Hitachi Sj7002 Owners Manual
Have a look at the manual Hitachi Sj7002 Owners Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 913 Hitachi manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
Using Intelligent Input Terminals Operations and Monitoring 4–40 Zero-Return Functions A zero-return operation (also called a home-return) occurs when the motor moves the load to a particular starting position. Us ing parameter P068, you may select one of three possible types of zero-return operations. Parameter P 069 selects the search direction. The zero pulse input (also called zone input) signals the arrival at the zero position. It is generally a requirement (or good practice) to perform a zero-return operation after every powerup of the inverter. It is possible that the previous power OFF occurred when the load was not at zero position. Or, it may be that an ex ternal force moved the load during the power OFF period. If you do not perform a zero-return operation after power ON, then the inverter uses the current position at powerup as the zero position. The three available zero-return modes differ in the overall search speed, final approach direction to the origin, and the limit switch in put transition (or encoder pulse, if used) causing the final stop. Choose the zero-return m ode that best fits your application. Low-speed Zero Return: 1. Motor accelerates for the specified acceleration time to the low zero- return speed 2. Motor runs at the low zero-return speed 3. Inverter stops motor and sets position value to zero when [ORL] signal turns ON High-speed 1 Zero Return: 1. Motor accelerates for specified acceleration time to high zero-return speed 2. Motor runs at high zero-return speed 3. Motor starts deceleration when [ORL] signal turns ON 4. Motor runs in reverse direction at low-speed zero-return speed 5. Inverter stops motor and sets position value to zero when [ORL] signal turns OFF Opt. Code and Symbol69=[ORL] 70=[ORG] Va l i d f o r Inputs[1] to [8] Required Settings P068, P069, P070, P071 Default terminal Requires config. CodeFunctionDataDescription P068 Zero-return mode selection 00 Low speed 01 High speed 1 02 High speed 2 P069 Zero return direction selection 00 Forward 01 Reverse Zero-return limit [ORL] Zero-return trigger [ORG] Encoder Z pulses [Z] InverterOutput to motor Output frequency [ORG] Po siti on 0 Low-speed zero-return level P070 [ORL] Origin1 2 Output frequency [ORG] Pos itio n 0 High zero-return level P071 [ORL] Origin1 23 4 P070 Low-speed zero- return level 5 Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
SJ7002 Inverter Operations and Monitoring 4–41 High-speed 2 Zero Return: 1. Motor accelerates for specified acceleration time to high zero- return speed 2. Motor runs at high zero-return speed 3. Motor starts deceleration when [ORL] signal turns ON 4. Motor runs in reverse direction at low-speed zero-return speed 5. Motor starts deceleration to stop when [ORL] signal turns OFF 6. Motor accelerates in forward direction to low-speed zero return level 7. Inverter stops motor and sets position value to zero when next [Z] signal pulse occurs Forward/Reverse Drive Stop The forward/reverse drive stop function prevents the motor from moving a load outside a desired position range. The end of travel in ea ch direction must cause the appropriate input signal, [FOT] or [ROT], to turn ON. Typically a limit switch or proximity switch is used to generate these signals. If the [FOT] turns ON during forward rotation (or [ROT] turns ON during reverse rotation), the inverter limits the motor torque to 10% in the current direction of travel. Speed/Position Control Select Turn ON the [SPD] terminal input to perform sp eed control while in absolute position control mode. The direction of rotation depends on the operation command (FWD or REV). When switching from speed control to position control, be sure to verify the sign of the value set in the operation command. While the [SPD] terminal is OFF, the current position count remains at zero. If the [SPD] terminal is turned OFF during motor operation, th e control mode switches to position control and pulse counting begins, starti ng from zero. If the target position value is also zero, the inverter stops the motor at the current positi on. Otherwise, rotation continues until motor rotation arrives at the target position. Output frequency [ORG] Posi tion 0 High zero-return level P071 [ORL] Origin 1 2 3 4 P070 Low-speed zero- return level 5 67 Opt. Code and Symbol71=[FOT] 72=[ROT] Valid for Inputs[1] to [8] RequiredSettings none Default terminal Requires config. Forward drive stop [ORL] Reverse drive stop [ORG]Inverter Output to motor Load FwdRev Opt. Code73 Symbol[SPD] Valid for Inputs[1] to [8] RequiredSettings A044=05, P012 Default terminal Requires config.Output frequency Speed/position switching [SPD] Position control t 0 Speed control Start of position counting Target position t Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Using Intelligent Input Terminals Operations and Monitoring 4–42 Pulse Counter Signals The intelligent pulse counter input [PCNT] allows you to input a pulse train up to 100 Hz via an intelligent input terminal. (For high-speed applications, use the encoder input expansion card instead.) Monitor the cumulative count with D028, pulse counter function. The value of the cumulative count cannot be stored in a separate register or parameter. The counter value is cleared to zero when inverter power is turn ON or the inverter is reset. You may also use the [PCC] Pulse Counter Clear input to clear the cumulative count. The frequency resolution of the input pulse ca n be calculated by the formula shown below (assuming a pulse signal input with 50% duty cycl e). Do not input higher frequencies than the calculated value. Opt. Code and Symbol74=[PCNT] 75=[PCC] Va l i d f o r Inputs[1] to [8] Monitor Settings D028 Default terminal Requires config. Counter value t t Pulse counter input [PCNT] 12 Filtered pulse train 34 Frequency resolution (Hz) = 250 / input terminal response setting (C160 to C168) + 1) Example: When the input terminal response time = 1, the frequency resolution = 125 Hz Phone: 800.894.0412
SJ7002 Inverter Operations and Monitoring 4–43 Using Intelligent Output Terminals The intelligent output terminals are programmable in a similar way to the intelligent input terminals. The inverter has several output functions that you can assign individually to five physical logic outputs. Along with these solid-state outputs, the alarm relay output has type Form C (normally open and normall y closed) contacts. The relay is assigned the alarm function by default, but you can assign it to any of th e functions that the open-collector outputs can use. TIP: The open-collector transistor outputs can handle up to 50mA each. We highly recommend that you use an external power source as shown. It must be capable of providing at least 250mA to drive the outputs at full load. If you need output current greater than 50mA, use the inverter output to drive a small relay. Be sure to use a diode across the coil of the relay as shown (reverse- biased) in order to suppress the turn-off spike, or use a solid-state relay. Output circuits +– 24VDC common External system SJ700 2 inverter Sinking outputs (open collector) 1314151112 LLLLL CM2 RY+ – 11CM2 Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Using Intelligent Output Terminals Operations and Monitoring 4–44 Run Signal When the [RUN] signal is selected as an intelligent output terminal, the inverter outputs a signal on that terminal when it is in Run Mode. The output logic is active low, and is the open collector type (switch to common). The timing diagram to the right shows the Run Signal operation in detail. The inverter outputs the [RUN] signal whenever the inverter output exceeds the start frequency specified by parameter B082 . The start frequency is the initial inverter output frequency when it turns ON. NOTE: If you use an intelligent output to drive an ex ternal relay, be sure to connect a diode across the relay coil. This will prevent the negative-going turn-off spike generated by the coil from damaging the inverter’s output transistor. Frequency Arrival Signals The Frequency Arrival group of outputs help coordinate external systems with the current velocity profile of the inverter. As the name implies, output [FA1] turns ON when the output frequency arrives at the standard set frequency (parameter F001). Outputs [FA2] through [FA5] provide variations on this function for increased flexibility, relying on two programmable accel/ decel thresholds. For example, you can have an output turn ON at one frequency during accel- eration, and have it turn OFF at a different frequency during deceleration. All transitions have hysteresis to avoid output chatter if the out put frequency is near one of the thresholds. Note the following: For most applications you will need to use only one or two of the frequency arrival type outputs (see example). However, it is possible to assign all five output terminals to output functions [FA1] through [FA5]. For each frequency arrival thre shold, the output anticipates the threshold (turns ON early) by an amount equal to 1% of the maximum frequency set for the inverter. The output turns OFF as the output frequency moves away from the threshold, delayed by an amount equal to 2% of the max. frequency. Opt. Code00 Symbol[RUN] Va l i d f o r Outputs[11 to [15], [ALx] Required Settings (none) Default terminal[12] [FW, RV] Motor speed Run Signal start freq.B82 ON t Opt. Code and Symbol 01=[FA1] 02=[FA2] 06=[FA3] 24=[FA4] 25=[FA5] Va l i d f o r Outputs[11 to [15], [ALx] Required Settings F001 for FA1 C042 and C043 for FA 2 a n d FA 3 C045 and C046 for FA 4 a n d FA 5 Default terminal[11]=[FA1] Other terminals Requires config. SymbolFunction NameDescription FA1 Frequency arrival type 1 – constant speed ON when output to motor is at the standard set frequency F001 FA2 Frequency arrival type 2 – over-frequency ON when output to motor is at or above the FA threshold 1 (C042) during accel FA3 Frequency arrival type 3 – at frequency ON when output to motor is at the FA threshold 1 (C042) during accel, or at C043 during decel FA4 Frequency arrival type 4 – over-frequency (2) ON when output to motor is at or above the FA threshold 2 (C045) during accel FA5 Frequency arrival type 5 – at frequency (2) ON when output to motor is at the FA threshold 2 (C045) during accel, or at C046 during decel Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
SJ7002 Inverter Operations and Monitoring 4–45 Frequency arrival output [FA1] uses the standard output frequency (parameter F001) as the threshold for switching. In the figure to the right, the inverter accelerates to the set output frequency, wh ich serves as the threshold for [FA1]. Parameters F on and Foff illustrate the hysteresis that prevents output chatter near the threshold value. on is 1% of the max. output frequency off is 2% of the max. output frequency The hysteresis effect causes the output to turn ON slightly early as the speed approaches the threshold. Then the turn- OFF point is slightly delayed. The 1% and 2% values also apply to the remaining Frequency arrival outputs, discussed below. Frequency Arrival outputs [FA2] and [FA4] work the same way; they just use two separate threshold pairs as shown in the figure. These provide for separate acceleration and deceleration thresholds to provide more flexibility than for [FA1]. [FA2] uses C042 and C045 for ON and OFF thresholds, respectively. [FA4] uses C043 and C046 for ON and OFF thresholds, respectively. Having different accel and decel thresholds provides an asymmetrical output function. However, you can use equal ON and OFF thresholds, if desired. Frequency Arrival outputs [FA3] and [FA5] use th e same threshold parameters as [FA2] and [FA4] above, but operate in a slightly different way. Refer to the diagram below. After the frequency arrives at the first threshold during acceleration and turns ON [FA3] or [FA5], they turn OFF again as the output frequency accele rates further. The second thresholds work similarly during deceleration. In this way, we have separate ON/OFF pulses for acceleration and deceleration. FA 1 Output frequency F001 ON t Hz Threshold F onFoff 0 FA 2 / FA 4 Output frequency C042/C045 C043/C046 ON t Hz Thresholds F on Foff 0 FA 3 / FA 5 Output frequency C042/C045 C043/C046 ON ONt Hz Thresholds F onFoffFon Foff 0 Phone: 800.894.0412
Using Intelligent Output Terminals Operations and Monitoring 4–46 Overload Advance Notice Signal When the output current exceeds a preset value, the [OL] or [OL2] terminal signal turns ON. Parameter C041 sets the overload threshold for [OL]; parameter C111 sets it for [OL2]. The overload detection circuit operates during powered motor opera- tion and during regenerative braking. The output circuits use open-collector transistors, and are active low. Note the following: The default threshold value is 100%. To change the level from the default, set C041 or C111(overload level). The accuracy of this function is the same as the function of the output current monitor on the [FM] terminal (see “ Analog Output Operation” on page 4–66). NOTE: If you use an intelligent output to drive an ex ternal relay, be sure to connect a diode across the relay coil. This will prevent the negative-going turn-off spike generated by the coil from damaging the inverter’s output transistor. Output Deviation for PID Control The PID loop error is defined as the magnitude (absolute value) of the differ- ence between the Setpoint (target value) and the Process Variable (actual value). When the error magnitude exceeds the preset value for C044, the [OD] terminal signal turns ON. The default deviation value is set to 3%. To change this value, change parameter C044 (deviation level). Refer to “ PID Loop Operation” on page 4–75. NOTE: If you use an intelligent output to drive an ex ternal relay, be sure to connect a diode across the relay coil. This will prevent the negative-going turn-off spike generated by the coil from damaging the inverter’s output transistor. Opt. Code and Symbol03=[OL] 26=[OL2] Va l i d f o r Outputs[11 to [15], [ALx] Required Settings C041, C111 Default terminal Requires config. SymbolFunction NameDescription OL Overload advance notice signal (1) ON when output current is more than the set threshold for the overload signal (C041) OL2 Overload advance notice signal (2) ON when output current is more than the set threshold for the overload signal (C111) Set value [OL] Signal C041 C041 ON ON t Current threshold power running regeneration threshold Opt. Code04 Symbol[OD] Va l i d f o r Outputs[11 to [15], [ALx] Required Settings C044 Default terminal Requires config. Set value [OD] Signal Error (SP-PV) C044 C044 ON ON t Process variable Setpoint Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
SJ7002 Inverter Operations and Monitoring 4–47 Alarm Signal The inverter Alarm Signal is active when a fault has occurred and it is in the Trip Mode (refer to the diagram at right). When the fault is cleared the Alarm Signal becomes inactive. We must make a distinction between the Alarm Signal AL and the alarm relay contacts [AL0], [AL1] and [AL2]. The signal AL is a logic function, which you can assign to the open collec- tor output terminals [11] to [15], or the relay outputs. The most common (and default) use of the relay is for AL, thus the labeling of its termi- nals. Use an open collector output (terminals [ 11] to [15]) for a low-current logic signal inter- face or to energize a small relay (50 mA maximum). Use the relay output to interface to higher voltage and current devices (10 mA minimum). Note the following: When the alarm output is set to normally closed, a time delay of less than 2 seconds occurs until the contact is closed when the power is turned ON. Terminals [11] – [15] are open collector outputs, so the electrical specifications of [AL] are different from the contact output terminals [AL0], [AL1], [AL2]. When the inverter power supply is turned OFF, the alarm signal output is valid as long as the external control circuit has power. This signal output has the delay time ( 300ms nominal) from the fault alarm output. The relay contact specifications are in “ Specifications of Control and Logic Connections” on page 4–9. The contact diagrams for different conditions are on the next page. The alarm output terminals operate as shown belo w (left) by default. The contact logic can be inverted as shown (below right) by using the parameter setting C036. The relay contacts normally open (N.O.) and normally closed (N.O .) convention uses “normal” to mean the inverter has power and is in Run or Stop Mode . The relay contacts switch to the opposite position when it is in Trip M ode or when input power is OFF. Opt. Code05 Symbol[AL] Valid for Outputs[11 to [15], [ALx] Required Settings C026, C036 Default terminals Relay [AL0], [AL1], [AL2] Run Stop Fault Tr i pFault Alarm signal active RUN STOP RESET STOPRESET Contact position after initializationContact position inverted by C036 setting During normal running When an alarm occurs or power is turned OFFDuring normal running or power is turned OFF When an alarm occurs AL1 AL0AL2 AL1 AL0AL2 AL1 AL0AL2 AL1 AL0AL2 ContactPowerRun StateAL0- AL1AL0- AL2 N.C. (after initialize, C036=01) ON Normal Closed Open ON Trip Open Closed OFF – Open ClosedContactPowerRun StateAL0- AL1AL0-AL2 N.O. (set C036=00) ON Normal Open Closed ON Trip Closed Open OFF – Open Closed Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Using Intelligent Output Terminals Operations and Monitoring 4–48 Over-torque Signal The Over-torque function [OTQ] turns ON when th e estimated value of output torque of motor increases more than the arbitrary level set for the output (see table below). Recall that the torque limit function, covered in “ Torque Limit” on page 4–30, actually limits the torque during certain operating conditions. Instead, the over-torque output feature only monitors the torque, turning ON output [OTQ] if the torque is above programmable thresholds you set. The [OTQ] function is valid only for sensorless vect or control, 0-Hz domain sensorless vector control, or vector control with sensor. Do no t use the [OTQ] output except for these inverter operational modes. The assignment of the Over-torque function to an output terminal [OTQ] is detailed in the table at the left. Instantaneous Power Failure / Under-voltage Signal An instantaneous power failure (complete loss) or under-voltage condition (partial loss) of inverter input voltage can occur without warning. SJ700 2 Series inverters can be configured to respond to these condition s in different ways. You can select wh ether the inverter trips or retries (restart attempt) when an instantaneous power failure or under-voltage condition occurs. You can select the retry func tion with parameter B001. When enabled, the Retry Function operates in the following ways: Under-voltage conditions – When an instantaneous power failure or under-voltage condition occurs, the inverter will attempt to restart up to 16 times. A trip condition will occur on the 17th attempt, which must be cleared with the St op/Reset key. When connecting control power supply terminals [Ro]–[To] to the DC bus [P]–[N ], an under-voltage may be detected at power- off and cause a trip. If this is undesirable, set B004 to 00 or 02. Over-current/voltage conditions – When retry function is selected and an over-current or an over-voltage condition occurs, a restart is attempte d 3 times. A trip will occur on the 4th failed restart attempt. Use parameter B004 to select the trip and alarm response to instantaneous power failure and under-voltage conditions. If an over-voltage or over-current trip occurs during the deceleration and an instantaneous power failure error (E16) is displayed the inverter goes into free-run stop. In this case make the deceleration time longer. Opt. Code07 Symbol[OTQ] Va l i d f o r Outputs[11 to [15], [ALx] Required Settings C055, C056, C057, C058 A044 = 03 or 04 or 05 Default terminals[14] CodeFunction/DescriptionData or Range C055 Over-torque, forward-driving level setting 0 to 200% C056 Over-torque, reverse-regenerating, level setting 0 to 200% C057 Over-torque, reverse-driving, level setting 0 to 200% C058 Over-torque, forward-regenerating, level setting 0 to 200% C021 to C025 Intelligent output terminal [11] to [15] function 07 Opt. Code and Symbol08=[IP] 09=[UV] Va l i d f o r Outputs[11 to [15], [ALx] Required Settings B001, B002, B003, B004, B005, B007 Default terminals Requires config. SymbolFunction NameDescription IP Instantaneous Power Failure ON when the inverter detects a loss of input power UV Under-voltage conditio nON when the inverter input power is less than the specified input range Phone: 800.894.0412
SJ7002 Inverter Operations and Monitoring 4–49 Use the parameters listed in the table belo w to define Instantaneous Power Failure and Under-voltage Signal operation. In the following examples, t 0= instantaneous power failure time, t1 = allowable under-voltage / power failure time (B002), and t 2= retry wait time (B003). CodeFunctionData or RangeDescription B001 Selection of automatic restart mode 00 Alarm output after trip, automatic restart disabled 01 Restart at 0 Hz 02 Retry with frequency matching to present motor speed 03 Retry with frequency matching followed by deceleration to stop— then trip alarm B002 Allowable under- voltage power failure time 0.3 to 1.0 sec. The amount of time a power input under-voltage can occur without tripping the power failure alarm. If under-voltage exists longer than this time, the inverter trips, even if the restart mode is selected. If it exists less than this time retry will be attempted. B003 Retry wait time before motor restart 0.3 to 100 sec. Time delay af ter a trip condition goes away before the inverter restarts the motor B004 Instantaneous power failure / voltage trip alarm enable 00 Disable 01 Enable 02 Disable during stop and ramp to stop B005 Number of restarts on power failure / under-voltage trip events 00 Restart up to 16 times on instantaneous power failure or under-voltage 01 Always restart on instantaneous power failure or an under-voltage condition B007 Restart frequency threshold 0.00 to 400.0 Hz; model -4000HFx2 is 0.00 to 120.0 Hz When frequency of the motor is less than this value, the inverter will restart at 0 Hz Power supply Inverter output Motor frequency After waiting for t2 seconds when t0 < t1; restart Example 1: Power failure within allowed limits; resu me Example 2: Power failure longer than limits; trip t0 t1 t2 Power supply Inverter output Motor frequency t0 t1 Inverter trips when t0 > t1 Free-runFree-run tt Phone: 800.894.0412