    							A-11
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      1000 W AC-Input Power Supply
    1000 W Power Supply Specifications
    Ta b l e A - 7 lists the specifications for the 1000 W AC-input power supply.
    Table A-7 1000 W Power Supply Specifications
    Specification Description
    AC-input type Autoranging input with power factor correction (PFC)
    NotePower factor correction is a standard feature on all Catalyst 6500 
    series AC-input power supplies. PFC reduces the reactive 
    component in the source AC current allowing higher power 
    factors (typically 99 percent or better) and lower harmonic 
    current components.
    AC-input voltage
    Low-line (120 VAC nominal)—90 VAC (min) to 132 VAC (max)
    High-line (230 VAC nominal)—170 VAC (min) to 264 VAC (max)
    AC-input current
    12 A @ 120 VAC
    6 A @ 230 VAC
    AC-input frequency 50/60 Hz (nominal)
    Branch circuit requirement  Each chassis power supply should have its own dedicated, fused-branch 
    circuit:
    For North America—15 A or 20 A
    For International—Circuits sized to local and national codes
    All Catalyst 6500 series AC-input power supplies require 
    single-phase source AC.
    All AC power supply inputs are fully isolated.
    –Source AC can be out of phase between multiple power supplies 
    in the same chassis, which means that PS1 can be operating 
    from phase A and PS2 can be operating from phase B.
    –For high-line operation, the power supply operates with the hot 
    conductor wired to a source AC phase and the neutral conductor 
    wired either to ground or to another source AC phase as long as 
    the net input voltage is in the range of 170 to 264 VAC.
    –Source AC can be out of phase between AC inputs on power 
    supplies that are equipped with multiple AC inputs, which 
    means that power cord 1 can be plugged into phase A and 
    power cord 2 can be plugged into phase B. 
    						
    							A-12
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      1000 W AC-Input Power Supply
    Ta b l e A - 8 list the power supply LEDs and their meanings. Power supply output 
    capacity1000 W
    Power supply output
    15 A @ +3.3 VDC
    5A @ +5VDC
    6A @ +12VDC 
    20.3A @ +42VDC
    Output holdup time 20 ms minimum
    kVA rating
    11.25 kVA
    Heat dissipation 4213 BTU/hour (approx.)
    Weight 14.8 lb (6.7 kg)
    1. The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard 
    circuits and transformers to power a switch.
    Table A-7 1000 W Power Supply Specifications (continued)
    Specification Description
    Table A-8 1000 W Power Supply LEDs
    LED Meaning
    INPUT OK
    Green—Source AC voltage is OK. (Input voltage is 85 VAC or 
    greater.)
    Off—Source AC voltage falls below 70 VAC, is not present, or the 
    power supply is turned off.
    FAN OK
    Green—Power supply fan is operating properly.
    Off—Power supply fan failure is detected.
    OUTPUT FAIL
    Red—Problem with one or more of the DC-output voltages of the 
    power supply is detected.
    Off—DC-output voltage with acceptable margins.
    NoteFor proper operation of the OUTPUT FAIL LED, systems with 
    single power supplies must be configured with a minimum of 
    one fan tray and one supervisor engine. Systems with dual power 
    supplies must have a minimum configuration of one fan tray, one 
    supervisor engine, and one additional module. Failure to meet 
    these minimum configuration requirements can cause a false 
    power supply output fail signal. 
    						
    							A-13
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      1300 W AC-Input and DC-Input Power Supplies
    1000 W Power Supply AC Power Cords
    Ta b l e A - 9 lists the specifications for the AC power cords that are available for the 1000 W AC-input 
    power supply. The table includes references to power cord illustrations.
    NoteAll 1000 W power supply power cords are 8 feet 2 inches (2.5 meters) in length.
    NoteAll 1000 W power supply power cords have an IEC60320/C15 appliance plug at one end. 
    1300 W AC-Input and DC-Input Power Supplies
    The 1300 W AC-input power supply (WS-CAC-1300W) and 1300 W DC-input power supply 
    (WS-CDC-1300W) are supported in the following Catalyst 6500 series switches:
    Catalyst 6506
    Catalyst 6509
    Catalyst 6509-NEB
    The 1300 W power supply (see Figure A-5 for the 1300 W AC-input power supply and Figure A-6 for 
    the 1300 W DC-input power supply) shares the same form factor as the 1000 W, 2500 W, 3000 W, 
    4000 W, and 6000 W AC-input power supplies.
    Table A-9 1000 W AC-Input Power Supply Power Cords
    Locale Power Cord
    Part NumberAC Source Plug Type  Cordset Rating Power Cord 
    Reference 
    Illustration
    Argentina CAB-7KACR= IRAM 2073 10 A, 250 VACFigure A-25
    Australia, New Zealand CAB-7KACA= SAA AS 3112 15 A, 250 VAC Figure A-26
    Continental Europe CAB-7KACE= CEE 7/7 16 A, 250 VACFigure A-27
    Italy CAB-7KACI= CEI 23-16/7 10 A, 250 VACFigure A-28
    Japan, North America CAB-7KAC-15= NEMA 5-15 15 A, 125 VACFigure A-29
    United Kingdom CAB-7KACU= BS 1363
    1
    1. Plug contains a 13 A fuse.
    10 A, 250 VACFigure A-30 
    						
    							A-14
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      1300 W AC-Input and DC-Input Power Supplies
    Figure A-5 1300 W AC-input Power Supply
    Figure A-6 1300 W DC-Input Power Supply
    Power
    switchCable 
    retention
    deviceAC power
    connectionINPU
    T
    O
    KFA N
    O
    KOUTPUT
    FAIL
    Captive installation
    screwStatus LEDs
    16029I
    0
    Terminal
    block
    cover
    Captive installation screw
    o
    16030
    INPUT
    OKFA N
    OKOUTPUT
    FAIL 
    						
    							A-15
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      1300 W AC-Input and DC-Input Power Supplies
    1300 W Power Supply Specifications
    Ta b l e A - 1 1 lists the specifications for the 1300 W AC-input power supply.
    Table A-10 1300 W AC-Input Power Supply Specifications
    Specification Description
    AC-input type Autoranging input with power factor correction (PFC).
    NotePower factor correction is a standard feature on all Catalyst 6500 
    series AC-input power supplies. PFC reduces the reactive 
    component in the source AC current allowing higher power 
    factors (typically 99 percent or better) and lower harmonic 
    current components.
    AC-input voltage
    Low-line (120 VAC nominal)—90 VAC (min) to 132 VAC (max)
    High-line (230 VAC nominal)—170 VAC (min) to 264 VAC (max)
    AC-input current
    16 A @ 120 VAC
    8 A @ 230 VAC
    AC-input frequency 50/60 Hz (nominal) (±3 Hz for full range)
    Branch circuit requirement  Each chassis power supply should have its own dedicated, fused-branch 
    circuit:
    For North America—15 A or 20 A
    For International—Circuits sized to local and national codes
    All Catalyst 6500 series AC-input power supplies require 
    single-phase source AC.
    All AC power supply inputs are fully isolated.
    –Source AC can be out of phase between multiple power supplies 
    in the same chassis, which means that PS1 can be operating 
    from phase A and PS2 can be operating from phase B.
    –For high-line operation, the power supply operates with the hot 
    conductor wired to a source AC phase and the neutral conductor 
    wired either to ground or to another source AC phase as long as 
    the net input voltage is in the range of 170 to 264 VAC.
    –Source AC can be out of phase between AC inputs on power 
    supplies that are equipped with multiple AC inputs, which 
    means that power cord 1 can be plugged into phase A and 
    power cord 2 can be plugged into phase B.
    Power supply output 
    capacity
    1300 W maximum (AC-input)
    1360 W maximum (DC-input)
    Power supply output 
    15 A @ +3.3 VDC
    5A @ +5VDC
    6A @ +12VDC
    27.46 A @ +42 VDC
    Output holdup time 20 ms minimum 
    						
    							A-16
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      1300 W AC-Input and DC-Input Power Supplies
    Ta b l e A - 1 1 lists the specifications for the 1300 W DC-input power supply.
    Ta b l e A - 1 2 lists the 1300 W power supply LEDS and their meanings. kVA rating
    11.625 kVA
    Heat dissipation 5478 BTU/hour (approx.) 
    Weight 18.4 lb (8.3 kg)
    1. The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard 
    circuits and transformers to power a switch.
    Table A-10 1300 W AC-Input Power Supply Specifications (continued)
    Specification Description
    Table A-11 1300 W DC-Input Power Supply Specifications
    Specification Description
    DC-input voltage –48 VDC to –60 VDC continuous
    DC-input current
    39 A @ –48 VDC
    31 A @ –60 VDC
    Power supply output 
    capacity1360 W maximum (DC-input)
    Power supply output 
    15 A @ +3.3 VDC
    5A @ +5VDC
    6A @ +12VDC
    28.9A @ +42VDC
    DC input terminal block Accepts 3 AWG to 10 AWG copper conductors. Actual size of the wire 
    needed is determined by the installer or local electrician. Terminal block 
    material is rated at 120°C.
    Output holdup time 8 ms 
    Heat dissipation 6447 BTU/hour (approx.) 
    Weight 21.0 lb (9.5 kg) 
    						
    							A-17
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      1300 W AC-Input and DC-Input Power Supplies
    1300 W Power Supply AC Power Cords
    Ta b l e A - 1 3 lists the specifications for the AC power cords that are available for the 1300 W AC-input 
    power supply. The table includes references to power cord illustrations.
    NoteAll 1300 W power supply power cords are 14 feet (4.3 meters) in length.
    NoteAll 1300 W power supply power cords have an IEC60320/C19 appliance connector at one end. 
    Table A-12 1300 W AC-Input and DC-Input Power Supply LEDs
    LED Meaning
    INPUT OK AC-input power supplies:
    Green—Source AC voltage is OK. (Input voltage is 85 VAC or 
    greater.)
    Off—Source AC voltage falls below 70 VAC, is not present, or the 
    power supply turned off.
    DC-input power supplies:
    Green—Source DC voltage is OK. (Input voltage is –40.5 VDC or 
    greater.)
    Off—Source DC voltage falls below –33 VDC, is not present, or the 
    power supply is turned off.
    FAN OK
    Green—Power supply fan is operating properly.
    Off—Power supply fan failure is detected.
    OUTPUT FAIL
    Red—Problem with one or more of the DC-output voltages of the 
    power supply is detected.
    Off—DC-output voltages within acceptable margins.
    NoteFor proper operation of the OUTPUT FAIL LED, systems with 
    single power supplies must be configured with a minimum of 
    one fan tray and one supervisor engine. Systems with dual power 
    supplies must have a minimum configuration of one fan tray, one 
    supervisor engine, and one additional module. Failure to meet 
    these minimum configuration requirements can cause a false 
    power supply output fail signal. 
    						
    							A-18
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      1400 W AC-Input Power Supply
    1400 W AC-Input Power Supply
    The 1400 W AC-input power supply (PWR-1400-AC) can be installed in the Catalyst 6503 switch and 
    Catalyst 6503-E switch chassis only. Due to form factor differences, the 1400 W AC-input power supply 
    cannot be installed in any other Catalyst 6500 series switch chassis.
    The 1400 W power supplies (see Figure A-7) do not connect directly to source AC but use power entry 
    modules (PEMs), located on the front of the Catalyst 6503 and Catalyst 6503-E switch chassis, to 
    connect the site power source to the power supply located in the back of the chassis.
    The AC-input PEM (PEM-20A-AC+) (shown in Figure A-8) provides an input power connection on the 
    front of the router chassis to connect the site power source to the power supply. 
    The PEMs have an illuminated power switch, current protection, surge and EMI suppression, and filtering 
    functions.
    TableA-13 1300W Power Supply AC Power Cords
    Locale Power Cord
    Part NumberAC Source Plug Type  Cordset Rating Power Cord 
    Reference 
    Illustration
    Argentina CAB-7513ACR= IRAM 2073 10 A, 250 VACFigure A-31
    Australia, New Zealand CAB-7513ACA= SAA AS 3112 15 A, 250 VACFigure A-32
    Continental Europe CAB-7513ACE= CEE 7/7 16 A, 250 VACFigure A-33
    Israel CAB-AC-2500W-ISRL= SI16S3 16 A, 250 VACFigure A-34
    Italy CAB-7513ACI= CEI 23-16/7 16 A, 250 VACFigure A-35
    Japan, North America CAB-7513AC= NEMA 5-20
    1
    1. For Japan, ask your local electrical contractor to prepare the NEMA 5-20 power plug.
    20 A, 125 VACFigure A-36
    People’s Republic of 
    ChinaCAB-AC16A-CH= GB16C 16 A, 250 VACFigure A-37
    South Africa CAB-7513ACSA= IEC 884-1 16 A, 250 VACFigure A-38
    Switzerland CAB-ACS-10= SEV 1011 10 A, 250 VACFigure A-39
    United Kingdom CAB-7513ACU= BS 1363
    2
    2. Plug contains a 13 A fuse.
    13 A, 250 VACFigure A-40
    Power Distribution Unit 
    (PDU)
    3
    3. The PDU power cable is designed for users who power their switch from a PDU. The end of the cable that plugs into the chassis power supply has 
    a C19 connector; the other end of the cable that connects to the PDU has a C20 connector.
    CAB-C19-CBN= IEC 60320 C19
    IEC 60320 C2016 A, 250 VACFigure A-47 
    						
    							A-19
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      1400 W AC-Input Power Supply
    Figure A-7 1400 W AC-Input Power Supply (PWR-1400-AC)
    Figure A-8 1400 W AC-Input PEM (PEM-20A-AC+)
    1400 W Power Supply Specifications
    Ta b l e A - 1 4 lists the specifications for the 1400 W AC-input power supply.
    63183
    INPUT
    OKF
    AN
    OKOUTPUT
    FAIL
    Captive installation screws
    Status LEDs
    Captive installation screwsIEC 60320 C19 connector
    AC power
    switch130057
    PEM-20A-AC+50-60 Hz 120-240V  15A
    Table A-14 1400 W AC-Input Power Supply Specifications
    Specification Description
    AC-input type Autoranging input with power factor correction (PFC).
    NotePower factor correction is a standard feature on all Catalyst 6500 
    series AC-input power supplies. PFC reduces the reactive 
    component in the source AC current allowing higher power 
    factors (typically 99 percent or better) and lower harmonic 
    current components.
    AC-input voltage
    Low-line (120 VAC nominal)—90 VAC (min) to 132 VAC (max)
    High-line (230 VAC nominal)—170 VAC (min) to 264 VAC (max)
    AC-input current
    16 A @ 120 VAC
    8 A @ 230 VAC
    AC-input frequency 50/60 Hz (nominal) (±3 Hz for full range) 
    						
    							A-20
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      1400 W AC-Input Power Supply
    Ta b l e A - 1 5 lists the 1400 W AC-input power supply LEDs and their meanings. Branch circuit requirement  Each chassis power supply should have its own dedicated, fused-branch 
    circuit:
    For North America—20 A
    For International—Circuits sized to local and national codes
    All AC power supply inputs are fully isolated.
    –Source AC can be out of phase between multiple power supplies 
    in the same chassis, which means that PS1 can be operating 
    from phase A and PS2 can be operating from phase B.
    –For high-line operation, the power supply operates with the hot 
    conductor wired to a source AC phase and the neutral conductor 
    wired either to ground or to another source AC phase as long as 
    the net input voltage is in the range of 170 to 264 VAC.
    –Source AC can be out of phase between AC inputs on power 
    supplies that are equipped with multiple AC inputs, which 
    means that power cord 1 can be plugged into phase A and 
    power cord 2 can be plugged into phase B.
    Power supply output 
    capacity1400 W
    Power supply output
    15 A @ +1.5 V
    2.5 A @ +3.3 V
    27.4A @ +50V
    Output holdup time 20 ms minimum
    kVA rating
    11.75 kVA
    Heat dissipation 5976 BTU/hour (approx.)
    Weight 7.8 lb (3.5 kg)
    1. The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard 
    circuits and transformers to power a switch.
    Table A-14 1400 W AC-Input Power Supply Specifications (continued)
    Specification Description 
    						