Home > Hitachi > Inverter > Hitachi Sj7002 Owners Manual

Hitachi Sj7002 Owners Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Hitachi Sj7002 Owners Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 913 Hitachi manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							“B” Group: Fine-Tuning Functions
    Configuring Drive Parameters
    3–48
    External Brake 
    ControlThe brake control function in the inverter contro ls external braking used in systems such as 
    elevators. The purpose of this function is to en sure the inverter is powering the motor before 
    releasing external brakes that would permit the load to move or coast. This function requires the 
    configuration and wiring of intellig ent input and output terminals. See  “
    External Brake Control 
    Function” on page 4–32 for more information.
    Func.
    CodeName/
    Description
    Keypad
    Range and Settings
    DefaultsRun 
    Mode Edit
    Lo HiSRWOPEFEF2
    FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    B120 Brake Control Enable OFF00Disable 000000✘ ✔
    ON
    0 1Enable
    B121 Brake Wait Time for Release 0.00 to 5.00 (seconds)0.00 0.00 0.00✘ ✔
    Sets time delay between arrival at release frequency and the brake release signal
    B122 Brake Wait Time for Acceleration 0.00 to 5.00 (seconds)0.00 0.00 0.00✘ ✔
    Sets time delay from receipt of brake confirma tion signal to start of motor acceleration
    B123 Brake Wait Time for Stopping 0.00 to 5.00 (seconds)0.00 0.00 0.00✘ ✔
    Sets time delay from brake confirmation signal  turns OFF to inverter deceleration to 0 Hz
    B124 Brake Wait Time for Confirmation 0.00 to 5.00 (seconds)0.00 0.00 0.00✘ ✔
    Sets the wait time for confirmatio n after turn ON/OFF of brake release. If confirmation is not 
    received during the specified wait  time, the inverter will trip with an external brake error.
    B125 Brake Release Frequency Setting 0.00 to 99.99, 100.0 to 400.0 (Hz)0.00 0.00 0.00✘ ✔
    Sets the frequency of the brake releas e output signal after delay set by B121
    B126 Brake Release Current Setting 0 to 1.80 x rated current Rated current for 
    inverter ✘ ✔
    Sets the minimum inverter current level abov e which the brake release signal is permitted
    B127 Braking Frequency 0.00 to 99.99, 100.0 to 400.0 (Hz)0.00 0.00 0.00✘ ✔
    [BRK] Brake release
    [BOK] Brake confirmation
    Inverter
    External Brake 
    System
    Emergency Brake(or alarm, etc.)[BER] Brake error
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Configuring Drive Parameters
    3–49
    Overvoltage  
    FunctionsB130/B131: Over-voltage LADSTOP Enable / Over-voltage LADSTOP Level –  The over-
    voltage LADSTOP function monitors the DC bu s voltage and actively changes the output 
    frequency profile to maintain the DC bus voltage  within settable limits. Although “LAD” refers 
    to “linear acceleration / deceleration,” the invert er only “STOPs” the deceleration slope so that 
    regenerative voltage will not cause the DC bus to rise enough to cause an over-voltage trip 
    event. Note that acceleration is not affected.
    The graph below shows an inverter output profile  that starts decelerating to a stop. At two 
    different points during the deceleration, regenerative voltage elevates the DC bus level, exceed-
    ing the LADSTOP threshold set by B131. When  the Over-voltage LADSTOP feature is 
    enabled by B130 = 01, the inverter stops the deceleration ramp in each case until the DC bus 
    level is again less than the threshold value.
    Inverter stops deceleration
    tB130=01OVLADSTOP = enable
    t
    Start deceleration
    Deceleration resumed
    Output 
    frequency
    Over-voltage protection 
    trip threshold
    Over-voltage protection  trip threshold
    DC bus level
    Func.CodeName/
    Description
    Keypad
    Range and Settings
    DefaultsRun 
    Mode
    Edit
    Lo HiSRWOPEFEF2FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    B130 Over-voltage LADSTOP enable OFF00Disable 000000✘ ✘
    Pauses deceleration ramp when 
    DC bus voltage rises above 
    threshold level, in order to avoid 
    over-voltage trip ON
    0 1Enable during deceleration and constant 
    speed
    ✘ ✘
    AON
    02Enable during  acceleration ✘ ✘
    B131 Over-voltage LADSTOP level 330 to 390 (V) for 200V class, 660 to 780 (V) for 400V class 380/
    760 380/
    760 380/
    760 ✘ ✔
    Sets the threshold level for over-voltage LADS TOP. When the DC bus voltage is above the 
    threshold value, the inverter stops decelera tion until the DC bus voltage is less than the 
    threshold setting again. ✘ ✔
    B132 Acceleration and decelera tion rate at overvoltage 
    suppression 0.10 to 30.00 (seconds) 1.00 1.00 1.00
    ✘ ✔
    B133 Overvoltage suppression proportional gain 0.00 to 2.55 0.50 0.50 0.50 ✘ ✘
    B134 Overvoltage suppression integral time 0.000 to 9.999, 10.00 to 63.53 (seconds) 0.060 0.060 0.060 ✘ ✘
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							“C” Group: Intelligent Terminal Functions
    Configuring Drive Parameters
    3–50
    “C” Group: Intelligent Terminal Functions
    The eight input terminals [ 1], [2], [ 3], [4], [ 5], [6], [7],  and [ 8] can be configured for any of 44 
    different functions. The next two  tables show how to configure the eight terminals. The inputs 
    are logical, in that they are either OFF or  ON. We define these states as OFF=0, and ON=1.
    The inverter comes with default options for th e eight terminals. These default settings are 
    initially unique, each one having its own setting. Note that  European and US versions have 
    different default settings. You ca n use any option on any terminal, and even use the same option 
    twice to create a logical OR (though usually not required).
    Input Terminal 
    ConfigurationFunctions and Options –The  function codes in the following table let you assign one of 44 
    options to any of the eight logic inputs for the SJ700
    2 inverters. The functions C001 through 
    C008 configure the terminals [1] through [8] respectively. The “value” of these particular 
    parameters is not a scalar value,  but it is a discrete number that selects one option from many 
    available  options.
    For example, if you set function C001=01, you have assigned option 01 (Reverse Run) to 
    terminal [1]. The option codes and the specifics of how each one works are in Chapter 4.
    The input logic convention is programmable for ea ch of the six inputs. Most inputs default to 
    normally open (active high), but yo u can select normally closed (active low) in order to invert 
    the sense of the logic.
    Func.
    CodeName/
    DescriptionRange and Settings
    DefaultsRun 
    Mode Edit
    Lo Hi
    FEF2FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    C001 Terminal [1] function
    63 programmable functions available for terminals (see  next section) 18 [RS] 18 [RS] 18 [RS]
    ✘ ✔
    C002 Terminal [2] function 16 [AT] 16 [AT] 16 [AT]✘ ✔
    C003 Terminal [3] function 06 [JG] 06 [JG] 06 [JG]✘ ✔
    C004 Terminal [4] function 11 [FRS] 11 [FRS] 11 [FRS]✘ ✔
    C005 Terminal [5] function 09 [2CH] 09 [2CH] 09 [2CH]✘ ✔
    C006 Terminal [6] function 03 [CF2] 13 [USP] 03 [CF2] ✘ ✔
    C007 Terminal [7] function 02 [CF1] 02 [CF1] 02 [CF1] ✘ ✔
    C008 Terminal [8] function 01 [RV] 01 [RV] 01 [RV]✘ ✔
    Func.
    CodeName/
    Description
    Keypad
    Range and Settings
    DefaultsRun 
    Mode Edit
    Lo HiSRWOPEFEF2FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    C011 Terminal [1] active state NO00Normally open (N.O.) 00 00 00 ✘ ✔
    NC
    0 1Normally closed (N.C.) ✘ ✔
    C012 Terminal [2] active state NO
    00Normally open (N.O.) 00 00 00 ✘ ✔
    NC
    0 1Normally closed (N.C.) ✘ ✔
    C013 Terminal [3] active state NO
    00Normally open (N.O.) 00 00 00 ✘ ✔
    NC
    0 1Normally closed (N.C.) ✘ ✔
    C014 Terminal [4] active state NO
    00Normally open (N.O.) 00 00 00 ✘ ✔
    NC
    0 1Normally closed (N.C.) ✘ ✔
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Configuring Drive Parameters
    3–51
    NOTE: An input terminal configured  for option code 18 ([RS] Reset command) cannot be 
    configured for normally closed operation.
    Intelligent Input 
    Terminal 
    OverviewEach of the eight intelligent terminals may be assigned any of  the options in the following 
    table. When you program one of the option code s for terminal assignments C001 to C008, the 
    respective terminal assumes the function role of  that option code. The terminal functions have a 
    symbol or abbreviation, which we  use to label a terminal using that function. For example the 
    “Reverse Run” command is [RV]. The physical labe l on the terminal block connector is simply 
    1, 2,  3, 4, 5, 6, 7, or 8 . However, schematic examples in th is manual also use the terminal 
    function symbol (such as [RV]) to show the  assigned option. The option codes for C011 to 
    C019 determine the active st ate of the logical input (active high or active low).
    Summary Table  - This table shows all forty-four in telligent input functions at a glance. 
    Detailed descriptions of thes e functions, related parameters and settings, and example wiring 
    diagrams are in  “
    Using Intelligent Input Terminals” on page 4–13.
    C015 Terminal [5] active state NO00Normally open (N.O.) 00 00 00 ✘ ✔
    NC
    0 1Normally closed (N.C.) ✘ ✔
    C016 Terminal [6] active state NO
    00Normally open (N.O.) 00 00 00 ✘ ✔
    NC
    0 1Normally closed (N.C.) ✘ ✔
    C017 Terminal [7] active state NO
    00Normally open (N.O.) 00 00 00 ✘ ✔
    NC
    0 1Normally closed (N.C.) ✘ ✔
    C018 Terminal [8] active state NO
    00Normally open (N.O.) 00 00 00 ✘ ✔
    NC
    0 1Normally closed (N.C.) ✘ ✔
    C019 Terminal [FW] active state NO
    00Normally open (N.O.) 00 00 00 ✘ ✔
    NC
    0 1Normally closed (N.C.) ✘ ✔
    Func.
    CodeName/
    Description
    Keypad
    Range and Settings
    DefaultsRun 
    Mode Edit
    Lo HiSRWOPEFEF2FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    Input Function Summary Table
    Option CodeTe r m i n a l  SymbolFunction NameDescription
    01 RV Reverse Run/Stop Puts the inverter in Run Mode, motor runs reverse
    02 CF1 Multi-speed select, Bit 0 (LSB) Binary encoded sp
    eed select, Bit 0
    03 CF2 Multi-speed select, Bit 1 Binary encoded sp
    eed select, Bit 1
    04 CF3 Multi-speed select, Bit 2 Binary encoded sp
    eed select, Bit 2
    05 CF4 Multi-speed select, Bit 3 (MSB) Binary encoded sp
    eed select, Bit 3
    06 JG Jogging Puts the inverter in Run Mode, output to motor runs at jog  parameter frequency A038
    07 DB External Signal for DC  Injection Braking Applies DC braking during deceleration
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							“C” Group: Intelligent Terminal Functions
    Configuring Drive Parameters
    3–52
    08 SET Set (select) 2nd Motor  Data Switch from normal (1st) to 2
    nd motor parameters for gener-
    ating frequency output to motor
    09 2CH 2-stage Acceleration and  Deceleration Frequency output uses 2nd-stag
    e acceleration and decelera-
    tion values
    11 FRS Free-run Stop Causes output to turn OFF, allowing motor to free run (coast) 
    to stop
    12 EXT External Trip At OFF to ON transition, inverter latches trip event and 
    displays E12 (until  a reset occurs)
    13 USP Unattended Start Protec- tion On powerup, the inverter will not resume a Run command 
    that was active before power 
    loss (mostly used in the US)
    14 CS Commercial Power  Source OFF-to-ON transition signals the inverter that the motor is 
    already running at powerup (v
    ia bypass), thus suppressing the 
    inverter’s motor output in Run Mode; ON-to-OFF transition 
    signals the inverter to apply  a time delay (B003), frequency 
    match its output to existing mo tor speed, and resume normal 
    Run Mode operation
    15 SFT Software Lock The keypad and remote programming devices are prevented 
    from changing parameters
    16 AT Analog Input Voltage/ current Select ON condition: If A005=00, term
    inal [OI] is enabled for  
    input. If A005=01, terminal [O2]  is enabled for input. (Use 
    terminal [L] for  signal return.)
    OFF condition: Terminal [O] is enabled for voltage input (use 
    terminal [L] for  signal return).
    17 SET3 Set (select) 3rd motor data Switch from no rmal (1st) to 3rd motor parameters for gener-
    ating frequency output to motor
    18 RS Reset Inverter Resets the trip condition, turns OFF the motor output, and 
    asserts powerup reset
    20 STA START (3-wire interface) Starts the motor rotation
    21 STP STOP (3-wire interface) Stops the motor rotation
    22 F/R FWD, REV (3-wire interface) Selects the direction of motor rotation: ON =FWD; 
    OFF =REV. While the motor is rotating, a change of F/R will 
    start a deceleration, followed by a change in direction.
    23 PID PID Disable Temporarily disables PID loop control. Inverter output turns 
    OFF as long as PID Enable is active (A071=1).
    24 PIDC PID Reset Resets the PID loop controller. The main consequence is that 
    the integrator sum is forced to zero.
    26 CAS Control gain setting To select the  source of internal speed loop gain...
     OFF selects paramete rs H050 to H052 (or H250 to H252 for 
    2nd motor); ON selects alternat e parameters H070 to H072
    27 UP Remote Control  UP Function (motorized 
    speed pot.) Accelerates (increases output frequency) motor from current 
    frequency
    28 DWN Remote Control DOWN  Function (motorized 
    speed pot.) Decelerates (decreases output frequency) motor from current 
    frequency
    Input Function Summary Table
    Option
    CodeTerminal SymbolFunction NameDescription
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Configuring Drive Parameters
    3–53
    29 UDC Remote Control Data  Clearing Clears the UP/DWN frequency memo
    ry by forcing it to equal 
    the set frequency parameter F001. Setting C101 must be 
    set=00 to enable this function to work.
    31 OPE Operator Control Forces the source of  the output frequency setting (A001) and 
    the RUN command (A002) to be from the digital operator 
    (F001 and the Run key, respectively)
    32 SF1 Multi-speed bit 1 Multi ple speed select, Bit 1
    33 SF2 Multi-speed bit 2 Multi ple speed select, Bit 2
    34 SF3 Multi-speed bit 3 Multi ple speed select, Bit 3
    35 SF4 Multi-speed bit 4 Multi ple speed select, Bit 4
    36 SF5 Multi-speed bit 5 Multi ple speed select, Bit 5
    37 SF6 Multi-speed bit 6 Multi ple speed select, Bit 6
    38 SF7 Multi-speed bit 7 Multi ple speed select, Bit 7
    39 OLR Overload restriction Turn ON to se lect current overload parameter set 2
    (B024, B025, B026); OFF selects set 1(B021, B022, B023)
    40 TL Torque limit enable ON enables torque limit feature; OFF disables all torque limit  sources and defaults to 200% of inverter rated torque output
    41 TRQ1 Torque limit selection, bit  1 Binary encoded torque limit select, Bit 1 (LSB)
    42 TRQ2 Torque limit selection, bit  2 Binary encoded torque limit select, Bit 2 (MSB)
    43 PPI Proportional /  Proportional/Integral 
    mode selection ON selects Proportional-only co
    ntrol; OFF selects Propor-
    tional-Integral control
    44 BOK Brake confirmation signal Ind icates external brake has released (used only for external 
    brake control function)
    45 ORT  Orientation (home sear ch) The encoder is in the home (oriented) position
    46 LAC LAC: LAD cancel Disables the normal Linear Accel / Decel (LAD) mode
    47 PCLR Position deviation reset Clears the posit ion deviation by setting the actual position 
    equal to the desired position
    48 STAT Pulse train position  command input enable Enables the pulse train control of motor
    50 ADD Add frequency enable Adds the A145 value (Add Frequency) to the output  frequency
    51 F-TM Force terminal mode Force inverter to  use input terminals for output frequency and 
    Run command sources
    52 ATR Torque control enable Inverter operates  by controlling torque instead of speed
    53 KHC Clear cumulative power  value Clears cumulative power data
     displayed by parameter D015
    54 SON Speed servo ON Enables the inverter to accept FW/REV commands; for use  with V/F curve vector control with sensor  (A044=05)
    Input Function Summary Table
    Option
    CodeTe r m i n a l  SymbolFunction NameDescription
    
    Phone: 800.894.0412   
    						
    							“C” Group: Intelligent Terminal Functions
    Configuring Drive Parameters
    3–54
    55 FOC Current forcing Forces excitation current in motor at 0 speed; for use with V/f 
    curve settings A044/A244 = 03, 04, and 05
    56 MI1 General-purpose input 1 Easy  sequence function, general input 1
    57 MI2 General-purpose input 2 Easy  sequence function, general input 2
    58 MI3 General-purpose input 3 Easy  sequence function, general input 3
    59 MI4 General-purpose input 4 Easy  sequence function, general input 4
    60 MI5 General-purpose input 5 Easy  sequence function, general input 5
    61 MI6 General-purpose input 6 Easy  sequence function, general input 6
    62 MI7 General-purpose input 7 Easy  sequence function, general input 7
    63 MI8 General-purpose input 8 Easy  sequence function, general input 8
    65 AHD Analog holding command Causes the inverter to  sample and hold the analog speed input, 
    maintaining constant spee d while this signal is ON 
    66 CP1 Multi-stage position  select 1 Binary-encoded position select, bit 1 (LSB)
    67 CP2 Multi-stage position  select 2 Binary-encoded position select, bit 2 (LSB)
    68 CP3 Multi-stage position  select 3 Binary-encoded position
     select, bit 3 (MSB)
    69 ORL Zero-return limit function Indicates that th e load has reached the zero-return point, so 
    the inverter stops the zero-return operation in progress
    70 ORG Zero-return trigger  function Starts a zero-return operation 
    (load moves toward the zero-
    return point)
    71 FOT Forward drive stop Limits the forward ro tational torque to 10%; for use at the end 
    of travel in position control mode
    72 ROT Reverse drive stop Limits the reverse rota tional torque to 10%; for use at the end 
    of travel in position control mode
    73 SPD Speed/position control  select Causes the inverter to perfor
    m only speed control (ignores 
    encoder pulses) while in position control mode
    74 PCNT Pulse counter in put Pulse counter input
    75 PCC Pulse counter clear Clears the pulse count
    no — Not selected (input ignored)
    Input Function Summary Table
    Option
    CodeTerminal SymbolFunction NameDescription
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Configuring Drive Parameters
    3–55
    Output Terminal 
    ConfigurationThe inverter provides configuration for logic (d iscrete) and analog outputs, shown in the table 
    below.
    NOTE: *Terminals [11] – [13] or [11] – [14] ar e automatically configured as AC0 – AC2 or
    AC0 – AC3 when C62 is configured to enable alarm code output.
    The output logic convention is programmable fo r terminals [11] – [15], and the alarm relay 
    terminals. The open-collector  output terminals [11] – [15] default to normally open (active 
    low), but you can select normally  closed (active high) for the terminals in order to invert the 
    sense of the logic. You can invert the logica l sense of the alarm relay output as well.
    Func.
    CodeName/
    DescriptionRange and Settings
    DefaultsRun 
    Mode Edit
    Lo Hi
    FEF2
    FE2
    (EU)
    FUF2FU2
    (USA)
    FF2 F2
    (Jpn)
    C021 Terminal [11] function *
    51 programmable functions available for logic 
    (discrete) outputs (see next  section) 01 [FA1] 01 [FA1] 01 [FA1]
    ✘ ✔
    C022 Terminal [12] function * 00 [RUN] 00 [RUN] 00 [RUN]✘ ✔
    C023 Terminal [13] function  * 03 [OL] 03 [OL] 03 [OL]✘ ✔
    C024 Terminal [14] function * 07 [OTQ] 07 [OTQ] 07 [OTQ]✘ ✔
    C025 Terminal [15] function 08 [IP] 08 [IP] 08 [IP]✘ ✔
    C026 Alarm relay terminal  function 05 [AL] 05 [AL] 05 [AL]
    ✘ ✔
    C027 [FM] signal selection 12 programmable functions 
    available for analog outputs
    (see after next section) 00 (output freq.)
    ✘ ✔
    C028 [AM] signal selection 00 (output freq.)✘ ✔
    C029 [AMI] signal selection 00 (output freq.)✘ ✔
    C030 Digital current monitor  reference value 0.20 x rated current to 2.00 
    x rated current (A) Rated current x 1.0
    ✔ ✔
    Current with digital current monitor output at 1.44 kHz ✔ ✔
    Func.
    CodeName/
    SRW Display
    Keypad
    Range and Settings
    DefaultsRun 
    Mode Edit
    Lo HiSRWOPEFEF2FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    C031 Terminal [11] active state NO00Normally open (N.O.) 00 00 00 ✘ ✔
    NC
    0 1Normally closed (N.C.)
    C032 Terminal [12] active state NO
    00Normally open (N.O.) 00 00 00 ✘ ✔
    NC
    0 1Normally closed (N.C.)
    C033 Terminal [13] active state NO
    00Normally open (N.O.) 00 00 00 ✘ ✔
    NC
    0 1Normally closed (N.C.)
    C034 Terminal [14] active state NO
    00Normally open (N.O.) 00 00 00 ✘ ✔
    NC
    0 1Normally closed (N.C.)
    C035 Terminal [15] active state NO
    00Normally open (N.O.) 00 00 00 ✘ ✔
    NC
    0 1Normally closed (N.C.)
    C036 Alarm relay terminal active  state NO
    00Normally open (N.O.) 01 01 01
    ✘ ✔
    NC
    0 1Normally closed (N.C.)
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							“C” Group: Intelligent Terminal Functions
    Configuring Drive Parameters
    3–56
    Output Summary Table  - This table shows all twenty-two functions for the logic output 
    terminals [11] – [15] at a glance. Detailed function descriptions, re lated parameters, settings, 
    and example wiring diagrams are in  “
    Using Intelligent Output Terminals” on page 4–43.
    Output Function Summary Table
    Option
    CodeTerminal SymbolFunction NameDescription
    00 RUN Run signal Inverter is in Run Mode, motor running
    01 FA1 Frequency arrival type 1 –  constant speed When output to motor is at th
    e standard set frequency F001
    02 FA2 Frequency arrival type 2 –  over-frequency Turns ON when output to motor is at or above the FA 
    Threshold 1 (C042) during accel; turns OFF when motor 
    output goes below the threshold during decel
    03 OL Overload advance notice  signal (1) Output current is more than
     the set Threshold 1 for the 
    overload signal (set with C041)
    04 OD Output deviation for PID  control PID error is more than the se
    t threshold for the deviation 
    signal
    05 AL Alarm signal Alarm  condition has been met and not reset
    06 FA3 Frequency arrival type 3 –  at frequency Output to motor is at the FA Threshold 1 (C042) during accel, 
    or at C043 during decel
    07 OTQ Over-torque signal Over-torque feature  is enabled and the motor is generating 
    excess torque
    08 IP Instantaneous power  failure signal Inverter input power has decreased below the acceptable input 
    voltage level
    09 UV Under-voltage signal Inverter input powe r has decreased below the acceptable input 
    voltage level
    10 TRQ In torque limit Output torque exceed s level set for the particular torque/
    frequency quadrant in effect during operation
    11 RNT Operation time over Inverter Run time exceeds the limit set by Run/power-on  warning time (B034)
    12 ONT Plug-in time over Inverter plug- in time exceeds the set limit
    13 THM Thermal alarm signal Thermal limit for the motor is exceeded
    19 BRK Brake release signal ON when the inverter  signals the external braking system to 
    release (open) its brake; OFF wh en the inverter is not driving 
    the motor and needs the external brake engaged
    20 BER Brake error signal ON when the output  current is less than the set releasing 
    current; OFF when the braking function is not in use, or when 
    the output current to the motor is correct and it is safe to 
    release the brake
    21 ZS Zero speed detect Encoder pulses of the motor have stopped
    22 DSE Speed deviation  maximum Velocity error exceeds the e
    rror threshold defined for the 
    encoder input
    23 POK Positioning completion Lo ad position is at the target
    24 FA4 Frequency arrival type 4 –  over-frequency (2) ON when output to motor is at or above the FA threshold 2 
    (C045) during accel; OFF when the output to motor is below 
    the FA threshold 2 (C046) during decel
    25 FA5 Frequency arrival type 5 –  at frequency (2) Output to motor is at the FA threshold 2 (C045) during accel 
    or at C046 during decel
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Configuring Drive Parameters
    3–57
    26 OL2 Overload notice advance  signal (2) Output current is more than the set Threshold 2 for the 
    overload signal (set with C111)
    27 Odc Analog [O] disconnect  detect Input signal level at terminal [O
    ] is below threshold (set with  
    B070)
    28 OIDc Analog [OI] disconnect  detect Input signal level at terminal [OI] is below threshold (set with  
    B071)
    29 O2Dc Analog [O2] disconnect  detect Input signal level at terminal [O2] is below threshold (set with  
    B072)
    31 FBV PID feedback second  stage output Stage #1 inverter is indicating to Stage # inverter that the 
    Process Variable (PV) is in
     saturation. The system needs 
    Stage #2 output contribution  to stabilize system control.
    32 NDc Network detection signal T he communications watchdog timer (period specified by 
    C077) has timed out
    33 LOG1 Logic output 1 Boolean operation sp ecified by C144 has a logical “1” result
    34 LOG2 Logic output 2 Boolean operation sp ecified by C147 has a logical “1” result
    35 LOG3 Logic output 3 Boolean operation sp ecified by C150 has a logical “1” result
    36 LOG4 Logic output 4 Boolean operation sp ecified by C153 has a logical “1” result
    37 LOG5 Logic output 5 Boolean operation sp ecified by C156 has a logical “1” result
    38 LOG6 Logic output 6 Boolean operation sp ecified by C159 has a logical “1” result
    39 WAC Capacitor life warning Capacitor ba nk on the main board needs replacement
    40 WAF Low cooling fan speed Cooling fan is enab led but it is rotating below normal speed
    41 FR Starting contact signal ON while the in verter receives a FW or REV command
    42 OHF Heat sink overheat  warning Inverter heat sink temperature 
    is above the threshold set by 
    C064
    43 LOC Low output current signal Output current to motor is below threshold set by C039
    44 MO1 General output 1 Easy sequ ence function, general output 1
    45 MO2 General output 2 Easy sequ ence function, general output 2
    46 MO3 General output 3 Easy sequ ence function, general output 3
    47 MO4 General output 4 Easy sequ ence function, general output 4
    48 MO5 General output 5 Easy sequ ence function, general output 5
    49 MO6 General output 6 Easy sequ ence function, general output 6
    50 IRDY Inverter ready signal Inverter is ready  to accept commands (FW, REV, JOG, etc.)
    51 FWR Forward rotation signal Inverter outp ut is driving motor in forward direction
    52 RVR Reverse rotation signal Inverter output is driving motor in reverse direction
    53 MJA Major failure signal Inverter trip  caused by internal hardware error
    54 WCO [O] terminal window  comparator [O] input is within comparator window set by B060 and B061
    55 WCOI [OI] terminal window  comparator [OI] input is within comparator window set by B063 and 
    B064
    Output Function Summary Table
    Option
    CodeTe r m i n a l  SymbolFunction NameDescription
    
    Phone: 800.894.0412   
    						
    All Hitachi manuals Comments (0)