    							A-41
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      4000 W AC-Input and DC-Input Power Supplies
    4000 W AC-Input and DC-Input Power Supplies
    The 4000 W AC-input and DC-input power supplies, (WS-CAC-4000W-US, WS-CAC-4000W-INT, and 
    PWR-4000-DC) are supported in the following Catalyst 6500 series switches:
    Catalyst 6506
    Catalyst 6506-E
    Catalyst 6509
    Catalyst 6509-E
    Catalyst 6509-NEB
    Catalyst 6509-NEB-A
    Catalyst 6509-V-E
    Catalyst 6513
    Catalyst 6513-E
    The 4000 W AC-input and DC-input power supplies, shown in Figure A-14 and Figure A-15, share the 
    same form factor as the 1000 W, 1300 W, 2500 W, and 3000 W power supplies. 
    Figure A-14 4000 W AC-Input Power Supply
    Power
    switchINPUT
    OKFA N
    OKOUTPU
    T
    FA IL
    Captive installation
    screwStatus LEDs
    85756I
    0 
    						
    							A-42
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      4000 W AC-Input and DC-Input Power Supplies
    Figure A-15 4000 W DC-Input Power Supply
    4000 W Power Supply Specifications
    Ta b l e A - 2 9 lists the specifications for the 4000 W AC-input power supply.
    INPUT OK
    FA N
    OKOUTPUT
    FAIL
    I
    0
    97297
    1
    3 2
    +VE-1
    -VE-1
    +VE-2
    -VE-2
    +VE-3
    -VE-3
    Table A-28 4000 W AC-Input Power Supply Specifications
    Specification Description
    AC-input type High-line input with power factor correction (PFC).
    NotePower factor correction is a standard feature on all Catalyst 6500 
    series AC-input power supplies. PFC reduces the reactive 
    component in the source AC current allowing higher power 
    factors (typically 99 percent or better) and lower harmonic 
    current components.
    AC-input voltage High-line (230 VAC nominal)—170 VAC (min) to 264 VAC (max)
    AC-input current 23 A
    AC-input frequency 50/60 Hz (nominal) (±3% for full range) 
    						
    							A-43
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      4000 W AC-Input and DC-Input Power Supplies
    Ta b l e A - 2 9 list the specification for the 4000 W DC-input power supply. Branch circuit requirement  Each chassis power supply should have its own dedicated, fused-branch 
    circuit:
    For North America—30 A
    For International—Circuits should be sized according to local and 
    national codes
    All AC power supply inputs are fully isolated.
    –Source AC can be out of phase between multiple power supplies 
    in the same chassis, which means that PS1 can be operating 
    from phase A and PS2 can be operating from phase B.
    –For high-line operation, the power supply operates with the hot 
    conductor wired to a source AC phase and the neutral conductor 
    wired either to ground or to another source AC phase as long as 
    the net input voltage is in the range of 170 to 264 VAC.
    –Source AC can be out of phase between AC inputs on power 
    supplies that are equipped with multiple AC inputs, which 
    means that power cord 1 can be plugged into phase A and 
    power cord 2 can be plugged into phase B.
    Output capacity  4000 W maximum
    Power supply output 
    15 A @ +3.3 VDC
    5A @ +5VDC
    10 A @ +12 VDC
    90.36 A @ +42 VDC
    Output holdup time 20 ms minimum 
    kVA rating
    15.4 kVA maximum
    Heat dissipation 17,065 BTU/hour (approx.) 
    Weight 22.2 lb (10.1 kg)
    1. The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard 
    circuits and transformers to power a switch.
    Table A-28 4000 W AC-Input Power Supply Specifications (continued)
    Specification Description 
    						
    							A-44
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      4000 W AC-Input and DC-Input Power Supplies
    Ta b l e A - 3 0 lists the power supply LEDs and their meanings.
    Table A-29 4000 W DC-Input Power Supply Specifications
    Specification Description
    DC-input voltage
    –48 VDC @ 37 A for nominal –48 V battery backup system 
    (operating range: –40.5 VDC to –56 VDC)
    –60 VDC @ 29 A for nominal –60 V battery backup system 
    (operating range: –55 VDC to –72 VDC)
    NoteThe 4000 W DC-input power supply requires two source 
    DC-inputs to be connected; it cannot operate with only one 
    positive (+)/negative (-) source DC terminal pair installed.
    DC-input current 40 A per each DC input (three inputs)
    NoteFor multiple DC input power supplies, each DC input must be 
    protected by a dedicated circuit breaker or a fuse. The circuit 
    breaker or the fuse must be sized according to the power supply 
    input power rating and any local or national electrical code 
    requirements.
    Power supply output 
    capacity 
    4000 W with three inputs active
    2700 W with two inputs active
    NoteThe 4000 W power supply cannot operate with only one source 
    DC-input connected.
    Power supply output 
    15 A @ + 3.3 VDC
    5A @ + 5 VDC
    12 A @ +12 VDC
    90.63 A (three inputs) or 59.68 A (two inputs) 
    @ +42 VDC
    NoteThe 4000 W power supply cannot operate with only one source 
    DC-input connected.
    DC input terminal block Accepts 4 AWG copper conductors. Actual size of the wire needed is 
    determined by the installer or local electrician.
    Output holdup time 8 ms 
    kVA rating
    1
    1. The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard 
    circuits and transformers to power a switch.
    5.4 kVA maximum
    Heat dissipation 17,730 BTU/hour (approx.)
    Weight 30.8 lb (14.0 kg) 
    						
    							A-45
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      4000 W AC-Input and DC-Input Power Supplies
    Table A-30 4000 W AC-Input and DC-Input Power Supplies LEDs
    LED Meaning
    INPUT OK AC-input power supplies:
    Green—Source AC voltage is OK. (Input 
    voltage is 85 VAC or greater.)
    Off—Source AC voltage falls below 70 VAC, 
    is not present, or the power supply is turned 
    off.
    DC-input power supplies:
    Green—Source DC voltage is OK. (Input 
    voltage is –40.5 VDC or greater.)
    Off—Source DC voltage falls below 
    –33 VDC, is not present, or the power supply 
    is turned off.
    FAN OK
    Green—Power supply fan is operating 
    properly.
    Off—Power supply fan failure is detected.
    OUTPUT FAIL
    Red—Problem with one or more of the 
    DC-output voltages of the power supply.
    Off—DC-output voltages within acceptable 
    margins.
    NoteFor proper operation of the OUTPUT 
    FAIL LED, systems with single power 
    supplies must be configured with a 
    minimum of one fan tray and one 
    supervisor engine. Systems with dual 
    power supplies must have a minimum 
    configuration of one fan tray, one 
    supervisor engine, and one additional 
    module. Failure to meet these minimum 
    configuration requirements can cause a 
    false power supply output fail signal. 
    						
    							A-46
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      6000 W AC-Input and DC-Input Power Supplies
    4000 W Power Supply AC Power Cords
    Ta b l e A - 3 1 lists the specifications for the AC power cords that are available for the 4000 W AC-input 
    power supply. Included in the table are references to illustrations of the power cords.
    NoteThe AC power cords for the 4000 W AC-input power supply are hardwired directly to the power supply; 
    they do not have an IEC 60320 C19 appliance plug and cannot be removed from the power supply.
    6000 W AC-Input and DC-Input Power Supplies
    Catalyst 6500 series switch support for the 6000 W AC-input (WS-CAC-6000W) and the 6000 W 
    DC-input (PWR-6000-DC) power supplies along with any power supply output restrictions are listed in 
    Ta b l e A - 3 2. 
    The 6000 W AC-input power supply, shown in Figure A-16, and the 6000 W DC-input power supply, 
    shown in Figure A-17, share the same form factor as the 1000 W, 1300 W, 2500 W, 3000 W, and 4000 W 
    power supplies. 
    TableA-31 4000W Power Supply AC Power Cords
    Locale Power Cord
    Part Number1
    1. This is the part number for the power supply. The AC power cords are hardwired to the 4000 W power supplies.
    AC Source Plug Type Cordset Rating Power Cord 
    Reference 
    Illustration
    International WS-CAC-4000W-INT= IEC 60309 32 A, 250 VACFigure A-48
    North America, Japan WS-CAC-4000W-US= NEMA L6-30
    2
    2. For Japan, ask your local electrical contractor to prepare the NEMA L6-30 power plug.
    30 A, 250 VACFigure A-49
    Table A-32 Chassis Support for the 6000 W AC-Input and DC-Input Power Supplies
    Catalyst 6500 Series Chassis  6000 W AC-Input Power Supply 
    Restriction6000 W DC-Input Power Supply 
    Restriction
    Catalyst 6506 Output limited to 4000 W Output limited to 4000 W
    Catalyst 6506-E No restrictions No restrictions
    Catalyst 6509 Output limited to 4000 W Output limited to 4000 W
    Catalyst 6509-E No restrictions No restrictions
    Catalyst 6509-NEB Output limited to 4000 W Output limited to 4000 W
    Catalyst 6509-NEB-A Output limited to 4500 W Output limited to 4500 W
    Catalyst 6509-V-E No restrictions No restrictions
    Catalyst 6513 No restrictions No restrictions
    Catalyst 6513-E No restrictions No restrictions 
    						
    							A-47
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      6000 W AC-Input and DC-Input Power Supplies
    NoteBecause of form-factor differences, the 6000 W AC-input and the 6000 W DC-input power supplies 
    cannot be installed in the Catalyst 6503, Catalyst 6503-E, and Catalyst 6504-E switch chassis.
    Figure A-16 6000 W AC-Input Power Supply
    Figure A-17 6000 W DC-Input Power Supply
    Power
    switchCable 
    retention
    deviceINPUT
    OK INPUT 1
    100 - 240V
    15A
    50/60 Hz
    INPUT 1
    100 - 240V
    15A
    50/60 HzFA N
    OKOUTPUT
    FA I L
    Captive installation
    screwStatus LEDs
    130056AC power
    connection 2AC power
    connection 1
    I
    0INSTALL
    RUN
    191307RUNINSTALL
    CISCO SYSTEMS, INC1
    2
    34
    INPUT OKFAN
    OKOUTPUT
    FAIL 
    						
    							A-48
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      6000 W AC-Input and DC-Input Power Supplies
    6000 W Power Supply Specifications
    Ta b l e A - 3 4 lists the specifications for the 6000 W AC-input power supply.
    Table A-33 6000 W AC-Input Power Supply Specifications
    Specification Description
    AC-input type 2 AC-inputs per power supply. High-line input 
    with power factor correction (PFC) included.
    NotePower factor correction is a standard 
    feature on all Catalyst 6500 series 
    AC-input power supplies. PFC reduces 
    the reactive component in the source AC 
    current allowing higher power factors 
    (typically 99 percent or better) and lower 
    harmonic current components.
    AC-input voltage
    Low-line (120 VAC nominal)—90 VAC 
    (min) to 132 VAC (max)
    High-line (230 VAC nominal)—170 VAC 
    (min) to 264 VAC (max)
    AC-input current  16 A each input 
    AC-input frequency 50/60 Hz (nominal) (±3% for full range) 
    						
    							A-49
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      6000 W AC-Input and DC-Input Power Supplies
    Branch circuit requirement  Each power supply input should have its own 
    dedicated, fused-branch circuit:
    For North America—20 A
    For International—Circuits should be sized 
    according to local and national codes
    All Catalyst 6500 series AC-input power 
    supplies require single-phase source AC.
    All AC power supply inputs are fully isolated.
    –Source AC can be out of phase between 
    multiple power supplies in the same 
    chassis, which means that PS1 can be 
    operating from phase A and PS2 can be 
    operating from phase B.
    –For high-line operation, the power supply 
    operates with the hot conductor wired to 
    a source AC phase and the neutral 
    conductor wired either to ground or to 
    another source AC phase as long as the 
    net input voltage is in the range of 170 to 
    264 VAC.
    –Source AC can be out of phase between 
    AC inputs on power supplies that are 
    equipped with multiple AC inputs, which 
    means that power cord 1 can be plugged 
    into phase A and power cord 2 can be 
    plugged into phase B.
    Table A-33 6000 W AC-Input Power Supply Specifications (continued)
    Specification Description 
    						
    							A-50
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      6000 W AC-Input and DC-Input Power Supplies
    Power supply output capacity The 6000 W power supply can operate at either 
    2900 W or 6000 W depending on the number of 
    AC power cords attached and the source AC 
    voltage.
    NoteThe 6000 W AC-input power supply is 
    limited to 4000 W maximum output when 
    it is installed in a Catalyst 6506, 
    Catalyst 6509, or Catalyst 6509-NEB 
    switch chassis. The power supply is 
    limited to 4500 W maximum output when 
    it is installed in the Catalyst 6509-NEB-A 
    switch chassis.
    2900 W maximum with the following source 
    AC arrangements:
    –INPUT 1 and INPUT 2 both connected to 
    low-line (120 VAC nominal)
    –INPUT 1 connected to high-line 
    (230 VAC nominal); INPUT 2 not 
    connected
    –INPUT 1 not connected; INPUT 2 
    connected to high-line (230 VAC 
    nominal)
    –INPUT 1 connected to high-line 
    (230 VAC nominal); INPUT 2 connected 
    to low-line (120 VAC nominal)
    –INPUT 1 connected to low-line 
    (120 VAC nominal); INPUT 2 connected 
    to high-line (230 VAC nominal)
    6000 W maximum with the following source 
    AC arrangements:
    –INPUT 1 and INPUT 2 both connected to 
    high-line (230 VAC nominal)
    NoteThe 6000 W power supply will not power 
    up if you have only one power cord 
    plugged into either INPUT 1 or INPUT 2 
    and source AC is low-line (120 VAC 
    nominal).
    Table A-33 6000 W AC-Input Power Supply Specifications (continued)