Home > Cisco > Ethernet Switch > Cisco 6500e Manual

Cisco 6500e Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Cisco 6500e Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 53 Cisco manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    Page
    of 454
    							A-31
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      2700 W AC-Input and DC-Input Power Supplies
    2700 W Power Supply Specifications
    Ta b l e A - 2 2 lists the specifications for the 2700 W AC-input power supply.
    Table A-21 2700 W AC-Input Power Supply Specifications
    Specification Description
    AC-input type Autoranging input with power factor correction (PFC).
    NotePower factor correction is a standard feature on all Catalyst 6500 
    series AC-input power supplies. PFC reduces the reactive 
    component in the source AC current allowing higher power 
    factors (typically 99 percent or better) and lower harmonic 
    current components.
    AC-input voltage
    Low-line (120 VAC nominal)—90 VAC (min) to 132 VAC (max)
    High-line (230 VAC nominal)—170 VAC (min) to 264 VAC (max)
    AC-input current
    16 A maximum at 230 VAC at 2700 W output
    16 A maximum at 120 VAC at 1350 W output
    AC-input frequency 50/60 Hz (nominal) (±3% for full range)
    Branch circuit requirement  Each chassis power supply should have its own dedicated, fused-branch 
    circuit:
    For North America—20 A
    For International—Circuits sized to local and national codes
    All AC power supply inputs are fully isolated.
    –Source AC can be out of phase between multiple power supplies 
    in the same chassis, which means that PS1 can be operating 
    from phase A and PS2 can be operating from phase B.
    –For high-line operation, the power supply operates with the hot 
    conductor wired to a source AC phase and the neutral conductor 
    wired either to ground or to another source AC phase as long as 
    the net input voltage is in the range of 170 to 264 VAC.
    –Source AC can be out of phase between AC inputs on power 
    supplies that are equipped with multiple AC inputs, which 
    means that power cord 1 can be plugged into phase A and 
    power cord 2 can be plugged into phase B.
    Power supply output 
    capacity
    1350 W maximum (100–120 VAC)
    2700 W maximum (200–240 VAC) 
    						
    							A-32
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      2700 W AC-Input and DC-Input Power Supplies
    Ta b l e A - 2 2 lists the 2700 W DC-input power supply specifications. Power supply output
    100/120 VAC operation
    –15 A @ +1.5 VDC
    –2.5 A @ +3.3 VDC
    –27.49 A @ +50 VDC
    200/240 VAC operation
    –15 A @ +1.5 VDC
    –2.5 A @ +3.3 VDC
    –55.61 A @ +50 VDC
    Output holdup time 20 ms minimum 
    kVA rating
    13.4 KVA (high-line operation)
    Heat dissipation 10,841 BTU/hour (approx.)
    Weight 18.5 lb (8.4 kg)
    1. The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard 
    circuits and transformers to power a switch.
    Table A-21 2700 W AC-Input Power Supply Specifications (continued)
    Specification Description
    Table A-22 2700 W DC-Input Power Supply Specifications
    Specification Description
    DC-input voltage
    –48 VDC @ 37 A for nominal –48 V battery backup system 
    (operating range: –40.5 VDC to –56 VDC)
    –60 VDC @ 29 A for nominal –60 V battery backup system 
    (operating range: –55 VDC to –72 VDC)
    DC-input current (per DC 
    input)
    43 A @ –40.5 VDC
    37 A @ –48 VDC
    29 A @ –60 VDC
    NoteFor multiple DC input power supplies, each DC input must be 
    protected by a dedicated circuit breaker or a fuse. The circuit 
    breaker or the fuse must be sized according to the power supply 
    input power rating and any local or national electrical code 
    requirements.
    Power supply output 
    capacity
    1350 W maximum (–48 to –60 VDC, with one DC input)
    2700 W maximum (–48 to –60 VDC, with two DC inputs) 
    						
    							A-33
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      2700 W AC-Input and DC-Input Power Supplies
    Ta b l e A - 2 3 lists the power supply LEDs and their meanings. Power supply output 
    One DC input operation (1350 W operation)
    –15 A @ +1.5 VDC
    –5 A @ +3.3 VDC
    –27.49 A @ +50 VDC
    Two DC inputs operation (2700 W operation
    –15 A @ +1.5 VDC
    –5 A @ +3.3 VDC
    –55.61 A @ +50 VDC
    DC input terminal block Accepts 2–14 AWG copper conductors. Actual size of the wire needed 
    is determined by the installer or local electrician. Terminal block 
    material rated at 150°C.
    Output holdup time 4 ms 
    kVA rating
    13.5 KW 
    Heat dissipation 11,968 BTU/hour (approx.) 
    Weight 21.0 lb (9.5 kg)
    1. The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard 
    circuits and transformers to power a switch.
    Table A-22 2700 W DC-Input Power Supply Specifications (continued)
    Specification Description 
    						
    							A-34
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      2700 W AC-Input and DC-Input Power Supplies
    Table A-23 2700 W AC-Input and DC-Input Power Supply LEDs
    LED Meaning
    INPUT 1 OK
    INPUT 2 OK (DC-input 
    power supply only)AC-input power supplies:
    Green—Source AC voltage is OK. (Input voltage is 85 VAC or 
    greater.)
    Off—Source AC voltage falls below 70 VAC, is not present, or the 
    power supply is turned off.
    DC-input power supplies:
    Green—Source DC is OK. (Input voltage is –40.5 VDC or greater.)
    Off—Source DC voltage falls below –33 VDC, is not present, or the 
    power supply is turned off.
    FAN OK
    Green—Power supply fan is operating properly.
    Off—Power supply fan failure is detected.
    OUTPUT FAIL
    Red—Problem with one or more of the DC-output voltages of the 
    power supply.
    Off—DC-output voltages within acceptable margins.
    NoteFor proper operation of the OUTPUT FAIL LED, systems with 
    single power supplies must be configured with a minimum of 
    one fan tray and one supervisor engine. Systems with dual power 
    supplies must have a minimum configuration of one fan tray, one 
    supervisor engine, and one additional module. Failure to meet 
    these minimum configuration requirements can cause a false 
    power supply output fail signal. 
    						
    							A-35
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      2700 W AC-Input and DC-Input Power Supplies
    2700 W Power Supply AC Power Cords
    Ta b l e A - 2 4 lists the specifications for the AC power cords that are available for the 2700 W AC-input 
    power supply. The table includes references to power cord illustrations.
    NoteAll 2700 W power supply power cords are 14 feet (4.3 meters) in length.
    NoteAll 2700 W power supply power cords have an IEC60320/C19 appliance connector at one end. 
    TableA-24 2700W Power Supply AC Power Cords
    Locale Power Cord
    Part NumberAC Source Plug Type Cordset Rating Power Cord 
    Reference 
    Illustration
    Argentina CAB-7513ACR= or 
    CAB-IR2073-C19-AR=IRAM 2073 16 A, 250 VACFigure A-31
    Australia, New Zealand CAB-AC-16A-AUS= AU20S3 16 A, 250 VACFigure A-45
    People’s Republic of China CAB-AC16A-CH= GB16C 16 A, 250 VACFigure A-37
    Continental Europe CAB-AC-2500W-EU= CEE 7/7 16 A, 250 VACFigure A-41
    International CAB-AC-2500W-INT= IEC 309 16 A, 250 VACFigure A-42
    Israel CAB-AC-2500W-ISRL= SI16S3 16 A, 250 VACFigure A-34
    Italy CAB-7513ACI= CEI 23-16/7 16 A, 250 VACFigure A-35
    Japan, North America 
    200–240 VAC operationCAB-AC-2500W-US1= NEMA 6-20
    (nonlocking plug)16 A, 250 VACFigure A-43
    Japan, North America 
    200–240 VAC operationCAB-AC-C6K-TWLK= NEMA L6-20
    (locking plug)16 A, 250 VACFigure A-44
    Japan, North America
    100–120 VAC operationCAB-7513AC= NEMA 5-20 20 A, 125 VACFigure A-36
    Power Distribution Unit 
    (PDU)
    1
    1. The PDU power cable is designed for users who power their switch from a PDU. The end of the cable that plugs into the chassis power supply has a 
    C19 connector; the other end of the cable that connects to the PDU has a C20 connector.
    CAB-C19-CBN= IEC 60320 C19
    IEC 60320 C2016 A, 250 VACFigure A-47
    South Africa CAB-7513ACSA= IEC 884-1 16 A, 250 VACFigure A-38
    Switzerland CAB-ACS-16= SEV 5934-2 Type 23 16 A, 250 VACFigure A-45 
    						
    							A-36
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      3000 W AC-Input Power Supply
    3000 W AC-Input Power Supply
    The 3000 W AC-input power supply (WS-CAC-3000W) is supported in the following Catalyst 6500 
    series switches:
    Catalyst 6506
    Catalyst 6506-E
    Catalyst 6509
    Catalyst 6509-E
    Catalyst 6509-NEB
    Catalyst 6509-NEB-A
    Catalyst 6509-V-E
    Catalyst 6513
    Catalyst 6513-E
    The 3000 W power supply (see Figure A-13) shares the same form factor as the 1000 W, 1300 W, 
    2500 W, 4000 W, and 6000 W AC-input power supplies.
    NoteThe 3000 W AC-input power supply needs 220 VAC to deliver 3000 W of power. When operating with 
    110 VAC, it delivers only 1400 W. In addition, the power supply needs 16 A, regardless of whether it is 
    plugged into 110 VAC or 220 VAC.
    Figure A-13 3000 W AC-Input Power Supply
    INPUT
    OKFA N
    OKOUTPUT
    FA I LOUTPUT 42V  /17A42V  /17AOK
    IINSTALLRUN
    O
    110-120V - 15A
    200-240V - 15A
    60/50HZ
    +
    105069
    Power
    switch Cable 
    retention
    deviceAC power
    connection
    Captive installation
    screwStatus LEDs (3)
    External power
    connector cover 
    						
    							A-37
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      3000 W AC-Input Power Supply
    3000 W Power Supply Specifications
    Ta b l e A - 2 5 lists the specifications for the 3000 W AC-input power supply.
    Table A-25 3000 W Power Supply Specifications
    Specification Description
    AC-input type Autoranging input with power factor correction (PFC).
    NotePower factor correction is a standard feature on all Catalyst 6500 
    series AC-input power supplies. PFC reduces the reactive 
    component in the source AC current allowing higher power 
    factors (typically 99 percent or better) and lower harmonic 
    current components.
    AC-input voltage
    Low-line (120 VAC nominal)—90 VAC (min) to 132 VAC (max)
    High-line (230 VAC nominal)—170 VAC (min) to 264 VAC (max)
    AC-input current
    16 A @ 200 VAC (3000 W output)
    16 A @ 100 VAC (1400 W output)
    AC-input frequency 50/60 Hz (nominal) (±3% for full range)
    Branch circuit requirement  Each chassis power supply should have its own dedicated, fused-branch 
    circuit:
    For North America—20 A
    For International—Circuits sized to local and national codes
    All AC power supply inputs are fully isolated.
    –Source AC can be out of phase between multiple power supplies 
    in the same chassis, which means that PS1 can be operating 
    from phase A and PS2 can be operating from phase B.
    –For high-line operation, the power supply operates with the hot 
    conductor wired to a source AC phase and the neutral conductor 
    wired either to ground or to another source AC phase as long as 
    the net input voltage is in the range of 170 to 264 VAC.
    –Source AC can be out of phase between AC inputs on power 
    supplies that are equipped with multiple AC inputs, which 
    means that power cord 1 can be plugged into phase A and 
    power cord 2 can be plugged into phase B.
    Power supply output 
    capacity
    1400 W maximum (100–120 VAC)
    3000 W maximum (200–240 VAC) 
    						
    							A-38
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      3000 W AC-Input Power Supply
    Ta b l e A - 2 6 lists the power supply LEDs and their meanings. Power supply output
    100/120 VAC operation
    –25.0 A @ +3.3 V
    –5A @ +5V
    –12 A @ +12 V
    –27.89 A @ +42 V
    200/240 VAC operation
    –25.0 A @ +3.3 V
    –5A @ +5V 
    –12 A @ +12 V
    –65.98 A @ +42 V
    Front panel power 
    connectorA two-pin male Molex connector is located in the lower right corner of 
    the power supply front panel. The connector provides 42 VDC at a 
    maximum of 17 A. This connector provides power to the 
    WS-6509-NEB-UPGRD kit fan assembly through a power harness also 
    provided in the kit. A hinged protective flap secured by a captive screw 
    covers the connector when it is not in use.
    Output holdup time 20 ms minimum
    kVA rating
    13520 W (total input power) or 3.6 KVA (high-line operation)
    Heat dissipation 12,046 BTU/hour (approx.) 
    Weight 15.8 lb (7.2 kg)
    1. The kVA rating listed for the power supply should be used as the sizing criteria for both UPS outputs as well as standard 
    circuits and transformers to power a switch.
    Table A-25 3000 W Power Supply Specifications (continued)
    Specification Description 
    						
    							A-39
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      3000 W AC-Input Power Supply
    TableA-26 3000W AC-Input Power Supply LEDs
    LED Meaning
    INPUT OK
    Green—Source AC voltage is OK. (Input voltage is 85 VAC or 
    greater.)
    Off—Source AC voltage falls below 70 VAC, is not present, or the 
    power supply is turned off.
    FAN OK
    Green—Power supply fan is operating properly.
    Off—Power supply fan failure is detected.
    OUTPUT FAIL
    Red—Problem with one or more of the DC-output voltages of the 
    power supply.
    Off—DC-output voltages within acceptable margins.
    NoteFor proper operation of the OUTPUT FAIL LED, systems with 
    single power supplies must be configured with a minimum of 
    one fan tray and one supervisor engine. Systems with dual power 
    supplies must have a minimum configuration of one fan tray, one 
    supervisor engine, and one additional module. Failure to meet 
    these minimum configuration requirements can cause a false 
    power supply output fail signal.
    42V OK
    Green—42 VDC is present at the fan power connector.
    Off—42 VDC is not present at the fan power connector. 
    						
    							A-40
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Appendix A      Power Supply Specifications
      3000 W AC-Input Power Supply
    3000 W Power Supply AC Power Cords
    Ta b l e A - 2 7 lists the specifications for the AC power cords that are available for the 3000 W AC-input 
    power supply. The table includes references to power cord illustrations.
    NoteAll 3000 W power supply power cords are 14 feet (4.3 meters) in length.
    NoteAll 3000 W power supply power cords have an IEC60320/C19 appliance connector at one end. 
    TableA-27 3000W Power Supply AC Power Cords
    Locale Power Cord
    Part NumberAC Source Plug Type Cordset Rating Power Cord 
    Reference 
    Illustration
    Argentina CAB-7513ACR= or 
    CAB-IR2073-C19-AR=IRAM 2073 16 A, 250 VACFigure A-31
    Australia, New Zealand CAB-AC-16A-AUS= AU20S3 16 A, 250 VACFigure A-46
    People’s Republic of China CAB-AC16A-CH= GB16C 16 A, 250 VACFigure A-37
    Continental Europe CAB-AC-2500W-EU= CEE 7/7 16 A, 250 VACFigure A-41
    International CAB-AC-2500W-INT= IEC 309 16 A, 250 VACFigure A-42
    Israel CAB-AC-2500W-ISRL= SI16S3 16 A, 250 VACFigure A-34
    Italy CAB-7513ACI= CEI 23-16/7 16 A, 250 VACFigure A-35
    Japan, North America 
    (nonlocking plug)
    200–240 VAC operationCAB-AC-2500W-US1= NEMA 6-20 16 A, 250 VACFigure A-43
    Japan, North America 
    (locking plug)
    200–240 VAC operationCAB-AC-C6K-TWLK= NEMAL6-20 16A, 250VACFigure A-44
    Japan, North America
    100–120 VAC operation
    1
    1. The 3000 W power supply operating on 110 VAC delivers 1400 W.
    CAB-7513AC= NEMA 5-20 20 A, 125 VACFigure A-36
    Power Distribution Unit 
    (PDU)
    2
    2. The PDU power cable is designed for users who power their switch from a PDU. The end of the cable that plugs into the chassis power supply has a 
    C19 connector; the other end of the cable that connects to the PDU has a C20 connector.
    CAB-C19-CBN= IEC 60320 C19
    IEC 60320 C2016 A, 250 VACFigure A-47
    Switzerland CAB-ACS-16= SEV 5934-2 Type 23 16 A, 250 VACFigure A-45 
    						
    All Cisco manuals Comments (0)