    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Chapter 1      Removal and Replacement Procedures
      Removing and Installing the DC-Input Power Supplies
    Figure 1-44 Handling a DC-Input Power Supply without IPM
    Figure 1-45 Handling a DC-Input Power Supply with IPM
    191308
    RUNINSTALL
    CISCO SYSTEMS, INC1
    2
    34
    INPUT OKFAN
    OKOUTPUT
    FAIL
    RUNINSTALL
    CISCO SYSTEMS, INC1
    2
    34
    INPUT OKFAN
    OKOUTPUT
    FAIL 
    						
    							1-64
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Chapter 1      Removal and Replacement Procedures
      Removing and Installing the DC-Input Power Supplies
    Installing a 6000 W DC-Input Power Supply
    NoteWith the PWR-6000-DC power supply, you have the option of installing an Input Power Module (IPM) 
    (previously removed) with the DC-input wires and the ground wires still connected. You can then install 
    your power supply and insert the fully-wired IPM. Read through this procedure carefully before 
    installing your power supply.
    WarningBefore performing any of the following procedures, ensure that power is removed from the DC 
    circuits. To ensure that all power is removed, locate the circuit breakers or fuses on the DC power 
    lines that service the DC circuits. Turn OFF the DC power line circuit breakers and remove the DC 
    power line fuses. Statement 322
    NoteFor proper 6000W DC-input redundant power configuration, all input wires (two pairs for 2800W 
    DC-input, three pairs for 4500W DC-input, and four pairs for 6000W DC-input) for one 6000W 
    DC-input power supply must come from the same battery system (A feed); all input wires (two pairs for 
    2800W DC-input, three pairs for 4500W DC-input, and four pairs for 6000W DC-input) for the other 
    6000W DC-input power supply must come from another battery system (B feed).
    NoteFor multiple DC input power supply, each DC input must be protected by dedicated circuit breaker or 
    fuse. The circuit breaker or fuse should be sized according to the power supply input rating and local or 
    national electrical code requirements.
    WarningWhen installing or replacing the unit, the ground connection must always be made first and 
    disconnected last. Statement 1046
    NoteThe 6000 W DC-input power supply provides power of 2800 W, 4500 W, or 6000 W. Select 2800 W by 
    wiring any two positive (+)/negative (-) terminal pairs in any sequence. Select 4500 W by wiring any 
    three positive (+)/negative (-) terminal pairs in any sequence. Select 6000 W by wiring all four positive 
    (+)/negative (-) terminal pairs. The Cisco IOS software detects the wired inputs and sets the proper 
    system power.
    NoteThe 6000 W DC-input power supply ground provides the system ground connection when the 
    PWR-6000-DC power supply is installed in a Catalyst 6500 series chassis. Install the ground as 
    described in this procedure.
    NoteFor redundant power supplies, you must connect the 6000 W DC-input power supply ground for both 
    power supplies. 
    						
    							1-65
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Chapter 1      Removal and Replacement Procedures
      Removing and Installing the DC-Input Power Supplies
    NoteYou should allow a minimum of 2.5 to 3 inches (63.5 mm to 76.2 mm) of space between the side of the 
    power supply and any obstructions (such as the side of an enclosed equipment rack). This space is needed 
    to install and secure the DC-input power cables correctly. Incorrectly routing the DC-input power cables 
    can cause airflow blockage into the power supply and inadequate strain relief in the cables. The exact 
    amount of space required depends upon the gauge and flexibility of the DC-input power cables you are 
    using.
    To install a 6000 W DC-input power supply, follow these steps:
    Step 1Verify that power is off to the DC circuit that is connected to the power supply you are installing. Place 
    appropriate safety flag and lockout devices at power switch handle to avoid any circuit inputs from 
    becoming energized.
    CautionUse both hands to install and remove power supplies. Each 6000 W DC-input power supply weighs 
    35 pounds (16 kg). 
    Step 2Grasp the power supply handle with one hand, and place your other hand underneath the power supply. 
    Slide the power supply into the power supply bay. Make sure that the power supply is fully seated in the 
    bay (Figure 1-46).
    Figure 1-46 Handling a DC-Input Power Supply 
    Step 3
    Tighten the power supply captive installation screw (see Figure 1-47).
    RUNINSTALL
    CISCO SYSTEMS, INC1
    2
    34
    INPUT OKFAN
    OKOUTPUT
    FAIL 
    						
    							1-66
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Chapter 1      Removal and Replacement Procedures
      Removing and Installing the DC-Input Power Supplies
    Figure 1-47 6000 W DC-Input Power Supply Front Panel
    WarningPower supply captive installation screws must be tight to ensure protective grounding continuity. 
    Statement 289
    NoteWith the PWR-6000-DC power supply, you have the option of installing an Input Power Module 
    (IPM) (previously removed) with the DC-input wires and the ground wires still connected. You 
    can then install your power supply and insert the fully-wired IPM. If you are going to install an 
    IPM with DC-input wires and ground wires still connected, skip steps 4 through 12 and go 
    directly to step 13. 1Terminal block cover6Captive installation screw
    2DC power cable terminal block7 Input Power Module (IPM) 
    3Ground8IPM captive screws
    4Status LEDs9IPM latches
    5 Power switch 
    191286RUNINSTALL
    CISCO SYSTEMS, INC1
    2
    34
    INPUT OKFA N
    OKOUTPUT
    FAIL
    1
    2
    3
    4
    5
    6
    7
    8
    99
    8 
    						
    							1-67
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Chapter 1      Removal and Replacement Procedures
      Removing and Installing the DC-Input Power Supplies
    Step 4Remove the two A4 screws securing the outer terminal block cover, and remove the cover from the power 
    supply (Figure 1-47).
    Step 5Attach the appropriate lugs to the DC-input wires and ground wire. The wires should be sized according 
    to local and national installation requirements. Use only copper wire.
    Note6000 W power supplies ship with AWG #4 lugs with 45-degree angled, 2-hole compression lug 
    for both power and ground wiring. Additional lugs for different wire size should be purchased 
    separately.
    NoteThe power supply terminal block lug opening width is 0.62 inch (15.8 mm). The terminal posts 
    are centered 0.625 inches (15.88 mm) apart and are 1/4-20 threaded. We recommend that you 
    use an appropriately sized industry standard 45 degree angled, 2-hole, standard barrel 
    compression lug for both power and ground lugs (for example, on AWG #4 wires, Panduit part 
    number LCC4-14AWH-L or equivalent). The power supply ground studs, located beside the 
    terminal block.
    NoteFor 6000 W power supplies, use fine-stranded copper conductors rated for 90-degrees Celsius 
    for North American installations. 
    NoteThe 6000 W DC-input power supply provides voltages of 2800 W, 4500 W, or 6000 W. Select 
    2800 W by wiring any two positive (+)/negative (-) terminal pairs in any sequence. Select 
    4500 W by wiring any three positive (+)/negative (-) terminal pairs in any sequence. Select 
    6000 W by wiring all four terminals. The Cisco IOS software detects the wired inputs and sets 
    the proper system power. 
    NoteIf you are wiring for 2800 W for a single power supply, proceed to Step 7; if you are wiring 
    2800 W for a redundant power supply, proceed to Step 7 and then Step 10. In either case, proceed 
    to step 14 upon completion.
    NoteIf you are wiring for 4500 W for a single power supply, proceed to Step 8; if you are wiring 
    4500 W for a redundant power supply, proceed to Step 8 and then Step 11. In either case, proceed 
    to step 14 upon completion.
    NoteIf you are wiring for 6000 W for a single power supply, proceed to Step 9; if you are wiring 
    6000 W for a redundant power supply, proceed to Step 9 and then Step 12. In either case, proceed 
    to step 14 upon completion. 
    						
    							1-68
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Chapter 1      Removal and Replacement Procedures
      Removing and Installing the DC-Input Power Supplies
    Step 6Wire for 2800 W (left side of power supply bay) as follows:
    a.From the left side of the power supply, connect the ground wire to the ground (Figure 1-48).
    Figure 1-48 DC-Input Wire Connections for 2700-W DC-Input Power Supply for Left Side of Power 
    Bay
    b.
    From the left side of the power supply, connect each of the DC-input wires to the terminal block 
    (Figure 1-48 and Figure 1-49) in this order:
    Negative (-) 
    Positive (+) 
    NoteWhen you tighten the terminal nuts, make sure they are snug. Do not over tighten them. 
    Recommended torque strength is 20 inch-pounds. Over tightening the terminal nuts can break 
    the terminal block (Maximum torque: 36 inch-pounds). 
    c.Secure outer block cover.
    Step 7Wire for 4500 W (left side of power supply bay) as follows:
    a.From the left side of the power supply, connect the ground wire to the ground (see Figure 1-49).
    191287
    RUNINSTALL
    CISCO SYSTEMS, INC1
    2
    34
    INPUT OKFA N
    OKOUTPUT
    FAIL
    Captive 
    installation
    screw
    Terminal
    block cover
    ( - ) Negative
    (+)  Positive
    ( - ) Negative
    (+)  PositivePower leads
    attached to
    terminal block
    (   ) Ground Input power
    module
    Power
    switch 
    						
    							1-69
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Chapter 1      Removal and Replacement Procedures
      Removing and Installing the DC-Input Power Supplies
    Figure 1-49 DC-Input Wire Connections for 4000-W DC-Input Power Supply for Left Side of Power 
    Bay
    b.
    From the left side of the power supply, connect each of the DC-input wires to the terminal block in 
    this order (see Figure 1-47 and Figure 1-49): 
    Negative (-) 
    Positive (+) 
    NoteWhen you tighten the terminal nuts, make sure they are snug. Do not over tighten them. 
    Recommended torque strength is 20 inch-pounds. Over tightening the terminal nuts can 
    break the terminal block (Maximum torque: 36 inch-pounds). 
    c.Secure outer block cover.
    Step 8Wire for 6000 W (left side of power supply bay) as follows:
    a.From the left side of the power supply, connect the ground wire to the ground (see Figure 1-50).
    191288
    RUNINSTALL
    CISCO SYSTEMS, INC1
    2
    34
    INPUT OKFA N
    OKOUTPUT
    FAIL
    Terminal
    block cover
    Power leads
    attached to
    terminal block
    (   ) Ground Input power
    module
    ( - ) Negative
    (+)  Positive
    ( - ) Negative
    (+)  Positive
    ( - ) Negative
    (+)  Positive
    Captive 
    installation
    screw
    Power
    switch 
    						
    							1-70
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Chapter 1      Removal and Replacement Procedures
      Removing and Installing the DC-Input Power Supplies
    Figure 1-50 DC-Input Wire Connections for 6000-W DC-Input Power Supply for Left Side of Power 
    Bay
    b.
    From the left side of the power supply, connect each of the DC-input wires to the terminal block in 
    this order (see Figure 1-47 and Figure 1-50):
    Negative (-) 
    Positive (+) 
    NoteWhen you tighten the terminal nuts, make sure they are snug. Do not over tighten them. 
    Recommended torque strength is 20 inch-pounds. Over tightening the terminal nuts can 
    break the terminal block (Maximum torque: 36 inch-pounds).
    Step 9Wire for 2800 W (right side of power supply bay) as follows:
    a.From the right side of the power supply, connect the ground wire to the ground (see Figure 1-51).
    191289
    RUNINSTALL
    CISCO SYSTEMS, INC1
    2
    34
    INPUT OKFA N
    OKOUTPUT
    FAIL
    Terminal
    block cover
    Power leads
    attached to
    terminal block
    (   ) Ground Input power
    module
    ( - ) Negative
    (+)  Positive
    ( - ) Negative
    (+)  Positive
    ( - ) Negative
    (+)  Positive
    ( - ) Negative
    (+)  Positive
    Captive 
    installation
    screw
    Power
    switch 
    						
    							1-71
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Chapter 1      Removal and Replacement Procedures
      Removing and Installing the DC-Input Power Supplies
    Figure 1-51 DC-Input Wire Connections for 2700-W DC-Input Power Supply, Right Side of Power 
    Bay
    b.
    From the right side of the power supply, connect the DC-input wires to the terminal block (see 
    Figure 1-47 and Figure 1-51) in this order:
    Negative (-) 
    Positive (+) 
    NoteWhen you tighten the terminal nuts, make sure they are snug. Do not over tighten them. 
    Recommended torque strength is 20 inch-pounds. Over tightening the terminal nuts can break 
    the terminal block (Maximum torque: 36 inch-pounds). 
    c.Secure outer block cover.
    NoteFor proper 2800W DC-input redundant power configuration, both pairs of input wires for one 
    6000W DC-input power supply must come from the same battery system (A feed); both pairs of 
    input wires for the other 6000W DC-input power supply must come from another battery system 
    (B feed).
    191290
    RUNINSTALL
    CISCO SYSTEMS, INC1
    2
    34
    INPUT OKFA N
    OKOUTPUT
    FA I L
    Captive 
    installation
    screw
    Terminal
    block cover
    ( - ) Negative
    (+)  Positive
    ( - ) Negative
    (+)  PositivePower leads
    attached to
    terminal block
    (   ) Ground Input power
    module
    Power
    switch 
    						
    							1-72
    Catalyst 6500 Series Switches Installation Guide
    OL-5781-08
    Chapter 1      Removal and Replacement Procedures
      Removing and Installing the DC-Input Power Supplies
    NoteFor multiple DC input power supply, each DC input must be protected by dedicated circuit 
    breaker or fuse. The circuit breaker or fuse should be sized according to the power supply input 
    rating and local or national electrical code requirements.
    Step 10Wire for 4500 W (right side of power supply bay) as follows:
    a.From the right side of the power supply, connect the ground wire to the ground (see Figure 1-52).
    Figure 1-52 DC-Input Wire Connections for 4000-W DC-Input Power Supply, Right Side of Power 
    Bay
    b.\
    From the right side of the power supply, connect each of the DC-input wires to the right power 
    supply terminal block (see Figure 1-47 and Figure 1-52) in this order:
    Negative (-) 
    Positive (+) 
    NoteWhen you tighten the terminal nuts, make sure they are snug. Do not over tighten them. 
    Recommended torque strength is 20 inch-pounds. Over tightening the terminal nuts can 
    break the terminal block (Maximum torque: 36 inch-pounds). 
    c.Secure outer block cover.
    191291
    RUNINSTALL
    CISCO SYSTEMS, INC1
    2
    34
    INPUT OKFA N
    OKOUTPUT
    FA I L
    Terminal
    block cover
    Power leads
    attached to
    terminal block
    (   ) Ground Input power
    module
    ( - ) Negative
    (+)  Positive
    ( - ) Negative
    (+)  Positive
    ( - ) Negative
    (+)  Positive
    Captive 
    installation
    screw
    Power
    switch 
    						