    							ModBus Data Listing
    Appendix B
    B–48
    A261 H Frequency upper limit setting, 2nd motor R/W Sets a limit on output 
    frequency less than the 
    maximum frequency (A004) 224Fh 08783 0, 50 to 
    400000.01 Hz
    A261 L R/W 2250h 08784
    A062 H Frequency lower limit  setting R/W Sets a limit on output 
    frequency greater than zero 1251h 04689 0, 50 to 
    400000.01 Hz
    A062 L R/W 1252h 04690
    A262 H Frequency lower limit  setting, 2nd motor R/W Sets a limit on output 
    frequency greater than zero 2251h 08785 0, 50 to 
    400000.01 Hz
    A262 L R/W 2252h 08786 — — (Reserved) — — 2253h  to 
    226Eh 08787 
    to 
    08814 ——
    A063 H Jump (center) frequency  setting R/W Up to 3 output frequencies 
    can be defined for the output 
    to jump past to avoid motor 
    resonances (c enter freq.) 1253h 04691 0 to 40000 0.01 Hz
    A063 L R/W1254h 04692
    A064 — Jump (hysteresis)  frequency width setting R/W Defines the distance from the 
    center frequency at which the 
    jump occurs 1255h 04693 0 to 1000 0.01 Hz
    A065 H Jump (center) frequency  setting R/W Up to 3 output frequencies 
    can be defined for the output 
    to jump past to avoid motor 
    resonances (c enter freq.) 1256h 04694 0 to 40000 0.01 Hz
    A065 L R/W1257h 04695
    A066 — Jump (hysteresis)  frequency width setting R/W Defines the distance from the 
    center frequency at which the 
    jump occurs 1258h 04696 0 to 1000 0.01 Hz
    A067 H Jump (center) frequency  setting R/W Up to 3 output frequencies 
    can be defined for the output 
    to jump past to avoid motor 
    resonances (c enter freq.) 1259h 04697 0 to 40000 0.01 Hz
    A067 L R/W125Ah 04698
    A068 — Jump (hysteresis)  frequency width setting R/W Defines the distance from the 
    center frequency at which the 
    jump occurs 125Bh 04699 0 to 1000 0.01 Hz
    A069 H Acceleration stop  frequency setting R/W 0.00 to 400.0 (Hz)
    125Ch 04700 0 to 40000 0.01 Hz
    A069 L R/W125Dh 04701
    A070 — Acceleration stop time  frequency setting R/W 0.0 to 60.0 (seconds) 125Eh 04702 0 to 600 0.1 sec.
    A071 — PID Function Enable R/ W 00 ..PID operation OFF
    01 ..PID operation ON
    02 ..PID operation ON with
          inverted output 125Fh 04703 0, 1, 2 —
    A072 — PID proportional gain R/W 0.2 to 5.0 1260h 0474 2 to 50 0.2
    A073 — PID integral time constant R/W 0.0 to 999.9, 1000. to 3600.  (seconds)1261h 04705 0 to 36000 0.1 sec.
    A074 — PID derivative gain R/W 0.0 to 99.99, 100.0 (seconds) 1262h 04706 0 to 10000 0.01 sec.
    A075 — PV scale conversion R/W 0.01 to 99.99, 100.0  (seconds)1263h 04707 1 to 9999 0.01
    Holding Registers, “A” Group  Standard Functions
    Func. CodeNameR/WDescription
    Network Data
    RegisterRangeRes.hexdec.
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Appendix B
    B–49
    A076 — PV source setting R/W 00 . [OI] (current input)01 . [O] (voltage input)
    02 . Communication input
    03 . Pulse train freq. input
    10 . Calculate function output1264h 04708 0 to 3, 10 —
    A077 — Reverse PID action R/W 00 . PID input = SP – PV       (normal)
    01 . PID input = –(SP – PV)
          (reverse)1265h 04709 0, 1 —
    A078 — PID output limit R/W Range is 0.0 to 100.0 1266h 04710 0 to 1000 0.1 sec.
    A079 — PID feed forward select R/W 00 . Disable 01 . [O] (voltage input)
    02 . [OI] (current input)
    03 . [O2] (voltage input)1267h 04711 0 to 3 —
    — (Reserved) — — 1268h 04712 — —
    A081 — AVR function select R/W 00 . AVR enabled 01 . AVR disabled
    02 . AVR enabled except 
    during deceleration1269h 04713 0, 1, 2 —
    A082 — AVR voltage select R/W 2 00V class inverter settings:
    200/215/220/230/240 (V)
    400V class inverter settings:
    380/400/415/440/460/480 
    (V) 126Ah 04714 — —
    — (Reserved) — — 126Bh 04715 — —
    — (Reserved) — — 126Ch 04716 — —
    A085 — Operation mode selection R/W 00 . Normal operation 01 . Energy-saver operation
    02 . Optimal accel/decel
          operation126Dh 04717 0, 1, 2 —
    A086 — Energy saving mode tuning R/W 0.0 to 100 (seconds) 126Eh 04718 0 to 1000 0.1 % — (Reserved) — — 126Fh  to 
    1273h 04719 
    to 
    04723 ——
    A092 H Acceleration (2) time  setting R/W Duration of 2nd segment of 
    acceleration 1274h 04724 1 to 
    3600000.01 sec.
    A092 L R/W 1275h 04725
    A292 H Acceleration (2) time  setting, 2nd motor R/W Duration of 2nd segment of 
    acceleration, 2nd motor 226Fh 08815 1 to 
    3600000.01 sec.
    A292 L R/W 2270h 08816
    A392 H Acceleration (2) time  setting, 3rd motor R/W Duration of 2nd segment of 
    acceleration, 3rd motor 326Dh 12909 1 to 
    3600000.01 sec.
    A392 L R/W 326Eh 12910
    A093 H Deceleration (2) time  setting R/W Duration of 2nd segment of 
    deceleration 1276h 04726 1 to 
    3600000.01 sec.
    A093 L R/W 1277h 04727
    A293 H Deceleration (2) time  setting, 2nd motor R/W Duration of 2nd segment of 
    deceleration, 2nd motor 2271h 08817 1 to 
    3600000.01 sec.
    A293 L R/W 2272h 08818
    A393 H Deceleration (2) time  setting, 3rd motor R/W Duration of 2nd segment of 
    deceleration, 3rd motor 326Fh 12911 1 to 
    3600000.01 sec.
    A393 L R/W 3270h 12912
    Holding Registers, “A” Group  Standard Functions
    Func. CodeNameR/WDescription
    Network Data
    RegisterRangeRes.hexdec.
    
    Phone: 800.894.0412   
    						
    							ModBus Data Listing
    Appendix B
    B–50
    — (Reserved)——3271h 
    to 
    330Bh 12913 
    to 
    13067 ——
    A094 — Select method to switch to  Acc2/Dec2 profile R/W 00 ..[2CH] terminal input
    01 ..transition frequency
    02 ..when motor direction
           reverses 1278h 04728 0, 1, 2 —
    A294 — Select method to switch to  Acc2/Dec2, 2nd motor R/W 00 ..[2CH] terminal input
    01 ..transition frequency
    02 ..when motor direction
           reverses 2273h 08819 0, 1, 2 —
    A095 H Acc1 to Acc2 frequency  transition point R/W Output frequency at which 
    Accel1 switches to Accel2 1279h 04729 0 to 40000 0.01 Hz
    A095 L R/W127Ah 04730
    A295 H Acc1 to Acc2 frequency  transition point, 2nd motor R/W Output frequency at which 
    Accel1 switches to Accel2 2274h 08820 0 to 40000 0.01 Hz
    A295 L R/W2275h 08821
    A096 H Dec1 to Dec2 frequency  transition point R/W Output frequency at which 
    Decel1 switches to Decel2 127Bh 04731 0 to 40000 0.01 Hz
    A096 L R/W127Ch 04732
    A296 H Dec1 to Dec2 frequency  transition point, 2nd motor R/W Output frequency at which 
    Decel1 switches to Decel2 2276h 08822 0 to 40000 0.01 Hz
    A296 L R/W2277h 08823
    — (Reserved) ——2278h 
    to 
    230Bh 08824 
    to 
    08971 ——
    A097 — Acceleration curve  selection R/W 00 ..Linear
    01 ..S-curve
    02 ..U-shape
    03 ..Reverse U-shape
    04 ..EL-S curve 127Dh 04733 0 to 4 —
    A098 — Deceleration curve setting R/W 00 ..Linear 01 ..S-curve
    02 ..U-shape
    03 ..Reverse U-shape
    04 ..EL-S curve127Eh 04734 0 to 4 —
    — (Reserved) ——127Fh 04735 — —
    — (Reserved) ——1280h 04736 — —
    A101 H [OI]–[L] input active range  start frequency R/W Output frequency corre-
    sponding to the current input 
    range starting point 1281h 04637 0 to 40000 0.01 Hz
    A101 L R/W1282h 04738
    A102 H [OI]–[L] input active range  end frequency R/W Output frequency corre-
    sponding to the current input 
    range ending point 1283h 04739 0 to 40000 0.01 Hz
    A102 L R/W1284h 04740
    A103 — [OI]–[L] input active range  start current R/W Starting point for the current 
    input range 1285h 04741 0 to A104 
    value1 %
    A104 — [OI]–[L] input active range  end current R/W Ending point for the current 
    input range 1286h 04742 A103 
    value to 
    100 1 %
    A105 — [OI]–[L] input start  frequency enable R/W 00 ..Use A101 start value
    01 ..Use 0Hz 1287h 04743 0, 1 —
    Holding Registers, “A” Group  Standard Functions
    Func. CodeNameR/WDescription
    Network Data
    RegisterRangeRes.hexdec.
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Appendix B
    B–51
    — (Reserved)——1288h 
    to 
    128Ch 04744 
    to 
    0448 ——
    A111 H [O2]–[L] input active  range start frequency R/W Output frequency corre-
    sponding to the bipolar 
    voltage input range starting 
    point 128Dh 04749 -40000 to 
    400000.01 Hz
    A111 L R/W128Eh 04750
    A112 H [O2]–[L] input active  range end frequency R/W Output frequency corre-
    sponding to the bipolar 
    voltage input range ending 
    point 128Fh 04751 -40000 to 
    400000.01 Hz
    A112 L R/W1290h 04752
    A113 — [O2]–[L] input active  range start voltage R/W Starting point for the bipolar 
    voltage input range 1291h 04753 -100 to 
    A114 value 1 %
    A114 — [O2]–[L] input active  range end voltage R/W Ending point for the bipolar 
    voltage input range 1292h 04754 A113 
    value to 100 1 %
    — (Reserved) ——1293h 
    to 
    12A4h 04755 
    to 
    04772 ——
    A131 — Acceleration curve  constants setting R/W Sets the curve deviation from 
    straight-line acceleration in 
    10 levels (01 to 10) 12A5h 04773 1 to 10 —
    A132 — Deceleration curve  constants setting R/W Sets the curve deviation from 
    straight-line de celeration in 
    10 levels  (01 to 10) 12A6h 04774 1 to 10 —
    — (Reserved) ——12A7h 
    to 
    12AEh 04775 
    to 
    04782 ——
    A141 — A input select for calculate  function R/W 00 . Digital operator (A020/
          A220/A320)
    01 . Keypad potentiometer
    02 . [O] input
    03 . [OI] input
    04 . Comm. port
    05 . Expansion card 1
    06 . Expansion card 2
    07 . Pulse train frequency
           train input 12AFh 04783 0 to 7 —
    A142 — B input select for calculate  function R/W 00 . Digital operator (A020/
          A220/A320)
    01 . Keypad potentiometer
    02 . [O] input
    03 . [OI] input
    04 . Comm. port
    05 . Expansion card 1
    06 . Expansion card 2
    07 . Pulse train frequency
           train input 12B0h 04784 0 to 7 —
    A143 — Calculation symbol R/W 0 0 . ADD (A input + B input)
    01 . SUB (A input – B input)
    02 . MUL (A input x B input) 12B1h 04785 0, 1, 2 —
    — (Reserved) ——12B2h 04786 — —
    Holding Registers, “A” Group  Standard Functions
    Func. CodeNameR/WDescription
    Network Data
    RegisterRangeRes.hexdec.
    
    Phone: 800.894.0412   
    						
    							ModBus Data Listing
    Appendix B
    B–52
    A145 H ADD frequencyR/W 0.00 to 99.99, 
    100.0 to 400.0 (Hz) 12B3h 04787 0 to 40000 0.01 Hz
    A145 L R/W12B4h 04788
    A146 — ADD direction select R/W 0 0 ..Plus (adds A145 value to
           output  frequency)
    01 ..Minus (subtracts A145
          value from output freq.) 12B5h 04789 0, 1 —
    — (Reserved) ——12B6h 
    to 
    12B8h 04790t
    o 
    04792 ——
    A150 — EL-S curve acceleration  ratio 1 R/W Range is 0. to 50.
    12B9h 04793 0 to 50 1 %
    A151 — EL-S curve acceleration  ratio 2 R/W Range is 0. to 50.
    12BAh 04794 0 to 50 1 %
    A152 — EL-S curve acceleration  ratio 3 R/W Range is 0. to 50.
    12BBh 04795 0 to 50 1 %
    A153 — EL-S curve acceleration  ratio 4 R/W Range is 0. to 50.
    12BCh 04796 0 to 50 1 %
    —(Reserved) — — 12BDh 
    to 
    1300h 04797 
    to 
    04864 ——
    Holding Registers, “A” Group  Standard Functions
    Func. CodeNameR/WDescription
    Network Data
    RegisterRangeRes.hexdec.
    Holding Registers, “B” Group Fine Tuning Functions
    Func. CodeNameR/WDescription
    Network Data
    RegisterRangeRes.hexdec.
    B001 — Selection of restart mode R/W 00 . Alarm output after trip,       automatic restart disabled
    01 . Resume operation after
          frequency matching
    02 . Resume operation after
          frequency matching
    03 . Resume previous freq.
           after freq. matching, then
          decelerate to stop and
          display trip info
    04 . Restart with active
          matching frequency 1301h 04865 0 to 4 —
    B002 — Allowable under-voltage  power failure time R/W The amount of time a power 
    input under-voltage can occur 
    without tripping the power 
    failure alarm 1302h 04866 3 to 250 0.1 sec.
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Appendix B
    B–53
    B003 — Retry wait time before motor restart R/W Time delay after a trip condition 
    goes away before the inverter 
    restarts the motor 1303h 04867 3 to 1000 0.1 sec.
    B004 — Instantaneous power  failure / under-voltage trip 
    alarm enable R/W 00 . Disable
    01 . Enable
    02 . Disable during stop and
          ramp to stop 1304h 04868 0, 1, 2 —
    B005 — Number of restarts on  power failure / under-
    voltage trip events R/W 00 . Restart 16 times
    01 . Always restart 1305h 04869 0, 1 —
    B006 — Phase loss detection enable R/W 00 . Disable 01 . Enable1306h 04870 0, 1 —
    B007 H Restart frequency thresh- old R/W When the frequency of the motor 
    is less than this value, the 
    inverter will restart at 0 Hz 1307h 04871 0 to 40000 0.01 Hz
    B007 L R/W 1308h 04872
    B008 — Retry after trip select R/W 00 . Always retry after trip
    01 . Start with 0 Hz
    02 . Start with frequency
          matching
    03 . Retry after deceleration
          and stop with matching
          frequency
    04 . Start with active
          matching frequency 1309h 04873 0 to 4 —
    B009 — Retry after undervoltage  select R/W 00 . Restart 16 times
    01 . Unlimited 130Ah 04874 0, 1 —
    B010 — Retry count select after  overvoltage or overcurrent R/W 1 to 3 (times) 130Bh 04875 1 to 3 times
    B011 — Retry wait time after trip R/W 0.3 to 1 00.0 (seconds) 130Ch 04876 3 to 1000 0.1 sec.
    B012 — Electronic thermal setting  (calculated within the 
    inverter from current 
    output) R/W Range is 0.2 * rated current to 
    1.2 * rated current 130Dh 04877 200 to 
    10000.1 %
    B212 — Electronic thermal setting  (calculated within the 
    inverter from current 
    output), 2nd motor R/W Range is 0.2 * rated current to 
    1.2 * rated current 230Ch 08972 200 to 
    10000.1 %
    B312 — Electronic thermal setting  (calculated within the 
    inverter from current 
    output), 3rd motor R/W Range is 0.2 * rated current to 
    1.2 * rated current 330Ch 13068 200 to 
    10000.1 %
    B013 — Electronic thermal charac- teristic R/W 00 . Reduced torque
    01 . Constant torque
    02 . Free-setting 130Eh 04878 0, 1, 2 —
    — (Reserved) — 130Fh 04879 — —
    B213 — Electronic thermal charac- teristic, 2nd motor R/W 00 . Reduced torque
    01 . Constant torque
    02 . Free-setting 230Dh 08973 0, 1, 2 —
    —(Reserved) — — 230Eh  to 
    2501h 08974 
    to 
    09493 ——
    Holding Registers, “B” Group Fine Tuning Functions
    Func. CodeNameR/WDescription
    Network Data
    RegisterRangeRes.hexdec.
    
    Phone: 800.894.0412   
    						
    							ModBus Data Listing
    Appendix B
    B–54
    B313 — Electronic thermal charac-teristic, 3rd motor R/W 00 . Reduced torque
    01 . Constant torque
    02 . Free-setting 330Dh 13069 0, 1, 2 —
    — (Reserved) — — 330Eh  to 
    3506h 13070 
    to 
    13574 ——
    B015 — Free setting, electronic  thermal frequency (1) R/W Data point coordinates for Hz 
    axis (horizontal)  in the free-form 
    curve 1310h 04880 0 to 400 1 Hz
    B016 — Free setting, electronic  thermal current (1) R/W Data point coordinates for 
    Ampere axis (vertical) in the 
    free-form curve 1311h 04881 0 to rated 
    current0.1 A
    B017 — Free setting, electronic  thermal frequency (2) R/W Data point coordinates for Hz 
    axis (horizontal)  in the free-form 
    curve 1312h 04882 0 to 400 1 Hz
    B018 — Free setting, electronic  thermal current (2) R/W Data point coordinates for 
    Ampere axis (vertical) in the 
    free-form curve 1313h 04883 0 to rated 
    current0.1 A
    B019 — Free setting, electronic  thermal frequency (3) R/W Data point coordinates for Hz 
    axis (horizontal)  in the free-form 
    curve 1314h 04884 0 to 400 1 Hz
    B020 — Free setting, electronic  thermal current (3) R/W Data point coordinates for 
    Ampere axis (vertical) in the 
    free-form curve 1315h 04885 0 to rated 
    current0.1 A
    B021 — Overload restriction opera- tion mode R/W 00 . Disable
    01 . Enable for acceleration
          and constant speed
    02 . Enable for constant
          speed only
    03 . Enable for accel, decel,
          and constant speed 1316h 04886 0 to 3 —
    B022 — Overload restriction setting R/W (0.20 x rated current) to (1.80 x 
    rated current) (A)1317h 04887 200 to 
    20000.1 %
    B023 — Deceleration rate at  overload restriction R/W 0.10 to 30.00 (seconds) 1318h 04888 10 to 3000 0.1 sec.
    B024 — Overload restriction opera- tion mode (2) R/W 00 . Disable
    01 . Enable for acceleration
          and constant speed
    02 . Enable for constant
          speed only
    03 . Enable for accel, decel,
          and constant speed 1319h 04889 0 to 3 —
    B025 — Overload restriction setting  (2) R/W (0.20 x rated current) to (1.80 x 
    rated current) (A) 131Ah 04890 200 to 
    20000.1 %
    B026 — Deceleration rate at  overload restriction (2) R/W 0.10 to 30.00 (seconds) 131Bh 04891 1 to 3000 0.01 sec.
    B027 — Overcurrent suppression  enable R/W 00 . Disable
    01 . Enable 131Ch 04892 0, 1 —
    B028 — Current limit for active  frequency-matching restart R/W (0.20 x rated current) to (1.80 x 
    rated current) (A) 131Dh 04893 200 to 
    20000.1
     %
    Holding Registers, “B” Group Fine Tuning Functions
    Func. CodeNameR/WDescription
    Network Data
    RegisterRangeRes.hexdec.
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Appendix B
    B–55
    B029 — Scan time constant for active freq. matching R/W 10 to 3000 131Eh 04894 0.01 sec. 0.01 sec.
    B030 — Restart freq. select for  active freq. matching R/W 00 . Frequency at last shutoff
    01 . Maximum frequency
    02 . Set frequency 131Fh 04895
    B031 — Software lock mode selec- tion R/W 00 . Low-level access, [SFT]
          input blocks all edits
    01 . Low-level access, [SFT]
          input blocks edits (except
          F001 and Multi-speed
          parameters)
    02 . No access to edits
    03 . No access to edits except
          F001 and Multi-speed
          parameters
    10 . High-level access,
           including B031 1320h 04896
    — (Reserved) — — 1321h 04897 — —
    — (Reserved) — — 1322h 04898 — —
    B034 H Run/power-on warning  time R/W 0 to 9999. (0 to 99990), 1000 to 
    6553 (10000 to 655300) (hours) 1323h 04899 0 to 65535 1 [10-
    hours] 
    B034 L R/W 1324h 04900
    B035 — Rotational direction 
    restriction R/W 00 . Enable for fwd. and rev.
    01 . Enable for forward only
    02 . Enable for reverse only 1325h 04901 0, 1, 2 —
    B036 — Reduced voltage start  selection R/W 000 (short) to 255 (long) 1326h 04902 0 to 255 —
    B037 — Function code display  restriction R/W 00 . Display all
    01 . Display only utilized
          functions 
    02 . Display user-selected
          functions only
    03 . Data comparison display
    04 . Basic display 1327h 04903 0 to 4 —
    B038 — Initial display selection R /W 00 . Last value dislayed when
          STR key was pressed
    01 . D001
    02 . D002
    03 . D003
    04 . D007
    05 . F001 1328h 04904 0 to 5 —
    B039 — Automatic user parameter  function enable R/W 00 . Disable
    01 . Enable 1329h 04905 0, 1 —
    B040 — Torque limit selec tion R/W 00 . 4-quadrant mode
    01 . Selected by two input
           terminals 
    02 . From analog [O2] input
    03 . From expansion card 1
    04 . From expansion card 2 132Ah 04906 0 to 4 —
    B041 — Torque limit (1) (forward- driving in 4-quadrant 
    mode) R/W 0. to 200. (%), no (disable torque 
    limit) 132Bh 04907 0 to 200, 
    255= (no)1 %
    Holding Registers, “B” Group Fine Tuning Functions
    Func. CodeNameR/WDescription
    Network Data
    RegisterRangeRes.hexdec.
    
    Phone: 800.894.0412   
    						
    							ModBus Data Listing
    Appendix B
    B–56
    B042 — Torque limit (2) (reverse-regenerating in 4-quadrant 
    mode) R/W 0. to 200. (%), 
    no (disable torque 
    limit) 132Ch 04908 0 to 200, 
    255= (no)1 %
    B043 — Torque limit (3) (reverse- driving in 4-quadrant 
    mode) R/W 0. to 200. (%), 
    no (disable torque 
    limit) 132Dh 04909 0 to 200, 
    255= (no)1 %
    B044 — Torque limit (4) (forward- regenerating in 4-quadrant 
    mode) R/W 0. to 200. (%), 
    no (disable torque 
    limit) 132Eh 04910 0 to 200, 
    255= (no)1 %
    B045 — Torque limit LADSTOP  enable R/W 00 . Disable
    01 . Enable 132Fh 04911 0, 1 —
    B046 — Reverse Run protection  enable R/W 00 . Disable
    01 . Enable 1330h 04912 0, 1 —
    — (Reserved) — — 1331h  to 
    1333h 04913 
    to 
    04915 ——
    B050 — Controller deceleration and  stop on power loss R/W 00 . Disable
    01 . Constant decel to stop
    02 . Constant DC voltage
           control with resume
    03 . Constant DC voltage
           control 1334h 04916 0 to 3 —
    B051 — DC bus voltage trigger  level during power loss R/W Sets trigger for 
    controlled decel-
    eration and stop on power loss 
    function 1335h 04917 0 to 10000 0.1 V
    B052 — Over-voltage threshold  during power loss R/W Sets over-voltage threshold for 
    controlled deceleration function 1336h 04918 0 to 10000 0.1 V
    B053 H Deceleration time setting  during power loss R/W 0.01 to 99.99, 100.0 to 999.9, 
    1000 to 3600 (seconds) 1337h 04919 0 to 
    3600000.01 sec.
    B053 L R/W 1338h 04920
    B054 — Initial output frequency  decrease during power loss R/W Sets the initial de
    crease in output 
    frequency upon power loss 1339h 04921 0 to 1000 0.01 Hz
    B055 — Proportional gain setting  for non-stop operation at 
    power loss R/W 0.00 to 2.55 133Ah 04922 0 to 255 0.01
    B056 — Integral time setting for  non-stop operation at 
    power loss R/W 0.0 to 9.999, 10.00 to 65.55 133Bh 04923 0 to 65535 0.001 
    sec.
    —(Reserved) — — 133Ch  to 
    133Eh 04924 
    to 
    04926 ——
    B060 — [O] input max. limit level  of window comparator R/W 0. to 100. (%)
    Lower limit = B061 + B062 / 2 133Fh 04927 0 to 100 1 %
    B061 — [O] input min. limit level  of window comparator R/W 0. to 100. (%)
    Lower limit = B060 – B062 / 2 1340h 04928 0 to 100 1 %
    B062 — [O] input hysteresis width  of window comparator R/W 0. to 10. (%)
    Lower limit = B061 – B062 / 2 13
    41h 04929 0
      to 10 1 %
    B063 — [OI] input max. limit level  of window comparator R/W 0. to 100. (%)
    Lower limit = B064 + B066 / 2 1342h 04930 0 to 100 1 %
    Holding Registers, “B” Group Fine Tuning Functions
    Func. CodeNameR/WDescription
    Network Data
    RegisterRangeRes.hexdec.
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Appendix B
    B–57
    B064 — [OI] input min. limit level of window comparator R/W 0. to 100. (%)
    Lower limit = B063 – B066 / 2 1343h 04931 0 to 100 1 %
    B065 — [OI] input hysteresis width  of window comparator R/W 0. to 10. (%)
    Lower limit = B063 – B064 / 2 1344h 04932 0 to 10 1 %
    B066 — [O/OI/O2] input maximum  limit level of window 
    comparator R/W –100. to 100. (%)
    Lower limit = B067 + B068 / 2 1345h 04933 0 to 100 1 %
    B067 — [O/OI/O2] input minimum  limit level of window 
    comparator R/W –100. to 100. (%)
    Lower limit = B066 – B068 / 2 1346h 04934 0 to 100 1 %
    B068 — [O/OI/O2] input hysteresis  width of window 
    comparator R/W 0. to 10. (%)
    Lower limit = B066 – B067 / 2 1347h 04935 0 to 10 1 %
    — (Reserved) — — 1348h 04936 — —
    B070 — [O] input disconnect  threshold R/W 0 to 100 (%); 
    255 = ignore setting 1349h 04937 0 to 100, 
    2551 %
    B071 — [OI] input disconnect  threshold R/W 0 to 100 (%); 
    255 = ignore setting 134Ah 04938 0 to 100, 
    2551 %
    B072 — [O2] input disconnect  threshold R/W 0 to 100 (%); 
    255 = ignore setting 134Bh 04939 0 to 100, 
    2551 %
    — (Reserved) — — 134Ch  to 
    1350h 04940 
    to 
    04944 ——
    B078 — Clear cumulative input  power data R/W 00 . No change
    01 . Clear the data 1351h 04945 0, 1 —
    B079 — Cumulative input power  display gain setting R/W 1. to 1000. 1352h 04946 1 to 1000 1
    — (Reserved) — — 1353h 04947 — —
    — (Reserved) — — 1354h 04948 — —
    B082 — Start frequency adjustment R/W 0.10 to 9.99 (Hz) 1355h 04949 10 to 999 0.01 Hz
    B083 — Carrier frequency setting R/W Sets the PWM carrier (internal 
    switching frequency)1356h 04950 5 to 150 0.1 kHz
    B084 — Initialization mode  (parameters or trip history) R/W 00 . Trip history clear
    01 . Parameter initialization
    02 . Trip history clear and 
          parameter initialization 1357h 04951 0, 1, 2 —
    B085 — Country code for initializa- tion R/W 00 . Japan version
    01 . Europe version
    02 . USA version 1358h 04952 0, 1, 2 —
    B086 — Frequency scaling conver- sion factor R/W Specify a constant to scale D007 
    to display in engineering units 1359h 04953 1 to 999 0.1
    B087 — STOP key enable R/W 00 . Enable 01 . Disable
    02 . Disable only the STOP
          function135Ah 04954 0, 1, 2 —
    Holding Registers, “B” Group Fine Tuning Functions
    Func. CodeNameR/WDescription
    Network Data
    RegisterRangeRes.hexdec.
    