ModBus Data Listing Appendix B B–48 A261 H Frequency upper limit setting, 2nd motor R/W Sets a limit on output frequency less than the maximum frequency (A004) 224Fh 08783 0, 50 to 400000.01 Hz A261 L R/W 2250h 08784 A062 H Frequency lower limit setting R/W Sets a limit on output frequency greater than zero 1251h 04689 0, 50 to 400000.01 Hz A062 L R/W 1252h 04690 A262 H Frequency lower limit setting, 2nd motor R/W Sets a limit on output frequency greater than zero 2251h 08785 0, 50 to 400000.01 Hz A262 L R/W 2252h 08786 — — (Reserved) — — 2253h to 226Eh 08787 to 08814 —— A063 H Jump (center) frequency setting R/W Up to 3 output frequencies can be defined for the output to jump past to avoid motor resonances (c enter freq.) 1253h 04691 0 to 40000 0.01 Hz A063 L R/W1254h 04692 A064 — Jump (hysteresis) frequency width setting R/W Defines the distance from the center frequency at which the jump occurs 1255h 04693 0 to 1000 0.01 Hz A065 H Jump (center) frequency setting R/W Up to 3 output frequencies can be defined for the output to jump past to avoid motor resonances (c enter freq.) 1256h 04694 0 to 40000 0.01 Hz A065 L R/W1257h 04695 A066 — Jump (hysteresis) frequency width setting R/W Defines the distance from the center frequency at which the jump occurs 1258h 04696 0 to 1000 0.01 Hz A067 H Jump (center) frequency setting R/W Up to 3 output frequencies can be defined for the output to jump past to avoid motor resonances (c enter freq.) 1259h 04697 0 to 40000 0.01 Hz A067 L R/W125Ah 04698 A068 — Jump (hysteresis) frequency width setting R/W Defines the distance from the center frequency at which the jump occurs 125Bh 04699 0 to 1000 0.01 Hz A069 H Acceleration stop frequency setting R/W 0.00 to 400.0 (Hz) 125Ch 04700 0 to 40000 0.01 Hz A069 L R/W125Dh 04701 A070 — Acceleration stop time frequency setting R/W 0.0 to 60.0 (seconds) 125Eh 04702 0 to 600 0.1 sec. A071 — PID Function Enable R/ W 00 ..PID operation OFF 01 ..PID operation ON 02 ..PID operation ON with inverted output 125Fh 04703 0, 1, 2 — A072 — PID proportional gain R/W 0.2 to 5.0 1260h 0474 2 to 50 0.2 A073 — PID integral time constant R/W 0.0 to 999.9, 1000. to 3600. (seconds)1261h 04705 0 to 36000 0.1 sec. A074 — PID derivative gain R/W 0.0 to 99.99, 100.0 (seconds) 1262h 04706 0 to 10000 0.01 sec. A075 — PV scale conversion R/W 0.01 to 99.99, 100.0 (seconds)1263h 04707 1 to 9999 0.01 Holding Registers, “A” Group Standard Functions Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. Phone: 800.894.0412
SJ7002 Inverter Appendix B B–49 A076 — PV source setting R/W 00 . [OI] (current input)01 . [O] (voltage input) 02 . Communication input 03 . Pulse train freq. input 10 . Calculate function output1264h 04708 0 to 3, 10 — A077 — Reverse PID action R/W 00 . PID input = SP – PV (normal) 01 . PID input = –(SP – PV) (reverse)1265h 04709 0, 1 — A078 — PID output limit R/W Range is 0.0 to 100.0 1266h 04710 0 to 1000 0.1 sec. A079 — PID feed forward select R/W 00 . Disable 01 . [O] (voltage input) 02 . [OI] (current input) 03 . [O2] (voltage input)1267h 04711 0 to 3 — — (Reserved) — — 1268h 04712 — — A081 — AVR function select R/W 00 . AVR enabled 01 . AVR disabled 02 . AVR enabled except during deceleration1269h 04713 0, 1, 2 — A082 — AVR voltage select R/W 2 00V class inverter settings: 200/215/220/230/240 (V) 400V class inverter settings: 380/400/415/440/460/480 (V) 126Ah 04714 — — — (Reserved) — — 126Bh 04715 — — — (Reserved) — — 126Ch 04716 — — A085 — Operation mode selection R/W 00 . Normal operation 01 . Energy-saver operation 02 . Optimal accel/decel operation126Dh 04717 0, 1, 2 — A086 — Energy saving mode tuning R/W 0.0 to 100 (seconds) 126Eh 04718 0 to 1000 0.1 % — (Reserved) — — 126Fh to 1273h 04719 to 04723 —— A092 H Acceleration (2) time setting R/W Duration of 2nd segment of acceleration 1274h 04724 1 to 3600000.01 sec. A092 L R/W 1275h 04725 A292 H Acceleration (2) time setting, 2nd motor R/W Duration of 2nd segment of acceleration, 2nd motor 226Fh 08815 1 to 3600000.01 sec. A292 L R/W 2270h 08816 A392 H Acceleration (2) time setting, 3rd motor R/W Duration of 2nd segment of acceleration, 3rd motor 326Dh 12909 1 to 3600000.01 sec. A392 L R/W 326Eh 12910 A093 H Deceleration (2) time setting R/W Duration of 2nd segment of deceleration 1276h 04726 1 to 3600000.01 sec. A093 L R/W 1277h 04727 A293 H Deceleration (2) time setting, 2nd motor R/W Duration of 2nd segment of deceleration, 2nd motor 2271h 08817 1 to 3600000.01 sec. A293 L R/W 2272h 08818 A393 H Deceleration (2) time setting, 3rd motor R/W Duration of 2nd segment of deceleration, 3rd motor 326Fh 12911 1 to 3600000.01 sec. A393 L R/W 3270h 12912 Holding Registers, “A” Group Standard Functions Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. Phone: 800.894.0412
ModBus Data Listing Appendix B B–50 — (Reserved)——3271h to 330Bh 12913 to 13067 —— A094 — Select method to switch to Acc2/Dec2 profile R/W 00 ..[2CH] terminal input 01 ..transition frequency 02 ..when motor direction reverses 1278h 04728 0, 1, 2 — A294 — Select method to switch to Acc2/Dec2, 2nd motor R/W 00 ..[2CH] terminal input 01 ..transition frequency 02 ..when motor direction reverses 2273h 08819 0, 1, 2 — A095 H Acc1 to Acc2 frequency transition point R/W Output frequency at which Accel1 switches to Accel2 1279h 04729 0 to 40000 0.01 Hz A095 L R/W127Ah 04730 A295 H Acc1 to Acc2 frequency transition point, 2nd motor R/W Output frequency at which Accel1 switches to Accel2 2274h 08820 0 to 40000 0.01 Hz A295 L R/W2275h 08821 A096 H Dec1 to Dec2 frequency transition point R/W Output frequency at which Decel1 switches to Decel2 127Bh 04731 0 to 40000 0.01 Hz A096 L R/W127Ch 04732 A296 H Dec1 to Dec2 frequency transition point, 2nd motor R/W Output frequency at which Decel1 switches to Decel2 2276h 08822 0 to 40000 0.01 Hz A296 L R/W2277h 08823 — (Reserved) ——2278h to 230Bh 08824 to 08971 —— A097 — Acceleration curve selection R/W 00 ..Linear 01 ..S-curve 02 ..U-shape 03 ..Reverse U-shape 04 ..EL-S curve 127Dh 04733 0 to 4 — A098 — Deceleration curve setting R/W 00 ..Linear 01 ..S-curve 02 ..U-shape 03 ..Reverse U-shape 04 ..EL-S curve127Eh 04734 0 to 4 — — (Reserved) ——127Fh 04735 — — — (Reserved) ——1280h 04736 — — A101 H [OI]–[L] input active range start frequency R/W Output frequency corre- sponding to the current input range starting point 1281h 04637 0 to 40000 0.01 Hz A101 L R/W1282h 04738 A102 H [OI]–[L] input active range end frequency R/W Output frequency corre- sponding to the current input range ending point 1283h 04739 0 to 40000 0.01 Hz A102 L R/W1284h 04740 A103 — [OI]–[L] input active range start current R/W Starting point for the current input range 1285h 04741 0 to A104 value1 % A104 — [OI]–[L] input active range end current R/W Ending point for the current input range 1286h 04742 A103 value to 100 1 % A105 — [OI]–[L] input start frequency enable R/W 00 ..Use A101 start value 01 ..Use 0Hz 1287h 04743 0, 1 — Holding Registers, “A” Group Standard Functions Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. Phone: 800.894.0412
SJ7002 Inverter Appendix B B–51 — (Reserved)——1288h to 128Ch 04744 to 0448 —— A111 H [O2]–[L] input active range start frequency R/W Output frequency corre- sponding to the bipolar voltage input range starting point 128Dh 04749 -40000 to 400000.01 Hz A111 L R/W128Eh 04750 A112 H [O2]–[L] input active range end frequency R/W Output frequency corre- sponding to the bipolar voltage input range ending point 128Fh 04751 -40000 to 400000.01 Hz A112 L R/W1290h 04752 A113 — [O2]–[L] input active range start voltage R/W Starting point for the bipolar voltage input range 1291h 04753 -100 to A114 value 1 % A114 — [O2]–[L] input active range end voltage R/W Ending point for the bipolar voltage input range 1292h 04754 A113 value to 100 1 % — (Reserved) ——1293h to 12A4h 04755 to 04772 —— A131 — Acceleration curve constants setting R/W Sets the curve deviation from straight-line acceleration in 10 levels (01 to 10) 12A5h 04773 1 to 10 — A132 — Deceleration curve constants setting R/W Sets the curve deviation from straight-line de celeration in 10 levels (01 to 10) 12A6h 04774 1 to 10 — — (Reserved) ——12A7h to 12AEh 04775 to 04782 —— A141 — A input select for calculate function R/W 00 . Digital operator (A020/ A220/A320) 01 . Keypad potentiometer 02 . [O] input 03 . [OI] input 04 . Comm. port 05 . Expansion card 1 06 . Expansion card 2 07 . Pulse train frequency train input 12AFh 04783 0 to 7 — A142 — B input select for calculate function R/W 00 . Digital operator (A020/ A220/A320) 01 . Keypad potentiometer 02 . [O] input 03 . [OI] input 04 . Comm. port 05 . Expansion card 1 06 . Expansion card 2 07 . Pulse train frequency train input 12B0h 04784 0 to 7 — A143 — Calculation symbol R/W 0 0 . ADD (A input + B input) 01 . SUB (A input – B input) 02 . MUL (A input x B input) 12B1h 04785 0, 1, 2 — — (Reserved) ——12B2h 04786 — — Holding Registers, “A” Group Standard Functions Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. Phone: 800.894.0412
ModBus Data Listing Appendix B B–52 A145 H ADD frequencyR/W 0.00 to 99.99, 100.0 to 400.0 (Hz) 12B3h 04787 0 to 40000 0.01 Hz A145 L R/W12B4h 04788 A146 — ADD direction select R/W 0 0 ..Plus (adds A145 value to output frequency) 01 ..Minus (subtracts A145 value from output freq.) 12B5h 04789 0, 1 — — (Reserved) ——12B6h to 12B8h 04790t o 04792 —— A150 — EL-S curve acceleration ratio 1 R/W Range is 0. to 50. 12B9h 04793 0 to 50 1 % A151 — EL-S curve acceleration ratio 2 R/W Range is 0. to 50. 12BAh 04794 0 to 50 1 % A152 — EL-S curve acceleration ratio 3 R/W Range is 0. to 50. 12BBh 04795 0 to 50 1 % A153 — EL-S curve acceleration ratio 4 R/W Range is 0. to 50. 12BCh 04796 0 to 50 1 % —(Reserved) — — 12BDh to 1300h 04797 to 04864 —— Holding Registers, “A” Group Standard Functions Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. Holding Registers, “B” Group Fine Tuning Functions Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. B001 — Selection of restart mode R/W 00 . Alarm output after trip, automatic restart disabled 01 . Resume operation after frequency matching 02 . Resume operation after frequency matching 03 . Resume previous freq. after freq. matching, then decelerate to stop and display trip info 04 . Restart with active matching frequency 1301h 04865 0 to 4 — B002 — Allowable under-voltage power failure time R/W The amount of time a power input under-voltage can occur without tripping the power failure alarm 1302h 04866 3 to 250 0.1 sec. Phone: 800.894.0412
SJ7002 Inverter Appendix B B–53 B003 — Retry wait time before motor restart R/W Time delay after a trip condition goes away before the inverter restarts the motor 1303h 04867 3 to 1000 0.1 sec. B004 — Instantaneous power failure / under-voltage trip alarm enable R/W 00 . Disable 01 . Enable 02 . Disable during stop and ramp to stop 1304h 04868 0, 1, 2 — B005 — Number of restarts on power failure / under- voltage trip events R/W 00 . Restart 16 times 01 . Always restart 1305h 04869 0, 1 — B006 — Phase loss detection enable R/W 00 . Disable 01 . Enable1306h 04870 0, 1 — B007 H Restart frequency thresh- old R/W When the frequency of the motor is less than this value, the inverter will restart at 0 Hz 1307h 04871 0 to 40000 0.01 Hz B007 L R/W 1308h 04872 B008 — Retry after trip select R/W 00 . Always retry after trip 01 . Start with 0 Hz 02 . Start with frequency matching 03 . Retry after deceleration and stop with matching frequency 04 . Start with active matching frequency 1309h 04873 0 to 4 — B009 — Retry after undervoltage select R/W 00 . Restart 16 times 01 . Unlimited 130Ah 04874 0, 1 — B010 — Retry count select after overvoltage or overcurrent R/W 1 to 3 (times) 130Bh 04875 1 to 3 times B011 — Retry wait time after trip R/W 0.3 to 1 00.0 (seconds) 130Ch 04876 3 to 1000 0.1 sec. B012 — Electronic thermal setting (calculated within the inverter from current output) R/W Range is 0.2 * rated current to 1.2 * rated current 130Dh 04877 200 to 10000.1 % B212 — Electronic thermal setting (calculated within the inverter from current output), 2nd motor R/W Range is 0.2 * rated current to 1.2 * rated current 230Ch 08972 200 to 10000.1 % B312 — Electronic thermal setting (calculated within the inverter from current output), 3rd motor R/W Range is 0.2 * rated current to 1.2 * rated current 330Ch 13068 200 to 10000.1 % B013 — Electronic thermal charac- teristic R/W 00 . Reduced torque 01 . Constant torque 02 . Free-setting 130Eh 04878 0, 1, 2 — — (Reserved) — 130Fh 04879 — — B213 — Electronic thermal charac- teristic, 2nd motor R/W 00 . Reduced torque 01 . Constant torque 02 . Free-setting 230Dh 08973 0, 1, 2 — —(Reserved) — — 230Eh to 2501h 08974 to 09493 —— Holding Registers, “B” Group Fine Tuning Functions Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. Phone: 800.894.0412
ModBus Data Listing Appendix B B–54 B313 — Electronic thermal charac-teristic, 3rd motor R/W 00 . Reduced torque 01 . Constant torque 02 . Free-setting 330Dh 13069 0, 1, 2 — — (Reserved) — — 330Eh to 3506h 13070 to 13574 —— B015 — Free setting, electronic thermal frequency (1) R/W Data point coordinates for Hz axis (horizontal) in the free-form curve 1310h 04880 0 to 400 1 Hz B016 — Free setting, electronic thermal current (1) R/W Data point coordinates for Ampere axis (vertical) in the free-form curve 1311h 04881 0 to rated current0.1 A B017 — Free setting, electronic thermal frequency (2) R/W Data point coordinates for Hz axis (horizontal) in the free-form curve 1312h 04882 0 to 400 1 Hz B018 — Free setting, electronic thermal current (2) R/W Data point coordinates for Ampere axis (vertical) in the free-form curve 1313h 04883 0 to rated current0.1 A B019 — Free setting, electronic thermal frequency (3) R/W Data point coordinates for Hz axis (horizontal) in the free-form curve 1314h 04884 0 to 400 1 Hz B020 — Free setting, electronic thermal current (3) R/W Data point coordinates for Ampere axis (vertical) in the free-form curve 1315h 04885 0 to rated current0.1 A B021 — Overload restriction opera- tion mode R/W 00 . Disable 01 . Enable for acceleration and constant speed 02 . Enable for constant speed only 03 . Enable for accel, decel, and constant speed 1316h 04886 0 to 3 — B022 — Overload restriction setting R/W (0.20 x rated current) to (1.80 x rated current) (A)1317h 04887 200 to 20000.1 % B023 — Deceleration rate at overload restriction R/W 0.10 to 30.00 (seconds) 1318h 04888 10 to 3000 0.1 sec. B024 — Overload restriction opera- tion mode (2) R/W 00 . Disable 01 . Enable for acceleration and constant speed 02 . Enable for constant speed only 03 . Enable for accel, decel, and constant speed 1319h 04889 0 to 3 — B025 — Overload restriction setting (2) R/W (0.20 x rated current) to (1.80 x rated current) (A) 131Ah 04890 200 to 20000.1 % B026 — Deceleration rate at overload restriction (2) R/W 0.10 to 30.00 (seconds) 131Bh 04891 1 to 3000 0.01 sec. B027 — Overcurrent suppression enable R/W 00 . Disable 01 . Enable 131Ch 04892 0, 1 — B028 — Current limit for active frequency-matching restart R/W (0.20 x rated current) to (1.80 x rated current) (A) 131Dh 04893 200 to 20000.1 % Holding Registers, “B” Group Fine Tuning Functions Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. Phone: 800.894.0412
SJ7002 Inverter Appendix B B–55 B029 — Scan time constant for active freq. matching R/W 10 to 3000 131Eh 04894 0.01 sec. 0.01 sec. B030 — Restart freq. select for active freq. matching R/W 00 . Frequency at last shutoff 01 . Maximum frequency 02 . Set frequency 131Fh 04895 B031 — Software lock mode selec- tion R/W 00 . Low-level access, [SFT] input blocks all edits 01 . Low-level access, [SFT] input blocks edits (except F001 and Multi-speed parameters) 02 . No access to edits 03 . No access to edits except F001 and Multi-speed parameters 10 . High-level access, including B031 1320h 04896 — (Reserved) — — 1321h 04897 — — — (Reserved) — — 1322h 04898 — — B034 H Run/power-on warning time R/W 0 to 9999. (0 to 99990), 1000 to 6553 (10000 to 655300) (hours) 1323h 04899 0 to 65535 1 [10- hours] B034 L R/W 1324h 04900 B035 — Rotational direction restriction R/W 00 . Enable for fwd. and rev. 01 . Enable for forward only 02 . Enable for reverse only 1325h 04901 0, 1, 2 — B036 — Reduced voltage start selection R/W 000 (short) to 255 (long) 1326h 04902 0 to 255 — B037 — Function code display restriction R/W 00 . Display all 01 . Display only utilized functions 02 . Display user-selected functions only 03 . Data comparison display 04 . Basic display 1327h 04903 0 to 4 — B038 — Initial display selection R /W 00 . Last value dislayed when STR key was pressed 01 . D001 02 . D002 03 . D003 04 . D007 05 . F001 1328h 04904 0 to 5 — B039 — Automatic user parameter function enable R/W 00 . Disable 01 . Enable 1329h 04905 0, 1 — B040 — Torque limit selec tion R/W 00 . 4-quadrant mode 01 . Selected by two input terminals 02 . From analog [O2] input 03 . From expansion card 1 04 . From expansion card 2 132Ah 04906 0 to 4 — B041 — Torque limit (1) (forward- driving in 4-quadrant mode) R/W 0. to 200. (%), no (disable torque limit) 132Bh 04907 0 to 200, 255= (no)1 % Holding Registers, “B” Group Fine Tuning Functions Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. Phone: 800.894.0412
ModBus Data Listing Appendix B B–56 B042 — Torque limit (2) (reverse-regenerating in 4-quadrant mode) R/W 0. to 200. (%), no (disable torque limit) 132Ch 04908 0 to 200, 255= (no)1 % B043 — Torque limit (3) (reverse- driving in 4-quadrant mode) R/W 0. to 200. (%), no (disable torque limit) 132Dh 04909 0 to 200, 255= (no)1 % B044 — Torque limit (4) (forward- regenerating in 4-quadrant mode) R/W 0. to 200. (%), no (disable torque limit) 132Eh 04910 0 to 200, 255= (no)1 % B045 — Torque limit LADSTOP enable R/W 00 . Disable 01 . Enable 132Fh 04911 0, 1 — B046 — Reverse Run protection enable R/W 00 . Disable 01 . Enable 1330h 04912 0, 1 — — (Reserved) — — 1331h to 1333h 04913 to 04915 —— B050 — Controller deceleration and stop on power loss R/W 00 . Disable 01 . Constant decel to stop 02 . Constant DC voltage control with resume 03 . Constant DC voltage control 1334h 04916 0 to 3 — B051 — DC bus voltage trigger level during power loss R/W Sets trigger for controlled decel- eration and stop on power loss function 1335h 04917 0 to 10000 0.1 V B052 — Over-voltage threshold during power loss R/W Sets over-voltage threshold for controlled deceleration function 1336h 04918 0 to 10000 0.1 V B053 H Deceleration time setting during power loss R/W 0.01 to 99.99, 100.0 to 999.9, 1000 to 3600 (seconds) 1337h 04919 0 to 3600000.01 sec. B053 L R/W 1338h 04920 B054 — Initial output frequency decrease during power loss R/W Sets the initial de crease in output frequency upon power loss 1339h 04921 0 to 1000 0.01 Hz B055 — Proportional gain setting for non-stop operation at power loss R/W 0.00 to 2.55 133Ah 04922 0 to 255 0.01 B056 — Integral time setting for non-stop operation at power loss R/W 0.0 to 9.999, 10.00 to 65.55 133Bh 04923 0 to 65535 0.001 sec. —(Reserved) — — 133Ch to 133Eh 04924 to 04926 —— B060 — [O] input max. limit level of window comparator R/W 0. to 100. (%) Lower limit = B061 + B062 / 2 133Fh 04927 0 to 100 1 % B061 — [O] input min. limit level of window comparator R/W 0. to 100. (%) Lower limit = B060 – B062 / 2 1340h 04928 0 to 100 1 % B062 — [O] input hysteresis width of window comparator R/W 0. to 10. (%) Lower limit = B061 – B062 / 2 13 41h 04929 0 to 10 1 % B063 — [OI] input max. limit level of window comparator R/W 0. to 100. (%) Lower limit = B064 + B066 / 2 1342h 04930 0 to 100 1 % Holding Registers, “B” Group Fine Tuning Functions Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. Phone: 800.894.0412
SJ7002 Inverter Appendix B B–57 B064 — [OI] input min. limit level of window comparator R/W 0. to 100. (%) Lower limit = B063 – B066 / 2 1343h 04931 0 to 100 1 % B065 — [OI] input hysteresis width of window comparator R/W 0. to 10. (%) Lower limit = B063 – B064 / 2 1344h 04932 0 to 10 1 % B066 — [O/OI/O2] input maximum limit level of window comparator R/W –100. to 100. (%) Lower limit = B067 + B068 / 2 1345h 04933 0 to 100 1 % B067 — [O/OI/O2] input minimum limit level of window comparator R/W –100. to 100. (%) Lower limit = B066 – B068 / 2 1346h 04934 0 to 100 1 % B068 — [O/OI/O2] input hysteresis width of window comparator R/W 0. to 10. (%) Lower limit = B066 – B067 / 2 1347h 04935 0 to 10 1 % — (Reserved) — — 1348h 04936 — — B070 — [O] input disconnect threshold R/W 0 to 100 (%); 255 = ignore setting 1349h 04937 0 to 100, 2551 % B071 — [OI] input disconnect threshold R/W 0 to 100 (%); 255 = ignore setting 134Ah 04938 0 to 100, 2551 % B072 — [O2] input disconnect threshold R/W 0 to 100 (%); 255 = ignore setting 134Bh 04939 0 to 100, 2551 % — (Reserved) — — 134Ch to 1350h 04940 to 04944 —— B078 — Clear cumulative input power data R/W 00 . No change 01 . Clear the data 1351h 04945 0, 1 — B079 — Cumulative input power display gain setting R/W 1. to 1000. 1352h 04946 1 to 1000 1 — (Reserved) — — 1353h 04947 — — — (Reserved) — — 1354h 04948 — — B082 — Start frequency adjustment R/W 0.10 to 9.99 (Hz) 1355h 04949 10 to 999 0.01 Hz B083 — Carrier frequency setting R/W Sets the PWM carrier (internal switching frequency)1356h 04950 5 to 150 0.1 kHz B084 — Initialization mode (parameters or trip history) R/W 00 . Trip history clear 01 . Parameter initialization 02 . Trip history clear and parameter initialization 1357h 04951 0, 1, 2 — B085 — Country code for initializa- tion R/W 00 . Japan version 01 . Europe version 02 . USA version 1358h 04952 0, 1, 2 — B086 — Frequency scaling conver- sion factor R/W Specify a constant to scale D007 to display in engineering units 1359h 04953 1 to 999 0.1 B087 — STOP key enable R/W 00 . Enable 01 . Disable 02 . Disable only the STOP function135Ah 04954 0, 1, 2 — Holding Registers, “B” Group Fine Tuning Functions Func. CodeNameR/WDescription Network Data RegisterRangeRes.hexdec. Phone: 800.894.0412