    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Troubleshooting
      Troubleshooting the Fan Assembly
    Troubleshooting the Fan Assembly
    To isolate a fan assembly problem, follow these steps:
    Step 1Verify that the FAN LED on the fan assembly is green.
    If the FAN LED is not green, see the “Solving Problems at the System Component Level” section on 
    page A-2 to determine whether or not the power subsystem is functioning properly.
    Step 2Check to determine if the FAN LED is red. If the FAN LED is red, the fan assembly is not seated in the 
    backplane or has malfunctioned. 
    Do the following:
    To ensure that the fan assembly is seated properly, loosen the captive installation screws, remove the 
    fan assembly, and reinstall it.
    Tighten all captive installation screws, and then restart the system.
    If the FAN LED is still red, the system detects an individual fan failure. Contact a customer service 
    representative for instructions.
    Troubleshooting Modules
    To isolate a supervisor engine or switching module problem, follow these steps:
    Step 1Verify that all status LEDs are on.
    Step 2If any status LEDs on the supervisor engine or any switching modules are red or off, the module might 
    have shifted out of its slot. Reseat the module until both ejector levers are at right angles to the rear of 
    the chassis. Tighten the captive installation screws at the left and right of the module front panel, and 
    restart the system.
    STATUS LED Indications
    The STATUS LEDs can indicate two alarm types: major and minor. Major alarms indicate a critical 
    problem that could lead to the system being shut down. Minor alarms are for informational purposes 
    only, giving you notice of a problem that could turn critical if corrective action is not taken. 
    When the system has an alarm (major or minor) that indicates an overtemperature condition, the alarm 
    is not canceled and no action is taken (such as a module reset or a shutdown) for 5 minutes. If the 
    temperature falls 5°C (41°F) below the alarm threshold during this period, the alarm is canceled. 
    Ta b l e A - 1 lists the environmental indicators for the supervisor engine and switching modules.
    NoteRefer to the Catalyst 6500 Series Switch Module Installation Guide for additional information on LEDs, 
    including the supervisor engine SYSTEM LED. 
    						
    							A-6
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Troubleshooting
      Troubleshooting Modules
    Refer to the Catalyst 6500 Series Switch Software Configuration Guide, the Catalyst 6500 Series Switch 
    Cisco IOS Software Configuration Guide, the Catalyst 6500 Series Switch Command Reference, or the 
    Catalyst 6500 Series Switch Cisco IOS Command Reference publications to configure or enable the 
    interfaces. After the system reinitializes the interfaces, the status LED on the module should be green.
    If you still experience trouble with the startup, see the “Contacting Customer Service” section on 
    page A-7.
    Table A-1 Environmental Monitoring for Supervisor Engine and Switching Modules
    ComponentAlarm 
    Type LED Indication Action
    Supervisor engine temperature sensor 
    exceeds major threshold
    1 
    1. Temperature sensors monitor key supervisor engine components including daughter cards.
    Major STATUS2 LED red3 
    2. A STATUS LED is located on the supervisor engine front panel and all module front panels.
    3. The STATUS LED is red on the failed supervisor engine. If there is no redundant supervisor, the SYSTEM LED is red also.
    Syslog message and SNMP trap generated.
    If redundancy, system switches to redundant 
    supervisor engine and the active supervisor engine 
    shuts down.
    If there is no redundancy and the overtemperature 
    condition is not corrected, the system shuts down 
    after 5 minutes.
    Supervisor engine temperature sensor 
    exceeds minor threshold Minor STATUS LED 
    orange Syslog message and SNMP trap generated.
    Monitor the condition.
    Redundant supervisor engine 
    temperature sensor exceeds major or 
    minor threshold Major
    MinorSTATUS LED red
    STATUS LED 
    orangeSyslog message and SNMP trap generated.
    If major alarm and the overtemperature condition is 
    not corrected, the system shuts down after 5 minutes.
    If minor alarm, monitor the condition.
    Switching module temperature sensor 
    exceeds major threshold Major  STATUS LED red Syslog message and SNMP trap generated.
    Power down the module.
    Switching module temperature sensor 
    exceeds minor threshold Minor STATUS LED 
    orangeSyslog message and SNMP trap generated.
    Monitor the condition. 
    						
    							A-7
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Troubleshooting
      Contacting Customer Service
    Contacting Customer Service
    If you are unable to solve a startup problem after using the troubleshooting suggestions in this chapter, 
    contact a customer service representative for assistance and additional instructions. Before you call, have 
    the following information ready to help your service provider assist you as quickly as possible:
    Date you received the switch
    Chassis serial number (located on a label on the right of the rear panel of the chassis)
    Type of software and release number
    Maintenance agreement or warranty information
    Brief description of the problem
    Brief explanation of the steps you have already taken to isolate and resolve the problem 
    						
    							A-8
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Troubleshooting
      Contacting Customer Service 
    						