    							ModBus Data Listing
    Appendix B
    B–38
    D081 —Trip monitor 1 R Factor code 0012h 00018 (see codes in 
    next table)—
    R Inverter status 0013h 00019 —
    R Frequency (high) 0014h 00020 0 to 40000 0.01 Hz
    R Frequency (low) 0015h 00021
    R Current 0016h 00022 — 0.1 A
    R Voltage 0017h 00023 — 1 V
    R Run time (high) 0018h 00024 — 1 hour
    R Run time (low) 0019h 00025
    R ON time (high) 001Ah 00026 — 1 hour
    R ON time (low) 001Bh 00027
    D082 —
    Trip monitor 2 R Factor code 001Ch 00028 (see codes in 
    next table)—
    R Inverter status 001Dh 00029 —
    R Frequency (high) 001Eh 00030 0 to 40000 0.01 Hz
    R Frequency (low) 001Fh 00031
    R Current 0020h 00032 — 0.1 A
    R Voltage 0021h 00033 — 1 V
    R Run time (high) 0022h 00034 — 1 hour
    R Run time (low) 0023h 00035
    R ON time (high) 0024h 00036 — 1 hour
    R ON time (low) 0025h 00037
    D083 —
    Trip monitor 3 R Factor code 0026h 00038 (see codes in 
    next table)—
    R Inverter status 0027h 00039 —
    R Frequency (high) 0028h 00040 0 to 40000 0.01 Hz
    R Frequency (low) 0029h 00041
    R Current 002Ah 00042 — 0.1 A
    R Voltage 002Bh 00043 — 1 V
    R Run time (high) 002Ch 00044 — 1 hour
    R Run time (low) 002Dh 00045
    R ON time (high) 002Eh 00046 — 1 hour
    R ON time (low) 002Fh 00047
    Holding Registers, “D” Group Monitor Functions
    Func. CodeNameR/WDescription
    Network Data
    RegisterRangeRes.hexdec.
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Appendix B
    B–39
    D084 — Trip monitor 4R Factor code0030h 00048 (see codes in 
    next table)—
    R Inverter status 0031h 00049—
    R Frequency (high) 0032h 00050 0 to 40000 0.01 Hz
    R Frequency (low) 0033h 00051
    R Current 0034h 00052 — 0.1 A
    R Voltage 0035h 00053 — 1 V
    R Run time (high) 0036h 00054 — 1 hour
    R Run time (low) 0037h 00055
    R ON time (high) 0038h 00056 — 1 hour
    R ON time (low) 0039h 00057
    D085 — Trip monitor 5 R Factor code003Ah 00058 (see codes in 
    next table)—
    R Inverter status 003Bh 00059—
    R Frequency (high) 003Ch 00060 0 to 40000 0.01 Hz
    R Frequency (low) 003Dh 00061
    R Current 003Eh 00062 — 0.1 A
    R Voltage 003Fh 00063 — 1 V
    R Run time (high) 0040h 00064 — 1 hour
    R Run time (low) 0041h 00065
    R ON time (high) 0042h 00066 — 1 hour
    R ON time (low) 0043h 00067
    D086 — Trip monitor 6 R Factor code0044h 00068 (see codes in 
    next table)—
    R Inverter status 0045h 00069—
    R Frequency (high) 0046h 00070 0 to 40000 0.01 Hz
    R Frequency (low) 0047h 00071
    R Current 0048h 00072 — 0.1 A
    R Voltage 0049h 00073 — 1 V
    R Run time (high) 004Ah 00074 — 1 hour
    R Run time (low) 004Bh 00075
    R ON time (high) 004Ch 00076 — 1 hour
    R ON time (low) 004Dh 00077
    D090 — Programming error  monitor R Displays programming error 
    code 004Eh 00078 Warning 
    code—
    — (Reserved) ——004Fh 
    to 
    08FFh 00079 
    to 
    02303 ——
    Holding Registers, “D” Group Monitor Functions
    Func. CodeNameR/WDescription
    Network Data
    RegisterRangeRes.hexdec.
    
    Phone: 800.894.0412   
    						
    							ModBus Data Listing
    Appendix B
    B–40
    Note 1:Assume that the inverter current rating is 1000 (for D002).
    Note 2: When the value is 10000 (100.0 seconds),  a value in the second decimal place is 
    ignored.
    — — Write to EEPROM W 00 . Motor constant calculation 01 .  Set data storage in 
    EEPROM
    Other... Motor constant recalcu-
    lation and set data storage in 
    EEPROM 0900h 02304 0000,
    0001,
    other —
    — (Reserved) ——0901h 
    to 
    1000h 02305 
    to 
    4096 ——
    D102 — DC voltage monitoring Displays the DC Bus voltage 1026h 04134 0 to 9999 0.1 V
    D103 — BRD load factor monitor- ing Displays the running average 
    Dynamic Braking usage ratio 
    (%ED)1027h 04135 0 to 1000 0.1 %
    D104 — Electronic thermal  overload monitoring Displays the motor electronic 
    thermal overload estimated 
    temperature ratio. If the value 
    reaches 100%, th
    e inverter will 
    trip (E05) 1028h 04136 0 to 1000 0.1 %
    — (Reserved) ——1029h 
    to 
    102Dh 04137 
    to 
    04141 ——
    Holding Registers, “D” Group Monitor Functions
    Func. CodeNameR/WDescription
    Network Data
    RegisterRangeRes.hexdec.
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Appendix B
    B–41
    Trip Factor Code, HIGH orderTrip Factor Code, LOW order (inverter status)
    CodeNameCodeName
    0 No trip 0 Reset
    1 Over current event while at constant  speed 1Stop
    2 Over current event during  deceleration 2 Deceleration
    3 Over current event during acceleration 3 Constant speed
    4 Over current event during other condi- tions 4 Acceleration
    5 Overload protection 5 Run Command active with 0 Hz speed  reference
    6 Braking resistor  overload 6 Starting
    7 Over voltage protection 7 DC braking
    8 EEPROM error 8 Overload restriction
    9 Under-voltage error 9 SON or FOC operation in progress
    10 CT (current tr ansformer) error
    11 CPU error
    12 External trip
    13 USP
    14 Ground fault
    15 Input over-voltage
    16 Instantaneous power failure
    20 Inverter thermal trip with low fan  speed
    21 Inverter thermal trip
    23 Gate array error
    24 Phase failure detection
    25 Main circuit error
    30 IGBT error
    35 Thermistor
    36 Brake error
    37 Emergency stop
    38 Low-speed overload protection
    43 Easy sequence erro r (invalid instruc-
    tion)
    44 Easy sequence erro r (invalid nesting 
    count)
    45 Easy sequence execution error 1
    50 to 59 Easy sequence user trip 0 to 9
    60 to 69 Expansion card #1 error 0 to 9
    70 to 79 Expansion card #2 error 0 to 9
    
    Phone: 800.894.0412   
    						
    							ModBus Data Listing
    Appendix B
    B–42
    Holding Registers, “F” Group Main Profile Parameters
    Func. CodeNameR/WDescription
    Network Data
    RegisterRangeRes.hexdec.
    F001 H Output frequency setting R/W Standard default target  frequency that deter-
    mines constant motor 
    speed (when A001 = 03)0001h 00001 0 to 40000 0.01 Hz
    F001 L R/W 0002h 00002
    F002 H Acceleration (1) time  setting R/W Standard default acceler-
    ation 1103h 04355 1 to 
    3600000.01 sec.
    F002 L R/W 1104h 04356
    F202 H Acceleration (1) time  setting, 2nd motor R/W Standard default acceler-
    ation, 2nd motor 2103h 08451 1 to 
    3600000.01 sec.
    F202 L R/W 2104h 08452
    F302 H Acceleration (1) time  setting, 3rd motor R/W Standard default acceler-
    ation, 3rd motor 3103h 12547 1 to 
    3600000.01 sec.
    F302 L R/W 3104h 12548
    F003 H Deceleration (1) time  setting R/W Standard default deceler-
    ation 1105h 04357 1 to 
    3600000.01 sec.
    F003 L R/W 1106h 04358
    F203 H Deceleration (1) time  setting, 2nd motor R/W Standard default deceler-
    ation, 2nd motor 2105h 08453 1 to 
    3600000.01 sec.
    F203 L R/W 2106h 08454 — — (Reserved) — — 2107h  to 
    2202h 08455 
    to 
    08706 ——
    F303 H Deceleration (1) time  setting, 3rd motor R/W Standard default deceler-
    ation, 3rd motor 3105h 12549 1 to 
    3600000.01 sec.
    F303 L R/W 3106h 12550 — — (Reserved) — — 3107h  to 
    3202h 12551 
    to 
    12802 ——
    F004 — Keypad Run key routing R/W 1107h 04359 — — (Reserved) — — 1108h  to 
    1200h 04360 
    to 
    04608 ——
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Appendix B
    B–43
           
    Holding Registers, “A” Group  Standard Functions
    Func. CodeNameR/WDescription
    Network Data
    RegisterRangeRes.hexdec.
    A001 — Frequency source setting R/W 00 . Keypad potentiometer 01 . Control terminal
    02 . Function F001 setting
    03 . RS485 serial command
    04 . Expansion board #1
    05 . Expansion board #2
    06 . Pulse train input
    07 . Easy sequence
    10 . Caltulate function input1201h 04609 00 to 07, 
    10—
    A002 — Run command source  setting R/W 01 . Input [FW] or [RV]
    02 . Run key on keypad
    03 . RS485 serial command
    04 . Start/stop, Exp. card #1
    05 . Start/stop. exp. card #2 1202h 04610 01 to 05 —
    A003 — Base frequency setting R/W 30. to  max. frequency (Hz) 1203h 04611 30 to 
    A004 val.1 Hz
    A203 — Base frequency setting,  2nd motor R/W 30. to max. frequency (Hz) 2203h 08707 30 to 
    A004 val.1 Hz
    A303 — Base frequency setting, 3rd  motor R/W 30. to max. frequency (Hz) 3203h 12803 30 to 
    A004 val.1 Hz
    A004 — Maximum frequency  setting R/W 30. to 400. (Hz) 1204h 04612 30 to 400 1 Hz
    A204 — Maximum frequency  setting, 2nd motor R/W 30. to 400. (Hz) 2204h 08708 30 to 400 1 Hz
    — (Reserved) — — 2205h  to 
    2215h 08709 
    to 
    08725 ——
    A304 — Maximum frequency  setting, 3rd motor R/W 30. to 400. (Hz) 3204h 12804 30 to 400 1 Hz
    — (Reserved) — — 3205h  to 
    3215h 12805 
    to 
    12821 ——
    A005 — [AT] selection R/W 00 . Select between [O] and       [OI] at [AT]
    01 . Select between [O] and
          [O2] at [AT]
    02 . Select between [O] and
          keypad pot.
    03 . Select between [OI] and
          keypad pot.
    04 . Select between [O2] and
          keypad pot.1205h 04613 00 to 04 —
    A006 — [O2] selection R/W 00 . No summing, [O2] and       [OI]
    01 . Sum of [O2] and [OI],
          neg. sum (reverse speed
          reference) inhibited
    02 . Sum of [O2] and [OI],
          neg. sum (reverse speed
          reference) allowed
    03 . Disable [O2] input1206h 046 00 to 03 —
    
    Phone: 800.894.0412   
    						
    							ModBus Data Listing
    Appendix B
    B–44
    — (Reserved)——1207h 
    to 
    120Ah 04614 
    to 
    04618 ——
    A011 H [O]–[L] input active range  start frequency R/W The output frequency corre-
    sponding to the voltage input 
    range starting point 120Bh 04619 0 to 40000 0.01 Hz
    A011 L 120Ch 04620
    A012 H [O]–[L] input active range  end frequency R/W The output frequency corre-
    sponding to the voltage input 
    range ending point 120Dh 04621 0 to 40000 0.01 Hz
    A012 L 120Eh 04622
    A013 — [O]–[L] input active range  start voltage R/W The starting point for the 
    voltage input range 120Fh 04623 0 to A014 
    value1 %
    A014 — [O]–[L] input active range  end voltage R/W The ending point for the 
    voltage input range 1210h 04624 A013 
    value to 100 1 %
    A015 — [O]–[L] input start  frequency enable R/W 00 ..Use A011 start value
    01 ..Use 0 Hz 1211h 04625 0, 1 —
    A016 — External frequency filter  time const. R/W n = 1 to 30 (where n = 
    number of samples for 
    average); 31 = 500ms filter 1212h 04626 1 to 30, 31 1
    A017 — Easy sequence function  enable R/W 00 ..Disable
    01 ..Enable 1213h 04627 0, 1 —
    — (Reserved) ——1214h 04628 — —
    A019 — Multi-speed operation  selection R/W 00 ..Binary; up to 16-stage
          speed using 4 terminals
    01 ..Single-bit; up to 8-stage
         speed using 7 terminals 1215h 04629 0, 1 —
    A020 H Multi-spee d frequency 
    setting R/W Defines the first speed of a 
    multi-speed profile 1216h 04630 0 or start 
    freq. to 
    max. freq. 0.01 Hz
    A020 L 1217h 04631
    A220 H Multi-spee d frequency 
    setting, 2nd motor R/W Defines the first speed of a 
    multi-speed profile for 2nd 
    motor 2216h 08726 0 or start 
    freq. to 
    max. freq. 0.01 Hz
    A220 L 2217h 08727
    — (Reserved) ——2218h 
    to 
    223Ah 08728 
    to 
    08762 ——
    A320 H Multi-spee d frequency 
    setting, 3rd motor R/W Defines the first speed of a 
    multi-speed profile for 3rd 
    motor 3216h 12822 0 or start 
    freq. to 
    max. freq. 0.01 Hz
    A320 L 3217h 12823
    — (Reserved) ——3218h 
    to 
    323Bh 12824 
    to 
    12859 ——
    A021 H Multi-speed 1 setting R/W Def
    
    ines nth additional speed 1218h 04632 0 or start 
    freq. to 
    max. freq. 0.01 Hz
    A021 L 1219h 04633
    A022 H Multi-speed 2 setting R/W Defines nth additional speed 121Ah 04634 0 or start 
    freq. to 
    max. freq. 0.01 Hz
    A022 L 121Bh 04635
    A023 H Multi-speed 3 setting R/W Defines nth additional speed 121Ch 04636 0 or start 
    freq. to 
    max. freq. 0.01 Hz
    A023 L 121Dh 04637
    Holding Registers, “A” Group  Standard Functions
    Func. CodeNameR/WDescription
    Network Data
    RegisterRangeRes.hexdec.
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Appendix B
    B–45
    A024 H Multi-speed 4 setting R/W Defines nth additional speed 121Eh 04638 0 or start freq. to 
    max. freq. 0.01 Hz
    A024 L 121Fh 04639
    A025 H Multi-speed 5 setting R/W Defines nth additional speed 1220h 04640 0 or start  freq. to 
    max. freq. 0.01 Hz
    A025 L 1221h 04641
    A026 H Multi-speed 6 setting R/W Defines nth additional speed 1222h 04642 0 or start  freq. to 
    max. freq. 0.01 Hz
    A026 L 1223h 04643
    A027 H Multi-speed 7 setting R/W Defines nth additional speed 1224h 04644 0 or start  freq. to 
    max. freq. 0.01 Hz
    A027 L 1225h 04645
    A028 H Multi-speed 8 setting R/W Defines nth additional speed 1226h 04646 0 or start  freq. to 
    max. freq. 0.01 Hz
    A028 L 1227h 04647
    A029 H Multi-speed 9 setting R/W Defines nth additional speed 1228h 04648 0 or start  freq. to 
    max. freq. 0.01 Hz
    A029 L 1229h 04649
    A030 H Multi-speed  10 setting R/W Defines nth additiona l speed 122Ah 04650 0 or start 
    freq. to 
    max. freq. 0.01 Hz
    A030 L 122Bh 04651
    A031 H Multi-speed  11 setting R/W Defines nth additiona l speed 122Ch 04652 0 or start 
    freq. to 
    max. freq. 0.01 Hz
    A031 L 122Dh 04653
    A032 H Multi-speed  12 setting R/W Defines nth additiona l speed 122Eh 04654 0 or start 
    freq. to 
    max. freq. 0.01 Hz
    A032 L 122Fh 04655
    A033 H Multi-speed  13 setting R/W Defines nth additiona l speed 1230h 04656 0 or start 
    freq. to 
    max. freq. 0.01 Hz
    A033 L 1231h 04657
    A034 H Multi-speed  14 setting R/W Defines nth additiona l speed 1232h 04658 0 or start 
    freq. to 
    max. freq. 0.01 Hz
    A034 L 1233h 04659
    A035 H Multi-speed  15 setting R/W Defines nth additiona l speed 1234h 04660 0 or start 
    freq. to 
    max. freq. 0.01 Hz
    A035 L 1235h 04661
    — (Reserved) — — 1236h 04662 — —
    — (Reserved) — — 1237h 04663 — —
    A038 — Jog frequency setting R/W De fines limited speed for jog1238h 04664 0 to 999 0.01 Hz
    Holding Registers, “A” Group  Standard Functions
    Func. CodeNameR/WDescription
    Network Data
    RegisterRangeRes.hexdec.
    
    Phone: 800.894.0412   
    						
    							ModBus Data Listing
    Appendix B
    B–46
    A039 — Jog stop modeR/W 00 ..Free-run stop, jogging
          disabled during motor run
    01 ..Controlled deceleration,
          jogging disabled during
          motor run
    02 ..DC braking to stop,
          jogging  disabled during
          motor run
    03 ..Free-run stop, jogging
          always enabled
    04 ..Controlled deceleration,
          jogging always enabled
    05 ..DC braking to stop,
          jogging  always enabled 1239h 04665 0 to 5 —
    — (Reserved) ——123Ah 04666 — —
    A041 — Torque boost method  selection R/W 00 ..Manual torque boost
    01 ..Automatic torque boost 123Bh 04667 0, 1 —
    A241 — Torque boost method  selection, 2nd motor R/W 00 ..Manual torque boost
    01 ..Automatic torque boost 223Bh 08763 0, 1 —
    A042 — Manual torque boost value R/W Can boost starting torque  between 0 and 20% above 
    normal V/f curve123Ch 04668 0 to 200 0.1 %
    A242 — Manual torque boost value,  2nd motor R/W Can boost starting torque 
    between 0 and 20% above 
    normal V/f curve 223Ch 08764 0 to 200 0.1 %
    A342 — Manual torque boost value,  3rd motor R/W Can boost starting torque 
    between 0 and 20% above 
    normal V/f curve 323Ch 12860 0 to 200 0.1 %
    A043 — Manual torque boost  frequency adjustment R/W Sets the frequency of the V/f 
    breakpoint for torque boost 123Dh 04669 0 to 500 0.1 %
    A243 — Manual torque boost  frequency adjustment, 2nd 
    motor R/W Sets the frequency of the V/f 
    breakpoint for torque boost 223Dh 08765 0 to 500 0.1 %
    A343 — Manual torque boost  frequency adjustment, 3rd 
    motor R/W Sets the frequency of the V/f 
    breakpoint for torque boost 323Dh 12861 0 to 500 0.1 %
    A044 — V/F characteristic curve  selection R/W 00 ..V/f constant torque
    01 ..V/f variable torque
    02 ..V/f free-setting curve
    03 ..Sensorless vector SLV
    04 ..0Hz domain SLV
    05 ..Vector control with
           encoder feedback 123Eh 04670 0 to 5 —
    A244 — V/F characteristic curve  selection, 2nd motor R/W 00 ..V/f constant torque
    01 ..V/f variable torque
    02 ..V/f free-setting curve
    03 ..Sensorless vector SLV
    04 ..0Hz domain SLV 223Eh 08766 0 to 4 —
    — (Reserved) ——223Fh 08767 — —
    A344 V/F characteristic curve  selection, 3rd motor R/W 00 ..V/f constant torque
    01 ..V/f variable torque 323Eh 12862 0, 1 —
    Holding Registers, “A” Group  Standard Functions
    Func. CodeNameR/WDescription
    Network Data
    RegisterRangeRes.hexdec.
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Appendix B
    B–47
    — (Reserved)——323Fh 
    to 
    326Ch 12863 
    to 
    12908 ——
    A045 — V/f gain setting R/W Sets voltage gain of the 
    inverter 123Fh 04671 20 to 200 1 %
    A046 — Automatic torque boost  voltage gain R/W Voltage compensation gain 
    for automatic  torque boost 1240h 04672 0 to 255 1
    A246 — Automatic torque boost  voltage gain, 2nd motor R/W Voltage compensation gain 
    for automatic  torque boost 2240h 08768 0 to 255 1
    A047 — Automatic torque boost  slip gain R/W Slip compensa
    tion gain for 
    automatic to rque boost 1241h 04673 0 to 255 1
    — (Reserved) ——1242h 
    to 
    1244h 04674 
    to 
    04676 ——
    A247 — Automatic torque boost  slip gain, 2nd motor Slip compensa
    tion gain for 
    automatic to rque boost 2241h 08769 0 to 255 1
    — (Reserved) ——2242h 
    to 
    224Eh 08770 
    to 
    08782 ——
    A051 — DC braking enable R/W 00 . Disable 01 . Enable
    02 . Brake at set frequency
          only1245h 04677 0, 1, 2 —
    A052 — DC braking frequency  setting R/W Frequency at which DC 
    braking activates during 
    decel. 1246h 04678 0 to 40000 0.01 Hz
    A053 — DC braking wait time R/W Th e delay after reaching the 
    DC braking frequency, or 
    [DB] signal, before DC 
    braking begins 1247h 04679 0 to 50 0.1 sec.
    A054 — DC braking force during  deceleration R/W Variable DC braking force 1248h 04680 0 to 80 1 %
    A055 — DC braking  time for decel-
    eration R/W Sets the duration for DC 
    braking during decel 1249h 04681 0 to 600 0.1 sec.
    A056 — DC braking / edge or level  detection for [DB] input R/W 00 . Edge detection
    01 . Level detection 124Ah 04682 0, 1 —
    A057 — DC braking force for  starting R/W Variable DC braking force 124Bh 04683 0 to 80 1 %
    A058 — DC braking time for  starting R/W Sets the duration for DC 
    braking before accel. 124Ch 04684 0 to 600 0.1 sec.
    A059 — DC braking carrier  frequency setting R/W 0.5 to 15 (kHz) for models 
    up to –550xxx, 0.5 to 10 
    (kHz) for 750xxx to 1500xxx 
    models 124Dh 04685 5 to 150;
    5 to 1000.1 kHz
    — (Reserved) ——124Eh 04686 — —
    A061 H Frequency upper limit  setting R/W Sets a limit on output 
    frequency less than the 
    maximum frequency (A004) 124
    Fh 0468 7
     0, 50 to 
    40000 0.01 Hz
    A061 L 1250h 04688
    Holding Registers, “A” Group  Standard Functions
    Func. CodeNameR/WDescription
    Network Data
    RegisterRangeRes.hexdec.
    
    Phone: 800.894.0412   
    						