Home > Hitachi > Inverter > Hitachi Sj7002 Owners Manual

Hitachi Sj7002 Owners Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Hitachi Sj7002 Owners Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 913 Hitachi manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Using Intelligent Output Terminals
    Operations
    and Monitoring
    4–60
    Low Output 
    Current Signal   The inverter monitors the output current to  the motor according to parameter C038, Low 
    Current Indication Output M ode Select. Use parameter C039, Low Current Indication 
    Detection Level, to set the low-current threshol d. The Low Output Current Signal [LOC] will 
    turn ON if the output current is less than  the C038 threshold and motor operation corresponds 
    to the selected monitoring mode.
    Note 1: Note that when parameter A001 Frequency So urce Setting = 01 (control terminal), it 
    is possible that the inverter may not recogn ize a constant speed due to sampling, In 
    this case, change C038 = 00 to include accel./d ecel., or increase the analog input filter 
    A016 setting. 
    General Output 
    Signals   Refer to the Easy Sequence Inst ruction Manual for information on  how to configure and use the 
    general purpose outputs MO1 to MO6.
    Opt. Code43
    Symbol[LOC]
    Va l i d  f o r  
    Outputs[11 to [15],  [ALx]
    Required
    Settings C038, C039
    Default 
    terminals Requires 
    config.
    CodeFunctionData or RangeDescription
    C038 Low current indication  output mode select 00 Output during accele
    ration/deceleration 
    and constant speed operation
    01 Output only during constant speed *1
    C039 Low current indication  detection level 0.0 to 2.0 x 
    rated inverter 
    current Low current threshold, used for 
    intelligent output [LOC]
    Output current (A)
    t
    0
    t
    C038
    Low output current [LOC]
    Opt. Code  and 
    Symbol
    44=[MO1]
    45=[MO2]
    46=[MO3]
    47=[MO4]
    48=[MO5]
    49=[MO6]
    Va l i d  f o r   Outputs[11 to [15],  [ALx]
    Required
    Settings See Easy 
    Sequence
    Default 
    terminal Requires 
    config.
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–61
    Inverter Ready 
    Signal   The inverter turns ON the Inverter Ready Signal [I RDY] output when it is ready to receive an 
    operation command such as Run Forward, Run Reverse, or Jog. Otherwise, [IRDY] will be 
    OFF and the inverter cannot accept operation  commands. If [IRDY] is OFF, then check the 
    input power supply voltage at the [R], [S], and [T] terminals to be sure the voltage is within the 
    input specification range. The [IRDY] output is  OFF when the input power is provided only to 
    the control power supply,
    Forward/Reverse 
    Rotation Signals  The Forward Rotation Signal [FWR] is ON only when the inverter is driving the motor in the 
    foward  direction. Similarly, the Reverse Rotation Si gnal [RVR] is ON only when the inverter is 
    driving the motor in the  reverse direction. Both signals are OFF when the motor is stopped.
    Major Failure 
    Signal   The Major Failure Signal [MJA] indicates that a  particular type of error event has occurred, 
    resulting in an inverter trip. In addition to causing the normal trip alarm, the following error 
    events also will turn ON the [MJA] output, when  assigned to an intelligent output terminal.
    Opt. Code50
    Symbol[IRDY]
    Valid for 
    Outputs[11 to [15],  [ALx]
    Required
    Settings none
    Default 
    terminals Requires 
    config.
    Opt. Code 
    and 
    Symbol51=[FWR]
    52=[RVR]
    Valid for  Ouputs[11 to [15],  [ALx]
    Required
    Settings none
    Default 
    terminal Requires 
    config.
    Output frequency (Hz)
    t
    0
    t
    Forward Rotation Signal [FWR]
    t
    Reverse Rotation Signal [RVR]
    Opt. Code53
    Symbol[MJA]
    Valid for 
    Outputs[11 to [15],  [ALx]
    Required
    Settings none
    Default 
    terminals Requires 
    config.
    Error 
    CodeName
    E 10CT (current transformer) error
    E 1 1CPU error
    E 14Ground fault
    E20Inverter thermal trip with low fan speed
    E23Gate array error
    E25Main circuit error
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							Using Intelligent Output Terminals
    Operations
    and Monitoring
    4–62
    Window 
    Comparator 
    Signals   The window comparator function outputs turn  ON when You can also monitor each analog 
    input by comparing it to a thre shold value. This feature allows  the inverter to detect discon-
    nected signal wiring, loss of power at a signal tr ansmitter, etc. When the input is below the set 
    threshold value, the inverter substitutes the thre shold value for the input. The related parameters 
    are given in the following tables.   
    The following signal diagram shows the wind ow comparator output generated from input 
    signals and comparator setti ngs listed along the Y axis.
    Opt. Code 
    and 
    Symbol54=[WCO]
    55=[WCOI]
    56=[WCO2]
    Va l i d  f o r   Ouputs[11 to [15],  [ALx]
    Required
    Settings none
    Default 
    terminal Requires 
    config.
    Opt.
    CodeSymbolFunction Name
    54 WCO [O] terminal window comparator
    55 WCOI [OI] terminal window comparator
    54 WCO2 [O2] terminal window comparator
    CodeFunctionRangeDescription
    B060[O] input maximum limit level of 
    window comparator 0. to 100. (%) Lower limit = B061 + B062 x 2
    B061[O] input minimum limit level of 
    window comparator0. to 100. (%) Lower limit = B060 – B062 x 2
    B062[O] input hysteresis width of 
    window comparator 0. to 10. (%) Lower limit = B061 – B062 x 2
    B063[OI] input maximum limit level 
    of window comparator0. to 100. (%) Lower limit = B064 + B066 x 2
    B064[OI] input minimum limit level of 
    window comparator0. to 100. (%) Lower limit = B063 – B066 x 2
    B065[OI] input hysteresis width of 
    window comparator 0. to 10. (%) Lower limit = B063 – B064 x 2
    B066[O2] input maximum limit level 
    of window comparator
    –100. to 100. (%) Lower limit = B067 + B068 x 2
    B067[O2] input minimum limit level 
    of window comparator–100. to 100. (%) Lower limit = B066 – B068 x 2
    B068[O2] input hysteresis width of 
    window comparator 0. to 10. (%) Lower limit = B066 – B067 x 2
    [O], [OI], or [O2]
    t
    0
    Hysteresis region
    t
    B062B065B068
    [WCO], [WCOI], or [WCO2]
    B060B063B066
    B061B064B067Hysteresis region
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–63
    Analog Input Operation
    Input Terminal 
    SignalsSJ7002 inverters provide for an external analog 
    input to command the inverter frequency output 
    value. The analog input terminal group includes 
    the [L], [OI], [O], [O2], and [H] terminals on the 
    control connector, which provide for Voltage [O] 
    and [O2] or Current [OI]  input. All analog input 
    signals must use the analog ground [L].
    If you use either the voltage or current analog 
    input, you must select on e of them using the logic 
    input terminal function  [AT] analog type. If 
    terminal [AT] is OFF, the voltage input [O] can 
    command the inverter output  frequency. If terminal 
    [AT] is ON, the current input [OI] can command 
    the inverter output frequency. The [AT]  terminal function is covered in “
    Analog Input Current/
    Voltage Select” on page 4–24. Remember that you must also set A001 = 01 to select analog 
    input as the frequency source.
    Input FilterParameter A016 adjusts an analog input sampling  filter that evenly affects all analog inputs 
    shown above. The parameter range is from 1 to  30. Before increasing the filter setting, we 
    recommend trying to find the cause of inpu t analog noise. Check for the following:
     Look for nearby high-current wiring—avoid an y parallel runs to the analog signal wires
     Check the impedance between th e chassis grounds of the inverter and the analog signal 
    source equipment—a good connecti on will have a low impedance
     Check the analog signal ground impedance from  the inverter to the analog signal source
     Avoid ground loops... measure the current (or  voltage drop) on the chassis ground and signal 
    ground connections; the ideal value is zero
    After taking steps to minimize the analog signal no ise sources, increase the filter time constant 
    (A016) until the motor output frequency (when  commanded by analog inputs) becomes stable.
    HO2FMAM
    OOILAMI
    +V Ref.
    A GND
    0—10V input
    4—20mA input
    -10 / 0 / +10V 
    + –
    4-20 mA
    Frequency
    source setting
    1V – I select
    0 – 10V
    + –-10 / 0 / +10V
    O2 O
    O
    OI
    HO2FMAM
    OOILAMI
    A005A001=01
    A005=00
    A005=01
    AT = O N
    AT = O F F
    AT = O N
    0 1
    0
    10
    1
    0
    1
    Frequency setting
    Terminals
    (Keypad)
    OI
    O2 O
    L AT
    
    Phone: 800.894.0412   
    						
    							Analog Input Operation
    Operations
    and Monitoring
    4–64
    The following tables show the available anal og input settings. Parameters A006, A005, and 
    input terminal [AT] determine  the External Frequency Command input terminals that are avail-
    able and how they function. The Trim Freque ncy input [O2]—[L] is available (when check 
    marked) for some settings. Other settings make  the reverse direction (in addition to forward) 
    available for bipolar input sett ings (when check marked). A bi polar input responds to positive 
    input voltages with a forward motor rotation, and  to negative input voltages with reverse motor 
    rotation.
    The table below applies when the [AT]  input function is not assigned to any intelligent input 
    terminal. The A005 setting, nor mally used in conjunction with an [AT] input, is ignored.
    CAUTION: Whenever the [AT] input function is  not assigned to any input terminal and 
    reverse rotation is not desired or is unsafe, be  sure to set A006 = 01. This setting makes the 
    [O2] input unipolar only.
    A006A005[AT]External Frequency 
    Command InputTrim Frequency 
    Command InputReverse avail.
    (bipolar input)
    00
     OR 03 00 OFF [O]
    ✘✘
    ON [OI] ✘✘
    01 OFF [O]✘✘
    ON [O2] ✘✔
    01 00 Example 
    1 OFF
    [O] [O2] ✘
    ON [OI] [O2]✘
    01 OFF [O][O2] ✘
    ON [O2] ✘✔
    02 00 Example 2 OFF
    [O] [O2]✔
    ON [OI] [O2]✔
    01 OFF [O][O2]✔
    ON [O2 ✘✔
    —02OFF [O] [O2] ✘
    ON Keypad pot. [O2]✘
    03 OFF [OI][O2]✘
    ON Keypad pot. [O2]✘
    04 OFF [O2]✘✔
    ON Keypad pot. [O2]✘
    A006A005[AT]External Frequency 
    Command InputTrim Frequency 
    Command InputReverse avail.
    (bipolar input)
    00 —
    (not 
    assigned 
    to any input 
    terminal) [O2]
    ✘✔
    01 — Summation of
    [O] and [OI] [O2]
    ✘
    02 — Summation of
    [O] and [OI] [O2]
    ✔
    03 — Summation of
    [O] and [OI] ✘✘
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–65
    The examples below show how the use of the [AT] input during operation enables/disables the 
    Trim Frequency Command input [O2]—[L]. The [O2] —[L] input may be used alone, or as an 
    offset control for the primary analog input.
    Wiring ExamplesUsing an external potentiom eter is a common way to 
    control the inverter output frequency (and a good way 
    to learn how to use the analog inputs). The potentiome-
    ter uses the built-in 10V reference [H] and the analog 
    ground [L] for excitation, and  the voltage input [O] for 
    the signal. By default, the [AT] terminal selects the 
    voltage input when it is OFF. Take care to use the 
    proper resistance for the  potentiometer, which is
    1 to 2k Ω, 2 Watts.
    Voltage Input  – The 0–10V voltage input circuit uses terminals [L] and [O]. Attach the signal 
    cable’s shield wire to terminal [L] on the inve rter only. DO NOT ground the shield at its other 
    end. Maintain the voltage with in specifications (do not apply negative voltage). Normally a 
    full-span input level (10V) will give the ma ximum motor frequency. You can use parameter 
    A014 to select a lower voltage for full output  frequency (such as using a 5V input signal).
    Bipolar Voltage Input  – The -10 / 0 / +10V voltage input circuit uses terminals [L] and [O2]. 
    Attach the cable’s shield wire to  terminal [L] on the inverter only. Maintain the voltage within 
    specifications. Only apply a negative voltage  if this input is configured for bipolar use.
    Current Input  – The current input circui t uses terminals [OI] and [L]. The current comes from 
    a  sourcing type transmitter; a  sinking type will not work! This means the current must flow into 
    terminal [OI], and terminal [L] is  the return back to the transmitter. The input impedance from 
    [OI] to [L] is 250 Ohms. Attach the cable’s shie ld wire to terminal [L] on the inverter only.
    [FW] terminal
    External frequency  command
    [O/OI] terminal [AT] terminal
    Actual frequency  command
    0
    Example 1: Without reverse Example 2: With reverse
    Trim frequency  command
    [O2] terminal
    FOI
    FOI + FO2
    FO20
    FO
    0
    FO + FO2
    [FW] terminal
    External frequency  command
    [O/OI] terminal [AT] terminal
    Actual frequency  command
    0
    Trim frequency  command
    [O2] terminal
    FOI
    FOI + FO2
    FO20
    FO
    0
    FO + FO2
    forward
    reverse
    HO2FMAM
    OOILAMI
    1 to 2 k Ω, 2WL
    H
    HO2FMAM
    OOILAMI
    + –
    0 to 9.6 VDC,
    0 to 10V nominal4 to 19.6 mA DC,
    4 to 20 mA nominal
    See I/O specs on page 4–9.
    + –
    -10 to 9.6 VDC,
    0 to 10V nominal
    Standard Voltage Input Bipolar Voltage Input Current Input
    HO2FMAM
    OOILAMI
    HO2FMAM
    OOILAMI
    
    Phone: 800.894.0412   
    						
    							Analog Output Operation
    Operations
    and Monitoring
    4–66
    Analog Output Operation
    In the system design for inverter applications it  is sometimes useful to monitor inverter opera-
    tion from a remote location. In some cases, this requires only a pane l-mounted analog meter 
    (moving-coil type). In other  cases, a controller device such as a PLC may monitor and 
    command the inverter frequency and other function s. The inverter can transmit the (real-time) 
    output frequency, current, torque, or other para meters to the controller to confirm actual 
    operation. The monitor output term inal [FM] serves these purposes.
    [FM] TerminalThe inverter provides an analog/digital output on 
    terminal [FM] (frequenc y monitor). It uses 
    terminal [CM1] as digi tal GND reference. While 
    many applications use this terminal to monitor 
    the output frequency, you  can configure terminal 
    [FM] to transmit one of several parameters. 
    Most use pulse-width modulation  (PWM) to 
    represent the value, while one parameter uses 
    frequency modulation  (FM) to represent the 
    value. Do not confuse the notation for terminal 
    [FM] (with brackets) with FM signal type.
    The following table lists the configurations for  terminal [FM]. Use function C027 to configure.
    Note 1: Display substitutes only during sensorless vector control, 0Hz domain sensorless 
    vector control, and vector control
    PWM Signal TypeThe pulse-width modulated  signal at terminal 
    [FM] is primarily designed for driving a moving-
    coil meter. The pulse-width modulated signal is 
    automatically averaged by the inertia of the 
    moving-coil mechanism—converting the PWM 
    signal to an analog repr esentation. Be sure to use 
    a 10V full-scale DC voltmeter.
    The signal characteristic s of terminal [FM] in 
    PWM signal configuration is shown below
    Func.CodeDescriptionWav e fo r mFull Scale Value
    C027 00 Output frequency PWM 0 – Max. frequency (Hz)
    01 Output current PWM 0 – 200%
    02 Output torque *1 PWM 0 – 200%
    03 Output frequency FM 0 – Max. frequency (Hz)
    04 Output voltage PWM 0 – 100%
    05 Input electric power PWM 0 – 200%
    06 Thermal load ratio PWM 0 – 100%
    07 LAD frequency PWM 0 – Max. frequency (Hz)
    D GND Analog/digital Output
    See I/O specs on page 
    4–9.
    HO2FMAM
    OOIL
    FWTH
    PLCP24CM1AMI
    HO2FMAM
    OOIL
    FWTH
    PLCP24CM1AMI
    +–
    0 to 10V,
    1 mA
    [FM][FM] output value t
    T ---
    =
    Period T = 6.4ms constant (156 Hz) Selects FM type output= [FM] terminal 8-bit gain setting
    B081
    C27=00, 01, 02, 04, 05, 06, 07
    t
    10V
    0V t
    T
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–67
    To calibrate the meter reading, generate a full-s cale output (always ON) at terminal [FM]. Then 
    use parameter B081(gain setting from 0 to 255) to  adjust the corresponding full-scale reading 
    of the meter. For example, when the inverter  output frequency is 60 Hz, change the value of 
    B081 so that the meter reads 60 Hz.
    TIP:  When using the analog meter fo r monitoring, adjust the meter so it has a zero reading 
    when the [FM] output is zero. Then use scale factor B081 to adjust the [FM] output so the 
    maximum frequency in the inverter correspo nds to a full-scale reading on the meter.
    NOTE: The indicator accuracy af ter adjustment is about ±5%. Depending on the motor, the 
    accuracy may exceed this value.
    PWM Smoothing Circuit  – Note that 
    standard analog output signals are avail-
    able on terminals [AM] and [AMI], 
    covered in the next section. However, you 
    may also wish to smooth the PWM signal 
    at the [FM] terminal and convert it to an 
    analog signal. The [FM] terminal will then 
    generate a relatively stable DC analog 
    voltage that represents the output value. 
    To do this, use the circuit shown to the 
    right. Note the output  impedance of the 
    circuit is at least 82k Ω, so the monitoring 
    device needs an input impedance of 1M Ω 
    or greater. Otherwis e, the impedance of 
    the smoothing circuit will cause a non-
    linearity in the reading.
    FM Signal TypeThe  frequency-modulated  output at terminal [FM] varies its frequency with the inverter output 
    frequency (when C027=03). The signal at [FM] uses the parameter A004  Maximum frequency 
    setting . For example, if A004 = 60 Hz, then the  maximum signal value at [FM] will be at 
    60 Hz. This frequency is digita lly controlled for accuracy, and does not use the B081 gain 
    setting when C027=03  (frequency modulation). 
    HO2FMAM
    OOIL
    FWTH
    PLCP24CM1AMI
    +
    –+ –
    +
    33k
    Ω 82k
    Ω
    Vo l t s
    1 μ F
    T 1
    [FM] Output Frequency ---------------------------------------------------------
    =
    Selects FM type output
    [FM]
    T
    [FM] Output Frequency 1
    T
    ---
    =
    C027=03
    t
    10V
    0V 50% fixed duty cycle
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							Analog Output Operation
    Operations
    and Monitoring
    4–68
    [AM] and [AMI] 
    TerminalsThe [AM] and [AMI] terminals provide signals 
    to monitor various invert er parameters such as 
    output frequency, output current, and torque. 
    The terminals provide these analog signal types:
     [AM] terminal: 0–10V analog output signal
     [AMI] terminal: 4–20mA analog output 
    signal
    These signals both use the [L] terminal for signal 
    return. Eight different inverter parameters may 
    be monitored independently at either the [AM] 
    or [AMI] terminal, as listed in the table below. 
    Use C028 to configure terminal [AM], and C029 
    to configure terminal [AMI].
    Note 1: Display of torque is possible only during  sensorless vector control, 0Hz domain 
    sensorless vector control, and vector control with feedback
    The analog signals may need some adjustment for gain or offset to compensate for variances in 
    the system. For example, the signals may drive a panel meter and require a full-scale gain 
    adjustment. The table below list s the function codes and their descriptions. The [AM] and 
    [AMI] terminals have separate  gain and offset adjustments. Note the default values. 
    Func.Te r m i n a lCodeDescriptionFull Scale Value
    C028 /  C029 [AM] / 
    [AMI] 00 Output frequency 0 – Max. frequency (Hz)
    01 Output current 0 – 200%
    02 Output torque *1 0 – 200%
    04 Output voltage 0 – 100%
    05 Input electric power 0 – 200%
    06 Thermal load ratio 0 – 100%
    07 LAD frequency 0 – Max. frequency (Hz)
    Func.Te r m i n a lDescriptionRangeDefault
    B080 [AM] Gain adjustment 0 – 255 180
    C086 [AM] Offset Adjustment 0.0 – 10.0V 0.0V
    C087 [AMI] Gain adjustment 0 – 255 80
    C088 [AMI] Offset Adjustment 0.0 – 20.0mA 0.0mA
    HO2FMAM
    OOILAMI
    A GND
    See I/O specs on page 4–9.
    0–10V analog output
    4–20mA analog output
    
    Phone: 800.894.0412   
    						
    							SJ7002 Inverter
    Operations
    and Monitoring
    4–69
    Setting Motor Constants for Vector Control
    IntroductionThese advanced torque control algorithms impr ove performance, particularly at low speeds:
     Sensorless Vector Control –  improved torque control at outp ut frequencies down to 0.5 Hz. 
    Use A044=03 (1st motor) or A244=03 (2nd mo tor) to select sensorless vector control.
     Sensorless Vector Control, 0Hz Domain –  improved torque control at output frequencies 
    from 0 to 2.5 Hz. Use A044=04 (1st motor) or A244=04 (2nd motor) to select sensorless 
    vector control, 0Hz domain.
     Vector Control with Feedback –  improved torque control at all speeds, while providing the 
    most accurate speed regulation  of all torque control algorithms. Use A044=05 to select 
    vector control with feedback.
    These three control algorithms require the inverter’s motor constants to accurately match the 
    characteristics of the particular motor connected to your inverter. Simply using the inverter’s 
    default parameters with the vector control modes may not produce sati sfactory results. The 
    auto-tuning procedure desc ribed later in this section is recommended for most applications 
    needing vector control. It determines and reco rds the characteristics of the attached motor. 
    However, it is possible to enter the motor constants directly if the motor manufacturer has 
    provided that data.
    After performing an initial au to-tuning procedure for your motor, you have an additional 
    option: adaptive tuning. The adaptive tuning pa rameters use the auto-tuning procedure’s results 
    as starting values. Then, each time the motor runs normally in your application, the inverter 
    tunes the parameters again to match the motor.  This compensates for temperature changes, etc., 
    further optimizing the values.
    The following table lists the parameters associated with motor constant settings. Function H002 
    selects the set of motor constants that you want  the inverter to use in normal use. Standard 
    constants (select with H002=00) include H020  to H024. Auto-tuned constants (select with 
    H002=01) include H030 to H034. Remember that you have to do the auto-tuning procedure in 
    this section before using either auto-tuned constants or the adaptive mode (H002=02).
    Func.NameDataNotes
    A044 /
    A244 / A344  V/f characteristic curve selection, 
    1st / 2nd / 3rd motors 00 V/f constant torque
    01 V/f variable torque
    02 V/f free-setting curve
    03 Sensorless vector control (SLV)
    04 Sensorless vector control, 0Hz domain
    05 Vector control with encoder feedback
    H002 Motor data selection, 1st  motor 00 Standard  motor parameters
    01 Auto-tuning parameters
    02 Adaptive tuning parameters
    H003 Motor capacity, 1st motor 0.2 – 75,
    0.2 – 160kW, up to –550xxx models
    kW, –750xxx to –1500xxx models
    H004 Motor poles setting, 1st motor 2 / 4 / 6 / 8 Units: poles
    H020 Motor constant R1, 1st  motor 0.000–65.53 Units: ohms
    H021 Motor constant R2, 1st  motor 0.000–65.53 Units: ohms
    H022 Motor constant L, 1s t motor 0.00–655.3 Units: mH
    H023 Motor constant Io, 1s t motor 0.00–655.3 Units: A
    H024 Motor constant J, 1st motor 0.001–9999
    Units: kgm
    2
    H030 Auto-tuned constant R1, 1st motor 0.000–65.53 Units: ohms
    
    Phone: 800.894.0412   
    						
    All Hitachi manuals Comments (0)