A-41 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Appendix A Power Supply Specifications 4000 W AC-Input and DC-Input Power Supplies 4000 W AC-Input and DC-Input Power Supplies The 4000 W AC-input and DC-input power supplies, (WS-CAC-4000W-US, WS-CAC-4000W-INT, and PWR-4000-DC) are supported in the following Catalyst 6500 series switches: Catalyst 6506 Catalyst 6506-E Catalyst 6509 Catalyst 6509-E Catalyst 6509-NEB Catalyst 6509-NEB-A Catalyst 6509-V-E Catalyst 6513 Catalyst 6513-E The 4000 W AC-input and DC-input power supplies, shown in Figure A-14 and Figure A-15, share the same form factor as the 1000 W, 1300 W, 2500 W, and 3000 W power supplies. Figure A-14 4000 W AC-Input Power Supply Power switchINPUT OKFA N OKOUTPU T FA IL Captive installation screwStatus LEDs 85756I 0
A-42 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Appendix A Power Supply Specifications 4000 W AC-Input and DC-Input Power Supplies Figure A-15 4000 W DC-Input Power Supply 4000 W Power Supply Specifications Ta b l e A - 2 9 lists the specifications for the 4000 W AC-input power supply. INPUT OK FA N OKOUTPUT FAIL I 0 97297 1 3 2 +VE-1 -VE-1 +VE-2 -VE-2 +VE-3 -VE-3 Table A-28 4000 W AC-Input Power Supply Specifications Specification Description AC-input type High-line input with power factor correction (PFC). NotePower factor correction is a standard feature on all Catalyst 6500 series AC-input power supplies. PFC reduces the reactive component in the source AC current allowing higher power factors (typically 99 percent or better) and lower harmonic current components. AC-input voltage High-line (230 VAC nominal)—170 VAC (min) to 264 VAC (max) AC-input current 23 A AC-input frequency 50/60 Hz (nominal) (±3% for full range)
A-43 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Appendix A Power Supply Specifications 4000 W AC-Input and DC-Input Power Supplies Ta b l e A - 2 9 list the specification for the 4000 W DC-input power supply. Branch circuit requirement Each chassis power supply should have its own dedicated, fused-branch circuit: For North America—30 A For International—Circuits should be sized according to local and national codes All AC power supply inputs are fully isolated. –Source AC can be out of phase between multiple power supplies in the same chassis, which means that PS1 can be operating from phase A and PS2 can be operating from phase B. –For high-line operation, the power supply operates with the hot conductor wired to a source AC phase and the neutral conductor wired either to ground or to another source AC phase as long as the net input voltage is in the range of 170 to 264 VAC. –Source AC can be out of phase between AC inputs on power supplies that are equipped with multiple AC inputs, which means that power cord 1 can be plugged into phase A and power cord 2 can be plugged into phase B. Output capacity 4000 W maximum Power supply output 15 A @ +3.3 VDC 5A @ +5VDC 10 A @ +12 VDC 90.36 A @ +42 VDC Output holdup time 20 ms minimum kVA rating 15.4 kVA maximum Heat dissipation 17,065 BTU/hour (approx.) Weight 22.2 lb (10.1 kg) 1. The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard circuits and transformers to power a switch. Table A-28 4000 W AC-Input Power Supply Specifications (continued) Specification Description
A-44 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Appendix A Power Supply Specifications 4000 W AC-Input and DC-Input Power Supplies Ta b l e A - 3 0 lists the power supply LEDs and their meanings. Table A-29 4000 W DC-Input Power Supply Specifications Specification Description DC-input voltage –48 VDC @ 37 A for nominal –48 V battery backup system (operating range: –40.5 VDC to –56 VDC) –60 VDC @ 29 A for nominal –60 V battery backup system (operating range: –55 VDC to –72 VDC) NoteThe 4000 W DC-input power supply requires two source DC-inputs to be connected; it cannot operate with only one positive (+)/negative (-) source DC terminal pair installed. DC-input current 40 A per each DC input (three inputs) NoteFor multiple DC input power supplies, each DC input must be protected by a dedicated circuit breaker or a fuse. The circuit breaker or the fuse must be sized according to the power supply input power rating and any local or national electrical code requirements. Power supply output capacity 4000 W with three inputs active 2700 W with two inputs active NoteThe 4000 W power supply cannot operate with only one source DC-input connected. Power supply output 15 A @ + 3.3 VDC 5A @ + 5 VDC 12 A @ +12 VDC 90.63 A (three inputs) or 59.68 A (two inputs) @ +42 VDC NoteThe 4000 W power supply cannot operate with only one source DC-input connected. DC input terminal block Accepts 4 AWG copper conductors. Actual size of the wire needed is determined by the installer or local electrician. Output holdup time 8 ms kVA rating 1 1. The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard circuits and transformers to power a switch. 5.4 kVA maximum Heat dissipation 17,730 BTU/hour (approx.) Weight 30.8 lb (14.0 kg)
A-45 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Appendix A Power Supply Specifications 4000 W AC-Input and DC-Input Power Supplies Table A-30 4000 W AC-Input and DC-Input Power Supplies LEDs LED Meaning INPUT OK AC-input power supplies: Green—Source AC voltage is OK. (Input voltage is 85 VAC or greater.) Off—Source AC voltage falls below 70 VAC, is not present, or the power supply is turned off. DC-input power supplies: Green—Source DC voltage is OK. (Input voltage is –40.5 VDC or greater.) Off—Source DC voltage falls below –33 VDC, is not present, or the power supply is turned off. FAN OK Green—Power supply fan is operating properly. Off—Power supply fan failure is detected. OUTPUT FAIL Red—Problem with one or more of the DC-output voltages of the power supply. Off—DC-output voltages within acceptable margins. NoteFor proper operation of the OUTPUT FAIL LED, systems with single power supplies must be configured with a minimum of one fan tray and one supervisor engine. Systems with dual power supplies must have a minimum configuration of one fan tray, one supervisor engine, and one additional module. Failure to meet these minimum configuration requirements can cause a false power supply output fail signal.
A-46 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Appendix A Power Supply Specifications 6000 W AC-Input and DC-Input Power Supplies 4000 W Power Supply AC Power Cords Ta b l e A - 3 1 lists the specifications for the AC power cords that are available for the 4000 W AC-input power supply. Included in the table are references to illustrations of the power cords. NoteThe AC power cords for the 4000 W AC-input power supply are hardwired directly to the power supply; they do not have an IEC 60320 C19 appliance plug and cannot be removed from the power supply. 6000 W AC-Input and DC-Input Power Supplies Catalyst 6500 series switch support for the 6000 W AC-input (WS-CAC-6000W) and the 6000 W DC-input (PWR-6000-DC) power supplies along with any power supply output restrictions are listed in Ta b l e A - 3 2. The 6000 W AC-input power supply, shown in Figure A-16, and the 6000 W DC-input power supply, shown in Figure A-17, share the same form factor as the 1000 W, 1300 W, 2500 W, 3000 W, and 4000 W power supplies. TableA-31 4000W Power Supply AC Power Cords Locale Power Cord Part Number1 1. This is the part number for the power supply. The AC power cords are hardwired to the 4000 W power supplies. AC Source Plug Type Cordset Rating Power Cord Reference Illustration International WS-CAC-4000W-INT= IEC 60309 32 A, 250 VACFigure A-48 North America, Japan WS-CAC-4000W-US= NEMA L6-30 2 2. For Japan, ask your local electrical contractor to prepare the NEMA L6-30 power plug. 30 A, 250 VACFigure A-49 Table A-32 Chassis Support for the 6000 W AC-Input and DC-Input Power Supplies Catalyst 6500 Series Chassis 6000 W AC-Input Power Supply Restriction6000 W DC-Input Power Supply Restriction Catalyst 6506 Output limited to 4000 W Output limited to 4000 W Catalyst 6506-E No restrictions No restrictions Catalyst 6509 Output limited to 4000 W Output limited to 4000 W Catalyst 6509-E No restrictions No restrictions Catalyst 6509-NEB Output limited to 4000 W Output limited to 4000 W Catalyst 6509-NEB-A Output limited to 4500 W Output limited to 4500 W Catalyst 6509-V-E No restrictions No restrictions Catalyst 6513 No restrictions No restrictions Catalyst 6513-E No restrictions No restrictions
A-47 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Appendix A Power Supply Specifications 6000 W AC-Input and DC-Input Power Supplies NoteBecause of form-factor differences, the 6000 W AC-input and the 6000 W DC-input power supplies cannot be installed in the Catalyst 6503, Catalyst 6503-E, and Catalyst 6504-E switch chassis. Figure A-16 6000 W AC-Input Power Supply Figure A-17 6000 W DC-Input Power Supply Power switchCable retention deviceINPUT OK INPUT 1 100 - 240V 15A 50/60 Hz INPUT 1 100 - 240V 15A 50/60 HzFA N OKOUTPUT FA I L Captive installation screwStatus LEDs 130056AC power connection 2AC power connection 1 I 0INSTALL RUN 191307RUNINSTALL CISCO SYSTEMS, INC1 2 34 INPUT OKFAN OKOUTPUT FAIL
A-48 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Appendix A Power Supply Specifications 6000 W AC-Input and DC-Input Power Supplies 6000 W Power Supply Specifications Ta b l e A - 3 4 lists the specifications for the 6000 W AC-input power supply. Table A-33 6000 W AC-Input Power Supply Specifications Specification Description AC-input type 2 AC-inputs per power supply. High-line input with power factor correction (PFC) included. NotePower factor correction is a standard feature on all Catalyst 6500 series AC-input power supplies. PFC reduces the reactive component in the source AC current allowing higher power factors (typically 99 percent or better) and lower harmonic current components. AC-input voltage Low-line (120 VAC nominal)—90 VAC (min) to 132 VAC (max) High-line (230 VAC nominal)—170 VAC (min) to 264 VAC (max) AC-input current 16 A each input AC-input frequency 50/60 Hz (nominal) (±3% for full range)
A-49 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Appendix A Power Supply Specifications 6000 W AC-Input and DC-Input Power Supplies Branch circuit requirement Each power supply input should have its own dedicated, fused-branch circuit: For North America—20 A For International—Circuits should be sized according to local and national codes All Catalyst 6500 series AC-input power supplies require single-phase source AC. All AC power supply inputs are fully isolated. –Source AC can be out of phase between multiple power supplies in the same chassis, which means that PS1 can be operating from phase A and PS2 can be operating from phase B. –For high-line operation, the power supply operates with the hot conductor wired to a source AC phase and the neutral conductor wired either to ground or to another source AC phase as long as the net input voltage is in the range of 170 to 264 VAC. –Source AC can be out of phase between AC inputs on power supplies that are equipped with multiple AC inputs, which means that power cord 1 can be plugged into phase A and power cord 2 can be plugged into phase B. Table A-33 6000 W AC-Input Power Supply Specifications (continued) Specification Description
A-50 Catalyst 6500 Series Switches Installation Guide OL-5781-08 Appendix A Power Supply Specifications 6000 W AC-Input and DC-Input Power Supplies Power supply output capacity The 6000 W power supply can operate at either 2900 W or 6000 W depending on the number of AC power cords attached and the source AC voltage. NoteThe 6000 W AC-input power supply is limited to 4000 W maximum output when it is installed in a Catalyst 6506, Catalyst 6509, or Catalyst 6509-NEB switch chassis. The power supply is limited to 4500 W maximum output when it is installed in the Catalyst 6509-NEB-A switch chassis. 2900 W maximum with the following source AC arrangements: –INPUT 1 and INPUT 2 both connected to low-line (120 VAC nominal) –INPUT 1 connected to high-line (230 VAC nominal); INPUT 2 not connected –INPUT 1 not connected; INPUT 2 connected to high-line (230 VAC nominal) –INPUT 1 connected to high-line (230 VAC nominal); INPUT 2 connected to low-line (120 VAC nominal) –INPUT 1 connected to low-line (120 VAC nominal); INPUT 2 connected to high-line (230 VAC nominal) 6000 W maximum with the following source AC arrangements: –INPUT 1 and INPUT 2 both connected to high-line (230 VAC nominal) NoteThe 6000 W power supply will not power up if you have only one power cord plugged into either INPUT 1 or INPUT 2 and source AC is low-line (120 VAC nominal). Table A-33 6000 W AC-Input Power Supply Specifications (continued) Specification Description