Home > Hitachi > Inverter > Hitachi Sj7002 Owners Manual

Hitachi Sj7002 Owners Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Hitachi Sj7002 Owners Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 913 Hitachi manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Using Intelligent Input Terminals
    Operations
    and Monitoring
    4–20
    Two - s t ag e
    Acceleration and 
    Deceleration   When terminal [2CH] is turned ON, the 
    inverter changes the rate of acceleration and 
    deceleration from  the initial settings (F002 
    and F003) to use the  second set of accelera-
    tion/deceleration values (A092 and A093). 
    When the terminal is turned OFF, the 
    inverter returns to the original acceleration 
    and deceleration time (F002 acceleration 
    time 1 and F003 deceleration time 1). Use 
    A092 (acceleration time 2) and A093 
    (deceleration time 2) to set the second stage 
    acceleration and de celeration times.
    In the graph shown above, the [2CH] signal become s active during acceleration. This causes the 
    inverter to switch from using acceler ation 1 (F002) to acceleration 2 (A092).
    Note the following:
     Function A094 selects the me thod for second stage acceleration.  It must be set = 00 to select 
    the input terminal method in order for the [2CH] terminal assi gnment to operate.
    Free-run Stop   When the terminal [FRS] is turned ON, the inverter turns OFF the output and the motor enters 
    the free-run state (coasting). If  terminal [FRS] is turned OFF, the output resumes sending power 
    to the motor if the Run command is still active. The free-run stop feature works with other 
    parameters to provide flexibility in  stopping and starting motor rotation.
    In the diagram below, parameter B088 selects whether the inverter resumes operation from 
    0 Hz (left graph) or the current motor rotation  speed (right graph) when the [FRS] terminal 
    turns OFF. The application de termines the best setting.
    Parameter B003 specifies a delay time before resuming operation from a free-run stop. To 
    disable this feature,  use a zero delay time.
    In the diagram above, [FRS] signal is active hi gh. If you want the [FRS] terminal to be active 
    low (normally closed logic), chan ge the setting (C011 to C018) that corresponds to the input [1] 
    to [8] that is assigned the [FRS] function (C001 to C008).
    Opt. Code09
    Symbol[2CH]
    Va l i d  f o r  
    Inputs[1] to [8]
    RequiredSettings A092, A093, 
    A094=0
    Default 
    terminal[5]
    Output
    frequency
    [FW, RV]
    t
    target frequency
    initial second
    Input
    signals
    [2CH]
    Opt. Code11
    Symbol[FRS]
    Va l i d  f o r  Inputs[1] to [8]
    RequiredSettings B003, B088, 
    C011 to C018
    Default 
    terminal[4]
    FRS
    Switches
    Motor 
    speed
    [FW, RV]
    Zero-frequency start
    FRS
    Switches
    Motor 
    speed
    Resume from current speed
    wait time
    [FW, RV]B003
    B088=01B088=00Resume from 0Hz tt
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–21
    External Trip   When the terminal [EXT] transitions OFF-to-ON,  the inverter enters the trip state, indicates 
    error code E12, and stops the output. This is a  general purpose interrupt type feature, and the 
    meaning of the error depends on what you connect  to the [EXT] terminal. Even if [EXT] is 
    turned OFF, the inverter remains in the trip stat e. You must reset the inverter or cycle power to 
    clear the error, returning the inverter to the Stop Mode.
    In the graph below, the [EXT] input turns ON during normal Run Mode operation. The inverter 
    lets the motor free-run to a stop, and the alarm output turns ON immediately. When the 
    operator initiates a Reset comman d, the alarm and error are cleared. When the Reset is turned 
    OFF, the motor begins rotation since the Run command is already active. 
    If the USP (Unattended Start Prot ection) feature is in use, the inverter will not automatically 
    restart after cancelling the EXT trip event. In  that case, it must receive either another Run 
    command (OFF-to-ON transition), a keypad Reset  command, or an [RS] intelligent terminal 
    input signal.
    Unattended Start 
    Protection   If the Run command is already present when powe r is turned ON, the inverter starts running 
    immediately after powerup. The Unattended Start Protection (USP) function prevents that 
    automatic startup. If the [USP] input is active, the inverter  will not run without outside interven-
    tion. In this case, there are two ways to reset an alarm and resume running:
    1. Turn the Run command OFF, or
    2. Perform a reset operation by the terminal [R S] input or the keypad Stop/reset key
    The three examples below show how the USP func tion works in the scenarios described at the 
    bottom of the diagram. The error code E13 indi cates the USP trip state and corresponds to the 
    Alarm  signal in the diagram. 
    Note the following;
     Note that when a USP error occurs and it is ca nceled by a reset from the [RS] terminal input 
    or keypad, the inverter restarts immediately.
     Even when the trip state is canceled by turn ing the terminal [RS] ON and OFF after an 
    under- voltage trip E09 occurs, the USP function will be performed.
    Opt. Code12
    Symbol[EXT]
    Valid for 
    Inputs[1] to [8]
    RequiredSettings (none)
    Default 
    terminal Requires 
    config.[EXT]
     [FW, RV]
    [RS]
    Motor revolution speed
    Alarm output terminal
    t
     free run
    Opt. Code13
    Symbol[USP]
    Valid for 
    Inputs[1] to [8]
    RequiredSettings (none)
    Default 
    terminal[6]*
    * Default for -FU2 models 
    only; others require input 
    configuration
    Powe r
    supply
    [FW]
    Output
    frequency
    When USP is ON after powerup, the 
    alarm (E13) will clear when the Run 
    command (FW or RV) turns OFF. [USP]
    [RS]
    AlarmIf the alarm is cleared 
    during Run command, 
    the inverter output 
    restarts automatically. If the Run command is 
    already OFF at powerup, 
    the inverter output starts 
    normally.
    Example 1 Example 2 Example 3
    t
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							Using Intelligent Input Terminals
    Operations
    and Monitoring
    4–22
     When the Run command is active immediately after the power is turned ON, a USP error  will occur. When this function is used, wait  for at least three (3) seconds after powerup 
    before applying a Run command.
    Commercial 
    Power Source 
    Enable   The commercial power source switching function is  useful in systems with excessive starting 
    torque requirements. This feature permits the mo tor to be started “across the line,” sometimes 
    called a  bypass configuration. After the motor is runnin g, the inverter takes over to control the 
    speed. This feature can eliminate the need to  oversize the inverter, reducing cost. However, 
    additional hardware such  as magnetic contactors wi ll be required to realize this function. For 
    example, a system may require  55KW to start, but only 15KW to run at constant speed. There-
    fore, a 15KW rated inverter would be suffic ient when using the commercial power source 
    switching.
    The [CS] Commercial Power Source Enable  input signal operation is as follows:
     OFF-to-ON transition signals the inverter that  the motor is already running at powerup (via 
    bypass), thus suppressing the inverter’s motor output in Run Mode.
     ON-to-OFF transition signals the inverter to a pply a time delay (B003), frequency match its 
    output to existing motor speed, and  resume normal Run Mode operation
    The following block diagram shows an inverter system with  bypass capability. When starting 
    the motor directly across the  line, relay contacts Mg2 are closed, and Mg1 and Mg3 are open. 
    This is the bypass configuration, since the inverter  is isolated from the power source and motor. 
    Then Mg1 contacts close about 0.5 to 1 second after that, supplying power to the inverter.
    Opt. Code14
    Symbol[CS]
    Va l i d  f o r  
    Inputs[1] to [8]
    RequiredSettings B003, B007
    Default 
    terminal Requires 
    config.
    U
    V
    W
    Motor
    R
    S
    T
    R0
    T0
    SJ7002
    H
    O
    L
    FW
    [RV]
    [CS]
    CM1
    Mg3
    MCCB
    Mg1
    GFI
    Mg2
    Thermal
    switch
    Power source, 3-phase
    AL0
    AL2
    AL1
    L1
    L2
    L3
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–23
    Switching to inverter control occurs after the mo tor is running at full speed. First, Mg2 relay 
    contacts open. Then about 0.5 to 1 seconds later, relay Mg3 contacts  close, connecting the 
    inverter to the motor. The following timing diagram shows the event sequence:
    In the previous timing diagram, when the mo tor has been started across the line, Mg2 is 
    switched OFF and Mg3 is switched ON. With the Forward command to the inverter already 
    ON, the [CS] terminal is switched ON and relay Mg 1 contacts close. The inverter will then read 
    the motor RPM (frequency matching). When the [C S] terminal is switched OFF, the inverter 
    applies the  Retry wait time before motor restar t parameter (B003).
    Once the delay time has elapsed the inverter wi ll then start and match the frequency (if greater 
    than the threshold set by B007). If an over-current trip occurs during frequency matching, 
    extend the retry wait time B003. If the ground  fault interrupter breaker (GFI) trips on a ground 
    fault, the bypass circuit will not operate the mo tor. When an inverter backup is required, take 
    the supply from the bypass circuit GFI. Use  control relays for [FW], [RV], and [CS]. 
    Software Lock   When the terminal [SFT] is ON, the data of all the parameters and func tions (except the output 
    frequency, depending on the setting of B031) is locked (prohibited from editing). The keypad 
    and remote programming devices will be preven ted from changing parameters. To edit parame-
    ters again, turn OFF the [SFT] terminal input. Use parameter B031 to select whether the output 
    frequency is excluded from the lock state or is locked as well. Note the following:
     When the [SFT] terminal is  turned ON, only the output frequency can be changed.
     Software lock can include the output frequency by setting B031.
     Software lock by the operator is also possibl e without the [SFT] terminal being used (B031).
    Mg1
    Mg2
    Mg3
    FW
    [CS]
    Mg2/Mg3 delay time 0.5 to 1 sec.
    Set to 0.5 to 1 sec. typical
    Frequency matching
    Inverter output
    Normal operationB003 (Retry wait timebefore motor restart)
    Opt. Code15
    Symbol[SFT]
    Valid for 
    Inputs[1] to [8]
    RequiredSettings B031 
    (excluded 
    from lock)
    Default 
    terminal Requires 
    config.
    
    Phone: 800.894.0412   
    						
    							Using Intelligent Input Terminals
    Operations
    and Monitoring
    4–24
    Analog Input 
    Current/Voltage 
    Select   The [AT] terminal operates in c onjunction with parameter setting A005 to determine the analog 
    input terminals that are enabled for current or  voltage input. Setting A006 determines whether 
    the signal will be bipolar, allowing for a reverse direction range. Note th at current input signal 
    cannot be bipolar and cannot reverse direction  (must use [FW] and [RV] command with current 
    input operation). The basic operation of th e [AT] intelligent input is as follows:
     [AT] = ON and A005 = 00 –  [AT] will enable terminals [OI]–[L] for current input, 
    4to20mA
     [AT] = ON and A005 = 01 –  [AT] will enable terminals [O2]–[L] for voltage input
     [AT] = OFF –  Terminals [O]–[L] are enabled for vo ltage input (A005 may be equal to 
    00 or 01) in this case
    Be sure to set the frequency source setting A0 01=01 to select the analog input terminals. 
    Please refer to  “
    Analog Input Operation” on page 4–63 for more informati on on bipolar input 
    configuration, and the operating ch aracteristics of analog inputs.
    Reset Inverter   The [RS] terminal causes the inverter to 
    turn OFF the motor output and execute a 
    powerup reset. If the inverter is in Trip 
    Mode, the reset cancels the Trip state. 
    When the signal [RS] is turned ON and 
    OFF, the inverter executes the reset opera-
    tion. The minimum pulse width for [RS] 
    must be 12 ms or greater. The alarm output 
    will be cleared within 30 ms after the onset 
    of the Reset command. Note the following:
     When the control terminal [RS]  input is already ON at powerup for more than 4 seconds, the 
    remote operator display is “R-ERROR COMM”  (the display of the digital operator is 
    –  –  –  –). However, the inverter has no error. To clear the digital operator error, turn OFF the 
    terminal [RS] input and press one of the operator keys.
     The active edge (leading or trailing) of the [R S] signal is determined by the setting of C102.
     A terminal configured with the [RS] functi on can only be configured as a normally open 
    contact. The terminal cannot be used in the normally closed contact state.
     When input power is turned ON, the inverter performs the same reset operation as it does  when a pulse on the [RS] terminal occurs.
    NOTE:  For inverter models –1850Hxx to –4000Hxx: Af ter an external reset input [RS] occurs, 
    the internal cooling fan turn ON after stopping once.
    WARNING: After the Reset command is given and th e alarm reset occurs, the motor will 
    restart suddenly if the Run command is already  active. Be sure to set the alarm reset after 
    verifying that the Run command is OFF to prevent injury to personnel.
    Opt. Code16
    Symbol[AT]
    Va l i d  f o r  
    Inputs[1] to [8]
    RequiredSettings A001 = 01
    A005 = 00 /  01
    A006 = 00 / 
    01 / 02
    Default 
    terminal[2]
    Opt. Code18
    Symbol[RS]
    Va l i d  f o r   Inputs[1] to [8]
    RequiredSettings B003, B007, 
    C102, C103
    Default 
    terminal[1]
    [RS]
    Alarm  output
    t
    12 ms
    minimum
    approx. 30 ms
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–25
    Thermistor 
    Thermal
    Protection   Motors that are equipped with a thermistor ca n be protected from overheating. Input terminal 
    [TH] is dedicated to sense ther mistor resistance. The input can be set up (via B098 and B099) 
    to accept a wide variety of NTC  or PTC type thermistors. Use this function to protect the motor 
    from overheating.
    When a thermistor is connected between terminals [TH] 
    and [CM1], the inverter checks for over-temperature and 
    will cause a trip (E35) and turn OFF the output to the 
    motor. Be sure the thermistor is connected to terminals 
    [TH] and [CM1]. If the resistance is above or below 
    (depending on whether NTC or PTC) the threshold the 
    inverter will trip. When the motor cools down enough, the 
    thermistor resistance will ch ange enough to permit you to 
    clear the error. Press the STOP/Reset key to clear the error.
    An open circuit in the thermistor causes a trip, and the 
    inverter turns OFF the motor output.
    Three-wire
    Interface
    Operation   The 3-wire interface is an industry standard motor control interface. This function uses two 
    inputs for momentary contact start/stop control, and a third for selecting forward or reverse 
    direction.
    To implement the 3-wire interface, assign 20  [STA] (Start), 21 [STP] (Stop), and 22 [F/R] 
    (Forward/Reverse) to three of the intelligent input terminals. Use momentary contacts for Start 
    and Stop. Use a selector switch, such as SPST for  the Forward/Reverse input. Be sure to set the 
    operation command selection A002=01 for input terminal control of motor. Note the following:
     If you have a motor control interface that ne eds logic-level control (rather than momentary 
    pulse control), use the [FW] and [RV] inputs instead.
     The STP logic is inverted. Normally the switch  will be closed, so you open the switch to 
    stop. In this way, a broken wire causes the motor to stop automatically (safe design).
     When you configure the inverter for 3-wire interface control, the dedicated [FW] terminal is  automatically disabled. The [RV] intelligen t terminal assignment is also disabled.
    The diagram below shows the use of 3-wire control. STA (Start Motor) is an edge-sensitive 
    input; an OFF-to-ON transition gives the Start command. The control of direction is level-
    sensitive, and the direction may be changed at any time. STP (Stop Motor) is also a level-
    sensitive input.
    Opt. Code—
    Symbol[TH]
    Valid for  Inputs [TH only]
    Required
    Settings B098, B099, 
    and C085
    Default 
    terminal[TH]
    531
    7642
    8FWTH
    PLC
    CM1
    P24CM1
    TH
    thermistor
    Motor
    Opt. Code  and 
    Symbol20=[STA]
    21=[STP]
    22=F/R
    Valid for  Inputs[1] to [8]
    RequiredSettings A002=01
    Default 
    terminal Requires 
    config.
    SymbolFunction NameDescription
    STA Start Motor Start motor rotation  on momentary contact (uses accel-
    eration profile)
    STP Stop Motor Stop motor rotation on momentary open (OFF is active  state), (uses deceleration profile)
    F/R Forward/Reverse ON = Reverse; OFF = Forward
    [STA] terminal
    [F/R] terminal
    [STP] terminal
    Motor revolution speed
    Forward Reverse
    t
    
    Phone: 800.894.0412   
    						
    							Using Intelligent Input Terminals
    Operations
    and Monitoring
    4–26
    PID Disable
    and PID Clear   The PID loop function is useful for controlling  motor speed to achieve constant flow, pressure, 
    temperature, etc. in many process applications. 
    PID Disable –  This function temporarily suspends PID  loop execution via an intelligent input 
    terminal. It overrides the parameter A071 (PID  Enable) to stop PID execution and return to 
    normal motor frequency output char acteristics. the use of PID Disable on an intelligent input 
    terminal is optional. Of course, any use of  the PID loop control requires setting PID Enable 
    function A071=01.
    PID Clear –  This function forces the PID loop integrator sum = 0. So, when you turn ON an 
    intelligent input configured as [PIDC], the integrat or sum is reset to zero. This is useful when 
    switching from manual control to PID  loop control and the motor is stopped.
    Note the following:
     The use of [PID] and [PIDC] terminals are  optional. Use A071=01 if you want PID loop 
    control enabled all the time.
     Do not enable/disable PID control while the motor is running (inverter is in Run Mode).
     Do not turn ON the [PIDC] input while the  motor is running (inverter is in Run Mode).
    CAUTION: Be careful not to turn PID Clear ON and re set the integrator sum when the inverter 
    is in Run Mode (output to motor is ON). Otherwise, this could cause the motor to decelerate 
    rapidly, resulting in a trip.
    Internal Speed 
    Loop Gain 
    Settings   When sensorless vector control, 0Hz sensorless vector control, or vector control with sensor is 
    selected for the control method, the Control Gain  Switching function selects between two sets 
    of gains in the internal speed loop. These gains  are used in proportional and integral compensa-
    tion. When Control Gain Switchi ng is not selected for an intelligent input terminal, the default 
    gains in effect correspond to the OFF state of [CAS].
    Use [PPI] P/PI Control Switching to select be tween proportional and proportional-integral 
    control.
    The table below lists the functions and parameter se ttings related to internal speed loop gains. 
    Opt. Code 
    and 
    Symbol23=[PID]
    24=[PIDC]
    Va l i d  f o r   Inputs[1] to [8]
    Required
    Settings A071
    Default 
    terminal Requires 
    config.
    Opt. Code 
    and 
    Symbol26=[CAS]
    43=[PPI]
    Va l i d  f o r   Inputs[1] to [8]
    Required
    Settings A044 / A244 
    / A344 = 03, 
    04, or 05
    Default 
    terminal Requires 
    config.
    SymbolFunction NameInput 
    StateDescription
    CAS Control Gain Switching ON Gains in  parameters H070, H071, and H072 
    are selected
    OFF Gains in parameters H050, H051, H052; or,  H250, H251, H252 (2nd motor) are selected
    PPI P / PI Control Switching ON Sel ects Proportional control (P)
    OFF Selects Proportional-Integral control (PI)
    Function CodeParameterSetting RangeDescription
    A044 / A244 / A344 Control method 
    selection 03 SLV (does not use A344)
    04 0-Hz Domain SLV (does not 
    use A344) 
    05 V2 (does not use A244 or  A344)
    C001 - C008 Intelligent input  selection 43 PPI : P/I switching
    H005 / H205 Speed response 0.001 to 65.53 No dimension
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–27
    The speed control mode is normally proportional-
    integral compensation (PI), which attempts to 
    keep the deviation betwee n the actual speed and 
    speed command equal to zero. You can also select 
    proportional (P) control function, which can be 
    used for  droop control (i.e. several inverters 
    driving one load).  Droop is the speed difference 
    resulting from P control versus PI control at 100% 
    output torque as shown in the graph. Set the P/PI 
    switching function (option 43) to one of the intel-
    ligent input terminals [1] to [8]. When the P/PI 
    input terminal is ON, th e control mode becomes 
    proportional control (P). When the P/PI input 
    terminal is OFF, the control mode becomes 
    proportional-integral control.
    The proportional gain Kpp value determines the 
    droop. Set the desired  value using parameter 
    H052. The relationship between the Kpp  value and the droop is shown below: 
    The relationship between the droop and th e rated rotation speed is shown below:
    H050 / H250 PI proportional gain 0.0 to 999.9/1000 % gain
    H051 / H251 PI integral gain 0.0 to 999.9/1000 % gain
    H052 / H252 P proportional gain 0.01 to 10.00 No dimension
    H070 PI proportional gain 
    for switching 0.0 to 999.9/1000 % gain
    H071 PI integral gain for  switching 0.0 to 999.9/1000 % gain
    H072 P proportional gain  for switching 0.0 to 10.0 No dimension
    H073 Gain switching time 0. to 999. Millisceonds
    Function CodeParameterSetting RangeDescription
    0 Speed of rotation
    Torque
    P Control
    Droop
    100% PI Control
    Droop
    10
    (Kpp Set Value)--------------------------------%
    ()
    =
    Droop Speed error at rated torque
    Synchronous speed base frequency
    --------------------------------------------------------------------- -=
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							Using Intelligent Input Terminals
    Operations
    and Monitoring
    4–28
    Remote Control 
    Up and Down 
    Functions   The [UP] [DWN] terminal functions can adjust the output frequency for remote control while 
    the motor is running. The acceleration time and deceleration time used with this function is the 
    same as for normal operation ACC1 and DEC1  (2ACC1,2DEC1). The input terminals operate 
    as follows:
    In the graph below, the [UP] and [DWN] terminals activate while the Run command remains 
    ON. The output frequency responds to the [UP] and [DWN] commands. 
    It is possible for the inverter to retain the frequency set from the [UP] and [DWN] terminals 
    through a power loss. Parameter C101 enables/di sables the memory. If disabled, the inverter 
    retains the last frequency before an UP/DWN ad justment. Use the [UDC] terminal to clear the 
    memory and return to the original set output frequency.
    Force Operation 
    from Digital 
    Operator   This function permits a digital operator interfac e to override the Run command source setting 
    (A002) when it is configured for a source other than the operator interface. When the [OPE] 
    terminal is ON, the operator interface Run  command over-rides commands from input termi-
    nals (such as [FW], [RV]). The inverter will use the standard output  frequency settings to 
    operate the motor. When the [OPE] terminal is  OFF, the Run command operates normally, as 
    configured by A002.
    When changing the [OPE] state during Run Mode  (inverter is driving the motor), the inverter 
    will stop the motor before the new [OPE] state  takes effect. If the [OPE] input turns ON and the 
    digital operator gives a Run comm and while the inverter is already running, the inverter stops 
    the motor. Then the digital operator can control the motor.
    Opt. Code 
    and 
    Symbol27=[UP]
    28=[DWN]
    29=[UDC]
    Va l i d  f o r   Inputs[1] to [8]
    RequiredSettings A001 = 02;
    C101 = 01  (enables 
    memory)
    Default 
    terminal Requires 
    config.
    SymbolFunction NameDescription
    UP Remote Control UP Function Accelerate s (increases output frequency) motor 
    from current frequency
    DWN Remote Control DOWN  Function Decelerates (decreas
    es output frequency)
     motor 
    from current frequency
    UDC Remote Control Data Clear Clears the Up/down frequency memory
    Output
    frequency
    [UP]
    [FW, RV] [DWN]
    t
    Opt. Code31
    Symbol[OPE]
    Va l i d  f o r  
    Inputs[1] to [8]
    RequiredSettings A001,
    A002 (set not 
    equal to 02)
    Default 
    terminal Requires 
    config.
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–29
    Overload
    Restriction   The inverter constantly moni tors the motor current during  acceleration, deceleration, and 
    constant speed. If the inverter reaches the ove rload restriction level, it adjusts the output 
    frequency automatically to limit the amount of  overload. This function prevents an over-current 
    trip by inertia during rapid acce leration or large changes in load  at constant speed. It also 
    attempts to prevent an over-voltage trip on dece leration due to regeneration. It accomplishes 
    this by temporarily suspending  deceleration and/or increasing th e frequency in order to dissi-
    pate regenerative energy. Once the DC bus volt age falls sufficiently, deceleration will resume.
    OLR Parameter Selection  – Two sets of overload restriction parameter settings and values are 
    available as outlined in the table below.
    Use the B021—B026 group of settings to config ure the two set of parameters as needed. By 
    assigning the Overload Restriction function [OLR] to an intelligent terminal, you can select the 
    set of restriction paramete rs that is in effect.
    Note the following:
     If the overload restriction constant (B023 or  B026) is set too short, an over-voltage trip 
    during deceleration will occur due to regenerative energy from the motor.
     When an overload restri ction occurs during acceleration, the motor will take longer to reach 
    the target frequency, or may not reach it. The  inverter will make the following adjustments:
    a) Increase the acceleration time
    b) Raise torque boost
    c) Raise overload restriction level
    Opt. Code39
    Symbol[OLR]
    Valid for 
    Inputs[1] to [8]
    RequiredSettings B021 – B023 
    (Set 1), 
    B024 – B026 
    (Set 2)
    Default 
    terminal Requires 
    config.
    SymbolFunction NameInput 
    StateDescription
    OLR Overload Restriction  Selection ON Selects Overload Restriction Set 2,
    B024, B025, B026 settings in effect
    OFF Selects Overload Restriction Set 1, B021, B022, B023 settings in effect
    Function
    Function Code
    Data or RangeDescription
    Set 1Set 2
    Overload Restriction 
    Operation Mode B021 B024 00 Disable
    01 Enabled during accel and constant speed
    02 Enabled during constant  speed
    03 Enabled during accel,  constant speed, and 
    decel
    Overload Restriction 
    Setting B022 B025 Rated current * 0.5 
    to rated current * 2Current value at which 
    the restriction begins
    Deceleration Rate at 
    Overload Restriction B023 B026 0.1 to 30 seconds Deceleration time when 
    overload restriction 
    operates
    
    Phone: 800.894.0412   
    						
    All Hitachi manuals Comments (0)