    9. Faulty backplane cable connections. 
    10. 
    Problem with DTMF Receivers (not enough for peak traffic load, see Note 2). 
    Note: 1. Useful maintenance commands: SHOW STATUS, TEST, SHOW ALARMS - see the f!S-232 
    Maintenance Terminal Practice. 
    2* Refer to the Engineering hformation Practice, for details on CO Busy Hour and receiver 
    provisioning. 
    3-4 Issue 1 Revision 0 March 1997  
    						
    All Mitel manuals Comments (0)

    Related Manuals for Mitel Sx 200 Ml Pabx Lightware 16 Instructions Guide