ModBus Data Listing Appendix B B–38 D081 —Trip monitor 1 R Factor code 0012h 00018 (see codes in next table)— R Inverter status 0013h 00019 — R Frequency (high) 0014h 00020 0 to 40000 0.01 Hz R Frequency (low) 0015h 00021 R Current 0016h 00022 — 0.1 A R Voltage 0017h 00023 — 1 V R Run time (high) 0018h 00024 — 1 hour R Run time (low) 0019h 00025 R ON time (high) 001Ah 00026 — 1 hour R ON time (low) 001Bh 00027 D082 — Trip monitor 2 R Factor code 001Ch 00028 (see codes in next table)— R Inverter status 001Dh 00029 — R Frequency (high) 001Eh 00030 0 to 40000 0.01 Hz R Frequency (low) 001Fh 00031 R Current 0020h 00032 — 0.1 A R Voltage 0021h 00033 — 1 V R Run time (high) 0022h 00034 — 1 hour R Run time (low) 0023h 00035 R ON time (high) 0024h 00036 — 1 hour R ON time (low) 0025h 00037 D083 — Trip monitor 3 R Factor code 0026h 00038 (see codes in next table)— R Inverter status 0027h 00039 — R Frequency (high) 0028h 00040 0 to 40000 0.01 Hz R Frequency (low) 0029h 00041 R Current 002Ah 00042 — 0.1 A R Voltage 002Bh 00043 — 1 V R Run time (high) 002Ch 00044 — 1 hour R Run time (low) 002Dh 00045 R ON time (high) 002Eh 00046 — 1 hour R ON time (low) 002Fh 00047 Holding Registers, “D” Group Monitor Functions Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. Phone: 800.894.0412
SJ7002 Inverter Appendix B B–39 D084 — Trip monitor 4R Factor code0030h 00048 (see codes in next table)— R Inverter status 0031h 00049— R Frequency (high) 0032h 00050 0 to 40000 0.01 Hz R Frequency (low) 0033h 00051 R Current 0034h 00052 — 0.1 A R Voltage 0035h 00053 — 1 V R Run time (high) 0036h 00054 — 1 hour R Run time (low) 0037h 00055 R ON time (high) 0038h 00056 — 1 hour R ON time (low) 0039h 00057 D085 — Trip monitor 5 R Factor code003Ah 00058 (see codes in next table)— R Inverter status 003Bh 00059— R Frequency (high) 003Ch 00060 0 to 40000 0.01 Hz R Frequency (low) 003Dh 00061 R Current 003Eh 00062 — 0.1 A R Voltage 003Fh 00063 — 1 V R Run time (high) 0040h 00064 — 1 hour R Run time (low) 0041h 00065 R ON time (high) 0042h 00066 — 1 hour R ON time (low) 0043h 00067 D086 — Trip monitor 6 R Factor code0044h 00068 (see codes in next table)— R Inverter status 0045h 00069— R Frequency (high) 0046h 00070 0 to 40000 0.01 Hz R Frequency (low) 0047h 00071 R Current 0048h 00072 — 0.1 A R Voltage 0049h 00073 — 1 V R Run time (high) 004Ah 00074 — 1 hour R Run time (low) 004Bh 00075 R ON time (high) 004Ch 00076 — 1 hour R ON time (low) 004Dh 00077 D090 — Programming error monitor R Displays programming error code 004Eh 00078 Warning code— — (Reserved) ——004Fh to 08FFh 00079 to 02303 —— Holding Registers, “D” Group Monitor Functions Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. Phone: 800.894.0412
ModBus Data Listing Appendix B B–40 Note 1:Assume that the inverter current rating is 1000 (for D002). Note 2: When the value is 10000 (100.0 seconds), a value in the second decimal place is ignored. — — Write to EEPROM W 00 . Motor constant calculation 01 . Set data storage in EEPROM Other... Motor constant recalcu- lation and set data storage in EEPROM 0900h 02304 0000, 0001, other — — (Reserved) ——0901h to 1000h 02305 to 4096 —— D102 — DC voltage monitoring Displays the DC Bus voltage 1026h 04134 0 to 9999 0.1 V D103 — BRD load factor monitor- ing Displays the running average Dynamic Braking usage ratio (%ED)1027h 04135 0 to 1000 0.1 % D104 — Electronic thermal overload monitoring Displays the motor electronic thermal overload estimated temperature ratio. If the value reaches 100%, th e inverter will trip (E05) 1028h 04136 0 to 1000 0.1 % — (Reserved) ——1029h to 102Dh 04137 to 04141 —— Holding Registers, “D” Group Monitor Functions Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. Phone: 800.894.0412
SJ7002 Inverter Appendix B B–41 Trip Factor Code, HIGH orderTrip Factor Code, LOW order (inverter status) CodeNameCodeName 0 No trip 0 Reset 1 Over current event while at constant speed 1Stop 2 Over current event during deceleration 2 Deceleration 3 Over current event during acceleration 3 Constant speed 4 Over current event during other condi- tions 4 Acceleration 5 Overload protection 5 Run Command active with 0 Hz speed reference 6 Braking resistor overload 6 Starting 7 Over voltage protection 7 DC braking 8 EEPROM error 8 Overload restriction 9 Under-voltage error 9 SON or FOC operation in progress 10 CT (current tr ansformer) error 11 CPU error 12 External trip 13 USP 14 Ground fault 15 Input over-voltage 16 Instantaneous power failure 20 Inverter thermal trip with low fan speed 21 Inverter thermal trip 23 Gate array error 24 Phase failure detection 25 Main circuit error 30 IGBT error 35 Thermistor 36 Brake error 37 Emergency stop 38 Low-speed overload protection 43 Easy sequence erro r (invalid instruc- tion) 44 Easy sequence erro r (invalid nesting count) 45 Easy sequence execution error 1 50 to 59 Easy sequence user trip 0 to 9 60 to 69 Expansion card #1 error 0 to 9 70 to 79 Expansion card #2 error 0 to 9 Phone: 800.894.0412
ModBus Data Listing Appendix B B–42 Holding Registers, “F” Group Main Profile Parameters Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. F001 H Output frequency setting R/W Standard default target frequency that deter- mines constant motor speed (when A001 = 03)0001h 00001 0 to 40000 0.01 Hz F001 L R/W 0002h 00002 F002 H Acceleration (1) time setting R/W Standard default acceler- ation 1103h 04355 1 to 3600000.01 sec. F002 L R/W 1104h 04356 F202 H Acceleration (1) time setting, 2nd motor R/W Standard default acceler- ation, 2nd motor 2103h 08451 1 to 3600000.01 sec. F202 L R/W 2104h 08452 F302 H Acceleration (1) time setting, 3rd motor R/W Standard default acceler- ation, 3rd motor 3103h 12547 1 to 3600000.01 sec. F302 L R/W 3104h 12548 F003 H Deceleration (1) time setting R/W Standard default deceler- ation 1105h 04357 1 to 3600000.01 sec. F003 L R/W 1106h 04358 F203 H Deceleration (1) time setting, 2nd motor R/W Standard default deceler- ation, 2nd motor 2105h 08453 1 to 3600000.01 sec. F203 L R/W 2106h 08454 — — (Reserved) — — 2107h to 2202h 08455 to 08706 —— F303 H Deceleration (1) time setting, 3rd motor R/W Standard default deceler- ation, 3rd motor 3105h 12549 1 to 3600000.01 sec. F303 L R/W 3106h 12550 — — (Reserved) — — 3107h to 3202h 12551 to 12802 —— F004 — Keypad Run key routing R/W 1107h 04359 — — (Reserved) — — 1108h to 1200h 04360 to 04608 —— Phone: 800.894.0412
SJ7002 Inverter Appendix B B–43 Holding Registers, “A” Group Standard Functions Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. A001 — Frequency source setting R/W 00 . Keypad potentiometer 01 . Control terminal 02 . Function F001 setting 03 . RS485 serial command 04 . Expansion board #1 05 . Expansion board #2 06 . Pulse train input 07 . Easy sequence 10 . Caltulate function input1201h 04609 00 to 07, 10— A002 — Run command source setting R/W 01 . Input [FW] or [RV] 02 . Run key on keypad 03 . RS485 serial command 04 . Start/stop, Exp. card #1 05 . Start/stop. exp. card #2 1202h 04610 01 to 05 — A003 — Base frequency setting R/W 30. to max. frequency (Hz) 1203h 04611 30 to A004 val.1 Hz A203 — Base frequency setting, 2nd motor R/W 30. to max. frequency (Hz) 2203h 08707 30 to A004 val.1 Hz A303 — Base frequency setting, 3rd motor R/W 30. to max. frequency (Hz) 3203h 12803 30 to A004 val.1 Hz A004 — Maximum frequency setting R/W 30. to 400. (Hz) 1204h 04612 30 to 400 1 Hz A204 — Maximum frequency setting, 2nd motor R/W 30. to 400. (Hz) 2204h 08708 30 to 400 1 Hz — (Reserved) — — 2205h to 2215h 08709 to 08725 —— A304 — Maximum frequency setting, 3rd motor R/W 30. to 400. (Hz) 3204h 12804 30 to 400 1 Hz — (Reserved) — — 3205h to 3215h 12805 to 12821 —— A005 — [AT] selection R/W 00 . Select between [O] and [OI] at [AT] 01 . Select between [O] and [O2] at [AT] 02 . Select between [O] and keypad pot. 03 . Select between [OI] and keypad pot. 04 . Select between [O2] and keypad pot.1205h 04613 00 to 04 — A006 — [O2] selection R/W 00 . No summing, [O2] and [OI] 01 . Sum of [O2] and [OI], neg. sum (reverse speed reference) inhibited 02 . Sum of [O2] and [OI], neg. sum (reverse speed reference) allowed 03 . Disable [O2] input1206h 046 00 to 03 — Phone: 800.894.0412
ModBus Data Listing Appendix B B–44 — (Reserved)——1207h to 120Ah 04614 to 04618 —— A011 H [O]–[L] input active range start frequency R/W The output frequency corre- sponding to the voltage input range starting point 120Bh 04619 0 to 40000 0.01 Hz A011 L 120Ch 04620 A012 H [O]–[L] input active range end frequency R/W The output frequency corre- sponding to the voltage input range ending point 120Dh 04621 0 to 40000 0.01 Hz A012 L 120Eh 04622 A013 — [O]–[L] input active range start voltage R/W The starting point for the voltage input range 120Fh 04623 0 to A014 value1 % A014 — [O]–[L] input active range end voltage R/W The ending point for the voltage input range 1210h 04624 A013 value to 100 1 % A015 — [O]–[L] input start frequency enable R/W 00 ..Use A011 start value 01 ..Use 0 Hz 1211h 04625 0, 1 — A016 — External frequency filter time const. R/W n = 1 to 30 (where n = number of samples for average); 31 = 500ms filter 1212h 04626 1 to 30, 31 1 A017 — Easy sequence function enable R/W 00 ..Disable 01 ..Enable 1213h 04627 0, 1 — — (Reserved) ——1214h 04628 — — A019 — Multi-speed operation selection R/W 00 ..Binary; up to 16-stage speed using 4 terminals 01 ..Single-bit; up to 8-stage speed using 7 terminals 1215h 04629 0, 1 — A020 H Multi-spee d frequency setting R/W Defines the first speed of a multi-speed profile 1216h 04630 0 or start freq. to max. freq. 0.01 Hz A020 L 1217h 04631 A220 H Multi-spee d frequency setting, 2nd motor R/W Defines the first speed of a multi-speed profile for 2nd motor 2216h 08726 0 or start freq. to max. freq. 0.01 Hz A220 L 2217h 08727 — (Reserved) ——2218h to 223Ah 08728 to 08762 —— A320 H Multi-spee d frequency setting, 3rd motor R/W Defines the first speed of a multi-speed profile for 3rd motor 3216h 12822 0 or start freq. to max. freq. 0.01 Hz A320 L 3217h 12823 — (Reserved) ——3218h to 323Bh 12824 to 12859 —— A021 H Multi-speed 1 setting R/W Def ines nth additional speed 1218h 04632 0 or start freq. to max. freq. 0.01 Hz A021 L 1219h 04633 A022 H Multi-speed 2 setting R/W Defines nth additional speed 121Ah 04634 0 or start freq. to max. freq. 0.01 Hz A022 L 121Bh 04635 A023 H Multi-speed 3 setting R/W Defines nth additional speed 121Ch 04636 0 or start freq. to max. freq. 0.01 Hz A023 L 121Dh 04637 Holding Registers, “A” Group Standard Functions Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. Phone: 800.894.0412
SJ7002 Inverter Appendix B B–45 A024 H Multi-speed 4 setting R/W Defines nth additional speed 121Eh 04638 0 or start freq. to max. freq. 0.01 Hz A024 L 121Fh 04639 A025 H Multi-speed 5 setting R/W Defines nth additional speed 1220h 04640 0 or start freq. to max. freq. 0.01 Hz A025 L 1221h 04641 A026 H Multi-speed 6 setting R/W Defines nth additional speed 1222h 04642 0 or start freq. to max. freq. 0.01 Hz A026 L 1223h 04643 A027 H Multi-speed 7 setting R/W Defines nth additional speed 1224h 04644 0 or start freq. to max. freq. 0.01 Hz A027 L 1225h 04645 A028 H Multi-speed 8 setting R/W Defines nth additional speed 1226h 04646 0 or start freq. to max. freq. 0.01 Hz A028 L 1227h 04647 A029 H Multi-speed 9 setting R/W Defines nth additional speed 1228h 04648 0 or start freq. to max. freq. 0.01 Hz A029 L 1229h 04649 A030 H Multi-speed 10 setting R/W Defines nth additiona l speed 122Ah 04650 0 or start freq. to max. freq. 0.01 Hz A030 L 122Bh 04651 A031 H Multi-speed 11 setting R/W Defines nth additiona l speed 122Ch 04652 0 or start freq. to max. freq. 0.01 Hz A031 L 122Dh 04653 A032 H Multi-speed 12 setting R/W Defines nth additiona l speed 122Eh 04654 0 or start freq. to max. freq. 0.01 Hz A032 L 122Fh 04655 A033 H Multi-speed 13 setting R/W Defines nth additiona l speed 1230h 04656 0 or start freq. to max. freq. 0.01 Hz A033 L 1231h 04657 A034 H Multi-speed 14 setting R/W Defines nth additiona l speed 1232h 04658 0 or start freq. to max. freq. 0.01 Hz A034 L 1233h 04659 A035 H Multi-speed 15 setting R/W Defines nth additiona l speed 1234h 04660 0 or start freq. to max. freq. 0.01 Hz A035 L 1235h 04661 — (Reserved) — — 1236h 04662 — — — (Reserved) — — 1237h 04663 — — A038 — Jog frequency setting R/W De fines limited speed for jog1238h 04664 0 to 999 0.01 Hz Holding Registers, “A” Group Standard Functions Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. Phone: 800.894.0412
ModBus Data Listing Appendix B B–46 A039 — Jog stop modeR/W 00 ..Free-run stop, jogging disabled during motor run 01 ..Controlled deceleration, jogging disabled during motor run 02 ..DC braking to stop, jogging disabled during motor run 03 ..Free-run stop, jogging always enabled 04 ..Controlled deceleration, jogging always enabled 05 ..DC braking to stop, jogging always enabled 1239h 04665 0 to 5 — — (Reserved) ——123Ah 04666 — — A041 — Torque boost method selection R/W 00 ..Manual torque boost 01 ..Automatic torque boost 123Bh 04667 0, 1 — A241 — Torque boost method selection, 2nd motor R/W 00 ..Manual torque boost 01 ..Automatic torque boost 223Bh 08763 0, 1 — A042 — Manual torque boost value R/W Can boost starting torque between 0 and 20% above normal V/f curve123Ch 04668 0 to 200 0.1 % A242 — Manual torque boost value, 2nd motor R/W Can boost starting torque between 0 and 20% above normal V/f curve 223Ch 08764 0 to 200 0.1 % A342 — Manual torque boost value, 3rd motor R/W Can boost starting torque between 0 and 20% above normal V/f curve 323Ch 12860 0 to 200 0.1 % A043 — Manual torque boost frequency adjustment R/W Sets the frequency of the V/f breakpoint for torque boost 123Dh 04669 0 to 500 0.1 % A243 — Manual torque boost frequency adjustment, 2nd motor R/W Sets the frequency of the V/f breakpoint for torque boost 223Dh 08765 0 to 500 0.1 % A343 — Manual torque boost frequency adjustment, 3rd motor R/W Sets the frequency of the V/f breakpoint for torque boost 323Dh 12861 0 to 500 0.1 % A044 — V/F characteristic curve selection R/W 00 ..V/f constant torque 01 ..V/f variable torque 02 ..V/f free-setting curve 03 ..Sensorless vector SLV 04 ..0Hz domain SLV 05 ..Vector control with encoder feedback 123Eh 04670 0 to 5 — A244 — V/F characteristic curve selection, 2nd motor R/W 00 ..V/f constant torque 01 ..V/f variable torque 02 ..V/f free-setting curve 03 ..Sensorless vector SLV 04 ..0Hz domain SLV 223Eh 08766 0 to 4 — — (Reserved) ——223Fh 08767 — — A344 V/F characteristic curve selection, 3rd motor R/W 00 ..V/f constant torque 01 ..V/f variable torque 323Eh 12862 0, 1 — Holding Registers, “A” Group Standard Functions Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. Phone: 800.894.0412
SJ7002 Inverter Appendix B B–47 — (Reserved)——323Fh to 326Ch 12863 to 12908 —— A045 — V/f gain setting R/W Sets voltage gain of the inverter 123Fh 04671 20 to 200 1 % A046 — Automatic torque boost voltage gain R/W Voltage compensation gain for automatic torque boost 1240h 04672 0 to 255 1 A246 — Automatic torque boost voltage gain, 2nd motor R/W Voltage compensation gain for automatic torque boost 2240h 08768 0 to 255 1 A047 — Automatic torque boost slip gain R/W Slip compensa tion gain for automatic to rque boost 1241h 04673 0 to 255 1 — (Reserved) ——1242h to 1244h 04674 to 04676 —— A247 — Automatic torque boost slip gain, 2nd motor Slip compensa tion gain for automatic to rque boost 2241h 08769 0 to 255 1 — (Reserved) ——2242h to 224Eh 08770 to 08782 —— A051 — DC braking enable R/W 00 . Disable 01 . Enable 02 . Brake at set frequency only1245h 04677 0, 1, 2 — A052 — DC braking frequency setting R/W Frequency at which DC braking activates during decel. 1246h 04678 0 to 40000 0.01 Hz A053 — DC braking wait time R/W Th e delay after reaching the DC braking frequency, or [DB] signal, before DC braking begins 1247h 04679 0 to 50 0.1 sec. A054 — DC braking force during deceleration R/W Variable DC braking force 1248h 04680 0 to 80 1 % A055 — DC braking time for decel- eration R/W Sets the duration for DC braking during decel 1249h 04681 0 to 600 0.1 sec. A056 — DC braking / edge or level detection for [DB] input R/W 00 . Edge detection 01 . Level detection 124Ah 04682 0, 1 — A057 — DC braking force for starting R/W Variable DC braking force 124Bh 04683 0 to 80 1 % A058 — DC braking time for starting R/W Sets the duration for DC braking before accel. 124Ch 04684 0 to 600 0.1 sec. A059 — DC braking carrier frequency setting R/W 0.5 to 15 (kHz) for models up to –550xxx, 0.5 to 10 (kHz) for 750xxx to 1500xxx models 124Dh 04685 5 to 150; 5 to 1000.1 kHz — (Reserved) ——124Eh 04686 — — A061 H Frequency upper limit setting R/W Sets a limit on output frequency less than the maximum frequency (A004) 124 Fh 0468 7 0, 50 to 40000 0.01 Hz A061 L 1250h 04688 Holding Registers, “A” Group Standard Functions Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. Phone: 800.894.0412