Home > Hitachi > Inverter > Hitachi Sj7002 Owners Manual

Hitachi Sj7002 Owners Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Hitachi Sj7002 Owners Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 913 Hitachi manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							“B” Group: Fine-Tuning Functions
    Configuring Drive Parameters
    3–38
    Software Lock 
    ModeThe software lock function keeps personnel fro m accidentally changing parame ters in the 
    inverter memory. Use B031 to select from various protection levels.
    The table below lists all combinati ons of B031 option codes and the 
    ON/OFF state of the [SFT] input. Each Check ✔  or Ex ✘ indicates 
    whether the corresponding parameter(s ) can be edited. The Standard 
    Parameters column below lists Low and High level access for some 
    lock modes. These refer to the  parameter tables throughout this 
    chapter, each of which includes a column titled Run Mode Edit  as 
    shown to the right. The two marks (Check  ✔ or Ex  ✘) under the “Lo 
    Hi” subtitle indicate whether Low-level and/or High-level access 
    applies to each parameter as defi ned in the table below. In some lock modes, you can edit only 
    F001 and the Multi-speed parameter group that includes A020, A220 , A320, A021–A035, and 
    A038 (Jog). However, it does not include A 019, Multi-speed operation selection. The editing 
    access to B031 itself is unique, and is spec ified in the right-most two columns below.
    NOTE: Since the software lock function B031 is al ways accessible when the motor is stopped, 
    this feature is not the same as password protec tion used in other industrial control devices.
    NOTE: To disable parameter editing when using B 031 lock modes 00 and 01, assign the [SFT] 
    function to one of the intelligent input terminals. See  “Software Lock” on page 4–23.
    B031 Lock 
    Mode[SFT] 
    Intelligent  InputStandard ParametersF001 and 
    Multi-speedB031
    StopRunStop or RunStopRun
    00 OFF ✔
    Low-level✔✔✘
    ON ✘✘
    ✘✔✘
    01 OFF ✔
    Low-level✔✔✘
    ON ✘✘ ✔ ✔✘
    02 (ignored) ✘✘ ✘ ✔✘
    03 (ignored) ✘✘ ✔ ✔✘
    10 (ignored) ✔
    High-level✔✔✔
    Run 
    Mode 
    Edit
    Lo Hi
    ✘ ✔
    Func.CodeName/
    Description
    Keypad
    Range and Settings
    DefaultsRun 
    Mode Edit
    Lo HiSRWOPEFEF2
    FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    B031 Software lock mode  selection MD000Low-level access, [SFT] in
    put blocks all edits 01 01 01 ✘ ✔
    MD1
    0 1Low-level access, [SFT] input blocks edits 
    (except F001 and Multi -speed parameters)
    MD2
    02No access to edits
    MD3
    03No access to edits except  F001 and Multi-speed 
    parameters
    MD10
    10High-level access, including B031
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Configuring Drive Parameters
    3–39
    Miscellaneous 
    SettingsThe miscellaneous settin gs include scaling factors, initialization mode s, and others. This 
    section covers some of th e most important settings you may need to configure.
    Function Display 
    SettingsThe inverter has the (optional) capability to su ppress the display and editing of certain parame-
    ters. Use B037 to select the display options. The  purpose of this feature is to hide particular 
    secondary parameters that become unused or no t applicable based on more fundamental param-
    eter settings. For example, setting A001 = 01  configures the inverter to get its frequency 
    command from the front keypad potentiometer. In th is case, the inverter will not use the analog 
    inputs nor their adjustment paramete rs for an external frequency command.
    For example, you can set B037=01 to have the in verter suppress the displaying of all analog 
    input parameters when A001=01, as shown in the first row of the following table.       
    Func.
    CodeName/
    Description
    Keypad
    Range and Settings
    DefaultsRun 
    Mode Edit
    Lo HiSRWOPEFEF2
    FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    B034 Run/power-on warning time — — 0 to 9999. (0 to 99990), 1000 to  6553 (10000 to 655300) (hours)0. 0. 0.
    ✘ ✔
    B035 Rotational direction restriction FREE
    00Enable for both directions 00 00 00 ✘ ✘
    FW
    0 1Enable for forward only ✘ ✘
    RV
    02Enable for reverse only ✘ ✘
    B036 Reduced voltage start selection — — 000 (short) to 255 (long) 06 06 06✘ ✔
    Func.
    CodeName/
    DescriptionKeypad
    Range and Settings
    DefaultsRun 
    Mode Edit
    Lo HiSRWOPExFE2(EU)xFU2(USA)xFF2(Jpn)
    B037 Function code display  restriction ALL00Display all
    040404✘ ✔
    FUNCTION
    0 1Display only utilized  functions (see 
    table on next page)
    USER
    02Display user-selected functions only 
    (configure with U01 to U12)
    COMPARE
    03Data comparison display
    BASIC
    04Basic display
    B038 Initial display selection STR
    00Last value dislayed when STR key 
    was pressed 01 01 01
    ✘ ✔
    FM
    0 1D001
    Iout
    02D002
    Dir
    03D003
    F-CNV
    04D007
    F-SET
    05F001
    B039 Automatic user parame- ter function enable OFF
    00Disable
    000000✘ ✔
    ON
    0 1Enable
    Function  CodeDataResulting Non-displayed 
    Functions (when B37 = 01)Notes
    A001 01 A005, A006, A011 – A016, A101 –  A114, C081 – C083, C121 – C123 [O], [OI], [O2] terminal 
    functions
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							“B” Group: Fine-Tuning Functions
    Configuring Drive Parameters
    3–40
    A002 01, 03, 04,  05B087 Stop key function
    A019 00 A028 – A035 Multi-speed function
    C001 – C008 02, 03, 04,  05
    Function 
    CodeDataResulting Non-displayed 
    Functions (when B37 = 01)Notes
    A044, A244 02 B100 – B113 Control methods
    A051 01 A052 – A059 DC braking
    A071 01 A072 – A076, C044 PID function
    A094 01 A095 – A096 2-stage adjustable frequency
    A294 01 A0295 – A296
    B013, B213,  B313 02 B015 – B020
    Electric thermal characteris-
    tic
    B021 01, 02 B022, B023 Overload restriction
    B024 01, 02 B025, B026 Overload restriction 2
    B095 01, 02 B090 – B096 Dynamic braking function
    C001 – C008 06 A038, A039
    Jogging
    08 F202, F203, A203, A204, A220, 
    A241 – A244, A261, A262, 
    A292 – A296, B212, B213, H202 
    – H206, H220 – H224, H230 – 
    H234, H250 – H252, H260 2nd motor control
    11 B088 Free-run stop
    17 F302, F303, A303, A304, A320,  A342 – A344, A392, A393, 
    B312, B313, H306 3rd motor control
    18 C102 Reset
    27, 28, 29 C101 UP/DWN
    A044 00, 01 A041 – A043
    Torque boost function
    04 H060 0Hz domain SLV limiter
    A244 00, 01 A241 – A243
    Torque boost function
    04 H260 0Hz SLV limiter
    A044 03, 04, 05 B040 – B046, H001, H070 – 
    H072, H002, H005, H020 – 
    H024, H030 – H034, H050 – 
    H052, H060 Vector control
    A244 03, 04 B040 – B046, H001, H070 – 
    H072, H202, H205, H220 – 
    H224, H230 – H234, H250 – 
    H252, H260 Vector control
    A097 01, 02, 03 A131 Acceleration pattern constant
    A098 01, 02, 03 A132 Deceleration pattern constant
    Function 
    CodeDataResulting Non-displayed 
    Functions (when B37 = 01)Notes
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Configuring Drive Parameters
    3–41
    B098 01, 02 B099, C085 Thermistor function
    B050 01 B051 – B054 Instantaneous power failure
    B120 01 B121 – B126 External brake control
    Function 
    CodeDataResulting Non-displayed 
    Functions (when B37 = 01)Notes
    C021 – C025,  C026 02, 06 C042, C043 Frequency arrival signal
    03 C040, C041 Overload advance notice
    07 C055 – C058 Over-torque
    21 C063 Zero-speed detection signal
    24, 25 C045, C046 Frequency arrival signal 26 C011 Overload advance notice 2
    H002 00 H020 – H024 Motor constant
    01, 02 H030 – H034 Motor constant (auto-tuning)
    H202 00 H220 – H224 Motor constant 01, 02 H023 – H0234 Motor constant (auto-tuning)
    P010 01 P011 – P023, P025 – P027 Expansion card function
    Function  CodeDataResulting Non-displayed 
    Functions (when B37 = 01)Notes
    Func.
    CodeName/
    Description
    Keypad
    Range and Settings
    DefaultsRun 
    Mode
    Edit
    Lo HiSRWOPEFEF2FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    B040 Torque limit selection 4-SET004-quadrant mode00 00 00✘ ✔
    TM
    0 1Selected by two input terminals (see 
    p. 
    4–30)
    O2
    02From analog [O2] input (0 to 10V = 
    0 to 200%)
    OP1
    03From expansion card 1
    OP2
    04From expansion card 2
    B041 Torque limit (1) (forward-driving in  4-quadrant mode) 150%
    1500. to 200. (%)
    150. 150. 150.✘ ✔
    no
    noDisable torque limit
    B042 Torque limit (2) (reverse-regenerat- ing in 4-quadrant mode) 150%
    1500. to 200. (%)
    150. 150. 150.✘ ✔
    no
    noDisable torque limit
    B043 Torque limit (3) (reverse-driving in  4-quadrant mode) 150%
    1500. to 200. (%)
    150. 150. 150.✘ ✔
    no
    noDisable torque limit
    B044 Torque limit (4 ) (forward-regenerat-
    ing in 4-quadrant mode) 150%
    1500. to 200. (%)
    150. 150. 150.✘ ✔
    no
    noDisable torque limit
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							“B” Group: Fine-Tuning Functions
    Configuring Drive Parameters
    3–42
    Controlled Deceleration at Power Loss  – When enabled, this feature permits the inverter to 
    control final motor deceleration  upon loss of inverter input power. First, you must make a 
    wiring change to the inverter. See  “
    Optional Controlled Decel and Alarm at Power Loss” on 
    page 4–4 for complete instructions including wiring  and signal timing diagrams for using the 
    controlled decelera tion at power loss feature.
    After making the wiring change, use function B050  to enable the feature. Use B051 to deter-
    mine the point at which a decaying DC bus voltage will trigger the cont rolled deceleration. Use 
    parameter B054 to specify  an initial step-wise deceleration at power loss,  and B053 to specify 
    the duration of the linear deceleration.
    During the controlled deceleration the inverter itself  acts as a load to decelerate the motor. With 
    either a high-inertia load or a short deceleration  time (or both), it is possible that the inverter 
    impedance will not be low enough  to continue linear deceleration and avoid an over-voltage 
    condition on the DC bus. Use parameter B052 to  specify a threshold for the over-voltage. In 
    this case, the inverter pauses  deceleration (runs at constant  speed). When the DC bus decays 
    again below the threshold, linear  deceleration resumes. The pause/re sume process will repeat as 
    necessary until the DC bus energy is de pleted (under-voltage condition occurs).
    The case when setting B052 is  lower than the inverter supply voltage has special consider-
    ations:
     If B052 Over-voltage Threshold During Power Loss is less than B051 DC Bus Voltage  Trigger Level During Power Loss, the over-vo ltage threshold during power loss will be 
    increased to the DC bus voltage trigger level wi th the stop level is applied. However, the 
    parameter setting will not be changed.
     When B052 is less than the supply voltage (the  rectified DC voltage or the AC voltage times 
    square root of two), when power recovers the  inverter will be in the LAD-stop state and 
    cannot decelerate. (The  Stop Command and frequency ch ange command are ignored until 
    deceleration is complete.) be  sure to set B052 higher than the standard supply voltage.
     A non-stop decelera tion function cannot be canceled until it is complete. To restart the 
    inverter operations after power recovery, wait  until the inverter stops. Then enter a Stop 
    Command and then an operation command (FW, RV).
     Setting a higher value for B054 Initial Output Frequency Decrease During Power Loss  results in an over-current trip  due to sudden deceleration. Setting a lower value for B054 or 
    larger value for B053 Decelera tion Time Setting During Powe r Loss results in under-voltage 
    trip due to reduced regenerative energy.
    Non-stop deceleration at inst antaneous power failure (B050=01) has these characteristics:
     The nonstop deceleration at  instantaneous power failure is the function making the inverter 
    decelerate and stop the motor while maintaining the voltage below the overvoltage level 
    (over-voltage threshold during  power loss [b052]) when an instantaneous power failure 
    occurs during the inverter operation.
     To use this function, remove the J51 connector  cables from terminals R0 and T0, connect the 
    main circuit terminals P and R0 to each other,  and connect the main circuit terminals N and 
    T0 to each other. Use 0.75 mm2 or  heavier wires for the connections.
    B045 Torque limit LADSTOP enable OFF00Disable000000✘ ✔
    Temporarily stops accel/decel ramps 
    during torque limit. Available for 
    SLV, 0 Hz domain, or vector control 
    with feedback mode ON
    0 1Enable
    ✘ ✔
    B046 Reverse Run protection enable OFF
    00Disable000000✘ ✔
    Prohibits reverse motor rotation ON
    0 1Enable
    Func.
    CodeName/
    Description
    Keypad
    Range and Settings
    DefaultsRun 
    Mode Edit
    Lo HiSRWOPEFEF2FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Configuring Drive Parameters
    3–43
     If an instantaneous power failure has occurred while the inverter is operating the motor and the output voltage falls to the  DC bus voltage trigger level dur ing power loss (b051) or less, 
    the inverter reduces the output frequency by the initial output frequency decrease during 
    power loss (b054) once, and then decelerates the motor for th e deceleration time setting 
    during power loss (b053).
     If the voltage increases to an overvoltage le vel (exceeding the over-voltage threshold during 
    power loss [b052]) because of regeneration, the in verter enters the LAD stop state (deceler-
    ate to stop) until the voltage falls below the overvoltage level.
    If the over-voltage threshold during power loss (B 052) is less than the DC bus voltage trigger 
    level during power loss (B051), the over-voltage th reshold during power loss will be increased 
    to the DC bus voltage trigger level during power loss when the stop level is applied. (However, 
    the stored setting will not be changed.) And,  in case B052 is lower than the supply voltage 
    (equivalent to rectified DC voltage which is square root of 2 times the supply AC voltage), 
    when power recovers while this function is activa ted, inverter will be in the LAD stop status 
    and cannot decelerate. (Stop command and frequen cy change command are not accepted until 
    deceleration is complete). Be sure to se t b052 higher than the normal supply voltage. 
    Func.
    CodeName/
    Description
    Keypad
    Range and Settings
    DefaultsRun 
    Mode Edit
    Lo HiSRWOPEFEF2
    FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    B050 Controlled deceleration  and stop on power loss OFF00Disable
    000000✘ ✘
    Allows inverter control 
    using regenerative energy 
    to decelerate after loss of 
    input power (requires 
    jumper change) DEC
    0 1Constant decel to stop
    ✘ ✘
    NS1
    02Constant DC voltage control 
    with resume ✘ ✘
    NS2
    03Constant DC voltage control ✘ ✘
    B051 DC bus voltage trigger level during power  loss 0.0 to 999.9, 1000. (V) 220.0/
    440.0220.0/
    440.0 220.0/
    440.0 ✘ ✘
    Sets trigger for cont rolled deceleration and 
    stop on power loss function
    B052 Over-voltage threshold during power loss 0.0 to 999.9, 1000. (V) 360.0/ 720.0360.0/
    720.0 360.0/
    720.0 ✘ ✘
    Sets over-voltage thre shold for controlled 
    deceleration function
    B053 Deceleration time setting during power loss  0.01 to 99.99, 100.0 to 999.9,  1000 to 3600 (seconds)1.00 1.00 1.00
    ✘ ✘
    B054 Initial output frequency decrease during  power loss 0.00 to 10.00 (Hz) 0.00 0.00 0.00
    ✘ ✘
    Sets the initial decrea se in output frequency 
    upon power loss
    B055 Proportional gain setting for non-stop  operation at power loss
    0.00 to 2.550.20 0.20 0.20 ✘ ✘
    B056 Integral time settin g for non-stop operation 
    at power loss 0.0 to 9.999, 10.00 to 65.55 0.10 0.10 0.10
    ✘ ✘
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							“B” Group: Fine-Tuning Functions
    Configuring Drive Parameters
    3–44
    Window 
    ComparatorsThe window comparator function controls digi tal outputs based on the comparison of analog 
    input values to user-defined upper and lower limits.
    Miscellaneous 
    FunctionsB083: Carrier frequency adjustment  – The internal switching frequency  of the inverter 
    circuitry (also called the  chopper frequency). It is called the carrier frequency because the 
    lower AC output frequency of the inverter “rides” the carrier. The faint, high-pitched sound 
    you hear when the inverter is in Run Mode is  characteristic of switching power supplies in 
    general. The carrier frequency is adjustable fr om 500 Hz to 15 kHz (the upper limit varies, 
    depending on the inverter rating) . The audible sound decreases at  the higher frequencies, but 
    RFI noise and leakage current may  be increased. Refer to the specification derating curves in 
    Chapter 1 to determine the maximum allowable  carrier frequency setting for your particular 
    inverter and environmental conditions.
    NOTE: When the inverter is in sensorless vector  mode, use B083 to set the carrier frequency 
    greater than 2.1 kHz for proper operation.
    NOTE: The carrier frequency setting must stay within specified limits for inverter-motor 
    applications that must comply with particular regulatory agen cies. For example, a European 
    CE-approved application requires the inverter carrier to be less than 5 kHz.
    Func.
    CodeName/
    DescriptionKeypad
    Range and Settings
    DefaultsRun 
    Mode Edit
    Lo HiSRWOPExFE2(EU)xFU2(USA)xFF2(Jpn)
    B060 [O] input maximum limit level of  window comparator 0. to 100. (%)
    Lower limit = B061 + B062 x 2 100 100 100
    ✘ ✔
    B061 [O] input minimum limit level of  window comparator 0. to 100. (%)
    Lower limit = B060 – B062 x 2 000
    ✘ ✔
    B062 [O] input hysteresis width of window comparator 0. to 10. (%) Lower limit = B061 – B062 x 2000
    ✘ ✔
    B063 [OI] input maximum limit level of  window comparator 0. to 100. (%)
    Lower limit = B064 + B066 x 2 100 100 100
    ✘ ✔
    B064 [OI] input minimum limit level of  window comparator 0. to 100. (%)
    Lower limit = B063 – B066 x 2 000
    ✘ ✔
    B065 [OI] input hysteresis width of window comparator 0. to 10. (%) Lower limit = B063 – B064 x 2000
    ✘ ✔
    B066 [O2] input maximum limit level of window comparator –100. to 100. (%) Lower limit = B067 + B068 x 2100 100 100
    ✘ ✔
    B067 [O2] input minimum limit level of window comparator –100. to 100. (%) Lower limit = B066 – B068 x 2-100 -100 -100
    ✘ ✔
    B068 [O2] input hysteresis width of window comparator 0. to 10. (%) Lower limit = B066 – B067 x 2000
    ✘ ✔
    B070 [O] input disconnect threshold — — 0 to 100 (%) 255 255 255 ✘ ✔
    no
    255Ignore setting ✘ ✔
    B071 [OI] input disconnect threshold — — 0 to 100 (%)255 255 255✘ ✔
    no
    255Ignore setting ✘ ✔
    B072 [O2] input disconnect threshold — — 0 to 100 (%)127 127 127✘ ✔
    no
    127Ignore setting ✘ ✔
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Configuring Drive Parameters
    3–45
    B084, B085: Initialization codes –  These functions allow you to restore the factory default 
    settings. Please refer to “
    Restoring Factory Default Settings” on page 6–16.
    B086: Frequency display scaling –  You can convert the output frequency monitor on D001 to 
    a scaled number (e ngineering units) monitore d at function D007. For example, the motor may 
    run a conveyor that is monitored in fe et per minute. Use this formula:    
    B091/B088: Stop Mode / Rest art Mode Configuration – You can configure how the inverter 
    performs a standard stop (each time Run FWD an d REV signals turn OFF). Setting B091 deter-
    mines whether the inverter will  control the deceleration, or whet her it will perform a free-run 
    stop (coast to a stop). When usi ng the free-run stop selection, it is  imperative to also configure 
    how you want the inverter to resume control of  motor speed. Setting B088 determines whether 
    the inverter will ensure the motor always resu mes at 0 Hz, or whether the motor resumes from 
    its current coasting speed (also called  frequency matching). The Run command may turn OFF 
    briefly, allowing the motor to coast to a slow er speed from which normal operation can resume.
    In most applications a cont rolled deceleration is desirable, corresponding to B091=00. 
    However, applications such as HVAC fan contro l will often use a free-run stop (B091=01). This 
    practice decreases dynamic stre ss on system components, prolongin g system life. In this case, 
    you will typically set B088=01  in order to resume from the current speed after a free-run stop 
    (see diagram below, right). Note that using the  default setting, B088=00, can cause trip events 
    when the inverter attempts to force the load quickly to zero speed. Scaled output frequency (D007) Output
     frequency (D001) Factor (B086)×
    =
    Func.
    CodeName/
    Description
    Keypad
    Range and Settings
    DefaultsRun 
    Mode Edit
    Lo HiSRWOPEFEF2FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    B078 Clear cumulative input power  data  CNT00No change
    00 00 00✔ ✔
    Set = 01, press STR key to clear CLR
    0 1Clear the data
    B079 Cumulative input power displa y gain setting 1. to 1000. 1. 1. 1.✔ ✔
    B082 Start frequency adjustment 0.10 to 9.99 (Hz)0.50 0.50 0.50✘ ✔
    Sets the starting frequency  for the inverter output
    B083 Carrier frequency setting Most models, 0.5 to 15.0 (kHz);
    -1850 and -3150 are 0.5 to 10 (kHz);
    -4000 is 0.5 to 3 (kHz) 3.0
    2.1
    1.93.0
    2.1
    1.9 3.0
    2.1
    1.9
    ✘ ✔
    Sets the PWM carrier (internal switching freq.); 
    all models are su
    bject to derating✘ ✔
    B084 Initialization  mode (parameters 
    or trip history) TRP00Trip history clear
    00 00 00✘ ✘
    DATA
    0 1Parameter initialization
    TRP/
    DATA
    02Trip history clear and parameter 
    initialization
    B085 Country code for initialization JPN
    00Japan version01 02 00✘ ✘
    Select default pa rameter values 
    for country on initialization EUR
    0 1Europe version
    USA
    02USA version
    B086 Frequency scaling conversion factor 0.1 to 99.91.0 1.0 1.0✔ ✔
    Specify a constant to scale D007 to display in 
    engineering units
    B087 STOP key enable ON
    00Enable00 00 00✘ ✔
    Select whether the STOP key on 
    the keypad is enabled (req. 
    A002=01, 03, 04, or 05) OFF
    0 1Disable
    S-OFF
    02Disable only the STOP function
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							“B” Group: Fine-Tuning Functions
    Configuring Drive Parameters
    3–46
    NOTE: Other events can cause (or be configured to  cause) a free-run stop, such as power loss 
    (see  “
    Automatic Restart Mode and Phase Loss” on page 3–30), and inverter trip events in 
    general (see  “
    Miscellaneous  Functions” on page 3–62). If all free-run stop behavior is impor-
    tant to your applicat ion (such as HVAC), be sure to  configure each event accordingly.
    Some additional parameters further configure  all instances of a free-run stop. Parameter B003, 
    Retry Wait Time Before Motor Restart, sets the minimum time the inverter will free-run. For 
    example, if B003 = 4 seconds (and B091=01) an d the cause of the free-run stop lasts 10 
    seconds, the inverter will free -run (coast) for a total of 14 seconds before driving the motor 
    again. Parameter B007, Restart  Frequency Threshold, sets the motor frequency at which the 
    inverter will no longer resume  and accelerate, instead resumi ng from 0 Hz (complete stop).
    Motor 
    speed
    [FW, RV]
    Zero-frequency startMotor 
    speed
    Resume from current speed
    wait time
    [FW, RV]B003
    B088=01B088=00Resume from 0Hz
    B091=01 Stop Mode = free-run stopB091=01Stop Mode = free-run stop
    t t
    Func.
    CodeName/
    Description
    Keypad
    Range and Settings
    DefaultsRun 
    Mode
    Edit
    Lo HiSRWOPEFEF2FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    B088 Restart mode after FRS ZST00Restart from 0Hz 000000✘ ✔
    Selects how the inverter 
    resumes operation when 
    the free-run stop (FRS) is 
    cancelled fST
    0 1Restart from frequen
    cy detected from 
    actual speed of motor
    FIX
    02Restart from active  matching frequency
    B089 Automatic carrier  frequency reduction OFF
    00Disable
    000000✘ ✔
    ON
    0 1Enable ✘ ✔
    B090 Dynamic braking usage ratio 0.0 to 100.0 (%) 
    Set = 0.0 to disable dynamic braking 00 00 00
    ✘ ✔
    Selects the braking duty cycle fo r the dynamic braking resistor 
    (total brake % ON-time per 100 second interval) ✘ ✔
    B091 Stop mode selection DEC
    00DEC (decelerate and stop) 00 00 00✘ ✘
    Selects how the inverter 
    stops the motor FRS
    0 1FRS (free run to stop)
    ✘ ✘
    B092 Cooling fan control (see note below) OFF
    00Fan always ON
    00 00 00✘ ✘
    ON
    0 1Fan ON during RUN, OFF during STOP ✘ ✘
    B095 Dynamic braking control OFF
    00Disable 000000✘ ✔
    ON 
    STPOFF
    0 1Enable during RUN only ✘ ✔
    ON 
    STPON
    02Enable always ✘ ✔
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Configuring Drive Parameters
    3–47
    B090: Dynamic braking usage ratio –  This parameter limits the amount of time the inverter 
    can use the dynamic braking accessory device with out entering the Trip Mode. Please refer to 
    “
    Dynamic Braking” on page 5–6 for more information on  dynamic braking accessories.
    NOTE: When cooling fan control is enabled (B092=01) the inverter always turns the fan ON 
    for five minutes immediately after  powerup. This will cool the inverter in case the inverter / 
    motor is still warm from prior running before a short power outage.
    Free-setting
    V/f PatternThe free-setting V/f inverter mode of operation uses voltage and frequency parameter pairs to 
    define seven points on a V/f graph. This provides a way to define a multi-segment V/f curve 
    that best suits your application.
    The frequency settings do require that F1  ≤ F2  ≤ F3 ≤  F4 ≤ F5 ≤ F6 ≤  F7; their values must have 
    this ascending order relationship. To satisfy this  criterion during initial parameter editing, set 
    F7 (B112) and work backwards when setting th ese values, since the defaults are all 0 Hz. 
    However, the voltages V1 to V7 may either in crease or decrease from one to the next. There-
    fore, you may set these parameters in any order.
    B096 Dynamic braking activation level 330 to 380 (V) (200V class),
    660 to 760 (V) (400V class) 360/
    720 360/
    720 360/
    720 ✘ ✔
    B098 Thermistor for thermal  protection control OFF
    00Disable
    000000✘ ✔
    PTC
    0 1Enable-PTC thermistor ✘ ✔
    NTC
    02Enable-NTC thermistor ✘ ✔
    B099 Thermal protection level settin g0.0 to 9999 Ohms 3000 3000 3000✘ ✔
    Thermistor resistance thre shold at which trip occurs ✘ ✔
    Func.
    CodeName/
    Description
    Keypad
    Range and Settings
    DefaultsRun 
    Mode Edit
    Lo HiSRWOPEFEF2FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    Func.CodeName/
    DescriptionRange and Settings
    DefaultsRun 
    Mode Edit
    Lo Hi
    FEF2FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    B100 Free-setting V/f frequency (1) 0. to  Free-setting V/f frequency (2) (Hz) 0. 0. 0. ✘ ✘
    B101 Free-setting V/f voltage (1) 0.0 to 800.0 (V) 0.0 0.0 0.0✘ ✘
    B102 Free-setting V/f frequency (2) 0. to  Free-setting V/f frequency (3) (Hz) 0. 0. 0. ✘ ✘
    B103 Free-setting V/f voltage (2) 0.0 to 800.0 (V) 0.0 0.0 0.0✘ ✘
    B104 Free-setting V/f frequency (3) 0. to  Free-setting V/f frequency (4) (Hz) 0. 0. 0. ✘ ✘
    B105 Free-setting V/f voltage (3) 0.0 to 800.0 (V) 0.0 0.0 0.0✘ ✘
    B106 Free-setting V/f frequency (4) 0. to  Free-setting V/f frequency (5) (Hz) 0. 0. 0. ✘ ✘
    B107 Free-setting V/f voltage (4) 0.0 to 800.0 (V) 0.0 0.0 0.0✘ ✘
    B108 Free-setting V/f frequency (5) 0. to  Free-setting V/f frequency (6) (Hz) 0. 0. 0. ✘ ✘
    B109 Free-setting V/f voltage (5) 0.0 to 800.0 (V) 0.0 0.0 0.0✘ ✘
    B110 Free-setting V/f frequency (6) 0. to  Free-setting V/f frequency (7) (Hz) 0. 0. 0. ✘ ✘
    B111 Free-setting V/f voltage (6) 0.0 to 800.0 (V) 0.0 0.0 0.0✘ ✘
    B112 Free-setting V/f frequency (7) 0. to 400.0 (Hz) 0. 0. 0.✘ ✘
    B113 Free-setting V/f voltage (7) 0.0 to 800.0 (V) 0.0 0.0 0.0✘ ✘
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    All Hitachi manuals Comments (0)