    							“H” Group: Motor Constants Functions
    Configuring Drive Parameters
    3–68
    H260 0Hz SLV limit for 2nd motor 0.0 to 100.0100. 100. 100.✔ ✔
    H061 0Hz SLV starting boost current for 1st motor 0. to 50. (%) 100. 100. 100.✔ ✔
    H261 0Hz SLV starting boost current for 2nd  motor 0. to 50. (%)
    100. 100. 100.✔ ✔
    H070 Terminal selection PI proportional gain  setting 0.0 to 999.9, 1000
    100.0 100.0 100.0✔ ✔
    H071 Terminal selection PI integral gain setting 0.00 to 999.9, 1000. 100.0 100.0 100.0✔ ✔
    H072 Terminal selection P proportional gain  setting 0.00 to 10.00
    1.00 1.00 1.00✔ ✔
    H073 Gain switching time 0. to 999. (milliseconds) 100. 100. 100.✔ ✔
    Func.
    CodeName/
    Description
    Keypad
    Range and Settings
    DefaultsRun 
    Mode Edit
    Lo HiSRWOPEFEF2FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Configuring Drive Parameters
    3–69
    “P” Group: Expansion Card Functions
    The two (optional) expansion cards for the SJ 700 have associated configuration data. The 
    following table defines the functions and their va lue ranges. Please refer to the expansion card 
    manual for more details.
    Func.
    CodeName/
    Description
    Keypad
    Range and Settings
    DefaultsRun 
    Mode Edit
    Lo HiSRWOPEFEF2FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    P001 Operation mode on expan- sion card 1 error TRP00Trip (stop motor)
    00 00 00✘ ✔
    RUN
    0 1Continuous operation
    P002 Operation mode on expan- sion card 2 error TRP
    00Trip (stop motor)
    00 00 00✘ ✔
    RUN
    0 1Continuous operation
    P011 Encoder pulse-per-revolution (PPR) setting 128  to 65000 (pulses per revolution) 1024 1024 1024 ✘ ✘
    P012 Control pulse setting ASR
    00Automatic Speed Regulation (ASR) mode 00 00 00 ✘ ✘
    APR
    0 1Automatic Position Regulation (APR) mode ✘ ✘
    APR2
    02Absolute Position Control ✘ ✘
    HAPR
    03High-resolution Absolute Position Control ✘ ✘
    P013 Pulse input  mode settingMD0
    00Quadrature mode 00 00 00✘ ✘
    MD1
    0 1Count and direction
    MD2
    02Separate forward and reverse pulse trains
    P014 Home search stop position se tting0. to 4095. (pulses) 0. 0. 0.✘ ✔
    P015 Home search speed setting Start frequency to maximum frequency (up 
    to 120.0) (Hz) 5.00 5.00 5.00
    ✘ ✔
    P016 Home search direction  setting FW
    00Forward
    000000✘ ✘
    RV
    0 1Reverse ✘ ✘
    P017 Home search comp letion range setting 0. to 9999 ., 1000 (10,000) (pulses) 5 5 5✘ ✔
    P018 Home search co mpletion delay time setting 0.00 to  9.99 (seconds) 0.00 0.00 0.00✘ ✔
    P019 Electronic gear set position  selection FB
    00Position feedback side
    00 00 00✘ ✔
    REF
    0 1Position command side ✘ ✔
    P020 Electronic gear ratio nume rator setting 0. to 9999. 1. 1. 1.✘ ✔
    P021 Electronic gear ratio denom inator setting 1 to 9999 1. 1. 1.✘ ✔
    P022 Feed-forward gain setting 0.00 to 99.99, 100.0 to 655.30.00 0.00 0.00✘ ✔
    P023 Position loop gain setting 0.00 to 99.99, 100.0 0.50 0.50 0.50✘ ✔
    P024 Position bias setting -204 (-2048) / -999. to 20480. 0. 0.✘ ✔
    P025 Temperature compensation  thermistor enable OFF
    00No compensation
    00 00 00✘ ✔
    Allows for motor-mounted 
    thermistor to calibrate output 
    to motor temperature ON
    0 1With compensation
    P026 Over-speed error detection level setting 0.0 to 150.0 (%) 135.0 135.0 135.0✘ ✔
    P027 Speed deviation error detec tion level setting 0.00 to 99.99, 100.0 to 120.0 (Hz) 7.50 7.50 7.50✘ ✔
    P028 Motor gear ratio numerato r setting0. to 9999. 1. 1. 1.✘ ✔
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							“P” Group: Expansion Card Functions
    Configuring Drive Parameters
    3–70
    P029 Motor gear ratio  denominator setting 1 to 9999 1. 1. 1. ✘ ✔
    P031 Accel/decel ti me input selec-
    tion REM
    00Inverter
    00 00 00✘ ✘
    OP1
    0 1Expansion card 1
    OP2
    02Expansion card 2
    P032 Positioning  command input 
    selection REM
    00Inverter
    00 00 00✘ ✔
    OP1
    0 1Expansion card 1
    OP2
    02Expansion card 2
    P033 Torque command input  selection O
    00[O] terminal
    00 00 00✘ ✘
    OI
    0 1[OI] terminal
    O2
    02[O2] terminal
    REM
    03Inverter keypad (P034)
    P034 Torque command settin g0. to 180. (%) 0. 0. 0.✘ ✘
    P035 Torque command polarity  select NOR
    00Indicated by signal polar
    ity at [O2] terminal 00 00 00 ✘ ✘
    DIR
    0 1Depends on motor direction
    P036 Torque bias mode NO
    00Disable 000000✘ ✘
    DIR
    0 1Inverter keypad (P037)
    NOR
    02[O2] terminal input
    P037 Torque bias value 0. to 180. (%)0. 0. 0.✘ ✘
    P038 Torque bias polarity NOR
    00Indicated by polarity 00 00 00✘ ✔
    DIR
    0 1Depends on motor direction
    P039 Forward speed limit for torque-control mode 0.00 to maximum frequency (Hz) 0.00 0.00 0.00✘ ✘
    P040 Reverse speed limit for torque-control mode 0.00 to maximum frequency (Hz) 0.00 0.00 0.00✘ ✘
    P044 DeviceNet comm watchdog timer 0.00 to 99.99 (seconds)1.00 1.00 1.00✘ ✘
    P045 Inverter action on DeviceNet  comm error TRP
    00Trip
    01 01 01✘ ✘
    FTP
    0 1Decelerate and trip
    NO
    02Hold last speed
    FRS
    03Free run stop
    DEC
    04Decelerate and stop
    P046 DeviceNet polled I/ O: Output instance 
    number 20, 21, 100 21 21 21
    ✘ ✘
    P047 DeviceNet polled I/O: Input instance number 70, 71, 101 71 71 71 ✘ ✘
    P048 Inverter action on DeviceNet  idle mode  TRP
    00Trip
    01 01 01✘ ✘
    FTP
    0 1Decelerate and trip
    NO
    02Hold last speed
    FRS
    03Free run stop
    DEC
    04Decelerate and stop
    P049 DeviceNet  motor poles 
    setting for RPM poles poles 00 to 38 (even numbers only) 0 0 0
    ✘ ✘
    Func.
    CodeName/
    Description
    Keypad
    Range and Settings
    DefaultsRun 
    Mode Edit
    Lo HiSRWOPEFEF2FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Configuring Drive Parameters
    3–71
    NOTE: Parameters P044 to P049 are available onl y in inverters with manufacturing code 
    x8K xxxxxx xxxxx or later. The manufacturing co de is printed on the product specifications 
    labels, located on the front and side of the inverter housing.
    P055 Pulse train frequency scale 1.0 to 50.0 (kHz)25.0 25.0 25.0✘ ✔
    P056 Pulse train frequency filter time consta nt 0.01 to 2.00 (seconds) 0.10 0.10 0.10✘ ✔
    P057 Pulse train frequency bias -100. to 100. (%)0. 0. 0.✘ ✔
    P058 Pulse train frequency limit 0. to 100. (%)100. 100. 100.✘ ✔
    P060 
    to 
    P067 Multi-stage position setting 0
    to  Multi-stage 
    position setting 7 Reverse side to forward side (upper four 
    digits including sign “-”) 000
    ✔ ✔
    P068 Zero-return  mode selectionLOW
    00Low speed 000000✔ ✔
    Hi1
    0 1High speed
    Hi2
    02High speed 2
    P069 Zero return direction  selection FW
    00Forward
    000000✔ ✔
    RW
    0 1Reverse
    P070 Low speed zero return frequency 0.00 to 10.00 (Hz)0.00 0.00 0.00✔ ✔
    P071 High speed zero return frequency 0.00 to 99.99 / 100.0 to maximum frequency 
    setting, 1st motor (Hz) 0.00 0.00 0.00
    ✔ ✔
    P072 Forward position range 0 to 268435455 (when P012 = 02),
    0 to 1073741823 (when P013 = 03) (upper 
    four digits) 268435455
    ✔ ✔
    P073 Reverse position range -268435455 to 0 (when P012 = 02),
    1073741823 to 0 (when P013 = 03) 
    (upper four digits) -268435455
    ✔ ✔
    P074 Teaching selection X00
    00X00 000000✔ ✔
    X01
    0 1X01
    X02
    02X02
    X03
    03X03
    X04
    04X04
    X05
    05X05
    X06
    06X06
    X07
    07X07
    P100 
    to 
    P131 Easy sequence user parameters U(00) to 
    U(31)
    0. to 9999., 1000 to 6553 (10000 to 65535) 0. 0. 0.
    ✔ ✔
    Func.
    CodeName/
    Description
    Keypad
    Range and Settings
    DefaultsRun 
    Mode Edit
    Lo HiSRWOPEFEF2FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							“P” Group: Expansion Card Functions
    Configuring Drive Parameters
    3–72
    Absolute Position 
    Control ModeTo use the absolute position control mode, set A044 V/F characteristic curve setting (1st motor) 
    equal to “02” (V2) and set P012 Control Pulse Se tting equal to “02” APR – Automatic Position 
    Control Mode.
     If P012 = 03 (high-resolution absolute position  control, the inverter quadruples the number 
    of pulses used for positioning. In this case  multiply the multistage position settings and 
    position ranges by four.
     Position settings can be  sequenced in up to eight stages  in combination with control pulse 
    settings. You can select  zero-return mode from one low-speed and two high-speed modes. 
    (The home search function cannot  be used during a zero-return.)
     The teaching function allows you to set (store ) position settings while actually running the 
    machine (motor is turning).
     If intelligent terminal [SPD] Speed/position Co ntrol Select (option code 73) is assigned, you 
    can switch between speed control and position control.
     Only the four high-order digits of data are di splayed when the data (position setting) to be 
    displayed consists of a  large number of digits.
    In Absolute Position Control Mode, the inverter  runs the motor until the machine reaches the 
    target position according to the following setti ngs, and then set the machine into the position 
    servo-lock state (until the Stop Command occurs):
    1. Position setting
    2. Speed setting (output frequency)
    3. Acceleration and deceleration time
    In absolute position control mode, the frequency an d accel/decel settings selected at absolute 
    position control are applied. If th e position setting value is small, the inverter may decelerate 
    the motor for positioning before its speed reache d the set speed setting. In absolute position 
    control mode, the direction of the operations command (forward or reverse) is ignored. The 
    operation command simply functions as a signal to  run or stop the motor. Motor direction is 
    determined by the algebraic sign of the differen ce between the current position and the target 
    position.
    If zero return operation as described below is  not performed, the motor position detected at 
    powerup is assumed to be at the origin (position data = 0). When the operation commend is 
    turned ON with zero specified as the position  setting, positioning is completed without running 
    the motor. 
    Set C102 Reset Mode Selection =  03 so that the inverter only resets a trip condition (does not 
    turn OFF the motor output). Otherwise, the curren t position counter is cleared when the inverter 
    reset terminal turns ON. Be sure to set C102 = 03 if you intend to use the value of the current 
    position counter for operation after recovering the inverter from a trip by turning ON the reset 
    terminal (reset key).
    Output frequency
     [POK]
    0 Small position value 
    causes decel before 
    target speed is reached
    P017
    Operation command
    Speed setting
    P018
    Posit ion
    Home search 
    completion range 
    setting
    Home search completion 
    delay time setting
    0 1
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Configuring Drive Parameters
    3–73
    If intelligent termin al [PCLR] is assigned, when it is ON  the current position counter is cleared 
    and the position deviation  counter is also cleared.
    When the inverter is in Absolute Position  Control Mode, some functions are necessarily 
    disabled:
     Intelligent terminal  [ATR] is ignored (because torque control is disabled)
     Intelligent terminal [STAT]  is ignored (because pulse train position control is disabled)
     Home search function is disabled
    Teaching 
    FunctionThe teaching function allows you to make the  inverter run and stop the motor as desired and 
    store current position data to a position comm and memory location that you select. Assign the 
    [ORT] Orientation function (option code 45) to  an intelligent input. The [ORT] terminal 
    functions as the teaching input te rminal when P012 Control Pulse  Setting is set to 02 (Absolute 
    Position Control) or 03 (High-reso lution Absolute Position Control). 
    The teaching procedure is as follows:
    1. Select the teaching position memo ry location by setting P074.
    2. Move the work piece or machine to the desi red location. Enter an operation command while 
    the [ORT] terminal is in the ON state. The speed and accel/decel settings selected at the 
    operation command input are applied.
    Teaching operation can be perform ed when power is input to the power supply terminals [R0] 
    and [T0] of the inverter control circuit. The current position counter also operates when an 
    external device moves the work piece. Therefor e, the teaching operation can also be performed 
    when the inverter does not operate (move) the machine.
    NOTE:  When teaching position data to an inverter that is not operating the machine, be sure to 
    either disconnect input power  terminals ([R], [S], and [T]) or disconnect the motor output 
    terminals ([U], [V], and [W]). Otherwise, person al injury or damage to equipment may result.
    3. Press the STR key on the digital operator  when the target position is reached.
    4. The current position data is stored to the memory area selected by pa rameter P074 teaching 
    selection. (P074 value itself is not stored. After power O FF or reset, 00 is stored.)
    Output frequency [ORT]
    0
    Speed setting selected 
    at operation command 
    input is applied
    Operation command
    Posit ion
    0 1
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							“U” Group: User-selectable Menu Functions
    Configuring Drive Parameters
    3–74
    “U” Group: User-selectable Menu Functions
    The user-selectable menu functions allow you to configure (select) any twelve of the other 
    functions in the inverter and place them together  in a convenient list. This feature provides 
    quick access for the most-used functions needed  for your application. Each U Group function 
    can serve as a pointer to any of  the other parameters. You do not have to use the Store key to 
    retain each association; just  scroll to the desired standard parameter for each U Group function 
    and leave it. The setting can point to a monitor- only parameter (such as D001), or point to 
    editable parameters (such as A001). In the case  of pointing to an editable functions, you use the 
    Up/Down keys to change the value and the Stor e key to accept the change into memory—the 
    same procedure as a normal parameter edit. 
    TIP:  Function B037 selects which parameter groups are displayed. If you want to limit the 
    displayed parameters to  only the U Group functions, set B037=02.
    Func.
    CodeName/
    DescriptionRange and Settings
    DefaultsRun 
    Mode Edit
    Lo Hi
    FEF2FE2
    (EU)
    FUF2FU2
    (USA)
    FF2F2
    (Jpn)
    U001 User function 1
    “no” (disabled), or any of the functions D001 to P049 no no no
    ✘ ✔
    U002 User function 2 no no no✘ ✔
    U003 User function 3 no no no✘ ✔
    U004 User function 4 no no no✘ ✔
    U005 User function 5 no no no✘ ✔
    U006 User function 6 no no no✘ ✔
    U007 User function 7 no no no✘ ✔
    U008 User function 8 no no no✘ ✔
    U009 User function 9 no no no✘ ✔
    U010 User function 10 no no no✘ ✔
    U011 User function 11 no no no✘ ✔
    U012 User function 12 no no no✘ ✔
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Configuring Drive Parameters
    3–75
    Programming Error Codes
    The SJ7002 inverter operator keypad displays a spec ial code (begins with the   character) to 
    indicate a programming error. Programming errors  exist when one parameter conflicts with the 
    meaningful range permitted by  related parameter(s). Note that partic ular real-time frequency 
    (speed) input levels can cause a  conflict in some situations. After a conflict exists, the error 
    code will appear on the display,  or you can view it later with D090 in Monitor Mode. Also, the 
    PGM LED on the display will flash ON/OFF when programming. These indications are 
    automatically cleared when the parameter is corrected to the allowed range.  
    Programming Error 
    CodeParameter out of boundsBoundary defined by...
    CodeDescriptionCodeDescription
    001 201A8061 / A261 Frequency upper limit  setting; 1st, 2nd motor > A004 / 
    A204 / A304 Maximum frequency;
    1st, 2nd, 3rd motor
    002 202A062 / A262 Frequency lower limit 
    setting; 1st, 2nd motor >
    004 204 
    304A003 / A203 / 
    A303 Base frequency setting; 
    1st, 2nd, 3rd motor (*1) >
    005 205 
    305F001,
    A020 / A220 / 
    A320 Output frequency setting, 
    Multi-speed freq. setting; 
    1st, 2nd, 3rd motor (*2) >
    006 206 
    306A021 to A035 Multi-speed freq. settings >
    009P015 Home search speed 
    setting >
    012 212A062 / A262 Frequency lower limit 
    setting; 1st, 2nd motor > A061 / A261 Frequency 
    upper limit setting; 
    1st, 2nd motor
    015 215F001,
    A020 / A220 Output frequency setting, 
    Multi-speed freq. setting; 
    1st, 2nd motor >
    016 216A021 to A035 Multi-speed freq. settings >
    019A061 / A261 Frequency upper limit 
    setting; 1st, 2nd motor < P015 Home search speed setting
    021 221< A062 / A262 Frequency lower limit setting; 
    1st, 2nd motor
    025 225F001, 
    A020 / A220Output frequency setting, 
    Multi-speed freq. setting; 
    1st, 2nd motor (*2) <
    031 231A061 / A261 Frequency upper limit 
    setting; 1st, 2nd motor < B082 Start frequency adjustment
    032 232A062 / A262 Frequency lower limit 
    setting; 1st, 2nd motor <
    035 235 
    335F001,
    A020 / A220 / 
    A320 Output frequency setting, 
    Multi-speed freq. setting; 
    1st, 2nd, 3rd motor <
    036A021 to A035 Multi-speed freq. settings <
    037A038 Jog frequency setting <
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							Programming Error Codes
    Configuring Drive Parameters
    3–76
    085 285 385F001,
    A020 / A220 / 
    A320 Output frequency setting, 
    Multi-speed freq. setting; 
    1st, 2nd, 3rd motor >f-x,
    f-x,
     B112 Free-setting 
    V/f frequency (7)
    092 292A062 / A262 Frequency lower limit 
    setting; 1st, 2nd motor >
    095 295F001,
    A020 / A220Output frequency setting, 
    Multi-speed freq. setting; 
    1st, 2nd motor >
    096A021 to A035 Multi-s
    peed freq. settings >
    110B100, B102, 
    B104, B106, 
    B108, B110Free V/f frequency >
    B102, B104, 
    B106, B108, 
    B110 Free V/f frequency > B100 Fre
    e-setting V/f frequency (1)
    B100 Free V/f frequency < B102 F ree-setting V/f frequency (2)
    B104, B106, 
    B108, B110 Free V/f frequency >
    B100, B102 Free V/f frequency < B 104 Free-setting V/f frequency (3)
    B106, B108, 
    B110 Free V/f frequency >
    B100, B102, 
    B104 Free V/f frequency < B106 Fre
    e-setting V/f frequency (4)
    B108, B110 Free V/f frequency >
    B100, B102, 
    B104, B106 Free V/f frequency < B108 Fre
    e-setting V/f frequency (5)
    B110 Free V/f frequency >
    B100, B102, 
    B104, B106, 
    B108 Free V/f frequency < B110 Fre
    e-setting V/f frequency (6)
    120B017, B019 Free-setting electronic 
    thermal frequency < B015 Free-setting, electronic 
    thermal frequency (1)
    B015 Free-setting electronic  thermal frequency > B017 Free-setting, electronic 
    thermal frequency (2)
    B019 Free-setting electronic  thermal frequency <
    B015, B017 Free-setting electronic  thermal frequency > B019 Free-setting, electronic 
    thermal frequency (3)
    Programming Error 
    CodeParameter out of boundsBoundary defined by...
    CodeDescriptionCodeDescription
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Configuring Drive Parameters
    3–77
    Note 1: The base frequency is written when you  store the parameter. If the new base 
    frequency value is outside the permissi ble range, a motor burnout may result. 
    Therefore, if the warning occurs, change the base frequency to an appropriate value.
    Note 2: These parameters are checked even when the  digital operator (option code 02) is not 
    specified for the frequency source setting (A001).
    Note 3: Set frequency (speed) values are not perm itted to be inside the jump frequency 
    ranges, if defined. When a frequency refere nce value from a real-time source (such as 
    keypad potentiometer or analog input) are  inside a jump frequency range, the actual 
    speed is automatically forced to equa l the lowest point of the jump range.
    