1-19 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Chapter 1 Installing the Switch Installing a Catalyst 6506 or Catalyst 6506-E Switch Chassis Rack-Mounting the Chassis NoteThe chassis are designed to be mounted in equipment racks that meet ANSI/EIA 310-D and ETS 300-119 standards. WarningTwo people are required to lift the chassis. To prevent injury, keep your back straight and lift with your legs, not your back. Statement 164 TipWe recommend that you have a third person to assist in this procedure. To install the switch chassis into the equipment rack, follow these steps: Step 1With a person standing at each side of the chassis, grasp the chassis handle with one hand, and use the other hand near the back of the chassis for balance. Slowly lift the chassis in unison. Avoid sudden twists or moves to prevent injury. Step 2Rest the back end of the chassis on the edges of the rack-mount shelf kit rails and carefully slide the chassis fully into the rack. Step 3Locate the rack post holes that align with the chassis L bracket holes. If the rack post holes are prethreaded, determine if the threads are 10-32 or 12-24. If the rack post holes are unthreaded, install a minimum of eight (four on each side) either 10-32 or 12-24 clip or cage nuts over the rack post holes to accept the installation screws. NoteClip nuts or cage nuts are not included as part of the accessory kit that comes with the chassis. You must obtain them yourself. Step 4If you want to install one or both of the optional cable guides, position the cable guides so that the cable guide mounting holes are aligned with rack-mount bracket holes and the rack post holes. (See Figure 1-8.) Step 5Install a minimum of eight 10-32 or 12-24 screws (four on each side) through the cable guide mounting holes, rack-mount L bracket holes, rack post holes, and into the clip nuts to secure the cable guides and the chassis to the rack post. Tighten the screws securely.
1-20 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Chapter 1 Installing the Switch Installing a Catalyst 6506 or Catalyst 6506-E Switch Chassis Figure 1-8 Installing a Catalyst 6506 or a Catalyst 6506-E Switch in a Rack What is Next After installing the chassis in its location, complete the installation process by following these procedures: Connecting the chassis to system ground. See “Establishing the System Ground” section on page 1-52. Installing and connecting the power supplies to source power. Go to Chapter 4 for information on how to install and cable power supplies. Connecting the network interface cables to the supervisor engine and modules. This may involve installing transceivers before you attach the network interface cables. See “Attaching the Interface Cables” section on page 1-61. Powering-up the chassis and verifying the installation. See “Verifying Switch Chassis Installation” section on page 1-84. 113975 INPUT OKFA N OKOUTPUT FA I L o 8 P O R T G IG A B IT E T H E R N E TWS-X64081LINKSTATUS2 3 4 5 6 7 8LINKLINKLINKLINKLINKLINKLINK8 P O R T G IG A B I T E T H E R N E TWS-X64081LINKSTATUS2 3 4 5 6 7 8LINKLINKLINKLINKLINKLINKLINK 24 PORT 100FXW S - X 6 2 2 4S T A T U S1LIN K2LINK3LIN K4LINK5LINK6LIN K7LIN K8LIN K9LIN K10LIN K11L INK12LIN K13LIN K14LIN K15LIN K16LIN K17LIN K18LIN K19LIN K20LIN K21LIN K22LIN K23LIN K24LIN K FAN STATUS Shelf bracket Rack post 12 x 24 or 10 x 32 (10x) Cable guide 1 2 3 4 5 6
1-21 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Chapter 1 Installing the Switch Installing a Catalyst 6509 or Catalyst 6509-E Switch Chassis Optional Installation Kits An optional rubber feet installation kit is included in the accessory kit for the Catalyst 6506-E switch chassis. This kit contains the parts necessary to install four non-slip rubber feet on the bottom of the chassis allowing the chassis to placed on a shelf or a table. To install the rubber feet, go to “Installing the Rubber Feet Kit” section on page 1-50. A center rack-mount kit for 23-inch, telco-style racks is available as an option for both the Catalyst 6506 and the Catalyst 6506-E switch chassis. The kit is not included in the accessory kits, but is available as a separately orderable item (p/n WS-C6597=). Installation instructions are included with the kit. Installing a Catalyst 6509 or Catalyst 6509-E Switch Chassis This section provides procedures for installing either a Catalyst 6509 or a Catalyst 6509-E switch chassis in a rack assembly and installing the optional cable guide assemblies. Installation Accessory Kits The Catalyst 6509 and Catalyst 6509-E switch chassis are designed to be installed in a standard 19-inch rack, either open or enclosed. Both chassis are normally shipped with the 19-inch rack-mount L brackets factory installed on the left-front and right-front of the chassis. Included with the accessory kit are 10-32 x 0.75-inch and 12-24 x 0.75-inch screws that are used to secure the chassis in the rack enclosure. NoteDepending on the manufacturer, the rack posts might be prethreaded to accept either 10-32 or 12-24 screws. If the rack posts are not prethreaded, you must install 10-32 or 12-24 clip nuts or cage nuts to secure the rack-mount screws. The clip nuts or the cage nuts are not included as part of the accessory kit and must be obtained on your own. Depending on the chassis model, the accessory kit might also contain the following chassis installation kits: Rack-mount shelf kit (Catalyst 6509 and Catalyst 6509-E). The rack-mount shelf kit is used to support the weight of the chassis while you secure the chassis L brackets to the rack enclosure. Rubber feet mount kit (Catalyst 6509-E accessory kit only). This kit can be installed when you want to install the Catalyst 6509-E chassis as a freestanding unit on a shelf or a table. Also included in the accessory kit: Cable guides— Two cable guides can be installed on the front of the chassis using the same sets of screws that secure the chassis rack-mount brackets to the rack posts. Power supply blank panel—The power supply blank panel must be installed on an unused power supply bay to maintain chassis airflow and EMI shielding. L Brackets on the Catalyst 6509 and Catalyst 6509-E Switches The Catalyst 6509 and Catalyst 6509-E switch chassis are shipped with two L brackets installed on the front sides of the chassis. The L brackets are secured to the chassis with ten M3 Phillips-head countersunk screws (five M3 screws on each side) as shown in Figure 1-9.
1-22 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Chapter 1 Installing the Switch Installing a Catalyst 6509 or Catalyst 6509-E Switch Chassis NoteThe L brackets can also be reversed and installed on the rear of the chassis as an alternative method of installation. NoteThe L brackets for the Catalyst 6509 and the Catalyst 6509-E switches are stamped with an L and an R to identify them as left and right. Figure 1-9 L Brackets on the Catalyst 6509 and the Catalyst 6509-E Switch Chassis Installing the 3 RU Rack-Mount Shelf Kit The 3 RU rack-mount shelf kit is included as part of the accessory kit for both the Catalyst 6509 and the Catalyst 6509-E switch chassis. You need to install this kit first before you install the chassis in the rack. The shelf kit supports the weight of the chassis while you install and secure the chassis in the rack. The procedure for installing the shelf kit is located at “Installing the 3 RU Rack-Mount Shelf Kit” section on page 1-47. 1M4 Phillips-head countersunk screws (10x)2Rack-mount L bracket (2x) 280387 FA N STATUS INPUT OKFA N OKOUTPUT FA I L o 1 2 3 4 5 6 7 8 9 8 PORT GIGABIT ETHERNET WS-X64081L IN KS T AT US2 3 4 5 6 7 8LI NKLIN KL IN KLIN KL IN KLI NKLI NK 8 PORT GIGABIT ETHERNET WS-X64081LINKSTATUS2 3 4 5 6 7 8LINKLIN KLIN KLIN KLINKLIN KLINK 2 4 P O R T 1 0 0 F X W S - X 6 2 2 4S TA TU S 24 P O R T 1 0 0 F X W S -X 6 2 2 4S T AT U S 2 4 P O R T 1 0 0F X W S -X 6 2 2 4S T AT U S 24 P O R T 1 0 0 F X W S -X 6 2 2 4S T AT U S 1LI NK2L IN K3L IN K4L INK5L IN K6LI NK7L IN K8LI NK9LI NK10L INK11L IN K12L INK13L IN K14L INK15L IN K16LI NK17L IN K18LINK19L IN K20LIN K21L IN K22LI NK23L IN K24L INK1LINK2LINK3LINK4LINK5LINK6LINK7LINK8LINK9LINK1 0LINK1 1LINK1 2LINK1 3LINK1 4LINK1 5LINK1 6LINK1 7LINK1 8LINK1 9LINK2 0LINK2 1LINK2 2LINK2 3LINK2 4LINK1LINK2LINK3LI N K4LIN K5LINK6LI NK7LINK8LI NK9LIN K10LINK1 1LINK12LINK13LI NK14LI NK15L INK16LI NK17LI N K18LI NK19LINK20LI NK21L IN K22LI N K23L INK24LINK1LINK2LINK3LINK4LINK5LINK6LINK7LINK8LINK9LINK10LINK11LINK12LINK13LINK14LINK15LINK16LINK17LINK18LINK19LINK20LINK21LINK22LINK23LINK24LINK 12
1-23 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Chapter 1 Installing the Switch Installing a Catalyst 6509 or Catalyst 6509-E Switch Chassis Rack-Mounting the Chassis NoteThe chassis are designed to be mounted in equipment racks that meet ANSI/EIA 310-D and ETS 300-119 standards. WarningTwo people are required to lift the chassis. To prevent injury, keep your back straight and lift with your legs, not your back. Statement 164 TipWe recommend that you have a third person to assist in this procedure. To install the switch chassis in the equipment rack, follow these steps: Step 1With a person standing at each side of the chassis, grasp the chassis handle with one hand, and use the other hand near the back of the chassis for balance. Slowly lift the chassis in unison. Avoid sudden twists or moves to prevent injury. Step 2Rest the back end of the chassis on the edges of the rack-mount shelf kit rails and carefully slide the chassis fully into the rack. Step 3Locate the rack post holes that align with the chassis L bracket holes. If the rack post holes are prethreaded, determine if the threads are 10-32 or 12-24. If the rack post holes are unthreaded, install eight or ten (four or five on each side) either 10-32 or 12-24 clip or cage nuts over the rack post holes to accept the installation screws. NoteClip nuts or cage nuts are not included as part of the accessory kit that comes with the chassis. You must obtain them yourself. Step 4If you want to install one or both of the optional cable guide assemblies, position the cable guides so that the cable guide mounting holes are aligned with rack-mount bracket holes and the rack post holes as shown in Figure 1-10. Step 5Install a minimum of eight 10-32 or 12-24 screws (four on each side) through the cable guide mounting holes, rack-mount L bracket holes, rack post holes, and into the clip nuts to secure the cable guides and the chassis to the rack post. Tighten the screws securely.
1-24 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Chapter 1 Installing the Switch Installing a Catalyst 6509 or Catalyst 6509-E Switch Chassis Figure 1-10 Installing a Catalyst 6509 Switch or a Catalyst 6509-E Switch Chassis in a Rack 12 x 24 or 10 x 32 (10x) Shelf bracketCable guideRack post 113976 FA N STATUS INPUT OKFA N OKOUTPUT FA I L o 1 2 3 4 5 6 7 8 9 8 PORT GIGABIT ETHERNET WS-X64081LINKSTATUS2 3 4 5 6 7 8LINKLINKLINKLINKLINKLINKLINK 8 PORT GIGABIT ETHERNET WS-X64081LINKSTATUS2 3 4 5 6 7 8LIN KLINKLINKLINKLIN KLIN KLINK 2 4 P O R T 1 00 F X W S - X 6 2 2 4S T A T U S 2 4 P O R T 1 00 F X W S - X 6 2 2 4S T A T U S 2 4 P O R T 1 0 0 F X W S -X 6 2 2 4S T A T U S 24 P O R T 1 0 0 F X W S -X 6 2 2 4S T A T U S 1LINK2LINK3LINK4LINK5LINK6LINK7LINK8LINK9LINK10LINK11LINK12LINK13LINK14LINK15LINK16LINK17LINK18LINK19LINK20LINK21LINK22LINK23LINK24LINK1LINK2LINK3LINK4LINK5LINK6LINK7LINK8LINK9LINK1 0LINK1 1LINK1 2LINK1 3LINK1 4LINK1 5LINK1 6LINK1 7LINK1 8LINK1 9LINK2 0LINK2 1LINK2 2LINK2 3LINK2 4LINK1LINK2LINK3LINK4LINK5LINK6LINK7LINK8LINK9LINK10LINK11LINK12LINK13LINK14LINK15LINK16LINK17LINK18LINK19LINK20LINK21LINK22LINK23LINK24LINK1LINK2LINK3LINK4LINK5LINK6LINK7LINK8LINK9LINK10LINK11LINK12LINK13LINK14LINK15LINK16LINK17LINK18LINK19LINK20LINK21LINK22LINK23LINK24LINK
1-25 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Chapter 1 Installing the Switch Installing a Catalyst 6509 or Catalyst 6509-E Switch Chassis What is Next After installing the chassis in its location, complete the installation process by following these procedures: Connecting the chassis to system ground. See “Establishing the System Ground” section on page 1-52. Installing and connecting the power supplies to source power. Go to Chapter 4 for information on how to install and cable power supplies. Connecting the network interface cables to the supervisor engine and modules. This may involve installing transceivers before you attach the network interface cables. See “Attaching the Interface Cables” section on page 1-61. Powering-up the chassis and verifying the installation. See “Verifying Switch Chassis Installation” section on page 1-84. Optional Installation Kits An optional rubber feet installation kit is included in the accessory kit for the Catalyst 6509-E switch chassis. This kit contains the parts necessary to install four non-slip rubber feet on the bottom of the chassis allowing the chassis to placed on a shelf or a table. To install the rubber feet, go to “Installing the Rubber Feet Kit” section on page 1-50. A center rack-mount kit for 23-inch, telco-style racks is available as an option for both the Catalyst 6509 and the Catalyst 6509-E switch chassis. The kit is not included in the accessory kits, but is available as a separately orderable item (p/n WS-C6597=). Installation instructions are included with the kit.
1-26 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Chapter 1 Installing the Switch Installing a Catalyst 6509-NEB or Catalyst 6509-NEB-A Switch Chassis Installing a Catalyst 6509-NEB or Catalyst 6509-NEB-A Switch Chassis This section provides procedures for installing either a Catalyst 6509-NEB or a Catalyst 6509-NEB-A switch chassis in a rack assembly and installing the optional cable guides. Installation Accessory Kits The Catalyst 6509-NEB and Catalyst 6509-NEB-A switch chassis are designed to be installed in a standard 19-inch rack, either open or enclosed. Both chassis are normally shipped with the 19-inch rack-mount L brackets factory installed on the left-front and right-front of the chassis. Included with the accessory kit are 10-32 x 0.75-inch and 12-24 x 0.75-inch screws that are used to secure the chassis in the rack enclosure. NoteDepending on the manufacturer, the rack posts might be prethreaded to accept either 10-32 or 12-24 screws. If the rack posts are not prethreaded, you must install 10-32 or 12-24 clip nuts or cage nuts to secure the rack-mount screws. The clip nuts or the cage nuts are not included as part of the accessory kit and must be obtained on your own. Depending on the chassis model, the accessory kit might contain the following chassis installation kits: Rack-mount shelf kit (Catalyst 6509-NEB and Catalyst 6509-NEB-A). The rack-mount shelf kit is used to support the weight of the chassis while you secure the chassis L brackets to the rack enclosure. A stabilizer bracket kit (Catalyst 6509-NEB only). If you are not installing the Catalyst 6509-NEB switch in a rack, you must install the stabilizer brackets to the bottom of the chassis. The stabilizer brackets reduce the possibility that the freestanding switch chassis will tip over. Also included in the Catalyst 6509-NEB accessory kit: One cable guide—The optional cable guide can be mounted to the front of the chassis. Power supply blank panel—The power supply blank panel must be installed on an unused power supply bay to maintain chassis airflow and EMI shielding. Also included in the Catalyst 6509-NEB-A accessory kit: Cable management system—The optional cable management kit can be installed on the upper front of the chassis. Power supply blank panel—The power supply blank panel must be installed on an unused power supply bay to maintain chassis airflow and EMI shielding. L Brackets and the Optional Cable Guide on the Catalyst 6509-NEB Switch The Catalyst 6509-NEB switch chassis is shipped with the two L brackets installed on the front sides of the chassis. The L brackets are secured to the chassis with eight M4 Phillips-head countersunk screws (four screws on each side) as shown in Figure 1-12.
1-27 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Chapter 1 Installing the Switch Installing a Catalyst 6509-NEB or Catalyst 6509-NEB-A Switch Chassis NoteThe L brackets can also be reversed and installed on the rear of the chassis as an alternative method of installation. NoteThe Catalyst 6509-NEB L bracket screw holes are stamped + and –. You can install the brackets on either the left or right side of the chassis; use the + holes on one side and the – holes on the other side. The optional cable guide attaches to the front of the chassis using four M4 screws supplied in the accessory kit. (See Figure 1-11.) Figure 1-11 L Brackets and Cable Guide Attachment on the Catalyst 6509-NEB Switch Chassis L Brackets on the Catalyst 6509-NEB-A Switch Chassis The Catalyst 6509-NEB-A switch chassis is shipped with the two L brackets installed on the front sides of the chassis. The L brackets are secured to the chassis with 14 M3 Phillips-head countersunk screws (seven screws on each side) as shown in Figure 1-12. These brackets can also be installed on the rear of the chassis if necessary. FA N STATUS 8 PORT GIGABIT ETHERNETWS-X6408 1LINKSTATUS 2 3 4 5 6 7 8LINK LINK LINK LINK LINK LINK LINK 8 PORT GIGABIT ETHERNETWS-X6408 1LINKSTATUS 2 3 45 67 8LINK LINK LINK LINK LINK LINK LINK 8 PORT GIGABIT ETHERNETWS-X6408 1LINKSTATUS 2 3 45 6 7 8LINK LINK LINK LINK LINK LINK LINK 24 PORT 100FXWS-X6224S T A T U S24 PORT 100FXWS-X6224S TA TU S24 PORT 100FXWS-X6224S T AT U S1L I N K2L I N K3L I N K4L I N K5L I N K6L I N K7L I N K8L I N K9L IN K10L IN K11L IN K12L IN K13L IN K14L IN K15L IN K16L IN K17L IN K18L IN K19L IN K20L IN K21L IN K22L IN K23L IN K24L IN K 1L I N K2L IN K3L I N K4L IN K5L I N K6L I N K7L I N K8L IN K9L I N K10L IN K11L IN K12L IN K13L IN K14L IN K15L IN K16L IN K17L IN K18L IN K19L IN K20L IN K21L IN K22L IN K23L IN K24L IN K 1LINK2LINK3LINK4LINK5LINK6LINK7LINK8LINK9LINK10LINK11LINK12LINK13LINK14LINK15LINK16LINK17LINK18LINK19LINK20LINK21LINK22LINK23LINK24LINK 24 PORT 100FXWS-X6224ST AT U S1LINK2LINK3LINK4LINK5LINK6LINK7LINK8LINK9LINK10LINK11LINK12LINK13LINK14LINK15LINK16LINK17LINK18LINK19LINK20LINK21LINK22LINK23LINK24LINK S U P E R V IS O R 2 W S -X 6 K -S U P 2-2 G ES T A T U SS Y S T E MC O N S O L EP W R M G M TR E S E TCONSOLECONSOLE PORT MODE PCMCIA EJECT PORT 1 PORT 2 Switch Load 100% 1% L I N K L I N K S U P E R V IS O R 2 W S -X 6K -S U P 2 -2G ES T A T U SS Y S T E MC O N S O L EP W R M G M TR E S E TCONSOLECONSOLE PORT MODE PCMCIA EJECT PORT 1 PORT 2 Switch Load 100% 1% L I N K L I N K 48124 Cable guide M4 screwsL bracket L bracket
1-28 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Chapter 1 Installing the Switch Installing a Catalyst 6509-NEB or Catalyst 6509-NEB-A Switch Chassis Figure 1-12 L Brackets on the Catalyst 6509-NEB-A Switch Chassis Installing the 3 RU Rack-Mount Shelf Kit The 3 RU rack-mount shelf kit is included as part of the accessory kit for both the Catalyst 6509-NEB and the Catalyst 6509-NEB-A switch chassis. You need to install this kit first before you install the chassis in the rack. The shelf kit supports the weight of the chassis while you install the chassis in the rack. The procedure for installing the shelf kit is located in the “Installing the 3 RU Rack-Mount Shelf Kit” section on page 1-47. INPUT OKFA N OKOUTPUT FA I L o79896 L bracket L bracket POWER SUPPLY 1 POWER SUPPLY 2 W S -S U P 3 2-G E -3 BSTA TU S S YSTE M A CTI VE PWR M GMT R ES ETC ATA LY S T 650 0 S U PE RV IS O R E N G IN E 32 C O N S O L E E J E C TD IS K 0P O RT 1 P O RT 2 P O RT 3 P O RT 4P O RT 5 P O RT 6 P O RT 7P O RT 8P O RT 9 U SB 2 .0 L IN K L INK L INK LI NK LIN K LIN K L IN K L INK LI NK W S -SU P 32-G E-3BSTA T US SYSTE M A CT IVE PW R MG MT R ESETC AT A LY S T 650 0 S U PE R V IS O R E N G IN E 32 C O N S O L E E J E C TD I S K 0P O RT 1 P O R T 2 P O R T 3 P O R T 4P O RT 5 P O RT 6 P O RT 7P O R T 8P O R T 9 U SB 2 . 0 L IN K L INK L INK LIN K LIN K LIN K LIN K LIN K LIN K WS-X6548-GE-TX STATUS 48 PORT10/100/1000 BASE-T GESWITCHING MODULE 123456789101112 131415161718192021222324 252627282930313233343536 373839404142434445464748PHONE 1 211 1213 1423 2425 2635 3637 3847 48 WS-X6548-GE-TX STATUS 48 PORT10/100/1000 BASE-T GESWITCHING MODULE 123456789101112 131415161718192021222324 252627282930313233343536 373839404142434445464748PHONE 1 211 1213 1423 2425 2635 3637 3847 48WS-X6548-GE-TX STATUS 48 PORT10/100/1000 BASE-T GESWITCHING MODULE 123456789101112 131415161718192021222324 252627282930313233343536 373839404142434445464748PHONE 1 211 1213 1423 2425 2635 3637 3847 48WS-X6548-GE-TX STATUS 48 PORT10/100/1000 BASE-T GESWITCHING MODULE 123456789101112 131415161718192021222324 252627282930313233343536 373839404142434445464748PHONE 1 211 1213 1423 2425 2635 3637 3847 48WS-X6548-GE-TX STATUS 48 PORT10/100/1000 BASE-T GESWITCHING MODULE 123456789101112 131415161718192021222324 252627282930313233343536 373839404142434445464748PHONE 1 211 1213 1423 2425 2635 3637 3847 48WS-X6548-GE-TX STATUS 48 PORT10/100/1000 BASE-T GESWITCHING MODULE 123456789101112 131415161718192021222324 252627282930313233343536 373839404142434445464748PHONE 1 211 1213 1423 2425 2635 3637 3847 48WS-X6548-GE-TX STATUS 48 PORT10/100/1000 BASE-T GESWITCHING MODULE 123456789101112 131415161718192021222324 252627282930313233343536 373839404142434445464748PHONE 1 211 1213 1423 2425 2635 3637 3847 48