Home > Hitachi > Inverter > Hitachi Sj7002 Owners Manual

Hitachi Sj7002 Owners Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Hitachi Sj7002 Owners Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 913 Hitachi manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Using Intelligent Input Terminals
    Operations
    and Monitoring
    4–30
    The figure below shows the operation during  an overload restriction event. The overload 
    restriction level is set by B022 and B025. The overl oad restriction constant is the time to decel-
    erate to 0Hz from maximum frequency. When this fu nction operates, the acceleration time will 
    be longer than the normal acceleration time. 
    NOTE: The Overload Advance Notice function for intelligent outputs is related to Overload 
    Restriction operatio n, discussed in “Overload Advance Notice Signal” on page 4–46.
    Torque Limit   The Torque Limit function limits the motor output  torque for sensorless vector control, sensor-
    less vector control 0Hz domain, or vector control with feedback. Three intelligent inputs 
    control the Torque Limit function:
    In the torque limit function, the following oper ational modes are available (selected by B040):
    1. Four-quadrant individual setting mode – This  mode sets torque limit in 4 zones, forward 
    driving and regenerating, revers e driving and regenerating. Limits for each quadrant are set 
    with B041 – B044 individually.
    2. Terminal selection mode –  By use of torque limit 
    select intelligent input te rminals 1 and 2, this mode 
    changes and uses torque limits 1 – 4 set in B041 – 
    B044. Selected torque limit ra nge is valid in all four 
    quadrants. Inputs TRQ1 a nd TRQ2 apply only to 
    terminal selection mode.
    3. Analog input mode – This mode sets torque limit value 
    by the voltage applied to te rminal [O2] (referenced to 
    [L] for ground. An input of 0 – 10V corresponds to the 
    torque limit value of 0 to 200%. The selected torque 
    limit value is valid in all four quadrants (whether 
    forward or reverse move, driving or regenerating).
    4. Expansion Cards 1 and 2 – This function is  valid when using the expansion card (SJ-DG). 
    Please refer to the SJ-DG instruction manual.
    Overload
    restriction level
    Maximum 
    frequency
    Output
    frequency
    Target frequency
    Deceleration rate at overload restriction
    Deceleration rate
    at overload restriction
    A004
    F001
    B022 / B025
    B023 / B026
    B022 / B025
    t
    Opt. Code and 
    Symbol40=[TL]
    41=[TRQ1]
    42=[TRQ2]
    Va l i d  f o r   Inputs[1] to [8]
    Required
    Settings B040, B041, 
    B042, B043, 
    B044
    Default 
    terminal Requires 
    config.
    SymbolFunction NameDescription
    TL Torque limit enable Enables to rque limit function when ON
    TRQ1 Torque limit select 1, Bit 1 (LSB) B inary encoded bit for quadrant select
    TRQ2 Torque limit select 2, Bit 2 (MSB) B inary encoded bit for quadrant select
    Intelligent 
    InputsTorque limit parameter
    TRQ2TRQ1
    OFF OFF B041
    OFF ON B042 ON OFF B043
    ON ON B044
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–31
    When the torque limit enable function [TL] is assigned to an intelligent input terminal, torque 
    limiting occurs only when [TL] is ON. Both the  4-quadrant mode and terminal switching mode 
    of torque limiting use input [TL] for enable/disab le. When the [TL] input is OFF, the inverter 
    always uses the default torque control limit of  200% maximum. That torque limit value corre-
    sponds to 200% of the maximum inverter output current. Therefore, the output torque also 
    depends on the particular motor in use. When th e over-torque output [OTQ] is assigned in the 
    intelligent output selection, it turns ON when th e inverter is performing torque limiting. When 
    using the torque limit function at low spee d, also use the overload restriction feature.
    Note 1: Unavailable for A344
    Note 2: Unavailable for A244 and A344
    The 4-quadrant operation mode for torque 
    limiting (B040=00) is illustrated in the figure 
    to the right. The instantaneous torque depends 
    on inverter activity (acceleration, constant 
    speed, or deceleration),  as well as the load. 
    These factors determine  the operating quadrant 
    at any particular time.  The parameters in B041, 
    B042, B043 and B044 determine the amount of 
    torque limiting that the inverter applies.
    The terminal selectio n mode (B040=01) uses 
    two intelligent inputs  [TRQ1] and [TRQ2] for 
    the binary-encoded selection of one of the four 
    torque limit parameters B041, B042, B043 and 
    B044. 
    CodeFunctionData or RangeDescription
    A044 / A244 Control method 
    selection 00
    01
    02
    03
    04
    05V/f Constant torque
    V/f Variable torque
    V/f Free-setting torque *1
    Sensorless vector *1
    Sensorless vector, 0 Hz domain *1
    Vector control with sensor *2
    B040 Torque limitselection 00
    01
    02
    03
    044-quadrant indi
    vidual setting
    Terminal selection
    Analog [O2] input
    Expansion card 1
    Expansion card 2
    B041 Torque limit 1 0 to 200% Forward-driving in 4-quadrant mode
    B042 Torque limit 2 0 to 200% Reverse-regenerating in 4-quadrant  mode
    B043 Torque limit 3 0 to 200% Reverse-driving in 4-quadrant mode
    B044 Torque limit 4 0 to 200% Forward-regenerating in 4-quadrant  mode
    C001 to
    C008 Intelligent input 
    terminal [1] to [8] 
    function 40
    41
    42Torque limit enable
    Torque limit selection, bit 1 (LSB)
    Torque limit selection, bit 2 (MSB)
    C021 to
    C025 Intelligent output 
    terminal [11] to [15] 
    function 10 In torque limit
    Reverse-driving Forward-regenerating
    Reverse-regenerating Forward-driving
    Torque
    FW
    RV +
    B40=00
    B043B044
    B042B041
    
    Phone: 800.894.0412   
    						
    							Using Intelligent Input Terminals
    Operations
    and Monitoring
    4–32
    External Brake 
    Control Function   The External Brake Control function enables the inverter to control external electromechanical 
    brake systems with a particular safety characteristic. For example, elevator control systems 
    maintain the brake on the load until the drive motor has reached a  releasing frequency (point at 
    which the external mechanical brake is released).  This ensures that the load does not have an 
    opportunity to begin coasting befo re the inverter begins driving the motor. The External Brake 
    Control function can  be enabled by setting parameter B120=01.
    The diagram below shows the signals that are important to the External Brake Control function.
     Brake confirmation [BOK] turns ON to indicate that an external brake system has released  (is not engaged). If external brake control is enabled (B120=01), then the [BOK] signal must 
    work properly to avoid an inverter trip event.
     If [BOK] is not assigned to  an intelligent input, then setting B124 is ignored.
    The steps below describe th e timing diagram of events on the following page.
    1. When the Run command turns ON, the inverter be gins to operate and accelerate to releasing 
    frequency (B125).
    2. After the output frequency arrives at the set  releasing frequency (B125), the inverter waits 
    for the brake release confirmation, set by B121. The inverter outputs the braking release 
    signal [BRK]. However, if the output current of the inverter is less than the releasing current 
    set by B126, the inverter does not turn ON the brake release output [BRK]. The lack of the 
    proper current level indicates a fault (such as ope n wire to motor). In this case, the inverter 
    trips and outputs the braking error signal [B ER]. This signal is useful to engage an 
    emergency brake to ensure the load does not move, if the primary braking system has failed.
    3. While the brake release output [BRK] is ON, the inverter drives the motor but does not 
    accelerate immediately. The inverter waits for confirmation from the external brake. When 
    the external brake system properly releases, it  signals the inverter by using the Brake OK 
    input terminal [BOK]. If [BOK] is not assigned  to an intelligent input, B124 is ignored.
    4. When the brake operates properly and signals  with the [BOK] input, the inverter waits for 
    the required time for accelerati on (B122), and then begins to accelerate to the set target 
    frequency. If [BOK] is not assigned to an in telligent input, acceleration begins after the 
    delay time set by B122 af ter [BRK] signal occurs.
    5. When the Run command turns OFF, the procedure outlined above happens in reverse. The 
    idea is to engage the brake be fore the motor comes completely  to a stop. The inverter decel-
    erates to the releasing frequency (B125) and turns the brake release output [BRK] OFF to 
    engage the brake.
    6. The inverter does not decelerate further duri ng just the waiting time for brake confirmation 
    (B121). If the brake confirmation signal does not tu rn OFF within the waiting time for brake 
    confirmation, the inverter causes a trip al arm and outputs the brake error signal [BER] 
    (useful for engaging an emergency brake system).
    7. Normally, the brake confirmation signal [BOK]  turns OFF, and the inverter waits the 
    required waiting time. Then the inverter begins to decelerate again and brings motor and 
    load to a complete stop (see timing diagram on next page).
    Opt. Code44
    Symbol[BOK]
    Va l i d  f o r  
    Inputs[1] to [8]
    Required
    Settings B120=01; 
    Set B121 to  B127
    Default 
    terminal Requires 
    config.
    [BRK] Brake release
    [BOK] Brake confirmation
    Inverter
    External Brake 
    System
    Emergency Brake
    (or alarm, etc.)[BER] Brake error
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–33
    The following table lists the parameters related to the External Brake Control function.
    The diagram below shows the event sequence de scribed in the steps on the previous page.
    CodeFunctionData or RangeDescription
    B120 Brake control  enable 00=Disable
    01=Enable Enables external brake control function within the 
    inverter
    B121 Brake waiting  time for release 0.00 to 5.00 sec. Sets the time 
    delay after arrival at release 
    frequency (B125) before the inverter outputs brake 
    release signal [BRK]
    B122 Brake wait time  for acceleration 0.00 to 5.00 sec. Sets time delay 
    after brake confirmation signal 
    [BOK] is received until the inverter begins to accel-
    erate to the set frequency
    B123 Brake wait time  for stopping 0.00 to 5.00 sec. Sets the time dela
    y after brake confirmation signal 
    [BOK] turns OFF (after [BRK] turns OFF) until 
    decelerating the inverter to 0 Hz
    B124 Brake wait time  for confirmation 0.00 to 5.00 sec. Sets the wait time for [BOK] signal after turn ON/
    OFF of [BRK] signal. If [BOK] is not received 
    during the specified time, the inverter will trip with 
    an external brake error [BER].
    B125 Break release  frequency setting 0.00 to 99.99 Hz /
    100.0 to 400.0 Hz Sets the frequency at which the inverter outputs the 
    brake release signal [BRK
    ] after delay set by B121
    B126 Brake release  current setting 0% to 200% of 
    rated current Sets the minimum inverter current level above 
    which the brake release signal [BRK] will be 
    permitted
    B127 Braking  frequency 0 to 400 Hz 
    (0 to 120 Hz for  model -4000) Sets the frequency at which the inverter outputs the 
    braking signal
    Output
    frequency
    Run command
    Brake release output [BRK] Brake OK input [BOK]
    B122B123
    B121
    B125B125
    B124
    Brake release frequency
    Brake wait time to release
    Brake wait time for accel Brake wait time for stopping
    Brake wait time
    for confirmation
    B124Brake error output [BER] t
    0
    
    Phone: 800.894.0412   
    						
    							Using Intelligent Input Terminals
    Operations
    and Monitoring
    4–34
    Expansion Card 
    Input Signals   Other inputs listed below require the expansion card SJ-FB Encoder Fe edback. Please see the 
    SJ-FB manual for more information.
    The diagram below shows how the Input/Output  connections for the SJ–FB feedback board. 
    The inverter’s internal connections and paramete r configuration make these signals available on 
    intelligent input and output terminals.
    The information on outputs  related to the SJ-FB expansion card is in  “
    Expansion Card Output 
    Signals” on page 4–54.
    ADD Frequency 
    Enable   The inverter can add or subtract an offset value to the output frequency setting which is speci-
    fied by A001 (will work with any of the five possible sources). The ADD Frequency is a value 
    you can store in parameter A145. The ADD Frequenc y is summed with or subtracted from the 
    output frequency setting only  when the [ADD] terminal is ON.  Function A146 selects whether 
    to add or subtract. By configuring an intellig ent input as the [ADD] terminal, your application 
    can selectively appl y the fixed value in A145 to offset (positively or negatively) the inverter 
    output frequency in real time.
    Opt. Code 
    and 
    Symbol
    45=[ORT]
    46=[LAC]
    47=[PCLR]
    48=[STAT]
    Va l i d  f o r   Inputs[1] to [8]
    RequiredSettings B120=01;
    Set B121 to  B126
    Wiring 
    terminals ...on SJ-FB 
    Expansion 
    Card 
    SymbolFunction NameDescription
    ORT Orientation Orientation  (home search sequence)
    LAC LAD  Cancel Cancels the linear a cceleration/deceleration position 
    control in the feedback card
    PCLR Position deviation clear Forces the position error to zero STAT Pulse train input enable Starts the  pulse train control of motor frequency
    SJ7002 inverter
    SJ-FB Feedback 
    Expansion Card
    Input assignments Output assignments
    Input
    terminals Output
    terminals
    Control and logic connector
    ORT
    LAC
    PCLR
    STAT ZS
    DSE
    POK
    Opt. Code50
    Symbol[ADD]
    Va l i d  f o r  
    Inputs[1] to [8]
    RequiredSettings A145, A146
    Default 
    terminal Requires 
    config.
    Keypad potentiometer
    Control terminal
    Function F001 setting
    Network variable F001
    Calculate function output ADD direction select
    Intelligent input [ADD]
    Σ
    A001 Frequency source setting
    Output frequency setting
    A145Add frequency
    +/–
    A146
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–35
    Force Terminal 
    Mode   The purpose of this intelligent input is to allow a device to force the inverter to allow control of 
    the following two parameters via the control terminals:
     A001 - Frequency source setting (01  = control terminals [FW] and [RV])
     A002 - Run command source setting (0 1 = control terminals [O] or [OI])
    Some applications will  require one or both settings above to use a source other than the 
    terminals. You may prefer to normally use the inve rter’s keypad and potentiometer, or to use the 
    ModBus network for control, for example. However, an external device can turn ON the 
    [F-TM] input to force the inverter to (tempor arily) allow control (frequency source and Run 
    command) via control terminals. When the [F-TM] input is OFF, then the inverter uses the 
    regular sources specified by A001 and A002 again.
    When changing the [F-TM] state during Run Mode  (inverter is driving the motor), the inverter 
    will stop the motor before the new [F-TM] state takes effect.
    Torque Control 
    Enable   The torque control enable function is available in the  vector control with encoder feedback 
    mode (A044 = 05). You can use the inverter not only in speed control or pulse train position 
    control but also with the torque control function.  Suitable applications include material winding 
    machines.
    The torque command input is enabled when the  [ATR] intelligent input (assigned with option 
    code 52) is ON. You can select  one of four torque command input methods (digital operator 
    and three analog input terminals) by  the torque command input selection.
    Opt. Code51
    Symbol[F–TM]
    Valid for 
    Inputs[1] to [8]
    Required
    Settings A001, A002
    Default 
    terminal Requires 
    config.
    Opt. Code52
    Symbol[ATR]
    Valid for 
    Inputs[1] to [8]
    RequiredSettings A044 = 05, 
    P033, P034, 
    P035, P039, 
    P040, P036,  P037, P038
    Monitor 
    Settings D009, D010, 
    D012
    Default 
    terminal Requires 
    config.
    CodeFunctionData or RangeDescription
    P033 Torque command input  selection 00 [O] terminal
    01 [OI] terminal
    02 [O2] terminal
    03 Inverter keypad (P034)
    P034 Torque command settin g 0. to 200. (%) Torque setting for the input from 
    the digital operator (P033 = 03)
    P035 Torque command polarity  select 00 Indicated by signal polarity at 
    [O2] terminal 
    01 Depends on motor direction
    P039 Forward speed limit for  torque-control mode 0.00 to maximum 
    frequency (Hz) —
    P040 Reverse speed limit for  torque-control mode 0.00 to maximum 
    frequency (Hz) —
    P036 Torque bias mode 00 Disable 01 Inverter keypad (P037)
    02 [O2] terminal input
    P037 Torque bias value -200. to 200. (%)
    P038 Torque bias polarity 00 Indicated by polarity
    01 Depends on motor direction
    
    Phone: 800.894.0412   
    						
    							Using Intelligent Input Terminals
    Operations
    and Monitoring
    4–36
    The following block diagram shows the torque control operation. If the measured speed 
    exceeds the speed limit, the motor speed is  controlled in proportional control mode.
    Clear Cumulative 
    Power Value   When D015 cumulative power monitoring functi on is selected, the inverter displays the 
    cumulative value of electric power input to the inverter. You can also convert the value to other 
    engineering units by setting th e related parameter gain (B079  cumulative input power display 
    gain setting). The gain can be set within  the range of 1 to 1000 (resolution = 1).
    There are two ways to clear the cumulative power data:
     Set B078 = 01 and press the ST R key on the digital operator.
     Configure an intelligent input for the [KHC] function (option code = 53). Turn ON the input  to clear the cumulative power data.
    When B079 cumulative input power display gain  setting = 1000, cumulative power data up to 
    999000 kW/h can be displayed.
    Torque command input
    Intelligent input [ATR]Σ
    Torque bias
    Σ
    ++
    + +
    Torque command 
    (inverter output)
    Σ
    +
    –
    Speed limit
    Measured speed
    Speed 
    comparator
    Speed 
    control
    Opt. Code53
    Symbol[KHC]
    Va l i d  f o r  
    Inputs[1] to [8]
    RequiredSettings B078, B079
    Monitor 
    Settings D015
    Default 
    terminal Requires 
    config.
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–37
    Speed Servo ON  The servo-ON function allows you to set the inve rter in a speed-servo-lock state with an 
    intelligent input during operation. This function is available when A044=05  vector control with 
    sensor  for the characteristic V/f curve.
    To use the servo-ON function, assign option code  54 to an intelligent input. After making the 
    input assignment, the inverter will accept an  operation command only when the [SON] terminal 
    is ON.
    If the [SON] terminal is turned OFF during inve rter operation, the inverter output enters FRS 
    mode (free-run stop). If the [SON] is turned ON ag ain, the inverter restarts the motor according 
    to function B088, Restart Mode After FRS.
    The inverter does not allow [SON] terminal a ssignment and [FOC] (forcing function) assign-
    ment at the same time. If both are assigned, the  [FOC] has priority (operates normally) and the 
    [SON] function is not available.
    Current Forcing  The current forcing function applies an excitation current to pre-build magnetic flux in the 
    motor. The forcing function is available when  one of the following vector control modes is 
    configured for use at the inverter output:
     A044 = 03   sensorless vector control
     A044 = 04   0Hz-range sensorless vector control
     A044 = 05   vector control with sensor
    To use current forcing, assign option code 55 to  an intelligent input terminal. After making the 
    input assignment, the inverter will accept an  operation command only when the [FOC] terminal 
    is ON.
    If the [FOC] terminal is turned OFF during inve rter operation, the inverter output enters FRS 
    mode (free-run stop). If the [FOC] is turned ON  again, the inverter restarts the motor according 
    to function B088, Restart Mode After FRS.
    Opt. Code54
    Symbol[SON]
    Valid for 
    Inputs[1] to [8]
    RequiredSettings A044
    Default 
    terminal Requires 
    config.
    Output
    frequency
    Servo-ON [SON] FW/RV
    Free-run stop
    t
    0
    Speed-servo lock states
    Restart after FRS (B088)
    Inverter does not follow FW/RV 
    command because [SON] is OFF
    Opt. Code55
    Symbol[FOC]
    Valid for 
    Inputs[1] to [8]
    RequiredSettings A044, A244
    Default 
    terminal Requires 
    config.
    Output
    frequency
    Current forcing [FOC] FW/RV
    Free-run stop
    t
    0
    Excitation current flows
    Restart after FRS (B088)
    Inverter does not follow FW/RV 
    command because [FOC] is OFF
    
    Phone: 800.894.0412   
    						
    							Using Intelligent Input Terminals
    Operations
    and Monitoring
    4–38
    General Purpose 
    Inputs 1–8   Refer to the Easy Sequence Inst ruction Manual for information on  how to configure and use the 
    general purpose inputs MI1 to MI8.
    Analog Holding 
    Command   The analog holding function causes the inve rter to sample and hold the analog command 
    (external analog input). The hol d operation begins when the intelligent input [AHD] (assign 
    option code 65) turns ON.  While [AHD] terminal is ON, th e Up/Down function uses the held 
    input level as the reference speed (frequency)  value. Set parameter C101 (Up/Down memory 
    Mode Selection) = 01 to store the last  frequency adjusted by UP/DWN in memory.
    If the inverter power is cycled (OFF and ON) or  the [RS] reset terminal receives a reset (ON 
    and OFF) while [AHD] is ON (holding analog valu e), the data held at the moment of power 
    OFF or Reset ON will be used.
    The wave form below shows a typical sequenc e for use of the Analog Holding Command.
    NOTE: Frequent use of the Analog Hold function may damage the corresponding flash 
    memory register in the inverter.
    Opt. Code 
    and 
    Symbol
    56=[MI1]
    57=[MI2]
    58=[MI3]
    59=[MI4]
    60=[MI5]
    61=[MI6]
    62=[MI7]
    63=[MI8]
    Va l i d  f o r  
    Inputs[1] to [8]
    RequiredSettings See Easy 
    Sequence
    Default 
    terminal Requires 
    config.
    Opt. Code65
    Symbol[AHD]
    Va l i d  f o r  
    Inputs[1] to [8]
    RequiredSettings C101
    Default 
    terminal Requires 
    config.Analog input command
     Analog Holding Command [AHD]
    Analog hold ON
    t
    0
    Output frequency command
    0 1
    0
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–39
    Multi-stage 
    Position Select
    1, 2, and 3   Three Multi-stage Position Select inputs are bina ry-encoded to select one of eight settings, 
    P060 to P067. Input [CP1] is the LSB; [CP3] is  the MSB. If no position select inputs are 
    assigned, P060 becomes the  default position setting.
    The three multi-stage position select inputs [C F1, [CF2], and [CF3] are binary-encoded. When 
    more than one input changes state to select a  position, it is possible that skewing of input 
    transitions would briefly select undesired intermediate posi tions. To avoid this problem, a 
    determination time feature is av ailable. Parameter C169 sets a de lay time that applies uniformly 
    to all three inputs. It operates  according to the following process:
     The determination timer is initialized upon an  input transition. The transition is not yet 
    transferred to the output.
     The timer is initialized ag ain if an input transitions before the timer expires.
     When the timer expires, the state of all three posi tion select inputs is transferred to the output 
    (to generate a new positi on selection, P060 to P067).
    Note that excessively long determination time  settings will reduce the overall performance of 
    the position select inputs.
    Opt. Code 
    and 
    Symbol66=[CP1]
    67=[CP2]
    68=[CP3]
    Valid for  Inputs[1] to [8]
    RequiredSettings P060 to 
    P067, C169
    Default 
    terminal Requires 
    config.
    Function 
    CodeMulti-Position
    Input Function
    [CF3][CF2][CF1]
    P060 Position setting 0 0 0 0
    P061 Position setting 1 0 0 1
    P062 Position setting 2 0 1 0
    P063 Position setting 3 0 1 1
    P064 Position setting 4 1 0 0
    P065 Position setting 5 1 0 1
    P066 Position setting 6 1 1 0
    P067 Position setting 7 1 1 1
    Po s i t i o n
    selection
     [CP1]
    t
    0
    Determination time = 0C169
    Determination time > 0C169
     [CP2]
     [CP3]
    7
    1 3 7
    54
    0
    
    Phone: 800.894.0412   
    						
    All Hitachi manuals Comments (0)