Home > Hitachi > Inverter > Hitachi Sj7002 Owners Manual

Hitachi Sj7002 Owners Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Hitachi Sj7002 Owners Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 913 Hitachi manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Using Intelligent Input Terminals
    Operations
    and Monitoring
    4–40
    Zero-Return 
    Functions   A  zero-return  operation (also called a  home-return) occurs when the motor moves the load to a 
    particular starting position. Us ing parameter P068, you may select one of three possible types 
    of zero-return operations. Parameter P 069 selects the search direction. The zero pulse input 
    (also called  zone input) signals the arrival at the zero position.
    It is generally a requirement (or good practice)  to perform a zero-return operation after every 
    powerup of the inverter. It is possible that the previous power OFF occurred when the load was 
    not at zero position. Or, it may be that an ex ternal force moved the load during the power OFF 
    period. If you do not perform a zero-return operation after power ON, then the inverter uses the 
    current position at powerup as the zero position.
    The three available zero-return modes differ  in the overall search speed, final approach 
    direction to the origin, and the limit switch in put transition (or encoder pulse, if used) causing 
    the final stop. Choose the zero-return m ode that best fits your application.
    Low-speed Zero Return:
    1. Motor accelerates for the specified 
    acceleration time to the low zero-
    return speed
    2. Motor runs at the low zero-return 
    speed
    3. Inverter stops motor and sets position 
    value to zero when [ORL] signal 
    turns ON
    High-speed 1 Zero Return:
    1. Motor accelerates for specified 
    acceleration time to high zero-return 
    speed
    2. Motor runs at high zero-return speed
    3. Motor starts deceleration when 
    [ORL] signal turns ON
    4. Motor runs in reverse direction at 
    low-speed zero-return speed
    5. Inverter stops motor and sets 
    position value to zero when [ORL] 
    signal turns OFF
    Opt. Code 
    and 
    Symbol69=[ORL]
    70=[ORG]
    Va l i d  f o r   Inputs[1] to [8]
    Required
    Settings P068, P069, 
    P070, P071
    Default 
    terminal Requires 
    config.
    CodeFunctionDataDescription
    P068 Zero-return mode selection 00 Low speed
    01 High speed 1
    02 High speed 2
    P069 Zero return direction selection 00 Forward
    01 Reverse
    Zero-return limit [ORL]
    Zero-return trigger [ORG]
    Encoder Z pulses [Z]
    InverterOutput to motor
    Output 
    frequency
     [ORG]
    Po siti on
    0 Low-speed zero-return level
    P070
     [ORL]
    Origin1 2
    Output 
    frequency
     [ORG]
    Pos itio n
    0 High zero-return level
    P071
     [ORL]
    Origin1 23
    4
    P070 Low-speed zero-
    return level
    5
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–41
    High-speed 2 Zero Return:
    1. Motor accelerates for specified 
    acceleration time to high zero-
    return speed
    2. Motor runs at high zero-return 
    speed
    3. Motor starts deceleration when 
    [ORL] signal turns ON
    4. Motor runs in reverse direction at 
    low-speed zero-return speed
    5. Motor starts deceleration to stop 
    when [ORL] signal turns OFF
    6. Motor accelerates in forward 
    direction to low-speed zero return level
    7. Inverter stops motor and sets  position value to zero when next [Z] signal pulse occurs
    Forward/Reverse 
    Drive Stop   The forward/reverse drive stop function prevents the motor from moving a load outside a 
    desired position range. The end of travel in ea ch direction must cause the appropriate input 
    signal, [FOT] or [ROT], to turn ON. Typically a  limit switch or proximity switch is used to 
    generate these signals.
    If the [FOT] turns ON during forward rotation (or [ROT] turns ON during reverse rotation), the 
    inverter limits the motor torque to 10% in the current direction of travel.
    Speed/Position 
    Control Select   Turn ON the [SPD] terminal input to perform sp eed control while in absolute position control 
    mode. The direction of rotation depends on  the operation command (FWD or REV). When 
    switching from speed control to position control, be  sure to verify the sign of the value set in 
    the operation command.
    While the [SPD] terminal is OFF, the current  position count remains at zero. If the [SPD] 
    terminal is turned OFF during motor operation, th e control mode switches to position control 
    and pulse counting begins, starti ng from zero. If the target position value is also zero, the 
    inverter stops the motor at the current positi on. Otherwise, rotation continues until motor 
    rotation arrives at the target position.
    Output 
    frequency
     [ORG]
    Posi tion
    0 High zero-return level
    P071
     [ORL]
    Origin
    1 2
    3
    4
    P070 Low-speed zero-
    return level
    5
    67
    Opt. Code 
    and 
    Symbol71=[FOT]
    72=[ROT]
    Valid for  Inputs[1] to [8]
    RequiredSettings none
    Default 
    terminal Requires 
    config.
    Forward drive stop [ORL]
    Reverse drive stop [ORG]Inverter
    Output to 
    motor
    Load FwdRev
    Opt. Code73
    Symbol[SPD]
    Valid for 
    Inputs[1] to [8]
    RequiredSettings A044=05, 
    P012
    Default 
    terminal Requires 
    config.Output
    frequency
    Speed/position switching [SPD]
    Position control
    t
    0
    Speed control
    Start of position counting
    Target position
    t
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							Using Intelligent Input Terminals
    Operations
    and Monitoring
    4–42
    Pulse Counter 
    Signals   The intelligent pulse counter input [PCNT] allows  you to input a pulse train up to 100 Hz via an 
    intelligent input terminal. (For  high-speed applications, use the encoder input expansion card 
    instead.) Monitor the cumulative count with D028, pulse counter function. The value of the 
    cumulative count cannot be stored in a separate  register or parameter. The counter value is 
    cleared to zero when inverter power is turn ON  or the inverter is reset. You may also use the 
    [PCC] Pulse Counter Clear input to clear the cumulative count.
    The frequency resolution of the input pulse ca n be calculated by the formula shown below 
    (assuming a pulse signal input with 50% duty cycl e). Do not input higher frequencies than the 
    calculated value.
    Opt. Code 
    and 
    Symbol74=[PCNT]
    75=[PCC]
    Va l i d  f o r   Inputs[1] to [8]
    Monitor
    Settings D028
    Default 
    terminal Requires 
    config.
    Counter value
    t
    t
    Pulse counter 
    input [PCNT]
    12
    Filtered 
    pulse train
    34
    Frequency resolution (Hz) = 250 / input terminal response setting (C160 to C168) + 1)
    Example: When the input terminal response time = 1, the frequency resolution = 125 Hz
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–43
    Using Intelligent Output Terminals
    The intelligent output terminals are programmable in a similar way to the intelligent input 
    terminals. The inverter has several output functions that you can assign individually to five 
    physical logic outputs. Along with these solid-state outputs, the alarm  relay output has type 
    Form C (normally open and normall y closed) contacts. The relay is assigned the alarm function 
    by default, but you can assign it to any of th e functions that the open-collector outputs can use.
    TIP: The open-collector transistor outputs can handle up to 50mA each. We highly recommend 
    that you use an external power source as shown. It must be capable of providing at least 250mA 
    to drive the outputs at full load.
    If you need output current greater than 50mA, use the 
    inverter output to drive a small relay. Be sure to use a 
    diode across the coil of the relay as shown (reverse-
    biased) in order to suppress the turn-off spike, or use a 
    solid-state relay.
    Output circuits
    +–
    24VDC
    common
    External  system SJ700
    2 inverter
    Sinking outputs (open collector)
    1314151112
    LLLLL
    CM2
    RY+
    –
    11CM2
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							Using Intelligent Output Terminals
    Operations
    and Monitoring
    4–44
    Run Signal   When the [RUN] signal is selected as an 
    intelligent output terminal, the inverter 
    outputs a signal on that terminal when it is 
    in Run Mode. The output logic is active 
    low, and is the open collector type (switch 
    to common).
    The timing diagram to the right shows the 
    Run Signal operation in  detail. The inverter 
    outputs the [RUN] signal whenever the 
    inverter output exceeds the start frequency 
    specified by parameter B082 . The start 
    frequency is the initial inverter output frequency when it turns ON.
     
    NOTE: If you use an intelligent output to drive an ex ternal relay, be sure to connect a diode 
    across the relay coil. This will prevent the negative-going turn-off spike generated by the coil 
    from damaging the inverter’s output transistor.
    Frequency Arrival 
    Signals   The  Frequency Arrival  group of outputs help coordinate  external systems with the current 
    velocity profile of the inverter. As the name implies, output [FA1] turns ON when the output 
    frequency arrives  at the standard set frequency (parameter F001). Outputs [FA2] through [FA5] 
    provide variations on this function for increased flexibility, relying on two programmable accel/ 
    decel thresholds. For example, you can have an  output turn ON at one frequency during accel-
    eration, and have it turn OFF at a different  frequency during deceleration. All transitions have 
    hysteresis to avoid output chatter if the out put frequency is near one of the thresholds.
    Note the following:
     For most applications you will  need to use only one or two of the frequency arrival type 
    outputs (see example). However, it is possible  to assign all five output terminals to output 
    functions [FA1] through [FA5].
     For each frequency arrival thre shold, the output anticipates the threshold (turns ON early) by 
    an amount equal to 1% of the maximum frequency set for the inverter.
     The output turns OFF as the output frequency moves away from the threshold, delayed by an  amount equal to 2% of the max. frequency.
    Opt. Code00
    Symbol[RUN]
    Va l i d  f o r  
    Outputs[11 to [15],  [ALx]
    Required
    Settings (none)
    Default 
    terminal[12]
    [FW, RV]
    Motor 
    speed
    Run 
    Signal
    start freq.B82
    ON
    t
    Opt. Code 
    and 
    Symbol
    01=[FA1]
    02=[FA2]
    06=[FA3]
    24=[FA4]
    25=[FA5]
    Va l i d  f o r  
    Outputs[11 to [15],  [ALx]
    Required
    Settings F001 for FA1
    C042 and C043 for 
    FA 2  a n d  FA 3
    C045 and C046 for 
    FA 4  a n d  FA 5
    Default 
    terminal[11]=[FA1]
    Other 
    terminals Requires 
    config.
    SymbolFunction NameDescription
    FA1 Frequency arrival type 1 –  constant speed ON when output to motor is at the standard set 
    frequency F001
    FA2 Frequency arrival type 2 –  over-frequency ON when output to motor is at or above the FA 
    threshold 1 (C042) during accel
    FA3 Frequency arrival type 3 –  at frequency ON when output to motor is at the FA threshold 1 
    (C042) during accel, or
     at C043 during decel
    FA4 Frequency arrival type 4 –  over-frequency (2) ON when output to motor is at or above the FA 
    threshold 2 (C045) during accel
    FA5 Frequency arrival type 5 –  at frequency (2) ON when output to motor is at the FA threshold 2 
    (C045) during accel, or
     at C046 during decel
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–45
    Frequency arrival output [FA1] uses the 
    standard output frequency (parameter F001) 
    as the threshold for switching. In the figure 
    to the right, the inverter accelerates to the 
    set output frequency, wh ich serves as the 
    threshold for [FA1]. Parameters F
    on and Foff 
    illustrate the hysteresis  that prevents output 
    chatter near the threshold value.
    
    on is 1% of the max. output frequency
    
    off is 2% of the max. output frequency
    The hysteresis effect causes the output to 
    turn ON slightly  early as the speed 
    approaches the threshold. Then the turn-
    OFF point is slightly  delayed. The 1% and 
    2% values also apply to the remaining 
    Frequency arrival outputs, discussed below.
    Frequency Arrival outputs [FA2] and 
    [FA4] work the same way; they just use 
    two separate threshold pairs as shown in 
    the figure. These provide for separate 
    acceleration and deceleration thresholds 
    to provide more flexibility than for 
    [FA1]. [FA2] uses C042 and C045 for 
    ON and OFF thresholds, respectively. 
    [FA4] uses C043 and C046 for ON and 
    OFF thresholds, respectively. Having 
    different accel and decel thresholds 
    provides an asymmetrical output 
    function. However, you can use equal 
    ON and OFF thresholds, if desired.
    Frequency Arrival outputs [FA3] and [FA5] use th e same threshold parameters as [FA2] and 
    [FA4] above, but operate in a slightly different way. Refer to the diagram below. After the 
    frequency arrives at the first threshold during  acceleration and turns ON [FA3] or [FA5], they 
    turn OFF again as the output frequency accele rates further. The second thresholds work 
    similarly during deceleration. In this way, we  have separate ON/OFF pulses for acceleration 
    and deceleration.
    FA 1
    Output
    frequency
    F001
    ON t
    Hz
    Threshold F
    onFoff
    0
    FA 2 / FA 4
    Output
    frequency
    C042/C045
    C043/C046
    ON t
    Hz
    Thresholds F
    on
    Foff
    0
    FA 3 / FA 5
    Output
    frequency
    C042/C045
    C043/C046
    ON ONt
    Hz
    Thresholds
    F
    onFoffFon
    Foff
    0
    
    Phone: 800.894.0412   
    						
    							Using Intelligent Output Terminals
    Operations
    and Monitoring
    4–46
    Overload 
    Advance Notice 
    Signal   When the output current exceeds a 
    preset value, the [OL] or [OL2] 
    terminal signal turns ON. Parameter 
    C041 sets the overload threshold for 
    [OL]; parameter C111 sets it for 
    [OL2]. The overload detection circuit 
    operates during powered motor opera-
    tion and during regenerative braking. 
    The output circuits  use open-collector 
    transistors, and are active low.
    Note the following:
     The default threshold value is 100%. To change the level from the default, set C041 or  C111(overload level).
     The accuracy of this function is the same as  the function of the output current monitor on the 
    [FM] terminal (see  “
    Analog Output Operation” on page 4–66).
    NOTE: If you use an intelligent output to drive an ex ternal relay, be sure to connect a diode 
    across the relay coil. This will prevent the negative-going turn-off spike generated by the coil 
    from damaging the inverter’s output transistor.
    Output Deviation 
    for PID Control   The PID loop error is defined as the 
    magnitude (absolute value) of the differ-
    ence between the Setpoint (target value) 
    and the Process Variable (actual value). 
    When the error magnitude exceeds the 
    preset value for C044, the [OD] terminal 
    signal turns ON. The default deviation 
    value is set to 3%. To change this value, 
    change parameter C044 (deviation 
    level). Refer to “
    PID Loop Operation” 
    on page 4–75.
    NOTE: If you use an intelligent output to drive an ex ternal relay, be sure to connect a diode 
    across the relay coil. This will prevent the negative-going turn-off spike generated by the coil 
    from damaging the inverter’s output transistor.
    Opt. Code 
    and 
    Symbol03=[OL]
    26=[OL2]
    Va l i d  f o r   Outputs[11 to [15],  [ALx]
    Required
    Settings C041, C111
    Default 
    terminal Requires 
    config.
    SymbolFunction NameDescription
    OL Overload advance notice signal (1) ON when output current is more than the set  threshold for the overload signal (C041)
    OL2 Overload advance notice signal (2) ON when output current is more than the set  threshold for the overload signal (C111)
    Set 
    value
    [OL] 
    Signal
    C041
    C041
    ON ON
    t
    Current
    threshold
    power running
    regeneration
    threshold
    Opt. Code04
    Symbol[OD]
    Va l i d  f o r   Outputs[11 to [15],  [ALx]
    Required
    Settings C044
    Default 
    terminal Requires 
    config.
    Set 
    value
    [OD] 
    Signal
    Error 
    (SP-PV)
    C044
    C044
    ON ON
    t
    Process variable
    Setpoint
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–47
    Alarm Signal   The inverter Alarm Signal is active  when a fault 
    has occurred and it is in the Trip Mode (refer to the 
    diagram at right). When  the fault is cleared the 
    Alarm Signal becomes inactive.
    We must make a distinction between the Alarm 
    Signal  AL and the alarm relay  contacts [AL0], 
    [AL1] and [AL2]. The signal AL is a logic 
    function, which you can assign to the open collec-
    tor output terminals [11]  to [15], or the relay 
    outputs. The most common (and default) use of 
    the relay is for AL, thus the labeling of its termi-
    nals. Use an open collector output (terminals [ 11] to [15]) for a low-current logic signal inter-
    face or to energize a small relay (50 mA maximum). Use the relay output to interface to higher 
    voltage and current devices (10 mA minimum). Note the following:
     When the alarm output is set to  normally closed, a time delay of less than 2 seconds occurs 
    until the contact is closed when the power is turned ON.
     Terminals [11] – [15] are open collector outputs,  so the electrical specifications of [AL] are 
    different from the contact output terminals [AL0], [AL1], [AL2].
     When the inverter power supply is turned OFF,  the alarm signal output is valid as long as the 
    external control  circuit has power.
     This signal output has the delay time ( 300ms nominal) from the fault alarm output.
     The relay contact specifications are in  “
    Specifications of Control and Logic Connections” on 
    page 4–9. The contact diagrams for different conditions are on  the next page.
    The alarm output terminals operate as shown belo w (left) by default. The contact logic can be 
    inverted as shown (below right) by using the parameter setting C036. The relay contacts 
    normally open (N.O.) and normally closed (N.O .) convention uses “normal” to mean the 
    inverter has power and is in Run or Stop Mode . The relay contacts switch to the opposite 
    position when it is in Trip M ode or when input power is OFF.
    Opt. Code05
    Symbol[AL]
    Valid for 
    Outputs[11 to [15],  [ALx]
    Required
    Settings C026, C036
    Default 
    terminals Relay [AL0], 
    [AL1], [AL2]
    Run Stop
    Fault Tr i pFault
    Alarm signal 
    active
    RUN
    STOP
    RESET
    STOPRESET
    Contact position after initializationContact position inverted by C036 setting
    During normal running When an alarm occurs or  power is turned OFFDuring normal running or 
    power is turned OFF When an alarm occurs
    AL1
    AL0AL2
    AL1
    AL0AL2
    AL1
    AL0AL2
    AL1
    AL0AL2
    ContactPowerRun 
    StateAL0- AL1AL0- AL2
    N.C. 
    (after 
    initialize, 
    C036=01) ON Normal Closed Open
    ON Trip Open Closed
    OFF – Open ClosedContactPowerRun 
    StateAL0- AL1AL0-AL2
    N.O.  (set 
    C036=00) ON Normal Open Closed
    ON Trip Closed Open
    OFF – Open Closed
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							Using Intelligent Output Terminals
    Operations
    and Monitoring
    4–48
    Over-torque 
    Signal   The Over-torque function [OTQ] turns ON when th e estimated value of output torque of motor 
    increases more than the arbitrary level set for the output (see table below). Recall that the 
    torque limit function, covered in  “
    Torque Limit” on page 4–30, actually limits the torque 
    during certain operating conditions. Instead, the over-torque output feature only monitors the 
    torque, turning ON output [OTQ] if the torque is  above programmable thresholds you set. The 
    [OTQ] function is valid only for sensorless vect or control, 0-Hz domain sensorless vector 
    control, or vector control with sensor. Do no t use the [OTQ] output except for these inverter 
    operational modes.
    The assignment of the Over-torque function to an  output terminal [OTQ] is detailed in the table 
    at the left.
    Instantaneous 
    Power Failure / 
    Under-voltage 
    Signal   An instantaneous power failure (complete loss)  or under-voltage condition (partial loss) of 
    inverter input voltage can  occur without warning. SJ700
    2 Series inverters can be configured to 
    respond to these condition s in different ways. You can select wh ether the inverter trips or retries 
    (restart attempt) when an instantaneous power  failure or under-voltage condition occurs. You 
    can select the retry func tion with parameter B001.
    When enabled, the Retry Function  operates in the following ways:
    Under-voltage conditions  – When an instantaneous power  failure or under-voltage condition 
    occurs, the inverter will attempt to restart up to 16 times. A trip condition will occur on the 17th 
    attempt, which must be cleared with the St op/Reset key. When connecting control power 
    supply terminals [Ro]–[To] to the DC bus [P]–[N ], an under-voltage may be detected at power-
    off and cause a trip. If this is undesirable, set B004 to 00 or 02.
    Over-current/voltage conditions  – When retry function is selected and an over-current or an 
    over-voltage condition occurs, a restart is attempte d 3 times. A trip will occur on the 4th failed 
    restart attempt. Use parameter B004 to select the trip and alarm response to instantaneous 
    power failure and under-voltage conditions. 
    If an over-voltage or over-current trip occurs  during the deceleration and an instantaneous 
    power failure error (E16) is displayed the inverter  goes into free-run stop. In this case make the 
    deceleration time longer.
    Opt. Code07
    Symbol[OTQ]
    Va l i d  f o r  
    Outputs[11 to [15],  [ALx]
    Required
    Settings C055, C056, 
    C057, C058
    A044 = 03 or  04 or 05
    Default 
    terminals[14]
    CodeFunction/DescriptionData or Range
    C055 Over-torque, forward-driving level setting 0 to 200%
    C056 Over-torque, reverse-regenerating, level setting 0 to 200%
    C057 Over-torque, reverse-driving, level setting 0 to 200%
    C058 Over-torque, forward-regenerating, level setting 0 to 200%
    C021 to C025 Intelligent output terminal [11] to [15] function 07
    Opt. Code 
    and 
    Symbol08=[IP]
    09=[UV]
    Va l i d  f o r   Outputs[11 to [15],  [ALx]
    Required
    Settings B001, B002, 
    B003, B004, 
    B005, B007
    Default 
    terminals Requires 
    config.
    SymbolFunction NameDescription
    IP Instantaneous Power Failure ON when the inverter detects a loss of input  power
    UV Under-voltage conditio nON when the inverter input power is less 
    than the specified input range
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–49
    Use the parameters listed in the table belo w to define Instantaneous Power Failure and 
    Under-voltage Signal operation.
    In the following examples, t
    0= instantaneous power failure time, t1 = allowable under-voltage / 
    power failure time (B002), and t
    2= retry wait time (B003).
    CodeFunctionData or RangeDescription
    B001 Selection of  automatic restart 
    mode 00 Alarm output after trip, automatic 
    restart disabled
    01 Restart at 0 Hz
    02 Retry with frequency matching to  present motor speed
    03 Retry with frequency matching  followed by deceleration to stop— then 
    trip alarm
    B002 Allowable under- voltage power 
    failure time 0.3 to 1.0 sec. The amount of time a power input 
    under-voltage can occur without 
    tripping the power failure alarm. If 
    under-voltage exists longer than this 
    time, the inverter trips, even if the restart 
    mode is selected. If it exists less than 
    this time retry will be attempted. 
    B003 Retry wait time  before motor 
    restart 0.3 to 100 sec. Time delay af
    ter a trip condition goes 
    away before the inverter restarts the 
    motor
    B004 Instantaneous  power failure / 
    voltage trip alarm 
    enable 00 Disable
    01 Enable
    02 Disable during stop and ramp to stop 
    B005 Number of restarts  on power failure / 
    under-voltage trip 
    events 00 Restart up to 16 times on instantaneous 
    power failure or under-voltage
    01 Always restart on instantaneous power  failure or an under-voltage condition
    B007 Restart frequency  threshold 0.00 to 400.0 Hz;
    model -4000HFx2 
    is 0.00 to 120.0 Hz When frequency of the motor is less 
    than this value, the inverter will restart 
    at 0 Hz
    Power supply
    Inverter output
    Motor
    frequency
    After waiting for t2 seconds when t0 < t1; restart
    Example 1: Power failure within allowed limits; resu me Example 2: Power failure longer than limits; trip
    t0
    t1
    t2
    Power supply
    Inverter output
    Motor
    frequency
    t0
    t1
    Inverter trips when t0 > t1
    Free-runFree-run
    tt
    
    Phone: 800.894.0412   
    						
    All Hitachi manuals Comments (0)