Hitachi Sj7002 Owners Manual
Have a look at the manual Hitachi Sj7002 Owners Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 913 Hitachi manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
Using Intelligent Output Terminals Operations and Monitoring 4–50 Examples 3 and 4 relate to configuring the inverter to retry upon power failure. Frequency matching is possible if the inverter frequency is greater than the B007 value. In this case, the inverter reads the motor RPM and direction. If this speed is higher than the matching setting (B007), the inverter waits until they are equal and then engages the output to drive the motor (example 3). If the actual motor speed is less th an the restart frequency setting, the inverter waits for t 2 (value in B003) and restarts from 0 Hz (example 4). The display shows “ 0000” during an actual frequency matching event. The Instantaneous Power Failure and Alarm outp ut responses during various power loss condi- tions are shown in the diagram below. Use B004 to enable/disable the alarm output when instantaneous power failure or under-voltage oc curs. The alarm output will continue while the control power of the inverter is present, even if the motor is stopped. Examples 5 to 7 correspond to normal wiring of the inverter’s co ntrol circuit. Examples 8 to 10 correspond to the wiring of the inverter’s control circuit for controlled deceleration after power loss (see “ Optional Controlled Decel and Alarm at Power Loss” on page 4–4). Power supply Inverter output Motor frequency Motor frequency > B007 value at t2 Example 3: Motor resumes via frequency-matching Example 4: Motor restarts from 0Hz t0t2 Power supply Inverter output Motor frequency t0t2 Free-runFree-run Frequency matching 0Hz restart Motor frequency < B007 value at t2 B007B007 tt Instantaneous power failure operation with standard R0–T0 connections Instantaneous power failure operation with R0–T0 connected to P–N Example 5 Powe r1 0 1 0Run command Output Alarm Inst. Power Fail 1 0 1 0 Inverter : Stop Example 6 Powe r 1 0 1 0Run command Output Alarm Inst. Power Fail 1 0 1 0 Inverter : Stop 1 0 1 0 1 0 1 0 Power Run command Output Alarm Inst. Power Fail Example 7Inverter : Stop Power 1 0 1 0Run command Output Alarm Inst. Power Fail 1 0 1 0 Inverter : Run Power 1 0 Run command Output Alarm Inst. Power Fail 1 0 1 0 Inverter : Run 1 0 1 0 1 0 1 0 Powe r Run command Output Alarm Inst. Power Fail Inverter : Run 1 0 Example 8 Power 1 0 1 0Run command Output Alarm Inst. Power Fail 1 0 1 0 Inverter : Stop Example 9 Power 1 0 1 0Run command Output Alarm Inst. Power Fail 1 0 1 0 Inverter : Stop 1 0 1 0 1 0 1 0 Power Run command Output Alarm Inst. Power Fail Example 10Inverter : Stop Power 1 0 1 0Run command Output Alarm Inst. Power Fail 1 0 1 0 Inverter : Run Power 1 0 Run command Output Alarm Inst. Power Fail 1 0 1 0 Inverter : Run 1 0 1 0 1 0 1 0 Power Run command Output Alarm Inst. Power Fail Inverter : Run 1 0 (under-voltage) Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
SJ7002 Inverter Operations and Monitoring 4–51 To r q u e L i m i t Signal The Torque Limit output [TRQ] work s in conjunction with the torque limit function covered in the intelligent input section. The torque limit function limits the motor torque according to the criteria selected by parameter B040. When torque limiting occurs, the [TRQ] output turns ON, then turns OFF automatically when the output torque falls below the specified limits. Note that the Torque Limit input [TL] must be ON in order to enable torque limiting and its related output, [TRQ]. See “ To r q u e L i m i t” on page 4–30 in the intelligent input section. Run Time / Power-On Time Over Signals SJ7002 Series inverters accumulate the total hours in Run Mode (run time) and the total hours of power-ON time. You can set thresholds for thes e accumulating timers. Once the threshold is exceeded, an output terminal will turn ON. One us e of this is for preventative maintenance. A signal light or audible alert could signal the need for servicing, calibration, etc. The two outputs [RNT] and [ONT] share the same time threshold parameter, B034. Typically, you will use either the [RNT] or the [ONT] output only—not both at once. These outputs are useful for the notification that a preventative maintenance interval has expired. Opt. Code10 Symbol[TRQ] Valid for Outputs[11 to [15], [ALx] Required Settings B040... if B040=00 then set B041, B042, B043, B044 Default terminals Requires config. Opt. Code and Symbol11=[RNT] 12=[ONT] Valid for Outputs[11 to [15], [ALx] Required Settings B034 Default terminals Requires config. SymbolFunction NameDescription RNT Run Time Over ON when the accumulated time spent in Run Mode exceeds the limit (B034) ONT Power-ON Time Over ON when th e accumulated power-ON time exceeds the limit (B034) Phone: 800.894.0412
Using Intelligent Output Terminals Operations and Monitoring 4–52 Thermal Warning Signal The purpose of the electronic thermal setti ng is to protect the motor from overloading, overheating and being damaged. The setting is base d on the rated motor current. The inverter calculates the thermal rise (heating) of the moto r using the current output to the motor squared, integrated over the time spent at those levels. This feature allows the motor to draw excessive current for relatively short periods of time, allowing time for cooling. The Thermal Warning output [THM] turns ON to provide a warning before the inverter trips for electronic thermal protection. You can set a uniq ue thermal protection level for each of the three motor profiles, as shown in the table below. The electronic thermal overload function uses the output current and time to calculate thermal heating of the motor. Use parameter C061 to set the threshold from 0 to 100% of trip level for turning ON the intelligent output [THM] at that level. The thermistor input of the inverter is a separate function from the electronic thermal function. It has its own threshold to cause a trip alarm at a particular thermistor resistance. For example, suppose you have inverter model SJ700-110LFE2. The rated motor current is 46A. The setting range is (0.2 * 46) to (1.2 *46), or 9.2A to 55.2A. For a setting of B012=46A (current at 100%), the figure to the right shows the curve. The electronic thermal characteristic adjusts the way the inverter calculates thermal heating, based on the type of torque control the inverter uses. CAUTION: When the motor runs at lower speeds, the cooling effect of the motor’s internal fan decreases. Reduced Torque Characteristic – The example below shows the effect of the reduced torque characteristic curve (for example motor and curre nt rating). At 20Hz, the output current is reduced by a factor of 0.8 for given trip times. Opt. Code10 Symbol[THM] Va l i d f o r Outputs[11 to [15], [ALx] Required Settings C061 Default terminals Requires config. Function CodeFunction/DescriptionData or Range B012 / B212 / B312 Electronic thermal setting (calculated within the inverter from current output) Range is 0.2 * rated current to 1.2 * rated current B013 / B213 /B313 Electronic thermal characteristic (use the setting that matches your load) 00 Reduced torque 01 Constant torque 02 Free-setting Tr i p time (s) Trip current at 60 Hz 60 0.5 0 53.4 69 92 A 116% 150% 200% Tr i p time (s) Reduced trip current at 20 Hz Trip current reduction factor x 1.0 x 0.8 x 0.6 0 520 60 Hz A 60 0.5 0 73.6 42.7 55.2 92.8% 120% 160% Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
SJ7002 Inverter Operations and Monitoring 4–53 Constant Torque Characteristic – Selecting the constant torque characteristic for the example motor gives the curves below. At 2.5 Hz, the outp ut current is reduced by a factor of 0.9 for given trip times. Free Thermal Characteristic - It is possible to set the electronic thermal characteristic using a free-form curve defined by three data points, according to the table below. The left graph below shows the region for possi ble free-setting curves. The right graph below shows an example curve defined by three data points specified by B015 – B020. Suppose the electronic thermal setting (B012) is set to 44 Amperes. The graph below shows the effect of the free setting torque characteristic curve. For example, at (B017) Hz, the output current level to cause overheating in a fixed time period is reduced to (B018) A. Points (x), (y), and (z) show the adjusted trip current levels in those conditions for given trip times. Function CodeNameDescriptionRange B015 / B017 / B019 Free-setting electronic thermal frequency 1, 2, 3 Data point coordinates for Hz axis (horizontal) in the free-form curve 0 to 400Hz B016 / B018 / B020 Free setting electronic thermal current 1, 2, 3 Data point coordinates for Ampere axis (vertical) in the free-form curve 0.0 = (disable) 0.1 to 1000. Tr i p time (s) Reduced trip current at 2.5 Hz Trip current reduction factor x 1.0 x 0.9 x 0.8 0 2.5 5 60Hz A 60 0.5 0 82.8 47.8 62.1 104% 135% 180% Output current (A) Setting range max. freq. B020 B018 B016 B015B017B019Ax04 Trip current reduction factorOutput freq. x 1.0 x 0.8 0 5400 Hz Hz 0 Tr i p time (s) (x) = B018 value x 116% (y) = B018 value x 120% (z) = B018 value x 150% Reduced trip current at (B017) Hz 60 0 0.5 (x) (y) (z) A Phone: 800.894.0412
Using Intelligent Output Terminals Operations and Monitoring 4–54 Brake Control Signals The Brake Control function enables the inverter to control external braking systems with a particular safety characteristic. The brake releas e logic convention is such that an open circuit fault (such as loose wire) causes the external brake to engage. A complete discussion of the operation of brake control is in “ External Brake Control Function” on page 4–32. The diagram below shows the signals that are important to the External Brake Control function. Expansion Card Output Signals Other outputs listed below require expansion card SJ-FB Encoder Feedback board. Please see the SJ-FB manual for more information. Opt. Code and Symbol19=[BRK] 20=[BER] Va l i d f o r Outputs[11 to [15], [ALx] Required Settings B120, B121, B122, B123, B124, B125, B126 Default terminals Requires config. SymbolFunction NameInput StateDescription BRK Brake Release ON when the inverter signals the external brake system to release (open) its brake OFF when the inverter is not driving the motor, and needs the external brake engaged BER Brake Error ON when the output current is less than the set releasing current OFF when the brake function is not in use, or when the output current to the motor is correct and it is safe to release the brake [BRK] Brake release [BOK] Brake confirmation Inverter Brake System Emergency Brake[BER] Brake error Opt. Code and Symbol21=[ZS] 22=[DSE] 23=[POK] Va l i d f o r Outputs[11 to [15], [ALx] Required Settings C061 Default terminals Requires config. Opt. CodeSymbolFunction NameDescription 21 ZS Zero Speed Detect signal Signal indicates the encoder pulses of the motor have stopped 22 DSE Speed Deviation Excessive Velocit y error exceeds the error threshold defined by parameter P026 23 POK Positioning Completion Indicates the load position is at the target Phone: 800.894.0412
SJ7002 Inverter Operations and Monitoring 4–55 Analog Disconnect Detection The analog disconnect dete ction is useful when the inverter receives a speed reference from an external device. Upon input signal loss at either the [O], [OI], or [O2] terminal, the inverter normally just decelerates the motor to a stop. However, the inverter can use the intelligent output terminals [ODc], [OIdc], or [O2dc] to signal othe r machinery that a signal loss has occurred. Each analog disconnect output has independent thresholds, set by B070, B071, and B072. When the input is below the set threshold value, the inverter substitutes the threshold value for the input. Related parameters are gi ven in the following tables. The inverter can also detect when an analog input value is within a range (or window) of values. See “ Window Comparator Signals” on page 4–62. Opt. Code and Symbol27=[Odc] 28=[OIdc] 29=[O2dc] Valid for Outputs[11 to [15], [ALx] Required Settings B070, B071, B072 Default terminal Requires config. Opt. CodeSymbolFunction Name 27 Odc Analog [O] disconnect detect 28 OIdc Analog [OI] di sconnect detect 29 O2dc Analog [O2] disconnect detect CodeFunctionData or RangeDescription B070 [O] input disconnect threshold 0 to 100% If [O] value < B070, turn ON [Odc]; substitute B070 value for [O] input no (255) Ignore B070 setting B071 [OI] input disconnect threshold 0 to 100% If [OI] value < B071, turn ON [Odc]; substitute B071 value for [OI] input no (255) Ignore B071 setting B072 [O2] input disconnect threshold 0 to 100% If [O2] value < B072, turn ON [Odc]; substitute B072 value for [O2] input no (255) Ignore B072 setting [O], [OI], or [O2] t 0 Value applied to input t B070B071B072 [Odc], [OIdc], or [O2dc] Phone: 800.894.0412
Using Intelligent Output Terminals Operations and Monitoring 4–56 PID Feedback Second Stage Output The inverter has a built-in PID loop feature for tw o-stage control, useful for certain applications such as building ventilation or heating and cool ing (HVAC). In an ideal control environment, a single PID loop controller (stage) would be adequate. However, in certain conditions, the maximum output energy from the first stage is not enough to maintain the Process Variable (PV) at or near the Setpoint (SP). And, the output of the first stage is in saturation. A simple solution is to add a second stage, which puts an additional and constant amount of energy into the system under control. When sized properly, the boost from the second stage brings the PV toward the desired range, allowing the first stag e PID control to return to its linear range of operation. The two-stage method of control has some advantages for particular applications. The second stage is only ON in adverse condi tions, so there is an energy savings during normal conditions. Since the second stage is simple ON/OFF control, it is less expensive to add than just dupli- cating the first stage. At powerup, the boost provided by the second stage helps the process variable reach the desired setpoint sooner than it wo uld if the first stage acted alone. Even though the second stage is simple ON/OFF co ntrol, when it is an inverter you can still adjust the output frequency to vary the boost it provides. Refer to the example diagram below. Its two stages of control are defined as follows: Stage 1 - Inverter #1 operating in PI D loop mode, with motor driving a fan Stage 2 - Inverter #2 operating as an ON/ OFF controller, with motor driving a fan Stage #1 provides the ventilation needs in a build ing most of the time. On some days, there is a change in the building’s air volume because larg e warehouse doors are open. In that situation, Stage #1 alone cannot ma intain the desired air flow (PV sa gs under SP). Inverter #1 senses the low PV and its PID Second Stage Output at [F BV] terminal turns ON. This gives a Run FWD command to Inverter #2 to pr ovide the additional air flow. NOTE: The [FBV] is designed for implementing two- stage control. The PV high limit and PV low limit parameters, C052 and C053, do not func tion as process alarm thresholds. Terminal [FBV] does not provide a PID alarm function. Opt. Code31 Symbol[FBV] Va l i d f o r Outputs[11 to [15], [ALx] Required Settings C052, C053 Monitor Settings D004 Default terminals Requires config. Fan #1 Inverter #2[U, V, W] [FW] PID Second Stage Output Air flow Sensor Fan #2 [FBV] [U, V, W] Inverter #1 [O], [OI], or [O2] Stage #1 Stage #2 Process Variable PV Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
SJ7002 Inverter Operations and Monitoring 4–57 To use the PID Second Stage Output feature, you will need to choose upper and lower limits for the PV, via C053 and C052 respectively. As th e timing diagram below shows, these are the thresholds Stage #1 inverter uses to turn ON or OFF Stage #2 inverter via the [FBV] output. The vertical axis units are perc ent (%) for the PID setpoint, and for the upper and lower limits. The output frequency, in Hz, is superimposed onto the same diagram. When system control begins, the following even ts occur (in sequence in the timing diagram): 1. Stage #1 inverter turns ON via the [FW] Run command. 2. Stage #1 inverter turns ON the [FBV] output, because the PV is below the PV low limit C053. So, Stage #2 is assisting in lo op error correction from the beginning. 3. The PV rises and eventually ex ceeds the PV high limit C052. Stage #1 inverter then turns OFF the [FBV] output to Stage #2, si nce the boost is no longer needed. 4. When the PV begins decreasing, only Stage #1 is operating, and it is in the linear control range. This region is where a properly co nfigured system will operate most often. 5. The PV continues to decrease until it crosses under the PV low limit (apparent external process disturbance). Stage #1 inverter turns ON the [FBV] output, and Stage #2 inverter is assisting again. 6. After the PV rises above the PV low limit, the [FW] Run command to Stage #1 inverter turns OFF (as in a system shutdown). 7. Stage #1 inverter enters Stop Mode and au tomatically turns OFF the [FBV] output, which causes Stage #2 inverter to also stop. Network Detection Signal The intelligent output [Ndc] Network Detection Signal indicates the status of ModBus-RTU communications (not ASCII protocol). The [Ndc] terminal turns ON when the external device on the ModBus stops transmitting for a time that exceeds parame ter C077, Communication Time-out Before Trip. If a time-out occurs, the output [Ndc] remains ON until ModBus-RTU communication resumes. Use pa rameter C076 Action Upon Comm unication Error Selection to select the desired inverter re sponse to a time-out event. PV high limit t 0 tC052 C053 Stage #1 [FW] t [FBV] to Stage #2 [FW]PV low limit 1 0 1PID setpoint (SP) PID feedback (PV) Output frequency 1, 2 3 4 5 Example: 67 Opt. Code32 Symbol[Ndc] Valid for Outputs[11 to [15], [ALx] Required Settings C076, C077 Default terminals Requires config. Master t 0 C077 1 Slave (inver ter) Watchdog timer = xx.xx sec. 0 1 Alarm output [ALx] Time-out C076 = 00 or 01 (trip) Network detection [Ndc] Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Using Intelligent Output Terminals Operations and Monitoring 4–58 Logic Output Signals The Logic Output Function uses the inverter’s bu ilt-in logic feature. You can select any two of the other intelligent output options for use as in ternal inputs to the logic function. You may also select from three logical operators AND, OR, or XOR (exclusive OR), to be applied to the two inputs. A total of six outputs are avai lable, shown in the following tables. The example below shows a configuration for [LOG1] Logic Output 1. Parameters C142 and C143 contain option codes for two outpu ts we select to be used as inputs to the logic operation. Parameter C144 contains the select code for the logic operation. 00=AND, 01=OR, and 02=OR. Capacitor Life Warning The inverter calculates the capacitor life remaining based on the internal temperature of the inverter and the cumulative power-ON time. Th e [WAC] Capacitor Life Warning output turns ON to indicate that the capaci tors have reached end-of-life. If this event occurs, Hitachi recommends that you replace the main circuit board and logic circuit board. You may also use monitor parameter D022 at the di gital operator to monitor the status of capacitor life. Opt. Code and Symbol 33=[LOG1] 34=[LOG2] 35=[LOG3] 36=[LOG4] 37=[LOG5] 38=[LOG6] Va l i d f o r Outputs[11 to [15], [ALx] Required Settings C142 to C159 Default terminal Requires config. SymbolOption CodeFunctionA InputB InputLogical Operator LOG1 33 Logic Output 1C142 C143 C144 LOG2 34 Logic Output 2C145 C146C147 LOG3 35 Logic Output 3C148 C149C150 LOG4 36 Logic Output 4C151 C152C153 LOG5 37 Logic Output 5C154 C155C156 LOG6 38 Logic Output 6C157 C158C159 Input States[LOGx] Output State A InputB InputAND (00)OR (01XOR (02) 000 00 01011 10011 11110 C142 A input B input Logic function AND, OR, XOR [LOG1] Intelligent outputs used as internal inputs: RUN, FA1, FA2, OL, OD, etc.:C143 C144 [RUN] = option code 00 [FA2] = option code 02 Opt. Code39 Symbol[WAC] Va l i d f o r Outputs[11 to [15], [ALx] Monitor Settings D022 Default terminals Requires config. Phone: 800.894.0412
SJ7002 Inverter Operations and Monitoring 4–59 Low Cooling Fan Speed The inverter monitors the heat sink cooling fan speed to help prevent overheating. If the speed of the fan(s) decreases to 75% or less of full speed, output [WAF] Low Cooling Fan Speed turns ON. Note that if you set parameter B092 Cooling Fan Control = 01 (Fan ON only during RUN), the inverter will not output the [WAF ] signal when the cooling fan is stopped. If the [WAF] signal turns ON during operation, first check the cooling fan inlet for clogging by dust and debris. If the air circulation path is cl ear, the fans may need replacement. You may also use monitor parameter D022 at the digital ope rator to monitor the status of fan speed. Starting Contact Signal The inverter generates [FR] Starting Contact Signal to correspond with Run (FW or RV) input commands. The source of the Run command does no t matter (so the A002 setting is ignored). If both FW and RV inputs are ON, the inverter stops motor operation and turns OFF the [FR] output. The [FR] signal is useful for external devices that need a traditional starting contact signal to coordina te operation with the inverter. Heatsink Overheat Warning The inverter monitors its heat sink temperature to detect ove rheating. You can use parameter C064, Heatsink Overheat Warning Level, to se t the over-temperature threshold for the heatsink in degrees C. The inverter will turn ON intelligent output [OHF] Heatsink Overheat Warning if the heatsink temperature exceed s the value in parameter C064. Opt. Code40 Symbol[WAF] Valid for Outputs[11 to [15], [ALx] Required Settings B092 Monitor Settings D022 Default terminals Requires config. Opt. Code41 Symbol[FR] Valid for Outputs[11 to [15], [ALx] Required Settings none Default terminals Requires config. Forward command Reverse command Starting Contact Signal [FR] Opt. Code42 Symbol[OHF] Valid for Outputs[11 to [15], [ALx] Required Settings C064 Default terminals Requires config. Phone: 800.894.0412