Home > Hitachi > Inverter > Hitachi Sj7002 Owners Manual

Hitachi Sj7002 Owners Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Hitachi Sj7002 Owners Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 913 Hitachi manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Monitoring Trip Events, History, & Conditions
    Troubleshooting
    and Maintenance
    6–14
    Easy Sequence 
    Error CodesUse the following table to diagnose errors re lated to Easy Sequence programming. The error 
    code will appear when  the related program runs.
    DeviceNet Expansion Card Errors
    Error Code: OPE / SRWNameProbable Cause(s)
    E43.-Invalid instruction A program c ontains an invalid instruction
    PRG.CMDThe [PRG] terminal was turn ON but a 
    program was not loaded
    E44.-Nesting count error Subroutines with FOR and NEXT 
    instructions are nest ed more than eight 
    levels
    PRG.NST
    E45.-Execution error 1A FOR (or another) instruction to begin 
    nesting is not found at the jump destina-
    tion of a GO TO instruction, and the 
    NEXT (or another) instruction to end 
    nesting precedes the beginning of nesting
    PRG.ERR1 An arithmetic operation resulted in overflow 
    or underflow, or a divide-by-zero was 
    attempted
    A CHG PARAM or MON PARAM instruc-
    tion attempts to:
    
     e range for a parameter
    
    during inverter operation
    E50.- ... E59.-User trip event A TRIP instruction was executed in a  program
    PRG-0 ... PRG-9
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Troubleshooting
    and Maintenance
    6–15
    Trip History and 
    Inverter StatusWe recommend that you first find the cause of th e fault before attempting clearing it. When a 
    fault occurs, the inverter stores important performance data at the moment of the fault. To 
    access the data, use the monitor functions (Dxxx)  and select D081 for details about the present 
    fault (E
    n). The previous five faults are stored in D081 to D086, with D (En-1 to En-5). Each error 
    shifts D081–D085 to D082–D086, and writes the new error to D081.
    The following Monitor Menu map shows how to acc ess the error codes. When fault(s) exist, 
    you can review their details by first selecting  the proper function: D081 is most recent, and 
    D086 is the oldest.
    1
    Error Code
    Error
    exists?
    Output frequency at 
    trip point
    Motor current at  trip point
    DC bus voltage at  trip pointNo error
    Ye s
    No
    212
    2
    1
    1
    1
    1
    1
    Cumulative inverter 
    operation time
    at trip point
    Cumulative power-
    ON time at trip point
    1
    2
    Current Trip  Conditions Trip History
    Monitor Menu
    FUNC.
    FUNC.
    FUNC.
    d08 1
    d086
    d082
    E07.2
    60.00
    4.0 0
    270.0
    15
    18
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							Restoring Factory Default Settings
    Troubleshooting
    and Maintenance
    6–16
    Restoring Factory Default Settings
    You can restore all inverter parame ters to the original factory (default) settings for the intended 
    country of use. After initializing the inverter, us e the powerup test in Chapter 2 to get the motor 
    running again. To initialize the inverter, follow the steps below.
    No.ActionDisplayFunc./Parameter
    1 Use the , , and   keys to 
    navigate to the “B” Group. “B” Group selected
    2 Press the 
     key. First “B” parameter selected
    3 Press and hold the   key until -> Country code fo
    r initializa-
    tion selected
    4 Press the 
     key. 00 = Japan, 01 = Europe,
    02 = U.S. 
    5 Confirm the country code is correct. Do not  change it unless you are absolutely sure 
    the power input voltage ra nge and frequency match th e country code setting.
    To change the country code, press   or   to set;   to store.
    6 Press the   key. Country code fo
    r initializa-
    tion selected
    7 Press the   key. Initialization function selected
    8 Press the 
     key. 00 = initialization disabled, 
    clear trip history only
    9 Press the   key. 01 = enable initialization
    10 Press the   key. Initialization now enabled to 
    restore all defaults
    11 Press and hold the
      and  
    keys together, and immediately 
    press and hold the   key. Do not 
    release these keys yet. First part of special key 
    sequence, the “B” in the 
    display begins flashing
    12 Holding the keys above, press and  hold the 
     (STOP) key for 3 sec. Entire “B084” display will 
    begin flashing
    13 When the
     b084 display begins 
    flashing, release the   key.  
    or
     Default parameter country 
    code shown duri ng initializa-
    tion process (left-most charac-
    ter displays alternating 
    pattern)
    14 Release the 
    , , and  
    keys together. Final part of key sequence, 
    function code for output 
    frequency monitor shown after 
    initialization is complete
    FUNC.12b---
    FUNC.b00 1
    1d 104
    FUNC.02
    12STR
    FUNC.b085
    2b084
    FUNC.00
    10 1
    STRb084
    12
    FUNC.
    b084
    STOPRESETb084
    STOPRESET0  EU
    0USA
    12FUNC.d001
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Troubleshooting
    and Maintenance
    6–17
    Maintenance and Inspection
    Monthly and 
    Yearly Inspection 
    Chart
    Item InspectedCheck for...
    Inspection  Cycle
    Inspection MethodCriteria
    MonthYe a r
    General Ambient  environment Extreme
    temperatures
    & humidity ✔
    Thermometer, 
    hygrometer Ambient temperature 
    between -10 to 50°C, 
    non-condensing
    Major devices Abnormal  vibration, 
    noise ✔
    Visual and aural Stable environment for 
    electronic controls
    Power supply 
    voltage Vo l t a g e  
    tolerance ✔
    Digital volt meter, 
    measure between 
    inverter terminals 
    [L1], [L2], [L3] 200V class:
    200 to 240V 50/60 Hz
    400V class:
    380 to 460V 50/60 Hz
    Main 
    circuits Ground
    Insulation Adequate 
    resistance ✔
    Megger test 500VDC, reading of 5M 
    ohms or greater, see next 
    section for test details
    Mounting No loose  screws ✔
    Torque wrench M3: 0.5 – 0.6 Nm
    M4: 0.98 – 1.3 Nm
    M5: 1.5 – 2.0 Nm
    Components Overheating ✔Thermal trip events No trip events
    Housing Dirt, dust ✔Visual Vacuum dust and dirt
    Terminal block Secure  connections ✔
    Visual No abnormalities
    Smoothing 
    capacitor Leaking, 
    swelling ✔
    Visual No abnormalities
    Relay(s) Chattering ✔Aural Single click when 
    switching ON or OFF
    Resistors Cracks or  discoloring ✔
    Visual Use Ohm meter to check 
    braking resistors
    Cooling 
    system Cooling fan Noise
    ✔Power down, 
    manually rotate Rotation must be smooth
    Heat sink Dust ✔Visual Vacuum to clean
    Control 
    circuit General No odor, 
    discoloring, 
    corrosion ✔
    Visual No abnormalities
    Capacitor No leaks or  deformation ✔
    Visual Undistorted appearance
    Display LEDs Legibility ✔Visual All LED segments work
    
    Phone: 800.894.0412   
    						
    							Maintenance and Inspection
    Troubleshooting
    and Maintenance
    6–18
    Note 1: The life of a capacitor is affected by the ambient temperature. See  “Capacitor Life 
    Curve” on page 6–20.
    Note 2: The inverter must be cleaned periodically. If dust accumulates on the fan and heat 
    sink, it can cause overheating of the inverter .
    Motor General Vibration
    ✔Visual, touch Ordinary range
    Unusual odor ✔Look for signs of 
    overheating Normal appearance
    Insulation 
    resistance Isolation 
    boundary 
    fault ✔
    Disconnect motor 
    from inverter, do 
    megger test on 
    motor 500V class megger test 
    must pass
    Item InspectedCheck for...
    Inspection 
    Cycle
    Inspection MethodCriteria
    MonthYe a r
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Troubleshooting
    and Maintenance
    6–19
    Megger TestThe  megger  is a piece of test equipment that uses a  high voltage to determine if an insulation 
    degradation has occurred. For inverters, it is im portant that the power terminals be isolated 
    from the Earth GND terminal via  the proper amount of insulation.
    The circuit diagram below shows the inverter wiri ng for performing the megger test. Just follow 
    the steps to perform the test:
    1. Remove power from the inverter and wait at least 10 minutes  before proceeding.
    2. Open the front housing pane l to access the power wiring.
    3. Remove all wires to terminals [R, S, T, PD, P,  N, RB, U, V, and W]. Most importantly, the 
    input power and motor wires will be  disconnected from the inverter.
    4. Remove the jumper at connector J61. It is lo cated on the main circuit board beside the 
    power terminals.
    5. Use a bare wire and short terminals [R, S, T, PD, P, N, RB, U, V, and W] together as shown 
    in the diagram.
    6. Connect the megger to the inve rter Earth GND and to the shorted power terminals as shown. 
    Then perform the megger test at 500 VDC and verify 5M Ω or greater resistance.
    7. After completing the test, disconne ct the megger from the inverter.
    8. Reconnect the jumper at  connector J61 as before.
    9. Reconnect the original wires to terminals  [R, S, T, PD, P, N, RB, U, V, and W].
    CAUTION: Do not connect the megger to any control circuit terminals such as intelligent I/O, 
    analog terminals, etc. Doing so co uld cause damage to the inverter.
    CAUTION: Never test the withstand voltage (HIPOT) on the inverter. The inverter has a surge 
    protector between the main circuit te rminals above and the chassis ground.
    U
    V
    W
    Motor
    R
    S
    T
    Disconnect 
    power source
    P
    PD
    RB N
    J61 SJ700
    2Disconnect 
    motor wires
    Earth  GND
    Megger, 500VDC
    Add test
    jumper wire
    Disconnect jumper at 
    J61 before performing  the megger test
    L1
    L2
    L3
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							Maintenance and Inspection
    Troubleshooting
    and Maintenance
    6–20
    Spare partsWe recommend that you stock spare parts to reduce down time, including parts listed below:
    Capacitor
    Life CurveThe DC bus inside the inverter uses a large  capacitor as shown in the diagram below. The 
    capacitor handles high  voltage and current as it smooths the power for use by the inverter. So, 
    any degradation of the capacitor will affect th e performance of the inverter. The capacitor bank 
    in SJ700
    2 series inverters is replaceable. This sect ion will show you how to replace it in the 
    field.
    Capacitor life is reduce d in higher ambient temperatures, as  the graph below demonstrates. Be 
    sure to keep the ambient temper ature at acceptable levels, and perform maintenance inspections 
    on the fan, heat sink, and other co mponents. If the inverter is installed on a cabinet, the ambient 
    temperature is the temper ature inside the cabinet.
    Part descriptionSymbol
    Quantity
    Notes
    UsedSpare
    Cooling  fan FAN 1, 2, 3... (depends 
    on model) 1 or 2 Fan unit at top of housing 
    in all models
    Auxiliary cooling fan FAN 0 or 1... (depends  on model)0 or 1 –150Lxx, –185Lxx, and  
    –220Lxx models
    Capacitor bank CB 11 All models
    Power 
    Input Inverter
    L1/R
    Motor
    L2/S
    L3/T
    Rectifier
    Variable-frequency Drive
    Internal DC Bus
    +
    +
    – U/T1
    V/T2
    W/T3
    Converter
    Ambient
    temperature, °C
    Ye a r s
    Capacitor Life Curve
    24 hrs / day operation
    12 345678 910
    -10 0
    30 50
    10
    20
    40
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Troubleshooting
    and Maintenance
    6–21
    Capacitor 
    ReplacementThe DC section of the inverter main circuit uses  high-capacity aluminum electrolytic capacitors 
    as smoothing filter components. Since chemical  reactions occur inside the capacitors, the 
    service life of these parts depends mainly on th e ambient temperature and operating conditions, 
    Capacitors used in a standard operating environm ent must be replaced after about 10 years. 
    However, each capacitor must me immediately repl aced if it fails a visual inspection or if 
    periodic inspections shows the  capacity to be 80% or less of the component rating.
    WARNING: The screws that retain the capacitor bank assembly are part of the electrical 
    circuit of the high-voltage internal DC bus. Be  sure that all power has been disconnected from 
    the inverter, and that you have waited at leas t 10 minutes before accessing the terminals or 
    screws. Be sure the charge lamp is extinguished.  Otherwise, there is the danger of electrocution 
    to personnel.
    CAUTION: Do not operate the inverter unless you have  replaced the two screws that connect 
    the capacitor bank assembly to the internal DC  bus. Otherwise, damage to the inverter may 
    occur.
    For inverters above 11kW output with molded plastic housings...
    1.Loosen the two screws that secure the  lower front panel. Remove  the panel from the 
    inverter.
    2. Turn OFF power to the inverter and confir m that the Charge Indicator LED is OFF.
    3. Remove the wiring entry/exit plate from the inverter.
    4. Remove the screws that connect the capacito r unit to the main circuit terminal block.
    5. Remove the screws that secure the capacitor mounting plate to the inverter casing.
    6. Pull down the capacitor mounting plate.
    7. Remove the capacitor unit from the capacitor mounting plate.
    To install the new capacitor unit:
    1. Place the capacitor unit on the mounting plate.
    2. Slide the capacitor mounting plate into the guides in the inverter housing. Push the capacitor 
    unit until the metal plate is flush with the housing.
    3. Connect the capacitor unit to the main circuit terminal block by using the two (2) terminal 
    screws.
    4. Secure the capacitor mounting plate to th e inverter housing by using the screws.
    5. Replace the wire/entry plate.
    6. Replace the lower front panel cove r and secure it with screws.
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							Maintenance and Inspection
    Troubleshooting
    and Maintenance
    6–22
    For inverters with sheet metal housings...
    1. Loosen the two screws that secure the  lower front panel. Remove the panel from the 
    inverter.
    2. Turn OFF power to the inverter and confirm that the Charge Indicator LED is OFF.
    3. Remove the lower screws from term inal block terminals [P] and [N].
    4. Remove the screws that secure  the capacitor mounting plate.
    5. Pull down the capacitor mounting plate.
    6. Remove the bus bar and resistors. Then remove the capacitor unit from the capacitor 
    mounting plate.
    To install the new capacitor unit:
    1. Place the capacitor unit on  the mounting plate and secure the unit with screws.
    2. Mount the bus bar and resistors  in the original positions and secure them with screws.
    3. Slide the capacitor mounting plat e into the inverter housing.
    4. Secure the capacitor mounting plate to th e inverter housing by using the screws.
    5. Install the lower screws in the te rminal block terminals [P] and [N].
    6. Mount the terminal block cover.
    Capacitor mounting plate
    Lower screws, terminals [P] and [N]
    Capacitor unit
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Troubleshooting
    and Maintenance
    6–23
    For inverters 11kW output and belo w with molded plastic housings...
    The inverters in this category do not have separate  capacitor units. It is necessary to replace the 
    main circuit board, accessible by following the steps below.
    1. Loosen the two screws that secure the  lower front panel. Remove  the panel from the 
    inverter.
    2. Turn OFF power to the inverter and confir m that the Charge Indicator LED is OFF.
    3. Loosen the two screws that secure the  upper front panel. Remove the panel from the 
    inverter.
    4. Press the tabs inward on each  side of the cooling fan unit and lift the unit away from the top 
    of the inverter housing.
    5. Disconnect the fan unit wiring on the circuit board at the top of the inverter.
    6. Disconnect the ribbon cable that connects the control board and main board.
    7. Remove the wiring entry/exit plate and the ju mper between terminal [P] and [PD] on the 
    main board.
    8. Remove the two (2) screws in the plastic housing, and remove the top half of the housing. 
    Be careful not to damage the plastic tabs at the top corners of the housing.
    Fan Assembly 
    ReplacementThe SJ7002 Series inverters have field -replaceable fan units. The serv ice life of the cooling fan 
    bearings is approximately 100,000 hours. However, actual results vary with the inverter 
    operating environment. Inverters running contin uously usually need fan unit replacement at 
    10-year intervals. In addition,  fan unit replacement is require d immediately if the fan has 
    abnormal sound or vibration. The fan replacem ent procedure depends according to the model 
    (housing type).
    For inverters with molded plastic housings...
    1. Loosen the two screws that secure the  lower front panel. 
    Remove the panel from the inverter.
    2. Turn OFF power to the inverter and confirm that the Charge 
    Indicator LED is OFF.
    3. Loosen the two screws that secure the  upper front panel. 
    Remove the panel from the inverter.
    4. Press the tabs inward on each side of the cooling fan unit and 
    lift the unit away from the top of the inverter housing.
    5. Disconnect the fan unit wiring  on the circuit board at the top 
    of the inverter.
    6. Remove the defective fan(s) from the cooling fan mounting 
    plate.
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    All Hitachi manuals Comments (0)