    							“A” Group: Standard Functions
    Configuring Drive Parameters
    3–28
    Target Frequency 
    OperationAnalog Input Calculate Function –  The inverter can mathematically combine two input 
    sources into one value. The Calc ulate function can either add, subtract,  or multiply the two 
    selected sources. This provides the flexibility  needed by various applications.You can use the 
    result for the output frequency setting (use  A001=10) or for the PID Process Variable (PV) 
    input (use A075=03).
    A105 [OI]–[L] input start frequency enable OI-EXS00Use A101 start value 01 01 01✘ ✔
    0Hz
    0 1Use 0Hz
    A111 [O2]–[L] input active range start frequency — — –400. to 400. (Hz); model -4000HFx2 is 
    0.00 to 120.0 (Hz)0.00 0.00 0.00
    ✘ ✔
    Output frequency corresponding to the bipolar 
    voltage input range starting point
    A112 [O2]–[L] input active range end frequency — — –400. to 400. (Hz); model -4000HFx2 is 
    0.00 to 120.0 (Hz)0.00 0.00 0.00
    ✘ ✔
    Output frequency corresponding to the bipolar 
    voltage input range ending point
    A113 [O2]–[L] input active range start voltage — — –100 to 100 (%) -100. -100. -100. ✘ ✔
    Starting point for the bipolar voltage input range
    A114 [O2]–[L] input active range end voltage — — –100 to 100 (%) 100. 100. 100. ✘ ✔
    Ending point for the bipolar voltage input range
    Func. CodeName/
    Description
    Keypad
    Range and Settings
    DefaultsRun 
    Mode Edit
    Lo HiSRWOPEFEF2FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    Func.CodeName/
    Description
    Keypad
    Range and Settings
    DefaultsRun 
    Mode Edit
    Lo HiSRWOPEFEF2FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    A141 A input select for Calculate  Function REM00Digital operator (A020/A220/A320) 02 02 02
    ✘ ✔
    VR
    0 1Keypad potentiometer
    O
    02[O] input
    OI
    03[OI] input
    COM
    04Comm. port
    OP1
    05Expansion card 1
    OP2
    06Expansion card 2
    PLS
    07Pulse train frequency train input
    A142 B input select for Calculate  Function REM
    00Digital operator (A020/A220/A320) 03 03 03
    ✘ ✔
    VR
    0 1Keypad potentiometer
    O
    02[O] input
    OI
    03[OI] input
    COM
    04Comm. port
    OP1
    05Expansion card 1
    OP2
    06Expansion card 2
    PLS
    07Pulse train frequency train input
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Configuring Drive Parameters
    3–29
    Elevator Accel/
    Decel CurvesParameters A150 to A153 affect the slope of th e acceleration and deceleration for the elevator-
    related S curves.
    A143 Calculation symbol ADD00ADD (A input + B input) 00 00 00✘ ✔
    Calculates a value based on 
    the A input (A141 selects) 
    and the B input (A142 
    selects) SUB
    0 1SUB (A input – B input)
    MUL
    02MUL (A input x B input)
    A145 ADD frequency — — 0.00 to 99.99, 100.0 to 400.0 (Hz) 0.00 0.00 0.00 ✘ ✔
    A146 ADD direction select FW
    00Plus (adds A145 value to output  
    frequency) 00 00 00
    ✘ ✔
    RV
    0 1Minus (subtrac ts A145 value from output 
    frequency)
    Func.
    CodeName/
    Description
    Keypad
    Range and Settings
    DefaultsRun 
    Mode Edit
    Lo HiSRWOPEFEF2FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    Func.CodeName/
    DescriptionRange and Settings
    DefaultsRun 
    Mode
    Edit
    Lo Hi
    FEF2FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    A150 EL-S curve accel. ratio 1 Range is 0. to 50. (%) 25. 25. 25. ✘ ✘
    A151 EL-S curve accel. ratio 2 Range is 0. to 50. 25. 25. 25.✘ ✘
    A152 EL-S curve decel. ratio 1 Range is 0. to 50. 25. 25. 25.✘ ✘
    A153 EL-S curve decel. ratio 3 Range is 0. to 50. 25. 25. 25.✘ ✘
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							“B” Group: Fine-Tuning Functions
    Configuring Drive Parameters
    3–30
    “B” Group: Fine-Tuning Functions
    The “B” Group of functions and parameters adjust  some of the more subtle but useful aspects 
    of motor control and system configuration.
    Automatic 
    Restart Mode and 
    Phase LossThe restart mode determines how the inverter will resume operation after a fault causes a trip 
    event. The four options provide advantages fo r various situations. Frequency matching allows 
    the inverter to read the motor speed by virtue of  its residual magnetic flux and restart the output 
    at the corresponding frequency. The inverter can attempt a restart a certain number of times 
    depending on the particular trip event:
     Over-current trip, restart up to 3 times
     Over-voltage trip, restart up to 3 times
     Under-voltage trip, restart up to 16 times
    When the inverter reaches the maximum number of  restarts (3 or 16), you must power-cycle the 
    inverter to reset its operation.
    Other parameters specify the allowable under-voltage level and the delay time before restarting. 
    The proper settings depend on th e typical fault conditions for your  application, the necessity of 
    restarting the process in unattended situations, and whether re starting is always safe.  
    Input 
    power
    Motor 
    speed
    Power fail ure
    Inverter
    output
    Power failure > allowable power  fail time (B002), inverter trips
    Input 
    power
    Motor 
    speed
    Inverter
    output
    Power failure < allowable power fail  time (B002), inverter resumes
    Power fail ure
    Retry wait timeAllowable
    power fail time Allowable
    power fail time
    free-runningfree-running
    B002
    B003
    B002
    tt
    00
    Func.
    CodeName/
    DescriptionSRWOPERange  or Settings
    DefaultsRun 
    Mode Edit
    Lo Hi
    FEF2
    FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    B001 Selection of  automatic restart 
    mode ALM00Alarm output after trip, automatic restart 
    disabled 00 00 00
    ✘ ✔
    ZST
    0 1Restart at 0Hz
    RST
    02Resume operation afte r frequency matching
    FTP
    03Resume previous freq. after freq. matching, 
    then decelerate to stop  and display trip info
    FIX
    04Restart with active matching frequency
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Configuring Drive Parameters
    3–31
    CAUTION:  When a loss of phase occurs, increased ri pple current will markedly reduce main 
    capacitor life over time. Diode bridge failure ca n also result. If phase loss occurs under load, 
    the inverter could be damaged. Please pay partic ular attention to the setting of function B006.
    B002 Allowable under-voltage power failure time 0.3 to 25.0 (seconds) 1.0 1.0 1.0✘ ✔
    The amount of time a power input under-voltage  can occur without tripping the power failure 
    alarm. If under-voltage exists long er than this time, the inverter trips, even if the restart mode 
    is selected. If it exists less than  this time retry will be attempted.
    B003 Retry wait time before motor restart 0.3 to 100 (seconds) 1.0 1.0 1.0✘ ✔
    Time delay after a trip  condition goes away 
    before the inverter  restarts the motor
    B004 Instantaneous power failure /  under-voltage trip alarm 
    enable OFF
    00Disable
    000000✘ ✔
    ON
    0 1Enable
    DOFF
    02Disable during stop and ramp to stop
    B005 Number of restarts on power  failure / under-voltage trip 
    events 16
    00Restart 16 times
    00 00 00✘ ✔
    FREE
    0 1Always restart
    B006 Phase loss detection enable OFF
    00Disable – no trip on phase loss 00 00 00✘ ✔
    ON
    0 1Enable – trip  on phase loss
    B007 Restart frequency threshold 0.00 to 400.0 (Hz);
    model -4000HFx2 is 0.00 to 120.0 (Hz) 0.00 0.00 0.00
    ✘ ✔
    When the frequency of  the motor is less than 
    this value, the inverter will restart at 0 Hz
    B008 Retry after trip select ALM
    00Always retry after trip 00 00 00✘ ✔
    ZST
    0 1Start with 0 Hz
    RST
    02Start with frequency matching
    FTP
    03Retry after decelera tion and stop with 
    matching frequency
    FIX
    04Start with active matching frequency
    B009 Retry after undervoltage  select 16
    0016 times
    000000✘ ✔
    FREE
    0 1Unlimited
    B010 Retry count select  after over-voltage or 
    overcurrent 1 to 3 (times) 3 3 3
    ✘ ✔
    B011 Retry wait time after trip 0.3 to 100.0 (seconds) 1.0 1.0 1.0 ✘ ✔
    Func.
    CodeName/
    DescriptionSRWOPERange  or Settings
    DefaultsRun 
    Mode Edit
    Lo Hi
    FEF2
    FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							“B” Group: Fine-Tuning Functions
    Configuring Drive Parameters
    3–32
    Electronic 
    Thermal Overload 
    Alarm SettingThe thermal overload detection protects 
    the inverter and motor from overheating 
    due to an excessive load. It uses a current/
    inverse time curve to determine the trip 
    point. The thermal overload alarm [THM] 
    is the resulting intelligent output.
    First, use B013 to select the torque 
    characteristic that matches your load. 
    This allows the inverter to utilize the best 
    thermal overload characteristic for your 
    application.
    The torque developed in a motor is 
    directly proportional to the current in the 
    windings, which is also proporti onal to the heat generated (and temperature, over time). There-
    fore, you must set the thermal overload threshold in terms of current (amperes) with parameter 
    B012. The range is 50% to 120% of the rated curr ent for each inverter model. If the current 
    exceeds the level you specify, the inverter will trip and log an event (error E05) in the history 
    table. The inverter turns the motor output OFF when tripped. Separate settings are available for 
    the second and third motors (if applicable), as shown in the table below.
    Example 1, setting for SJ700-110LFE2 (0.4 to  55kW) - The rated motor current is 64A. The 
    setting range is (0.2 * 64) to rated current, or 12.8A to 64.0A. For a setting of B012 = 64A 
    (current at 100% rated curren t), the curve is shown below.
    Example 2, setting for SJ700-750LFE2 (75 to 150 kW) - The rated motor current is 149A. The 
    setting range is (0.2 * 149) to rated current, or 29.8A to 149A. For a setting of B012 = 149A 
    (current at 100% rated curren t), the curve is shown below.
    Function
    CodeFunction/DescriptionData or Range
    B012 / B212  / B312 Electronic thermal setting (calculated 
    within the inverter from current output)  Range is 0.2 x rated current to
    1.0 x rated current
    Output frequency
    Constant torque
    ReducedtorqueB013=01
    B013=00
    Trip current 
    reduction 
    factor
    x 1.0
    x 0.8
    x 0.6
    0 5 20 60 120 Hz
    Tr i p
    time (s)
    Trip current at 60 Hz
    60
    3.0 0 53.4 69 92 A
    109% 150% 200%
    Tr i p
    time (s)
    Trip current at 60 Hz
    60
    5.0 0 158 223.5 268 A
    106% 150% 180%
    SJ700-110LFE2 SJ700-750LFE2
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Configuring Drive Parameters
    3–33
    Example 3, setting for SJ700-3150LFE2 (185 to 
    400kW) - The rated motor current is 600A. The 
    setting range is (0.2 * 64)  to rated current, or 120A 
    to 600A. For a setting of  B012 = 600A (current at 
    100% rated current), the curve is shown to the 
    right.
    The electronic thermal characteristic adjusts the 
    way the inverter calculates thermal heating, based 
    on the type of load connected to the motor, as set 
    by parameter B013.
    CAUTION:  When the motor runs at lower 
    speeds, the cooling effect of the motor’s internal 
    fan decreases.
    The table below shows the torque profile settings. 
    Use the one that matches your load.
    Reduced Torque Characteristic  – The 
    example below shows the effect of the 
    reduced torque characteristic curve (for 
    example motor and current rating). At 20Hz, 
    the output current is reduced by a factor of 
    0.8 for given trip times.
     
    Function CodeDataFunction/Description
    B013 / B213 / B313
    00Reduced torque
    0 1Constant torque
    02Free-setting
    Tr i p
    time (s)
    Trip current at 60 Hz
    60
    5.0 0 636 900 1140 A
    106% 150% 190%
    SJ700-3150LFE2
    Trip current 
    reduction  factor
    x 1.0
    x 0.8
    x 0.6
    0 520 60 Hz
    Tr i p
    time (s)
    Reduced trip current at 20 Hz A
    60
    0.5 0 102.4
    55.8 76.8
    87.2% 120% 160%
    SJ700-150LFE2;
    rated current is 64A
    Tr i p
    time (s)
    Reduced trip current at 20 Hz A
    60
    0.5 0 912
    508.8 720
    84.8% 120% 152%
    SJ700-3150LFE2;
    rated current is 600A
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							“B” Group: Fine-Tuning Functions
    Configuring Drive Parameters
    3–34
    Constant Torque Characteristic  – Select-
    ing the constant torque characteristic for the 
    example motor gives the curves below. At 
    2.5 Hz, the output current is reduced by a 
    factor of 0.9 for given trip times.
    Free Thermal Characteristic  - It is possible to set the electronic thermal characteristic using a 
    free-form curve defined by  three data points, according to the table below.
    The left graph below shows the region for possi ble free-setting curves. The right graph below 
    shows an example curve defined by three data points specified by B015 – B020.
    Function
    CodeNameDescriptionRange
    B015 / B017 / B019 Free-setting electronic 
    thermal frequency 1, 2, 3 Data point coordinates for 
    Hz axis (horiz
    ontal) in the 
    free-form curve 0 to 400 (Hz);
    model -4000HFx2 is 
    0.00 to 120.0 (Hz)
    B016 / B018 / B020 Free setting electronic 
    thermal current 1, 2, 3 Data point coordinates for 
    Ampere axis (vertical) in the 
    free-form curve 0.0 = (disable)
    0.1 to 1000.
    Trip current 
    reduction 
    factor
    x 1.0
    x 0.9
    x 0.8
    0 2.5 5 60Hz
    Tr i p
    time (s)
    Reduced trip current at 2.5 Hz A
    60
    0.5 0 115.2
    62.8 86.4
    98.1% 135% 180%
    Tr i p
    time (s)
    Reduced trip current at 2.5 Hz A
    60
    0.5 0 1026
    572 810
    95.4% 135% 171%
    SJ700-150LFE2;
    rated current is 64A SJ700-3150LFE2;
    rated current is 600A
    Output
    current (A)
    Setting range
    max. freq.
    B020
    B018
    B016
    B015B017B019Ax04
    Trip current 
    reduction 
    factorOutput freq.
    x 1.0
    x 0.8
    0 5400 Hz
    Hz
    0
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Configuring Drive Parameters
    3–35
    Suppose the electronic thermal setting (B012) is  set to 44 Amperes. The left graph below shows 
    the effect of the free setting torque characterist ic curve. For example, at (B017) Hz, the output 
    current level to cause overheating in a fixed time period is reduced by a factor of (B018). The 
    right graph below shows the reduced trip current  levels in those conditions for given trip times.
    Any intelligent output terminal may be programmed to indicate a thermal warning [THM]. 
    Parameter C061 determines the wa rning threshold. Please see “
    Thermal Warning Signal” on 
    page 4–52 for more details.
    Tr i p
    time (s)
    (x) = B018 value x 116%
    (y) = B018 value x 120%
    (z) = B018 value x 150%
    Reduced trip current at (B017) Hz
    60
    0
    0.5
    (x) (y) (z) A
    Func.
    CodeName/
    Description
    Keypad
    Range and Settings
    DefaultsRun 
    Mode Edit
    Lo HiSRWOPEFEF2FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    B012 Level of electronic thermal  setting 0.20 x rated current) to 
    (2.00 x rated current) (A) rated current of inverter
    ✘ ✔
    B212 Level of electronic thermal settin g, 2nd motor 0.20 x rated current) to 
    (2.00 x rated current) (A) rated current of inverter
    ✘ ✔
    B312 Level of electronic thermal settin g, 3rd motor 0.20 x rated current) to 
    (2.00 x rated current) (A) rated current of inverter
    ✘ ✔
    B013 Electronic thermal characteristic SUB
    00Reduced torque01 01 00✘ ✔
    CRT
    0 1Constant torque
    FREE
    02V/f free-setting
    B213 Electronic thermal characteristic, 2nd motor SUB
    00Reduced torque
    01 01 00✘ ✔
    CRT
    0 1Constant torque
    FREE
    02V/f free-setting
    B313 Electronic thermal characteristic, 3rd motor SUB
    00Reduced torque
    01 01 00✘ ✔
    CRT
    0 1Constant torque
    FREE
    02V/f free-setting
    B015 Free setting, electronic therma l frequency (1)  0.0 to 400.0 (Hz);
    model -4000HFx2 is 
    0.00 to 120.0 (Hz) 0. 0. 0.
    ✘ ✔
    B016 Free setting, electronic thermal  current (1) 0.0 to 1000. (A) 0.0 0.0 0.0 ✘ ✔
    B017 Free setting, electronic therma l frequency (2) 0.0 to 400.0 (Hz);
    model -4000HFx2 is 
    0.00 to 120.0 (Hz) 0. 0. 0.
    ✘ ✔
    B018 Free setting, electronic thermal  current (2) 0.0 to 1000. (A) 0.0 0.0 0.0 ✘ ✔
    B019 Free setting, electronic therma l frequency (3) 0.0 to 400.0 (Hz);
    model -4000HFx2 is 
    0.00 to 120.0 (Hz) 0. 0. 0.
    ✘ ✔
    B020 Free setting, electronic thermal  current (3) 0.0 to 1000. (A) 0.0 0.0 0.0 ✘ ✔
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							“B” Group: Fine-Tuning Functions
    Configuring Drive Parameters
    3–36
    Overload
    RestrictionIf the inverter’s output current exceeds a 
    preset current level you specify during 
    acceleration or constant speed, the 
    overload restriction feature automati-
    cally reduces the ou tput frequency to 
    restrict the overload. This feature does 
    not generate an alarm or trip event. You 
    can instruct the inverter to apply 
    overload restriction only during 
    constant speed, thus allowing higher 
    currents for acceleration. Or, you may 
    use the same threshold for both acceler-
    ation and constant speed. In the case of 
    controlled deceleration, the inve rter monitors both output current and DC bus voltage. The 
    inverter will increase output frequency to try to  avoid a trip due to over-current or over-voltage 
    (due to regeneration).
    When the inverter detects an overload, it must de celerate the motor to reduce the current until it 
    is less than the threshold. You can choose the rate of deceleration that the inverter uses to lower 
    the output current. 
    Motor 
    Current
    Output
    Frequency
    B023
    B022
    t
    restriction area
    0 t
    Func.
    CodeName/
    Description
    Keypad
    Range and Settings
    DefaultsRun 
    Mode Edit
    Lo HiSRWOPEFEF2FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    B021 Overload restriction  operation mode OFF00Disable
    010101✘ ✔
    Select the operating 
    mode during overload 
    conditions ON
    0 1Enable for acceleration and constant speed
    CRT
    02Enable for constant speed only
    N-R
    03Enable for accel, decel, and constant speed
    B022 Overload restriction setting (0.20 x rated current) to (1.80 x rated 
    current) (A) rated current times 1.50
    ✘ ✔
    B023 Deceleration rate at ov erload restriction 0.10 to 30.00 (seconds) 1.00 1.00 1.00✘ ✔
    B024 Overload restriction  operation mode (2) OFF
    00Disable
    010101✘ ✔
    Select the operating 
    mode during overload 
    conditions ON
    0 1Enable for acceleration and constant speed
    CRT
    02Enable for constant speed only
    N-R
    03Enable for accel, decel, and constant speed
    B025 Overload restriction setting (2) Models -004xxx to -550xx x: (0.20 x rated 
    current) to (2.0 x rated current) (A);
    Models -750xxx to -4000xxx: (0.20 x rated 
    current) to (1.80 x rated current) (A) rated current times 1.50
    ✘ ✔
    B026 Deceleration rate at over load restriction (2) 0.10 to 30.00 (seconds) 1.00 1.00 1.00✘ ✔
    B027 Overcurrent suppres- sion enable OFF
    00Disable
    010101✘ ✔
    ON
    0 1Enable
    B028 Current limit for acti ve frequency-matching 
    restart Models -004xxx to -550xxx: (0.20 x rated 
    current) to (2.0 x rated current) (A);
    Models -750xxx to -4000xxx: (0.20 x rated 
    current) to (1.80 x rated current) (A)rated current times 1.0
    ✘ ✔
    B029 Scan time constant for active freq. matching 0.10 to 30.00 (seconds) 0.50 0.50 0.50 ✘ ✔
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Configuring Drive Parameters
    3–37
    NOTE:  Two sets of overload restricti on parameters are available. The set that is in use may be 
    selected by means of an intelligent input terminal (see “Overload Restriction” on page 4–29).
    B030 Restart freq. select for 
    active freq. matching CUTOFF00Frequency at last shutoff
    00 00 00✘ ✔
    MAX
    0 1Maximum frequency
    SET
    02Set frequency
    Func. CodeName/
    Description
    Keypad
    Range and Settings
    DefaultsRun 
    Mode Edit
    Lo HiSRWOPEFEF2FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    