    							Parameter Settings for Keypad Entry
    Appendix C
    C–4
    A034 Multi-speed 14 setting0.00 0.00 0.00
    A035 Multi-speed 15 setting 0.00 0.00 0.00
    A038 Jog frequency setting 1.00 1.00 1.00
    A039 Jog stop mode 00 00 00
    A041 Torque boost method selection 00 00 00
    A241 Torque boost method selection, 2nd motor 00 00 00
    A042 Manual torque boost value 1.0 1.0 1.0
    A242 Manual torque boost value, 2nd motor 1.0 1.0 1.0
    A342 Manual torque boost value, 3rd motor 1.0 1.0 1.0
    A043 Manual torque boost frequency adjustment 5.0 5.0 5.0
    A243 Manual torque boost frequency adjustment, 2nd  motor 5.0 5.0 5.0
    A343 Manual torque boost frequency adjustment, 3rd  motor 5.0 5.0 5.0
    A044 V/F characteristic curve selection 00 00 00
    A244 V/F characteristic curve selection, 2nd motor 00 00 00
    A344 V/F characteristic curve selection, 3rd motor 00 00 00
    A045 V/f gain setting 100. 100. 100.
    A046 Automatic torque boost voltage gain 100. 100. 100.
    A246 Automatic torque boost voltage gain, 2nd motor 100. 100. 100.
    A047 Automatic torque boost slip gain 100. 100. 100.
    A247 Automatic torque boost slip gain, 2nd motor 100. 100. 100.
    A051 DC braking enable 00 00 00
    A052 DC braking frequency setting 0.50 0.50 0.50
    A053 DC braking wait time 0.0 0.0 0.0
    A054 DC braking force during deceleration 0. 0. 0.
    A055 DC braking time for deceleration 0.0 0.0 0.0
    A056 DC braking / edge or level detection for [DB] input 01 01 01
    A057 DC braking force for starting 0. 0. 0.
    A058 DC braking time for starting 0.0 0.0 0.0
    A059 DC braking carrier frequency setting 5.0 5.0 5.0
    A061 Frequency upper limit setting 0.00 0.00 0.00
    A261 Frequency upper limit setting, 2nd motor 0.00 0.00 0.00
    A062 Frequency lower limit setting 0.00 0.00 0.00
    A262 Frequency lower limit  setting, 2nd motor0.00 0.00 0.00
    A063, 
    A065, 
    A067 Jump (center) frequency setting
    0.00 0.00 0.00
    “A” Group ParametersDefault Setting
    User 
    Setting
    Func. 
    CodeNameFEF2, FE2  (Europe)FU2, FU2 (U.S.A.)FF2, F2 (Japan)
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Appendix C
    C–5
    A064, 
    A066, 
    A068Jump (hysteresis) frequency width setting 0.50 0.50 0.50
    A069 Acceleration stop frequency setting 0.00 0.00 0.00
    A070 Acceleration stop time frequency setting 0.0 0.0 0.0
    A071 PID Function Enable 00 00 00
    A072 PID proportional gain 1.0 1.0 1.0
    A073 PID integral time constant 1.0 1.0 1.0
    A074 PID derivative gain 0.0 0.0 0.0
    A075 PV scale conversion 1.00 1.00 1.00
    A076 PV source setting 00 00 00
    A077 Reverse PID action 00 00 00
    A078 PID output limit 0.00 0.00 0.00
    A079 PID feed forward select 00 00 00
    A081 AVR function select 00 00 02
    A082 AVR voltage select 230/400 230/460 200/400
    A085 Operation mode selection 00 00 00
    A086 Energy saving mode tuning 50.0 50.0 50.0
    A092 Acceleration (2) time setting 15.0 15.0 15.0
    A292 Acceleration (2) time setting, 2nd motor 15.0 15.0 15.0
    A392 Acceleration (2) time setting, 3rd motor 15.0 15.0 15.0
    A093 Deceleration (2) time setting 15.0 15.0 15.0
    A293 Deceleration (2) time setting, 2nd motor 15.0 15.0 15.0
    A393 Deceleration (2) time setting, 3rd motor 15.0 15.0 15.0
    A094 Select method to switch to Acc2/Dec2 profile 00 00 00
    A294 Select method to switch to Acc2/Dec2, 2nd motor 00 00 00
    A095 Acc1 to Acc2 frequency transition point 0.0 0.0 0.0
    A295 Acc1 to Acc2 frequency transition point, 2nd  motor 0.0 0.0 0.0
    A096 Dec1 to Dec2 frequency transition point 0.0 0.0 0.0
    A296 Dec1 to Dec2 frequency transition point, 2nd  motor 0.0 0.0 0.0
    A097 Acceleration curve selection 00 00 00
    A098 Deceleration curve setting 00 00 00
    A101 [OI]–[L] input active ra nge start frequency 0.00 0.00 0.00
    A102 [OI]–[L] input active range end frequency 0.00 0.00 0.00
    A103 [OI]–[L] input active  range start current 20. 20. 20.
    A104 [OI]–[L] input active range end current 100. 100. 100.
    “A” Group ParametersDefault Setting
    User 
    Setting
    Func. 
    CodeNameFEF2, FE2  (Europe)FU2, FU2 (U.S.A.)FF2, F2 (Japan)
    
    Phone: 800.894.0412   
    						
    							Parameter Settings for Keypad Entry
    Appendix C
    C–6
    A105 [OI]–[L] input start frequency enable01 01 01
    A111 [O2]–[L] input active range start frequency 0.00 0.00 0.00
    A112 [O2]–[L] input active  range end frequency 0.00 0.00 0.00
    A113 [O2]–[L] input active range start voltage –100. –100. –100.
    A114 [O2]–[L] input active range end voltage 100. 100. 100.
    A131 Acceleration curve constants setting 02 02 02
    A132 Deceleration curve constants setting 02 02 02
    A141 A input select for  calculate function 02 02 02
    A142 B input select for calculate function 03 03 03
    A143 Calculation symbol 00 00 00
    A145 ADD frequency 0.00 0.00 0.00
    A146 ADD direction select 00 00 00
    A150 EL-S curve acceleration ratio 1 25. 25. 25.
    A151 EL-S curve acceleration ratio 2 25. 25. 25.
    A152 EL-S curve acceleration ratio 3 25. 25. 25.
    A153 EL-S curve acceleration ratio 4 25. 25. 25.
    “A” Group ParametersDefault Setting
    User 
    Setting
    Func. 
    CodeNameFEF2, FE2  (Europe)FU2, FU2 (U.S.A.)FF2, F2 (Japan)
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Appendix C
    C–7
    Fine Tuning 
    Functions
    “B” Group ParametersDefault Setting
    User 
    Setting
    Func.  CodeNameFEF2, FE2  (Europe)FU2, FU2 (U.S.A.)FF2, F2 (Japan)
    B001 Selection of restart mode 00 00 00
    B002 Allowable under-voltage power failure time 1.0 1.0 1.0
    B003 Retry wait time before motor restart 1.0 1.0 1.0
    B004 Instantaneous power failure / under-voltage trip  alarm enable 00 00 00
    B005 Number of restarts on power failure / under-voltage  trip events 00 00 00
    B006 Phase loss detection enable 00 00 00
    B007 Restart frequency threshold 0.00 0.00 0.00
    B008 Retry after trip select 00 00 00
    B009 Retry after undervoltage select 00 00 00
    B010 Retry count select after overvoltage or overcurrent 3 33
    B011 Retry wait time after trip 1.0 1.0 1.0
    B012 Electronic thermal setting (calculated within the  inverter from current output) Rated current for each inverter
    B212 Electronic thermal setting (calculated within the  inverter from current output), 2nd motor Rated current for each inverter
    B312 Electronic thermal setting (calculated within the  inverter from current output), 3rd motor Rated current for each inverter
    B013 Electronic thermal characteristic 01 01 00
    B213 Electronic thermal characteristic, 2nd motor 01 01 00
    B313 Electronic thermal characteristic, 3rd motor 01 01 00
    B015 Free setting, electroni c thermal frequency (1) 0. 0. 0.
    B016 Free setting, electronic thermal current (1) 0.0 0.0 0.0
    B017 Free setting, electroni c thermal frequency (2) 0. 0. 0.
    B018 Free setting, electronic thermal current (2) 0.0 0.0 0.0
    B019 Free setting, electroni c thermal frequency (3) 0. 0. 0.
    B020 Free setting, electronic thermal current (3) 0.0 0.0 0.0
    B021 Overload restriction operation mode 01 01 01
    B022 Overload restriction  setting Rated current x 1.50
    B023 Deceleration rate at ove rload restriction1.0 1.0 1.0
    B024 Overload restriction  operation mode (2) 01 01 01
    B025 Overload restriction setting (2) Rated current x 1.50
    B026 Deceleration rate at overl oad restriction (2)1.00 1.00 1.00
    B027 Overcurrent suppression enable 01 01 01
    B028 Current limit for active frequency -matching restartRated current x 1.0
    
    Phone: 800.894.0412   
    						
    							Parameter Settings for Keypad Entry
    Appendix C
    C–8
    B029 Scan time constant for active freq. matching 0.50 0.50 0.50
    B030 Restart freq. select for  active freq. matching 00 00 00
    B031 Software lock mode selection 01 01 01
    B034 Run/power-on warning time 0. 0. 0.
    B035 Rotational direction restriction 00 00 00
    B036 Reduced voltage start selection 06 06 06
    B037 Function code display restriction 04 04 04
    B038 Initial display selection 01 01 01
    B039 Automatic user parameter function enable 00 00 00
    B040 Torque limit selection 00 00 00
    B041 Torque limit (1) (forward-driving in 4-quadrant  mode) 150. 150. 150.
    B042 Torque limit (2) (reverse-regenerating in  4-quadrant mode) 150. 150. 150.
    B043 Torque limit (3) (reverse-driving in 4-quadrant  mode) 150. 150. 150.
    B044 Torque limit (4) (forward-regenerating in  4-quadrant mode) 150. 150. 150.
    B045 Torque limit LADSTOP enable 00 00 00
    B046 Reverse Run protection enable 00 00 00
    B050 Controller deceleration  and stop on power loss 00 00 00
    B051 DC bus voltage trigger level during power loss 0.0 0.0 0.0
    B052 Over-voltage threshold during  power loss 360.0/720.0 360.0/720.0 360.0/720.0
    B053 Deceleration time setti ng during power loss 1.00 1.00 1.00
    B054 Initial output frequency decrease during power loss 0.00 0.00 0.00
    B055 Proportional gain setting for non-stop operation at  power loss 0.20 0.20 0.20
    B056 Integral time setting for non-stop operation at  power loss .100 .100 .100
    B060 [O] input max. limit level of window comparator 100 100 100
    B061 [O] input min. limit level of window comparator 0 0 0
    B062 [O] input hysteresis width of window comparator 0 0 0
    B063 [OI] input max. limit level of window comparator 100 100 100
    B064 [OI] input min. limit level of window comparator 0 0 0
    B065 [OI] input hysteresis width of window comparator 0 0 0
    B066 [O2] input maximum limit level of window  comparator 100 100 100
    B067 [O2] input minimum limit level of window  comparator –100 –100 –100
    “B” Group ParametersDefault Setting
    User 
    Setting
    Func. 
    CodeNameFEF2, FE2  (Europe)FU2, FU2 (U.S.A.)FF2, F2 (Japan)
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Appendix C
    C–9
    B068 [O2] input hysteresis width of window comparator 000
    B070 [O] input disconnect threshold 255(no) 255(no) 255(no)
    B071 [OI] input disconnect threshold 255(no) 255(no) 255(no)
    B072 [O2] input disconnect threshold 127(no) 127(no) 127(no)
    B078 Clear cumulative input power data 00 00 00
    B079 Cumulative input power display gain setting 111
    B082 Start frequency adjustment 0.50 0.50 0.50
    B083 Carrier frequency setting 3.0
    2.1
    1.9 3.0
    2.1
    1.93.0
    2.1
    1.9
    B084 Initialization mode (parameters or trip history) 00 00 00
    B085 Country code for initialization 01 02 00
    B086 Frequency scaling conversion factor 1.0 1.0 1.0
    B087 STOP key enable 00 00 00
    B088 Restart mode after FRS 00 00 00
    B089 Automatic carrier  frequency reduction
    B090 Dynamic braking usage ratio 0.0 0.0 0.0
    B091 Stop mode selection 00 00 00
    B092 Cooling fan control 00 00 00
    B095 Dynamic braking control 00 00 00
    B096 Dynamic braking activation level 360/720 360/720 360/720
    B098 Thermistor for thermal protection control 00 00 00
    B099 Thermal protection level setting 3000. 3000. 3000.
    B100 Free-setting V/f frequency (1) 0. 0. 0.
    B101 Free-setting V/f voltage (1) 0.0 0.0 0.0
    B102 Free-setting V/f frequency (2) 0. 0. 0.
    B103 Free-setting V/f voltage (2) 0.0 0.0 0.0
    B104 Free-setting V/f frequency (3) 0. 0. 0.
    B105 Free-setting V/f voltage (3) 0.0 0.0 0.0
    B106 Free-setting V/f frequency (4) 0. 0. 0.
    B107 Free-setting V/f voltage (4) 0.0 0.0 0.0
    B108 Free-setting V/f frequency (5) 0. 0. 0.
    B109 Free-setting V/f voltage (5) 0.0 0.0 0.0
    B110 Free-setting V/f frequency (6) 0. 0. 0.
    B111 Free-setting V/f voltage (6) 0.0 0.0 0.0
    B112 Free-setting V/f frequency (7) 0. 0. 0.
    B113 Free-setting V/f voltage (7) 0.0 0.0 0.0
    “B” Group ParametersDefault Setting
    User 
    Setting
    Func. 
    CodeNameFEF2, FE2  (Europe)FU2, FU2 (U.S.A.)FF2, F2 (Japan)
    
    Phone: 800.894.0412   
    						
    							Parameter Settings for Keypad Entry
    Appendix C
    C–10
    Intelligent 
    Terminal 
    Functions
    B120 Brake Control Enable00 00 00
    B121 Brake Wait Time for Release 0.00 0.00 0.00
    B122 Brake Wait Time for Acceleration 0.00 0.00 0.00
    B123 Brake Wait Time for Stopping 0.00 0.00 0.00
    B124 Brake Wait Time for Confirmation 0.00 0.00 0.00
    B125 Brake Release Frequency Setting 0.00 0.00 0.00
    B126 Brake Release Current Setting Rated current for each inverter
    B127 Braking frequency 0.00 0.00 0.00
    B130 Over-voltage LADSTOP enable 00 00 00
    B131 Over-voltage LADSTOP level 380/760 380/760 380/760
    B132 Acceleration and decelera tion rate at overvoltage 
    suppression 1.0 1.0 1.0
    B133 Overvoltage suppression proportional gain 0.50 0.50 0.50
    B134 Overvoltage suppression integral time 0.060 0.060 0.060
    “B” Group ParametersDefault Setting
    User 
    Setting
    Func. 
    CodeNameFEF2, FE2  (Europe)FU2, FU2 (U.S.A.)FF2, F2 (Japan)
    “C” Group ParametersDefault Setting
    User 
    Setting
    Func.  CodeNameFEF2, FE2  (Europe)FU2, FU2 (U.S.A.)FF2, F2 (Japan)
    C001 Terminal [1] function 18 18 18
    C002 Terminal [2] function 16 16 16
    C003 Terminal [3] function 06 06 06
    C004 Terminal [4] function 11 11 11
    C005 Terminal [5] function 09 09 09
    C006 Terminal [6] function 03 13 03
    C007 Terminal [7] function 02 02 02
    C008 Terminal [8] function 01 01 01
    C011 Terminal [1] active state 00 00 00
    C012 Terminal [2] active state 00 00 00
    C013 Terminal [3] active state 00 00 00
    C014 Terminal [4] active state 00 00 00
    C015 Terminal [5] active state 00 00 00
    C016 Terminal [6] active state 00 00 00
    C017 Terminal (7) active state 00 00 00
    C018 Terminal [8] active state 00 00 00
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Appendix C
    C–11
    C019 Terminal [FW] active state00 00 00
    C021 Terminal [11] function 01 01 01
    C022 Terminal [12] function 00 00 00
    C023 Terminal [13] function 03 03 03
    C024 Terminal [14] function 07 07 07
    C025 Terminal [15] function 08 08 08
    C026 Alarm relay terminal function 05 05 05
    C027 [FM] signal selection 00 00 00
    C028 [AM] signal selection 00 00 00
    C029 [AMI] signal selection 00 00 00
    C030 Digital current monitor refe rence valueRated current x 1.0
    C031 Terminal [11] active state 00 00 00
    C032 Terminal [12] active state 00 00 00
    C033 Terminal [13] active state 00 00 00
    C034 Terminal [14] active state 00 00 00
    C035 Terminal [15] active state 00 00 00
    C036 Alarm relay active  state 01 01 01
    C038 Low current indication  output mode select 01 01 01
    C039 Low current indication dete ction levelRated current x 1.0
    C040 Overload signal output mode 01 01 01
    C041 Overload level setting Rated current for each inverter
    C042 Frequency arrival sett ing for accel. 0.00 0.00 0.00
    C043 Arrival frequency setting for decel. 0.00 0.00 0.00
    C044 PID deviation level setting 3.0 3.0 3.0
    C045 Frequency arrival setting  for acceleration (2) 0.00 0.00 0.00
    C046 Frequency arrival setting fo r deceleration (2) 0.00 0.00 0.00
    C052 Maximum PID feedback (PV) data 0.00 0.00 0.00
    C053 Minimum PID feedback (PV) data 100.0 100.0 100.0
    C055 Over-torque (forward-driving) level setting 100. 100. 100.
    C056 Over-torque (reverse regenerating) level setting 100. 100. 100.
    C057 Over-torque (reverse driving) level setting 100. 100. 100.
    C058 Over-torque (forward regenerating) level setting 100. 100. 100.
    C061 Electronic thermal warning level setting 80. 80. 80.
    C062 Alarm code output 00 00 00
    C063 Zero speed detection level 0.00 0.00 0.00
    C064 Heatsink overheat warning level 120 120 120
    “C” Group ParametersDefault Setting
    User 
    Setting
    Func. 
    CodeNameFEF2, FE2  (Europe)FU2, FU2 (U.S.A.)FF2, F2 (Japan)
    
    Phone: 800.894.0412   
    						
    							Parameter Settings for Keypad Entry
    Appendix C
    C–12
    C071 Communication speed selection04 04 04
    C072 Node allocation 1. 1. 1.
    C073 Communication data length selection 77 7
    C074 Communication parity selection 00 00 00
    C075 Communication stop bit selection 11 1
    C076 Action upon communication error selection 02 02 02
    C077 Communication timeout before trip 0.00 0.00 0.00
    C078 Communication wait time 0. 0. 0.
    C079 Communication protocol select 00 00 00
    C081 [O] input span calibration Factory set Factory  set Factory set
    C082 [OI] input span calibration Factory set Factory  set Factory set
    C083 [O2] input span calibration Factory set Factory  set Factory set
    C085 Thermistor input tuning 105.0 105.0 105.0
    C086 [AM] terminal offset tuning 0.0 0.0 0.0
    C087 [AMI] terminal meter tuning 80. 80. 80.
    C088 [AMI] terminal offset tuning Factory set Factory set Factory set
    C091 Debug mode enable 00 00 00 Do not edit
    C101 Up/Down memory mode selection 00 00 00
    C102 Reset mode selection 00 00 00
    C103 Restart mode after reset 00 00 00
    C105 FM gain adjustment 100. 100. 100.
    C106 AM gain adjustment 100. 100. 100.
    C107 AMI gain adjustment 100. 100. 100.
    C109 AM bias adjustment 0. 0. 0.
    C110 AMI bias adjustment 20. 20. 20.
    C111 Overload setting (2) Rated current for each inverter model
    C121 [O] input zero calibration Factory set
    C122 [OI] input zero calibration Factory set
    C123 [O2] input zero calibration Factory set
    C130 Terminal [11] ON-delay time 0.0 0.0 0.0
    C131 Terminal [11] OFF-delay time 0.0 0.0 0.0
    C132 Terminal [12] ON-delay time 0.0 0.0 0.0
    C133 Terminal [12] OFF-delay time 0.0 0.0 0.0
    C134 Terminal [13] ON-delay time 0.0 0.0 0.0
    C135 Terminal [13] OFF-delay time 0.0 0.0 0.0
    C136 Terminal [14] ON-delay time 0.0 0.0 0.0
    “C” Group ParametersDefault Setting
    User 
    Setting
    Func. 
    CodeNameFEF2, FE2  (Europe)FU2, FU2 (U.S.A.)FF2, F2 (Japan)
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Appendix C
    C–13
    C137 Terminal [14] OFF-delay time0.0 0.0 0.0
    C138 Terminal [15] ON-delay time 0.0 0.0 0.0
    C139 Terminal [15] OFF-delay time 0.0 0.0 0.0
    C140 Relay output ON-delay time 0.0 0.0 0.0
    C141 Relay output OFF-delay time 0.0 0.0 0.0
    C142 Logic output 1 function A 00 00 00
    C143 Logic output 1 function B 00 00 00
    C144 Logic output 1 operator 00 00 00
    C145 Logic output 2 function A 00 00 00
    C146 Logic output 2 function B 00 00 00
    C147 Logic output 2 operator 00 00 00
    C148 Logic output 3 function A 00 00 00
    C149 Logic output 3 function B 00 00 00
    C150 Logic output 3 operator 00 00 00
    C151 Logic output 4 function A 00 00 00
    C152 Logic output 4 function B 00 00 00
    C153 Logic output 4 operator 00 00 00
    C154 Logic output 5 function A 00 00 00
    C155 Logic output 5 function B 00 00 00
    C156 Logic output 5 operator 00 00 00
    C157 Logic output 6 function A 00 00 00
    C158 Logic output 6 function B 00 00 00
    C159 Logic output 6 operator 00 00 00
    C160 Terminal [1] input response time setting 111
    C161 Terminal [2] input response time setting 111
    C162 Terminal [3] input response time setting 111
    C163 Terminal [4] input response time setting 111
    C164 Terminal [5] input response time setting 111
    C165 Terminal [6] input response time setting 111
    C166 Terminal [7] input response time setting 111
    C167 Terminal [8] input response time setting 111
    C168 Terminal [FW] input response time setting 111
    C169 Multi-speed position determination time 000
    “C” Group ParametersDefault Setting
    User 
    Setting
    Func. 
    CodeNameFEF2, FE2  (Europe)FU2, FU2 (U.S.A.)FF2, F2 (Japan)
    
    Phone: 800.894.0412   
    						