Home > Hitachi > Inverter > Hitachi Sj7002 Owners Manual

Hitachi Sj7002 Owners Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Hitachi Sj7002 Owners Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 913 Hitachi manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Using Intelligent Output Terminals
    Operations
    and Monitoring
    4–50
    Examples 3 and 4 relate to configuring the inverter to retry upon power failure. Frequency 
    matching is possible if the inverter frequency is  greater than the B007 value. In this case, the 
    inverter reads the motor RPM and direction. If  this speed is higher than the matching setting 
    (B007), the inverter waits until they are equal  and then engages the output to drive the motor 
    (example 3). If the actual motor speed is less th an the restart frequency setting, the inverter 
    waits for t
    2 (value in B003) and restarts from 0  Hz (example 4). The display shows “ 0000” 
    during an actual frequency matching event.
    The Instantaneous Power Failure and Alarm outp ut responses during various power loss condi-
    tions are shown in the diagram below. Use B004 to enable/disable the alarm output when 
    instantaneous power failure or under-voltage oc curs. The alarm output will continue while the 
    control power of the inverter is present, even  if the motor is stopped. Examples 5 to 7 
    correspond to normal wiring of the inverter’s co ntrol circuit. Examples 8 to 10 correspond to 
    the wiring of the inverter’s control circuit for  controlled deceleration after power loss (see 
    “
    Optional Controlled Decel  and Alarm at Power Loss” on page 4–4).
    Power supply
    Inverter output
    Motor
    frequency
    Motor frequency > B007 value at t2
    Example 3: Motor resumes via frequency-matching Example 4: Motor restarts from 0Hz
    t0t2
    Power supply
    Inverter output
    Motor
    frequency
    t0t2
    Free-runFree-run
    Frequency matching 0Hz restart
    Motor frequency < B007 value at t2
    B007B007
    tt
    Instantaneous power failure operation with standard  R0–T0 connections Instantaneous power failure operation with R0–T0 
    connected to P–N
    Example 5
    Powe r1
    0
    1
    0Run command
    Output
    Alarm Inst. Power Fail
    1
    0
    1
    0
    Inverter : Stop
    Example 6
    Powe r 1
    0
    1
    0Run command
    Output
    Alarm Inst. Power Fail
    1
    0
    1
    0
    Inverter : Stop
    1
    0
    1
    0
    1
    0
    1
    0
    Power
    Run command
    Output
    Alarm Inst. Power Fail
    Example 7Inverter : Stop Power
    1
    0
    1
    0Run command
    Output
    Alarm Inst. Power Fail
    1
    0
    1
    0
    Inverter : Run
    Power 1
    0
    Run command
    Output
    Alarm Inst. Power Fail
    1
    0
    1
    0
    Inverter : Run
    1
    0
    1
    0
    1
    0
    1
    0
    Powe r Run command
    Output
    Alarm Inst. Power Fail Inverter : Run
    1
    0
    Example 8
    Power
    1
    0
    1
    0Run command
    Output
    Alarm Inst. Power Fail
    1
    0
    1
    0
    Inverter : Stop
    Example 9
    Power 1
    0
    1
    0Run command
    Output
    Alarm Inst. Power Fail
    1
    0
    1
    0
    Inverter : Stop
    1
    0
    1
    0
    1
    0
    1
    0
    Power
    Run command
    Output
    Alarm Inst. Power Fail
    Example 10Inverter : Stop Power
    1
    0
    1
    0Run command
    Output
    Alarm Inst. Power Fail
    1
    0
    1
    0
    Inverter : Run
    Power 1
    0
    Run command
    Output
    Alarm Inst. Power Fail
    1
    0
    1
    0
    Inverter : Run
    1
    0
    1
    0
    1
    0
    1
    0
    Power Run command
    Output
    Alarm Inst. Power Fail Inverter : Run
    1
    0
    (under-voltage)
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–51
    To r q u e  L i m i t  
    Signal   The Torque Limit output [TRQ] work s in conjunction with the torque limit function covered in 
    the intelligent input section. The torque limit function limits the motor torque according to the 
    criteria selected by parameter  B040. When torque limiting occurs, the [TRQ] output turns ON, 
    then turns OFF automatically when the output torque falls below the specified limits. Note that 
    the Torque Limit input [TL] must be ON in order to enable torque  limiting and its related 
    output, [TRQ]. See  “
    To r q u e  L i m i t” on page 4–30 in the intelligent input section.
    Run Time / 
    Power-On Time 
    Over Signals   SJ7002 Series inverters accumulate the total hours  in Run Mode (run time) and the total hours 
    of power-ON time. You can set thresholds for thes e accumulating timers. Once the threshold is 
    exceeded, an output terminal will turn ON. One us e of this is for preventative maintenance. A 
    signal light or audible alert  could signal the need for servicing, calibration, etc.
    The two outputs [RNT] and [ONT] share the same  time threshold parameter, B034. Typically, 
    you will use either the [RNT] or the [ONT]  output only—not both at once. These outputs are 
    useful for the notification that a preventative maintenance interval has expired.
    Opt. Code10
    Symbol[TRQ]
    Valid for 
    Outputs[11 to [15],  [ALx]
    Required
    Settings B040... if 
    B040=00  then set 
    B041, B042,  B043, B044
    Default 
    terminals Requires 
    config.
    Opt. Code 
    and 
    Symbol11=[RNT]
    12=[ONT]
    Valid for  Outputs[11 to [15],  [ALx]
    Required
    Settings B034
    Default 
    terminals Requires 
    config.
    SymbolFunction NameDescription
    RNT Run Time Over ON when the accumulated time spent in  Run Mode exceeds the limit (B034)
    ONT Power-ON Time Over ON when th e accumulated power-ON time 
    exceeds the limit (B034)
    
    Phone: 800.894.0412   
    						
    							Using Intelligent Output Terminals
    Operations
    and Monitoring
    4–52
    Thermal Warning 
    Signal   The purpose of the electronic thermal setti ng is to protect the motor from overloading, 
    overheating and being damaged. The setting is base d on the rated motor current. The inverter 
    calculates the thermal rise (heating) of the moto r using the current output to the motor squared, 
    integrated over the time spent at those levels. This feature allows the motor to draw excessive 
    current for relatively short periods  of time, allowing time for cooling.
    The Thermal Warning output [THM] turns ON to provide a warning before the inverter trips for 
    electronic thermal protection. You can set a uniq ue thermal protection level for each of the 
    three motor profiles, as shown in the table below.
     The electronic thermal overload function uses  the output current and time to calculate 
    thermal heating of the motor. Use parameter C061  to set the threshold from 0 to 100% of trip 
    level for turning ON the intelligent output [THM] at that level.
     The thermistor input of the inverter is a  separate function from the electronic thermal 
    function. It has its own threshold to cause a trip  alarm at a particular thermistor resistance.
    For example, suppose you have inverter model 
    SJ700-110LFE2. The rated motor current is 46A. 
    The setting range is (0.2 * 46) to (1.2 *46), or 
    9.2A to 55.2A. For a setting of B012=46A 
    (current at 100%), the figure to the right shows 
    the curve.
    The electronic thermal characteristic adjusts the 
    way the inverter calculates thermal heating, 
    based on the type of torque control the inverter 
    uses.
    CAUTION:  When the motor runs at lower 
    speeds, the cooling effect of the motor’s internal 
    fan decreases.
    Reduced Torque Characteristic  – The example below shows the effect of the reduced torque 
    characteristic curve (for example motor and curre nt rating). At 20Hz, the output current is 
    reduced by a factor of 0.8 for given trip times. 
    Opt. Code10
    Symbol[THM]
    Va l i d  f o r  
    Outputs[11 to [15],  [ALx]
    Required
    Settings C061
    Default 
    terminals Requires 
    config.
    Function
    CodeFunction/DescriptionData or Range
    B012 / B212  / B312 Electronic thermal setting (calculated 
    within the inverter from current output)  Range is 0.2 * rated current to
    1.2 * rated current
    B013 / B213  /B313 Electronic thermal characteristic (use 
    the setting that matches your load) 00 Reduced torque
    01 Constant torque
    02 Free-setting
    Tr i p
    time (s)
    Trip current at 60 Hz
    60
    0.5 0 53.4 69 92 A
    116% 150% 200%
    Tr i p
    time (s)
    Reduced trip current at 20 Hz
    Trip current 
    reduction  factor
    x 1.0
    x 0.8
    x 0.6
    0 520 60 Hz
    A
    60
    0.5 0 73.6
    42.7 55.2
    92.8% 120% 160%
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–53
    Constant Torque Characteristic  – Selecting the constant torque characteristic for the example 
    motor gives the curves below. At 2.5 Hz, the outp ut current is reduced by a factor of 0.9 for 
    given trip times.
    Free Thermal Characteristic  - It is possible to set the electronic thermal characteristic using a 
    free-form curve defined by three data  points, according to the table below.
    The left graph below shows the region for possi ble free-setting curves. The right graph below 
    shows an example curve defined by three data points specified by B015 – B020.
    Suppose the electronic thermal setting (B012) is  set to 44 Amperes. The graph below shows the 
    effect of the free setting torque  characteristic curve. For example, at (B017) Hz, the output 
    current level to cause overheating in a fixed time period is reduced to (B018) A. Points (x), (y), 
    and (z) show the adjusted trip current levels in those conditions for given trip times.
    Function CodeNameDescriptionRange
    B015 / 
    B017 / B019 Free-setting electronic 
    thermal frequency 1, 2, 3
    Data point coordinates for Hz axis 
    (horizontal) in the free-form curve 0 to 400Hz
    B016 / 
    B018 /  B020 Free setting electronic 
    thermal current 1, 2, 3
    Data point coordinates for Ampere 
    axis (vertical) in the free-form curve 0.0 = (disable)
    0.1 to 1000.
    Tr i p
    time (s)
    Reduced trip current at 2.5 Hz
    Trip current 
    reduction 
    factor
    x 1.0
    x 0.9
    x 0.8
    0 2.5 5 60Hz
    A
    60
    0.5 0 82.8
    47.8 62.1
    104% 135% 180%
    Output
    current (A)
    Setting range
    max. freq.
    B020
    B018
    B016
    B015B017B019Ax04
    Trip current 
    reduction  factorOutput freq.
    x 1.0
    x 0.8
    0 5400 Hz
    Hz
    0
    Tr i p
    time (s)
    (x) = B018 value x 116%
    (y) = B018 value x 120%
    (z) = B018 value x 150%
    Reduced trip current at (B017) Hz
    60
    0
    0.5
    (x) (y) (z) A
    
    Phone: 800.894.0412   
    						
    							Using Intelligent Output Terminals
    Operations
    and Monitoring
    4–54
    Brake Control
    Signals   The Brake Control function enables the inverter to control external braking systems with a 
    particular safety characteristic. The brake releas e logic convention is such that an open circuit 
    fault (such as loose wire) causes the external brake to engage. A complete discussion of the 
    operation of brake control is in  “
    External Brake Control Function” on page 4–32. The diagram 
    below shows the signals that are important to  the External Brake Control function.    
    Expansion Card 
    Output Signals   Other outputs listed below require expansion card  SJ-FB Encoder Feedback board. Please see 
    the SJ-FB manual for more information.
    Opt. Code 
    and 
    Symbol19=[BRK]
    20=[BER]
    Va l i d  f o r   Outputs[11 to [15],  [ALx]
    Required
    Settings B120, B121, 
    B122, B123, 
    B124, B125, 
    B126
    Default 
    terminals Requires 
    config.
    SymbolFunction NameInput 
    StateDescription
    BRK Brake Release ON when the inverter signals the external brake  system to release (open) its brake
    OFF when the inverter is not driving the motor, and  needs the external brake engaged
    BER Brake Error ON when the output  current is less than the set 
    releasing current
    OFF when the brake function is not in use, or when  the output current to the motor is correct and 
    it is safe to release the brake
    [BRK] Brake release
    [BOK] Brake confirmation
    Inverter
    Brake System
    Emergency Brake[BER] Brake error
    Opt. Code 
    and 
    Symbol21=[ZS]
    22=[DSE]
    23=[POK]
    Va l i d  f o r   Outputs[11 to [15],  [ALx]
    Required
    Settings C061
    Default 
    terminals Requires 
    config.
    Opt.
    CodeSymbolFunction NameDescription
    21 ZS Zero Speed Detect  signal Signal indicates the encoder pulses of the 
    motor have stopped
    22 DSE Speed Deviation Excessive Velocit y error exceeds the error threshold 
    defined by parameter P026
    23 POK Positioning Completion Indicates the load position is at the target
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–55
    Analog 
    Disconnect
    Detection   The analog disconnect dete ction is useful when the inverter  receives a speed reference from an 
    external device. Upon input signal loss at either the [O], [OI], or [O2] terminal, the inverter 
    normally just decelerates the motor to a stop.  However, the inverter can use the intelligent 
    output terminals [ODc],  [OIdc], or [O2dc] to signal othe r machinery that a signal loss has 
    occurred.
    Each analog disconnect output has independent thresholds, set by B070, B071, and B072. 
    When the input is below the set threshold value,  the inverter substitutes the threshold value for 
    the input. Related parameters are gi ven in the following tables.   
    The inverter can also detect when an analog input value is within a range (or  window) of values. 
    See  “
    Window Comparator Signals” on page 4–62.
    Opt. Code 
    and 
    Symbol27=[Odc]
    28=[OIdc]
    29=[O2dc]
    Valid for  Outputs[11 to [15],  [ALx]
    Required
    Settings B070, B071, 
    B072
    Default 
    terminal Requires 
    config.
    Opt.
    CodeSymbolFunction Name
    27 Odc Analog [O] disconnect detect
    28 OIdc Analog [OI] di sconnect detect
    29 O2dc Analog [O2]  disconnect detect
    CodeFunctionData or RangeDescription
    B070 [O] input disconnect  threshold 0 to 100% If [O] value < B070, turn ON [Odc]; 
    substitute B070 value for [O] input
    no (255) Ignore B070 setting
    B071 [OI] input disconnect  threshold 0 to 100% If [OI] value < B071, turn ON [Odc]; 
    substitute B071 value for [OI] input
    no (255) Ignore B071 setting
    B072 [O2] input disconnect  threshold 0 to 100% If [O2] value < B072, turn ON [Odc]; 
    substitute B072 value for [O2] input
    no (255) Ignore B072 setting
    [O], [OI], or [O2]
    t
    0
    Value applied to input
    t
    B070B071B072
    [Odc], [OIdc], or [O2dc]
    
    Phone: 800.894.0412   
    						
    							Using Intelligent Output Terminals
    Operations
    and Monitoring
    4–56
    PID Feedback 
    Second Stage 
    Output   The inverter has a built-in PID loop feature for tw o-stage control, useful for certain applications 
    such as building ventilation or heating and cool ing (HVAC). In an ideal control environment, a 
    single PID loop controller (stage) would be  adequate. However, in certain conditions, the 
    maximum output energy from the first stage is  not enough to maintain the Process Variable 
    (PV) at or near the Setpoint (SP). And, the output  of the first stage is in saturation. A simple 
    solution is to add a second stage, which puts an  additional and constant amount of energy into 
    the system under control. When  sized properly, the boost from the second stage brings the PV 
    toward the desired range, allowing the first stag e PID control to return to its linear range of 
    operation.
    The two-stage method of control has some  advantages for particular applications.
     The second stage is only ON in adverse condi tions, so there is an energy savings during 
    normal conditions.
     Since the second stage is simple ON/OFF control,  it is less expensive to add than just dupli-
    cating the first stage.
     At powerup, the boost provided by the second  stage helps the process variable reach the 
    desired setpoint sooner than it wo uld if the first stage acted alone.
     Even though the second stage is simple ON/OFF co ntrol, when it is an inverter you can still 
    adjust the output frequency to  vary the boost it provides.
    Refer to the example diagram  below. Its two stages of control are defined as follows:
     Stage 1 - Inverter #1 operating in PI D loop mode, with motor driving a fan
     Stage 2 - Inverter #2 operating as an ON/ OFF controller, with motor driving a fan
    Stage #1 provides the ventilation needs in a build ing most of the time. On some days, there is a 
    change in the building’s air volume because larg e warehouse doors are open. In that situation, 
    Stage #1 alone cannot ma intain the desired air flow (PV sa gs under SP). Inverter #1 senses the 
    low PV and its PID Second Stage Output at [F BV] terminal turns ON. This gives a Run FWD 
    command to Inverter #2 to pr ovide the additional air flow.
    NOTE: The [FBV] is designed for implementing two- stage control. The PV high limit and PV 
    low limit parameters, C052 and C053, do not func tion as process alarm thresholds. Terminal 
    [FBV] does not provide a PID alarm function.
    Opt. Code31
    Symbol[FBV]
    Va l i d  f o r  
    Outputs[11 to [15],  [ALx]
    Required
    Settings C052, C053
    Monitor 
    Settings D004
    Default 
    terminals Requires 
    config.
    Fan  #1
    Inverter #2[U, V, W]
    [FW]
    PID Second Stage Output Air flow Sensor
    Fan #2
    [FBV]
    [U, V, W]
    Inverter #1
    [O], [OI], or [O2]
    Stage #1 Stage #2
    Process Variable
    PV
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–57
    To use the PID Second Stage Output feature, you  will need to choose upper and lower limits for 
    the PV, via C053 and C052 respectively. As th e timing diagram below shows, these are the 
    thresholds Stage #1 inverter uses to turn ON  or OFF Stage #2 inverter via the [FBV] output. 
    The vertical axis units are perc ent (%) for the PID setpoint, and for the upper and lower limits. 
    The output frequency, in Hz, is  superimposed onto the same diagram.
    When system control begins, the following even ts occur (in sequence in the timing diagram):
    1. Stage #1 inverter turns ON via the [FW] Run command.
    2. Stage #1 inverter turns ON the [FBV] output, because the PV is below the PV low limit 
    C053. So, Stage #2 is assisting in lo op error correction from the beginning.
    3. The PV rises and eventually ex ceeds the PV high limit C052. Stage #1 inverter then turns 
    OFF the [FBV] output to Stage #2, si nce the boost is no longer needed.
    4. When the PV begins decreasing, only Stage #1 is operating, and it is  in the linear control 
    range. This region is where a properly co nfigured system will operate most often.
    5. The PV continues to decrease  until it crosses under the PV low limit (apparent external 
    process disturbance). Stage #1 inverter turns  ON the [FBV] output, and Stage #2 inverter is 
    assisting again.
    6. After the PV rises above the PV low limit, the [FW] Run command to Stage #1 inverter 
    turns OFF (as in a  system shutdown).
    7. Stage #1 inverter enters Stop Mode and au tomatically turns OFF the [FBV] output, which 
    causes Stage #2 inverter to also stop.
    Network 
    Detection Signal  The intelligent output [Ndc] Network Detection  Signal indicates the status of ModBus-RTU 
    communications (not ASCII protocol). The [Ndc]  terminal turns ON when the external device 
    on the ModBus stops transmitting for a time that exceeds parame ter C077, Communication 
    Time-out Before Trip. If a time-out occurs,  the output [Ndc] remains ON until ModBus-RTU 
    communication resumes. Use pa rameter C076 Action Upon Comm unication Error Selection to 
    select the desired inverter re sponse to a time-out event.
    PV high limit
    t
    0
    tC052
    C053
    Stage #1 [FW] t
    [FBV] to Stage #2 [FW]PV low limit 1
    0 1PID setpoint (SP)
    PID feedback (PV)
    Output frequency
    1, 2 3 4 5
    Example:
    67
    Opt. Code32
    Symbol[Ndc]
    Valid for 
    Outputs[11 to [15],  [ALx]
    Required
    Settings C076, C077
    Default 
    terminals Requires 
    config.
    Master
    t
    0
    C077
    1
    Slave (inver ter)
    Watchdog timer = xx.xx sec.
    0 1
    Alarm output [ALx] Time-out
    C076
    = 00 or 01 (trip)
    Network detection [Ndc]
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							Using Intelligent Output Terminals
    Operations
    and Monitoring
    4–58
    Logic Output 
    Signals   The Logic Output Function uses the inverter’s bu ilt-in logic feature. You can select any two of 
    the other intelligent output options for use as in ternal inputs to the logic function. You may also 
    select from three logical operators AND, OR, or XOR  (exclusive OR), to be applied to the two 
    inputs. A total of six outputs are avai lable, shown in the following tables.
    The example below shows a configuration for  [LOG1] Logic Output 1. Parameters C142 and 
    C143 contain option codes for two outpu ts we select to be used as inputs to the logic operation. 
    Parameter C144 contains the  select code for the logic operation. 00=AND, 01=OR, and 
    02=OR.    
    Capacitor Life 
    Warning   The inverter calculates the capacitor life remaining based on the internal temperature of the 
    inverter and the cumulative power-ON time. Th e [WAC] Capacitor Life Warning output turns 
    ON to indicate that the capaci tors have reached end-of-life. If this event occurs, Hitachi 
    recommends that you replace the  main circuit board and logic circuit board. You may also use 
    monitor parameter D022 at the di gital operator to monitor the status of capacitor life.
    Opt. Code 
    and 
    Symbol
    33=[LOG1]
    34=[LOG2]
    35=[LOG3]
    36=[LOG4]
    37=[LOG5]
    38=[LOG6]
    Va l i d  f o r   Outputs[11 to [15],  [ALx]
    Required
    Settings C142 to 
    C159
    Default 
    terminal Requires 
    config.
    SymbolOption 
    CodeFunctionA InputB InputLogical Operator
    LOG1 33 Logic Output 1C142 C143 C144
    LOG2 34 Logic Output 2C145 C146C147
    LOG3 35 Logic Output 3C148 C149C150
    LOG4 36 Logic Output 4C151 C152C153
    LOG5 37 Logic Output 5C154 C155C156
    LOG6 38 Logic Output 6C157 C158C159
    Input States[LOGx] Output State
    A InputB InputAND (00)OR (01XOR (02)
    000
    00
    01011
    10011
    11110
    C142
    A input
    B input Logic function 
    AND, OR, XOR
    [LOG1]
    Intelligent outputs used as internal 
    inputs: RUN, FA1, FA2, OL, OD, etc.:C143
    C144
    [RUN] = option code 00
    [FA2] = option code 02
    Opt. Code39
    Symbol[WAC]
    Va l i d  f o r  Outputs[11 to [15],  [ALx]
    Monitor
    Settings D022
    Default 
    terminals Requires 
    config.
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–59
    Low Cooling Fan 
    Speed   The inverter monitors the heat  sink cooling fan speed to help prevent overheating. If the speed 
    of the fan(s) decreases to 75% or less of full speed, output [WAF] Low Cooling Fan Speed 
    turns ON. Note that if you set parameter B092  Cooling Fan Control = 01 (Fan ON only during 
    RUN), the inverter will not output the [WAF ] signal when the cooling fan is stopped.
    If the [WAF] signal turns ON during operation,  first check the cooling fan inlet for clogging by 
    dust and debris. If the air circulation path is cl ear, the fans may need replacement. You may also 
    use monitor parameter D022 at the digital ope rator to monitor the status of fan speed.
    Starting Contact 
    Signal   The inverter generates [FR] Starting Contact Signal to correspond with Run (FW or RV) input 
    commands. The source of the Run command does no t matter (so the A002 setting is ignored). If 
    both FW and RV inputs are ON, the inverter  stops motor operation and turns OFF the [FR] 
    output. The [FR] signal is useful  for external devices that need a traditional starting contact 
    signal to coordina te operation with the inverter.
    Heatsink 
    Overheat 
    Warning   The inverter monitors its heat sink temperature to detect ove rheating. You can use parameter 
    C064, Heatsink Overheat Warning Level, to se t the over-temperature threshold for the heatsink 
    in degrees C. The inverter will turn ON intelligent output [OHF] Heatsink Overheat Warning if 
    the heatsink temperature exceed s the value in parameter C064.
    Opt. Code40
    Symbol[WAF]
    Valid for 
    Outputs[11 to [15],  [ALx]
    Required
    Settings B092
    Monitor
    Settings D022
    Default 
    terminals Requires 
    config.
    Opt. Code41
    Symbol[FR]
    Valid for 
    Outputs[11 to [15],  [ALx]
    Required
    Settings none
    Default 
    terminals Requires 
    config.
    Forward command
    Reverse command
    Starting Contact Signal [FR]
    Opt. Code42
    Symbol[OHF]
    Valid for 
    Outputs[11 to [15],  [ALx]
    Required
    Settings C064
    Default 
    terminals Requires 
    config.
    
    Phone: 800.894.0412   
    						
    All Hitachi manuals Comments (0)