1-23 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Chapter 1 Removal and Replacement Procedures Removing and Installing the DC-Input Power Supplies Figure 1-15 Handling a DC-Input Power Supply 48134 FA N S TAT U S 1 2 3 4 5 6 7 8 9 8 PORT GIGABIT ETHERNET WS-X64081LINKSTATUS2 3 4 5 6 7 8LINKL IN KLINKLIN KLIN KLINKLINK 8 PORT GIGABIT ETHERNET WS-X64081LINKSTATUS2 3 4 5 6 7 8LINKLINKLINKL IN KLIN KLINKLINK 8 PORT GIGABIT ETHERNET WS-X64081LINKSTATUS2 3 4 5 6 7 8LINKLINKLINKLIN KLIN KLINKLINK 24 P O R T 1 0 0 F X W S - X 6 2 2 4S T A T U S 2 4 P O R T 10 0F X W S -X 6 2 2 4S T A T U S 2 4 P O R T 1 0 0 F X W S -X 6 2 2 4S T A T U S 24 P O R T 1 0 0 F X W S - X 6 2 2 4S T A T U S 1LINK2LINK3LINK4LINK5LINK6LINK7LINK8LINK9LINK10LINK11LINK12LINK13LINK14LINK15LINK16LINK17LINK18LINK19LINK20LINK21LINK22LINK23LINK24LINK1LINK2LINK3LINK4LINK5LINK6LINK7LINK8LINK9LINK1 0LINK1 1LINK1 2LINK1 3LINK1 4LINK1 5LINK1 6LINK1 7LINK1 8LINK1 9LINK2 0LINK2 1LINK2 2LINK2 3LINK2 4LINK1LINK2LINK3LINK4LINK5LINK6LINK7LINK8LINK9LINK10LINK11LINK12LINK13LINK14LINK15LINK16LINK17LINK18LINK19LINK20LINK21LINK22LINK23LINK24LINK1LINK2LINK3LINK4LINK5LINK6LINK7LINK8LINK9LINK10LINK11LINK12LINK13LINK14LINK15LINK16LINK17LINK18LINK19LINK20LINK21LINK22LINK23LINK24LINK SUPERVISOR2 WS-X6K-SUP2-2GES T A T U SS Y S T E MC O N S O L EP W R M G M TR E S E TCONSOLECONSOLE PORT MODEPCMCIAEJECTPORT 1PORT 2Switch Load 100% 1% LINK LINK SUPERVISOR2 WS-X6K-SUP2-2GES T A T U SS Y S T E MC O N S O L EP W R M G M TR E S E TCONSOLECONSOLE PORT MODEPCMCIA EJECTPORT 1PORT 2Switch Load 100% 1% LINK LINK INPUT OKFA N OKOUTPUT FAIL I 0
1-24 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Chapter 1 Removal and Replacement Procedures Removing and Installing the DC-Input Power Supplies Installing a 1300 W or 2500 W DC-Input Power Supply WarningBefore performing any of the following procedures, ensure that power is removed from the DC circuits. To ensure that all power is removed, locate the circuit breakers or fuses on the DC power lines that service the DC circuits. Turn OFF the DC power line circuit breakers and remove the DC power line fuses. Statement 322 WarningWhen installing or replacing the unit, the ground connection must always be made first and disconnected last. Statement 1046 To install a DC-input power supply, follow these steps: Step 1Ensure that the system (earth) ground connection has been made. For ground connection installation instructions, see the “Establishing the System Ground” section on page 1-52. Step 2Verify that power is off to the DC circuit on the power supply that you are installing. As an added precaution, place the appropriate safety flag and lockout devices at the source power circuit breaker, or place a piece of adhesive tape over the circuit breaker handle to prevent accidental power restoration while you are working on the circuit. Step 3Verify that the power switch is in the off (0) position on the power supply that you are installing. See Figure 1-11 for the 1300 W DC power supply or Figure 1-12 for the 2500 W DC power supply. CautionUse both hands to install and remove power supplies. Each Catalyst 6500 series DC-input power supply weighs between 22 pounds (10 kg) and 28 pounds (12.7 kg). Step 4Grasp the power supply handle with one hand, and place your other hand underneath the power supply. Slide the power supply into the power supply bay. Make sure that the power supply is fully seated in the bay. (See Figure 1-15.) Step 5Tighten the power supply captive installation screw. (See Figure 1-11 for the 1300 W DC power supply or Figure 1-12 for the 2500 W DC power supply.) Step 6Remove the two screws securing the terminal block cover, and slide the cover off of the terminal block. See Figure 1-11 for the 1300 W DC power supply or Figure 1-12 for the 2500 W DC power supply.
1-25 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Chapter 1 Removal and Replacement Procedures Removing and Installing the DC-Input Power Supplies Step 7Attach the appropriate lugs to the DC-input wires. The maximum width of a lug is 0.300 inch (7.6 mm). NoteThe wire should be sized according to local and national installation requirements and electrical codes. Use only copper wire. For North American installations of 2500 WDC-input power supplies, use fine-stranded copper conductors rated for 90°C. Step 8Attach the source DC cables to the terminal block (see Figure 1-16 for the 1300 W DC power supply or Figure 1-17 for the 2500 W DC power supply) in this order: 1.Source ground cable to the power supply terminal block ground post 2.Source DC negative (–) cable to the power supply terminal block negative (–) post 3.Source DC positive (+) cable to the power supply terminal block positive (+) post NoteThe terminals on the 1300 W DC power supply DC power cable terminal block are labeled (from top to bottom) +, –, ground. The terminals on the 2500 W DC power supply DC power cable terminal block are labeled (from top to bottom) –, +, ground. Step 9After ensuring that all wire connections are secure, reinstall the terminal block cover. CautionTo prevent a short circuit or shock hazard after wiring the DC-input power supply, you must reinstall the terminal block cover. CautionIn a system with dual power supplies, connect each power supply to a separate power source. In case of a power source failure to one supply, the second power source should still be available. Step 10Remove any safety flag and lockout devices or any tape from the circuit breaker switch handle, and restore power by moving the circuit breaker switch handle to the on (|) position. Step 11Turn the power switch to the on (|) position on the power supply. Turning on the power switch also engages a pawl that locks the power supply in the chassis. Step 12Verify the power supply operation by ensuring that the power supply front panel LEDs are in these states: INPUT OK LED is green FAN OK LED is green OUTPUT FAIL LED is not lit If the LEDs indicate a power problem, see the “Identifying Startup Problems” section on page A-3.
1-26 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Chapter 1 Removal and Replacement Procedures Removing and Installing the DC-Input Power Supplies Figure 1-16 DC-Input Power Supply Connectors (WS-CDC-1300W) Figure 1-17 DC-Input Power Supply Connectors (WS-CDC-2500W) INPUT OKFA N OKOUTPUT FAIL I 0 18736 Power leads attached to terminal block (+) Positive ( - ) Negative ( ) Ground Captive installation screw DC-input power supply with the terminal block cover removed Power switch DC-input cable INPUT OKFA N OKOUTPUT FA I L I 0 85907 Power leads attached to terminal block ( - ) Negative (+) Positive ( ) Ground Captive installation screw Power switch DC-input cable
1-27 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Chapter 1 Removal and Replacement Procedures Removing and Installing the DC-Input Power Supplies Removing and Installing the 2700 W DC-Input Power Supply This section covers the power supply removal and installation procedures for the 2700 W DC-input power supply on the Catalyst 6504-E chassis and is divided into the following topics: Required Tools, page 1-28 Removing a 2700 W DC-Input Power Supply, page 1-29 Installing a 2700 W DC-Input Power Supply, page 1-32 The 2700 W DC-input power supply can operate at either 1350 W or at 2700 W. If you want to operate the power supply at 1350 W, you only need to connect one pair of source DC cables to either the VE-1 or the VE-2 pair of posts on the power supply terminal block. If you want to operate the power supply at 2700 W, you need to connect two pairs of source DC cables to the VE-1 and the VE-2 pairs of posts on the power supply terminal block. NoteFor proper 2700 W DC-input redundant power configurations, all of the source DC for one 2700 W DC-input power supply must come from the same battery system (A feed); all of the source DC for the other 2700 W DC-input power supply must come from another battery system (B feed). NoteFor multiple DC-input power supplies, each DC input must be protected by a dedicated circuit breaker or a fuse. The circuit breaker or fuse must be sized according to the power supply input rating and the local or national electrical code requirements. Figure 1-18 shows a 2700 W DC-input power supply (p/n PWR-2700-DC/4) cabled for 2700 W operation with the installation components identified. NoteThis illustration shows the source DC cables and the ground cable routed into the power supply from the right side. Two pairs of source DC cables are shown indicating that the power supply is operating at 2700 W. The source DC cables and the ground cable can also be routed out of the left-side of the power supply, if necessary. Use this illustration as a reference for identifying components when removing or installing the power supply.
1-28 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Chapter 1 Removal and Replacement Procedures Removing and Installing the DC-Input Power Supplies Figure 1-18 2700 W DC-Input Power Supply Features Required Tools The following tools are required for the power supply removal and installation procedures: Number 2 Phillips-head screwdriver 1/4-inch open-ended wrench or 1/4-inch nutdriver Wire cutters to cut the cable tie wraps Additional tools might be necessary to install the lugs on the source DC and the ground cables. Additionally, the lugs for the source DC cables and the ground cable are not provided; you must obtain them on your own.1Captive installation screw (4x)7Fixed cable guide, top half 2Source DC terminal block8Detached cable guide, bottom half 3Status LEDs9Tie wrap (for source DC cables) 4Terminal block cover10Fixed cable guide, bottom half 5Detached cable guide, top half11Tie wrap (for ground cable) 6Ground terminal block 132219 PWR-2700-DC/4 -VE-1 -VE-1 -VE-2 -VE-2IN PU T 1 O K 48V -60 V =40 AIN P U T2 O K 48V -60V =40AF A N O KO U T PU T FA IL ALL FASTENERS MUST BE F ULLY ENG AG ED PRIOR TO O PERATING THE PO W ER SUPPL Y 32 6 4 10 1 8 57 119
1-29 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Chapter 1 Removal and Replacement Procedures Removing and Installing the DC-Input Power Supplies Removing a 2700 W DC-Input Power Supply WarningBefore performing any of the following procedures, ensure that power is removed from the DC circuits. To ensure that all power is removed, locate the circuit breakers or fuses on the DC power lines that service the DC circuits. Turn OFF the DC power line circuit breakers and remove the DC power line fuses. Statement 322 WarningVoltage is present on the backplane when the system is operating. To reduce risk of an electric shock, keep hands and fingers out of the power supply bays and backplane areas. Statement 166 To remove a DC-input power supply, follow these steps: Step 1Verify that source DC power is off to the DC circuit that feeds the power supply that you are removing. As an added precaution, place the appropriate safety flag and lockout devices at the source DC power circuit breaker, or place a piece of adhesive tape over the circuit breaker handle to prevent accidental power restoration while you are working on the circuit. Step 2Remove the four screws that secure the terminal block cover (clear plastic) and slide the cover off of the terminal block. Set the cover and the screws aside. (See Figure 1-19.) Step 3Remove the two screws securing the fixed cable guide top half and set the cable guide piece and the screws aside. (See Figure 1-19.) Step 4Remove the two screws securing the detached cable guide top half to the bottom half. Remove both cable guide pieces and the screws and set them aside. NoteIn addition to the two cable guides, there might be a tie wrap securing the source DC cables and two tie wraps securing the ground cable to the fixed cable guide. You will need to cut all of these tie wraps in order to free the source DC cables and the ground cable for removal.
1-30 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Chapter 1 Removal and Replacement Procedures Removing and Installing the DC-Input Power Supplies Figure 1-19 Removing the Terminal Block Cover and the Cable Guides Step 5 Disconnect the DC-input cables from the terminal block (see Figure 1-20) in this order: Positive (+) source DC cable from the +VE-1 terminal block post Negative (-) source DC cable from the –VE-1 terminal block post NoteIf you have a second pair of source DC cables attached to the VE-2 terminal block posts, you need to remove the second positive (+) and negative (–) source DC cables, in that order, before you remove the ground cable. Ground cable from the ground terminal posts Save the 1/4-20 nut and the split-ring washer from each terminal block post and set them aside. WarningWhen installing the unit, always make the ground connection first and disconnect it last. Statement 42 1Terminal block cover4Detached cable guide, bottom half 2Detached cable guide, top half5Tie wrap (for source DC cables) 3Fixed cable guide, top half 270852 PWR-2700-DC/4 -VE-1 -VE-1 -VE-2 -VE-2IN PU T 1 O K 48V -60V = 40AIN P U T2 O K 48V-60V =4 0AFA N O KOU T PU T FA IL ALL FA STENERS MUST BE F ULLY ENGA GED PRIOR TO OPERATING TH E POW ER SUPPLY1 4 23 5
1-31 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Chapter 1 Removal and Replacement Procedures Removing and Installing the DC-Input Power Supplies Figure 1-20 Disconnecting the Source DC Cables and Ground Cable Step 6 Loosen the four captive installation screws on the power supply. CautionUse both hands to install and remove power supplies. Each PWR-2700-DC/4 DC-input power supply weighs 19.8 pounds (9.0 kg). Step 7Grasp both power supply handles, as shown in Figure 1-21, and slide the power supply completely out of the chassis and set it aside. Figure 1-21 Handling a DC-Input Power Supply Step 8 If the power supply bay is to remain empty, install a blank power supply filler plate (Cisco part number 700-03104-01) over the opening, and secure it with the captive installation screws. 270853 PW R-2700-DC/4 -V E-1 -V E-1 -V E-2 -V E-2INPU T 1 O K 48 V-60V = 4 0AI NPU T 2 OK 4 8V-6 0V = 4 0AF A N O KO U TP U T F AIL ALL F ASTE NERS MUST BE FUL LY ENGAGED PRIOR TO OPER AT I NG T HE POWER SUP PLY 126567 PWR-2700-DC/4 ALL FASTENERS MUST BE FULLY ENGAGED PRIOR TO OPERATING THE POWER SUPPLY INPUT1 OK 48V-60V =40AINPUT2 OK 48V-60V =40AFA N OKOUTPUT FA I L+VE-1 -VE-1 +VE-2 -VE-2 ALL FASTENERS MUST BE FULLY ENGAGED PRIOR TO OPERATING THE POWER SUPPLY INPUT1 OK 48V-60V =40AINPUT2 OK 48V-60V =40AFA N OKOUTPUT FA I L PWR-2700-DC/4 +VE-1 -VE-1 +VE-2 -VE-2+VE-1 -VE-1 +VE-2 -VE-2+VE-1 -VE-1 +VE-2 -VE-2 Power Supply 2 (redundant) Power Supply 1
1-32 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Chapter 1 Removal and Replacement Procedures Removing and Installing the DC-Input Power Supplies Installing a 2700 W DC-Input Power Supply This section provides the procedures for installing a 2700 W DC-input power supply in the Catalyst 6504-E switch chassis. The 2700 W DC-input power supply can operate at either 1350 W or at 2700 W. If you want to operate the power supply at 1350 W you only need to connect one pair of source DC cables to either the VE-1 or the VE-2 lugs on the power supply terminal block. If you want to operate the power supply at 2700 W, you need to connect two pairs of source DC cables to the VE-1 and the VE-2 lugs on the power supply terminal block. WarningBefore performing any of the following procedures, ensure that power is removed from the DC circuits. To ensure that all power is removed, locate the circuit breakers or fuses on the DC power lines that service the DC circuits. Turn OFF the DC power line circuit breakers and remove the DC power line fuses. Statement 322 NoteFor proper 2700 W DC-input redundant power configurations, all of the source DC for one 2700 W DC-input power supply must come from the same battery system (A feed); all of the source DC for the other 2700 W DC-input power supply must come from another battery system (B feed). NoteFor multiple DC-input power supplies, each DC input must be protected by a dedicated circuit breaker or a fuse. The circuit breaker or fuse must be sized according to the power supply input rating and the local or national electrical code requirements. To install the 2700 W DC-input power supply in the Catalyst 6504-E chassis and cable it to source DC, follow these steps: Step 1Ensure that the system (earth) ground connection has been made. For system ground connection installation instructions, see the “Establishing the System Ground” section on page 1-52. Step 2Remove the power supply from its shipping container and remove any packaging material. Step 3Locate the plastic bags that accompanied the power supply and set them aside. One bag contains one source DC cable guide, terminal block cover (plastic) with four screws, and two cable ties. The other plastic bag contains the 1/4-20 nuts and lock-washers for the terminal posts. You will use these items later in the procedure. Step 4Verify that source DC power is off to the DC circuit that feeds the power supply that you are installing. As an added precaution, place the appropriate safety flag and lockout devices at the source DC circuit breaker, or place a piece of adhesive tape over the circuit breaker handle to prevent accidental power restoration while you are working on the circuit. Step 5Grasp both power supply handles, as shown in Figure 1-22. Slide the power supply into the power supply bay. Make sure that the power supply is fully seated in the bay. Tighten the four captive installation screws. WarningPower supply captive installation screws must be tight to ensure protective grounding continuity. Statement 289