Hitachi Sj7002 Owners Manual
Have a look at the manual Hitachi Sj7002 Owners Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 913 Hitachi manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
Using Intelligent Output Terminals Operations and Monitoring 4–60 Low Output Current Signal The inverter monitors the output current to the motor according to parameter C038, Low Current Indication Output M ode Select. Use parameter C039, Low Current Indication Detection Level, to set the low-current threshol d. The Low Output Current Signal [LOC] will turn ON if the output current is less than the C038 threshold and motor operation corresponds to the selected monitoring mode. Note 1: Note that when parameter A001 Frequency So urce Setting = 01 (control terminal), it is possible that the inverter may not recogn ize a constant speed due to sampling, In this case, change C038 = 00 to include accel./d ecel., or increase the analog input filter A016 setting. General Output Signals Refer to the Easy Sequence Inst ruction Manual for information on how to configure and use the general purpose outputs MO1 to MO6. Opt. Code43 Symbol[LOC] Va l i d f o r Outputs[11 to [15], [ALx] Required Settings C038, C039 Default terminals Requires config. CodeFunctionData or RangeDescription C038 Low current indication output mode select 00 Output during accele ration/deceleration and constant speed operation 01 Output only during constant speed *1 C039 Low current indication detection level 0.0 to 2.0 x rated inverter current Low current threshold, used for intelligent output [LOC] Output current (A) t 0 t C038 Low output current [LOC] Opt. Code and Symbol 44=[MO1] 45=[MO2] 46=[MO3] 47=[MO4] 48=[MO5] 49=[MO6] Va l i d f o r Outputs[11 to [15], [ALx] Required Settings See Easy Sequence Default terminal Requires config. Phone: 800.894.0412
SJ7002 Inverter Operations and Monitoring 4–61 Inverter Ready Signal The inverter turns ON the Inverter Ready Signal [I RDY] output when it is ready to receive an operation command such as Run Forward, Run Reverse, or Jog. Otherwise, [IRDY] will be OFF and the inverter cannot accept operation commands. If [IRDY] is OFF, then check the input power supply voltage at the [R], [S], and [T] terminals to be sure the voltage is within the input specification range. The [IRDY] output is OFF when the input power is provided only to the control power supply, Forward/Reverse Rotation Signals The Forward Rotation Signal [FWR] is ON only when the inverter is driving the motor in the foward direction. Similarly, the Reverse Rotation Si gnal [RVR] is ON only when the inverter is driving the motor in the reverse direction. Both signals are OFF when the motor is stopped. Major Failure Signal The Major Failure Signal [MJA] indicates that a particular type of error event has occurred, resulting in an inverter trip. In addition to causing the normal trip alarm, the following error events also will turn ON the [MJA] output, when assigned to an intelligent output terminal. Opt. Code50 Symbol[IRDY] Valid for Outputs[11 to [15], [ALx] Required Settings none Default terminals Requires config. Opt. Code and Symbol51=[FWR] 52=[RVR] Valid for Ouputs[11 to [15], [ALx] Required Settings none Default terminal Requires config. Output frequency (Hz) t 0 t Forward Rotation Signal [FWR] t Reverse Rotation Signal [RVR] Opt. Code53 Symbol[MJA] Valid for Outputs[11 to [15], [ALx] Required Settings none Default terminals Requires config. Error CodeName E 10CT (current transformer) error E 1 1CPU error E 14Ground fault E20Inverter thermal trip with low fan speed E23Gate array error E25Main circuit error Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Using Intelligent Output Terminals Operations and Monitoring 4–62 Window Comparator Signals The window comparator function outputs turn ON when You can also monitor each analog input by comparing it to a thre shold value. This feature allows the inverter to detect discon- nected signal wiring, loss of power at a signal tr ansmitter, etc. When the input is below the set threshold value, the inverter substitutes the thre shold value for the input. The related parameters are given in the following tables. The following signal diagram shows the wind ow comparator output generated from input signals and comparator setti ngs listed along the Y axis. Opt. Code and Symbol54=[WCO] 55=[WCOI] 56=[WCO2] Va l i d f o r Ouputs[11 to [15], [ALx] Required Settings none Default terminal Requires config. Opt. CodeSymbolFunction Name 54 WCO [O] terminal window comparator 55 WCOI [OI] terminal window comparator 54 WCO2 [O2] terminal window comparator CodeFunctionRangeDescription B060[O] input maximum limit level of window comparator 0. to 100. (%) Lower limit = B061 + B062 x 2 B061[O] input minimum limit level of window comparator0. to 100. (%) Lower limit = B060 – B062 x 2 B062[O] input hysteresis width of window comparator 0. to 10. (%) Lower limit = B061 – B062 x 2 B063[OI] input maximum limit level of window comparator0. to 100. (%) Lower limit = B064 + B066 x 2 B064[OI] input minimum limit level of window comparator0. to 100. (%) Lower limit = B063 – B066 x 2 B065[OI] input hysteresis width of window comparator 0. to 10. (%) Lower limit = B063 – B064 x 2 B066[O2] input maximum limit level of window comparator –100. to 100. (%) Lower limit = B067 + B068 x 2 B067[O2] input minimum limit level of window comparator–100. to 100. (%) Lower limit = B066 – B068 x 2 B068[O2] input hysteresis width of window comparator 0. to 10. (%) Lower limit = B066 – B067 x 2 [O], [OI], or [O2] t 0 Hysteresis region t B062B065B068 [WCO], [WCOI], or [WCO2] B060B063B066 B061B064B067Hysteresis region Phone: 800.894.0412
SJ7002 Inverter Operations and Monitoring 4–63 Analog Input Operation Input Terminal SignalsSJ7002 inverters provide for an external analog input to command the inverter frequency output value. The analog input terminal group includes the [L], [OI], [O], [O2], and [H] terminals on the control connector, which provide for Voltage [O] and [O2] or Current [OI] input. All analog input signals must use the analog ground [L]. If you use either the voltage or current analog input, you must select on e of them using the logic input terminal function [AT] analog type. If terminal [AT] is OFF, the voltage input [O] can command the inverter output frequency. If terminal [AT] is ON, the current input [OI] can command the inverter output frequency. The [AT] terminal function is covered in “ Analog Input Current/ Voltage Select” on page 4–24. Remember that you must also set A001 = 01 to select analog input as the frequency source. Input FilterParameter A016 adjusts an analog input sampling filter that evenly affects all analog inputs shown above. The parameter range is from 1 to 30. Before increasing the filter setting, we recommend trying to find the cause of inpu t analog noise. Check for the following: Look for nearby high-current wiring—avoid an y parallel runs to the analog signal wires Check the impedance between th e chassis grounds of the inverter and the analog signal source equipment—a good connecti on will have a low impedance Check the analog signal ground impedance from the inverter to the analog signal source Avoid ground loops... measure the current (or voltage drop) on the chassis ground and signal ground connections; the ideal value is zero After taking steps to minimize the analog signal no ise sources, increase the filter time constant (A016) until the motor output frequency (when commanded by analog inputs) becomes stable. HO2FMAM OOILAMI +V Ref. A GND 0—10V input 4—20mA input -10 / 0 / +10V + – 4-20 mA Frequency source setting 1V – I select 0 – 10V + –-10 / 0 / +10V O2 O O OI HO2FMAM OOILAMI A005A001=01 A005=00 A005=01 AT = O N AT = O F F AT = O N 0 1 0 10 1 0 1 Frequency setting Terminals (Keypad) OI O2 O L AT Phone: 800.894.0412
Analog Input Operation Operations and Monitoring 4–64 The following tables show the available anal og input settings. Parameters A006, A005, and input terminal [AT] determine the External Frequency Command input terminals that are avail- able and how they function. The Trim Freque ncy input [O2]—[L] is available (when check marked) for some settings. Other settings make the reverse direction (in addition to forward) available for bipolar input sett ings (when check marked). A bi polar input responds to positive input voltages with a forward motor rotation, and to negative input voltages with reverse motor rotation. The table below applies when the [AT] input function is not assigned to any intelligent input terminal. The A005 setting, nor mally used in conjunction with an [AT] input, is ignored. CAUTION: Whenever the [AT] input function is not assigned to any input terminal and reverse rotation is not desired or is unsafe, be sure to set A006 = 01. This setting makes the [O2] input unipolar only. A006A005[AT]External Frequency Command InputTrim Frequency Command InputReverse avail. (bipolar input) 00 OR 03 00 OFF [O] ✘✘ ON [OI] ✘✘ 01 OFF [O]✘✘ ON [O2] ✘✔ 01 00 Example 1 OFF [O] [O2] ✘ ON [OI] [O2]✘ 01 OFF [O][O2] ✘ ON [O2] ✘✔ 02 00 Example 2 OFF [O] [O2]✔ ON [OI] [O2]✔ 01 OFF [O][O2]✔ ON [O2 ✘✔ —02OFF [O] [O2] ✘ ON Keypad pot. [O2]✘ 03 OFF [OI][O2]✘ ON Keypad pot. [O2]✘ 04 OFF [O2]✘✔ ON Keypad pot. [O2]✘ A006A005[AT]External Frequency Command InputTrim Frequency Command InputReverse avail. (bipolar input) 00 — (not assigned to any input terminal) [O2] ✘✔ 01 — Summation of [O] and [OI] [O2] ✘ 02 — Summation of [O] and [OI] [O2] ✔ 03 — Summation of [O] and [OI] ✘✘ Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
SJ7002 Inverter Operations and Monitoring 4–65 The examples below show how the use of the [AT] input during operation enables/disables the Trim Frequency Command input [O2]—[L]. The [O2] —[L] input may be used alone, or as an offset control for the primary analog input. Wiring ExamplesUsing an external potentiom eter is a common way to control the inverter output frequency (and a good way to learn how to use the analog inputs). The potentiome- ter uses the built-in 10V reference [H] and the analog ground [L] for excitation, and the voltage input [O] for the signal. By default, the [AT] terminal selects the voltage input when it is OFF. Take care to use the proper resistance for the potentiometer, which is 1 to 2k Ω, 2 Watts. Voltage Input – The 0–10V voltage input circuit uses terminals [L] and [O]. Attach the signal cable’s shield wire to terminal [L] on the inve rter only. DO NOT ground the shield at its other end. Maintain the voltage with in specifications (do not apply negative voltage). Normally a full-span input level (10V) will give the ma ximum motor frequency. You can use parameter A014 to select a lower voltage for full output frequency (such as using a 5V input signal). Bipolar Voltage Input – The -10 / 0 / +10V voltage input circuit uses terminals [L] and [O2]. Attach the cable’s shield wire to terminal [L] on the inverter only. Maintain the voltage within specifications. Only apply a negative voltage if this input is configured for bipolar use. Current Input – The current input circui t uses terminals [OI] and [L]. The current comes from a sourcing type transmitter; a sinking type will not work! This means the current must flow into terminal [OI], and terminal [L] is the return back to the transmitter. The input impedance from [OI] to [L] is 250 Ohms. Attach the cable’s shie ld wire to terminal [L] on the inverter only. [FW] terminal External frequency command [O/OI] terminal [AT] terminal Actual frequency command 0 Example 1: Without reverse Example 2: With reverse Trim frequency command [O2] terminal FOI FOI + FO2 FO20 FO 0 FO + FO2 [FW] terminal External frequency command [O/OI] terminal [AT] terminal Actual frequency command 0 Trim frequency command [O2] terminal FOI FOI + FO2 FO20 FO 0 FO + FO2 forward reverse HO2FMAM OOILAMI 1 to 2 k Ω, 2WL H HO2FMAM OOILAMI + – 0 to 9.6 VDC, 0 to 10V nominal4 to 19.6 mA DC, 4 to 20 mA nominal See I/O specs on page 4–9. + – -10 to 9.6 VDC, 0 to 10V nominal Standard Voltage Input Bipolar Voltage Input Current Input HO2FMAM OOILAMI HO2FMAM OOILAMI Phone: 800.894.0412
Analog Output Operation Operations and Monitoring 4–66 Analog Output Operation In the system design for inverter applications it is sometimes useful to monitor inverter opera- tion from a remote location. In some cases, this requires only a pane l-mounted analog meter (moving-coil type). In other cases, a controller device such as a PLC may monitor and command the inverter frequency and other function s. The inverter can transmit the (real-time) output frequency, current, torque, or other para meters to the controller to confirm actual operation. The monitor output term inal [FM] serves these purposes. [FM] TerminalThe inverter provides an analog/digital output on terminal [FM] (frequenc y monitor). It uses terminal [CM1] as digi tal GND reference. While many applications use this terminal to monitor the output frequency, you can configure terminal [FM] to transmit one of several parameters. Most use pulse-width modulation (PWM) to represent the value, while one parameter uses frequency modulation (FM) to represent the value. Do not confuse the notation for terminal [FM] (with brackets) with FM signal type. The following table lists the configurations for terminal [FM]. Use function C027 to configure. Note 1: Display substitutes only during sensorless vector control, 0Hz domain sensorless vector control, and vector control PWM Signal TypeThe pulse-width modulated signal at terminal [FM] is primarily designed for driving a moving- coil meter. The pulse-width modulated signal is automatically averaged by the inertia of the moving-coil mechanism—converting the PWM signal to an analog repr esentation. Be sure to use a 10V full-scale DC voltmeter. The signal characteristic s of terminal [FM] in PWM signal configuration is shown below Func.CodeDescriptionWav e fo r mFull Scale Value C027 00 Output frequency PWM 0 – Max. frequency (Hz) 01 Output current PWM 0 – 200% 02 Output torque *1 PWM 0 – 200% 03 Output frequency FM 0 – Max. frequency (Hz) 04 Output voltage PWM 0 – 100% 05 Input electric power PWM 0 – 200% 06 Thermal load ratio PWM 0 – 100% 07 LAD frequency PWM 0 – Max. frequency (Hz) D GND Analog/digital Output See I/O specs on page 4–9. HO2FMAM OOIL FWTH PLCP24CM1AMI HO2FMAM OOIL FWTH PLCP24CM1AMI +– 0 to 10V, 1 mA [FM][FM] output value t T --- = Period T = 6.4ms constant (156 Hz) Selects FM type output= [FM] terminal 8-bit gain setting B081 C27=00, 01, 02, 04, 05, 06, 07 t 10V 0V t T Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
SJ7002 Inverter Operations and Monitoring 4–67 To calibrate the meter reading, generate a full-s cale output (always ON) at terminal [FM]. Then use parameter B081(gain setting from 0 to 255) to adjust the corresponding full-scale reading of the meter. For example, when the inverter output frequency is 60 Hz, change the value of B081 so that the meter reads 60 Hz. TIP: When using the analog meter fo r monitoring, adjust the meter so it has a zero reading when the [FM] output is zero. Then use scale factor B081 to adjust the [FM] output so the maximum frequency in the inverter correspo nds to a full-scale reading on the meter. NOTE: The indicator accuracy af ter adjustment is about ±5%. Depending on the motor, the accuracy may exceed this value. PWM Smoothing Circuit – Note that standard analog output signals are avail- able on terminals [AM] and [AMI], covered in the next section. However, you may also wish to smooth the PWM signal at the [FM] terminal and convert it to an analog signal. The [FM] terminal will then generate a relatively stable DC analog voltage that represents the output value. To do this, use the circuit shown to the right. Note the output impedance of the circuit is at least 82k Ω, so the monitoring device needs an input impedance of 1M Ω or greater. Otherwis e, the impedance of the smoothing circuit will cause a non- linearity in the reading. FM Signal TypeThe frequency-modulated output at terminal [FM] varies its frequency with the inverter output frequency (when C027=03). The signal at [FM] uses the parameter A004 Maximum frequency setting . For example, if A004 = 60 Hz, then the maximum signal value at [FM] will be at 60 Hz. This frequency is digita lly controlled for accuracy, and does not use the B081 gain setting when C027=03 (frequency modulation). HO2FMAM OOIL FWTH PLCP24CM1AMI + –+ – + 33k Ω 82k Ω Vo l t s 1 μ F T 1 [FM] Output Frequency --------------------------------------------------------- = Selects FM type output [FM] T [FM] Output Frequency 1 T --- = C027=03 t 10V 0V 50% fixed duty cycle Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Analog Output Operation Operations and Monitoring 4–68 [AM] and [AMI] TerminalsThe [AM] and [AMI] terminals provide signals to monitor various invert er parameters such as output frequency, output current, and torque. The terminals provide these analog signal types: [AM] terminal: 0–10V analog output signal [AMI] terminal: 4–20mA analog output signal These signals both use the [L] terminal for signal return. Eight different inverter parameters may be monitored independently at either the [AM] or [AMI] terminal, as listed in the table below. Use C028 to configure terminal [AM], and C029 to configure terminal [AMI]. Note 1: Display of torque is possible only during sensorless vector control, 0Hz domain sensorless vector control, and vector control with feedback The analog signals may need some adjustment for gain or offset to compensate for variances in the system. For example, the signals may drive a panel meter and require a full-scale gain adjustment. The table below list s the function codes and their descriptions. The [AM] and [AMI] terminals have separate gain and offset adjustments. Note the default values. Func.Te r m i n a lCodeDescriptionFull Scale Value C028 / C029 [AM] / [AMI] 00 Output frequency 0 – Max. frequency (Hz) 01 Output current 0 – 200% 02 Output torque *1 0 – 200% 04 Output voltage 0 – 100% 05 Input electric power 0 – 200% 06 Thermal load ratio 0 – 100% 07 LAD frequency 0 – Max. frequency (Hz) Func.Te r m i n a lDescriptionRangeDefault B080 [AM] Gain adjustment 0 – 255 180 C086 [AM] Offset Adjustment 0.0 – 10.0V 0.0V C087 [AMI] Gain adjustment 0 – 255 80 C088 [AMI] Offset Adjustment 0.0 – 20.0mA 0.0mA HO2FMAM OOILAMI A GND See I/O specs on page 4–9. 0–10V analog output 4–20mA analog output Phone: 800.894.0412
SJ7002 Inverter Operations and Monitoring 4–69 Setting Motor Constants for Vector Control IntroductionThese advanced torque control algorithms impr ove performance, particularly at low speeds: Sensorless Vector Control – improved torque control at outp ut frequencies down to 0.5 Hz. Use A044=03 (1st motor) or A244=03 (2nd mo tor) to select sensorless vector control. Sensorless Vector Control, 0Hz Domain – improved torque control at output frequencies from 0 to 2.5 Hz. Use A044=04 (1st motor) or A244=04 (2nd motor) to select sensorless vector control, 0Hz domain. Vector Control with Feedback – improved torque control at all speeds, while providing the most accurate speed regulation of all torque control algorithms. Use A044=05 to select vector control with feedback. These three control algorithms require the inverter’s motor constants to accurately match the characteristics of the particular motor connected to your inverter. Simply using the inverter’s default parameters with the vector control modes may not produce sati sfactory results. The auto-tuning procedure desc ribed later in this section is recommended for most applications needing vector control. It determines and reco rds the characteristics of the attached motor. However, it is possible to enter the motor constants directly if the motor manufacturer has provided that data. After performing an initial au to-tuning procedure for your motor, you have an additional option: adaptive tuning. The adaptive tuning pa rameters use the auto-tuning procedure’s results as starting values. Then, each time the motor runs normally in your application, the inverter tunes the parameters again to match the motor. This compensates for temperature changes, etc., further optimizing the values. The following table lists the parameters associated with motor constant settings. Function H002 selects the set of motor constants that you want the inverter to use in normal use. Standard constants (select with H002=00) include H020 to H024. Auto-tuned constants (select with H002=01) include H030 to H034. Remember that you have to do the auto-tuning procedure in this section before using either auto-tuned constants or the adaptive mode (H002=02). Func.NameDataNotes A044 / A244 / A344 V/f characteristic curve selection, 1st / 2nd / 3rd motors 00 V/f constant torque 01 V/f variable torque 02 V/f free-setting curve 03 Sensorless vector control (SLV) 04 Sensorless vector control, 0Hz domain 05 Vector control with encoder feedback H002 Motor data selection, 1st motor 00 Standard motor parameters 01 Auto-tuning parameters 02 Adaptive tuning parameters H003 Motor capacity, 1st motor 0.2 – 75, 0.2 – 160kW, up to –550xxx models kW, –750xxx to –1500xxx models H004 Motor poles setting, 1st motor 2 / 4 / 6 / 8 Units: poles H020 Motor constant R1, 1st motor 0.000–65.53 Units: ohms H021 Motor constant R2, 1st motor 0.000–65.53 Units: ohms H022 Motor constant L, 1s t motor 0.00–655.3 Units: mH H023 Motor constant Io, 1s t motor 0.00–655.3 Units: A H024 Motor constant J, 1st motor 0.001–9999 Units: kgm 2 H030 Auto-tuned constant R1, 1st motor 0.000–65.53 Units: ohms Phone: 800.894.0412