Hitachi Sj7002 Owners Manual
Have a look at the manual Hitachi Sj7002 Owners Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 913 Hitachi manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
Troubleshooting Troubleshooting and Maintenance 6–4 The motor speed will not reach the target frequency (desired speed). • If using the analog input, is there current or voltage at [O] or [OI]? • Check the wiring. • Check the potentiometer or signal generating device. • Is the load too heavy? •Reduce the load. • Heavy loads activate the overload restriction feature (reduces output as needed). • Is the inverter internally limiting the output frequency? • Check max frequency setting (A004) • Check frequency upper limit setting (A061) •If using analog inputs, check their settings (A101– A104) or (A111–A114), or (A011–A014) The rotation is unstable. • Is the load fluctuation too great? • Is the supply voltage unstable? • Is the problem occurring at a particular frequency? • Increase the motor capacity (both inverter and motor). • Fix power supply problem. • Change the ou tput frequency slightly, or use the jump frequency setting to skip the problem frequency. The RPM of the motor does not match the inverter output frequency setting. • Is the maximum frequency setting A004 correct? • Does the monitor function D001 display the expected output frequency? • Verify the V/F settings match motor specifications. • Make sure all scaling (such as A011 to A014) is properly set. A parameter will not change after an edit (reverts to old setting). True for certain parameters • Is the inverter in Run Mode? Some parameters cannot be edited during Run Mode. • Put inverter in Stop Mode (press the Stop/reset key). Then edit the parameter. True for all parameters • If you’re using the [SFT] intelligent input (software lock function)—is the [SFT] input ON? • Change the state of the SFT input, and check the B031 parameter (SFT mode). Symptom/conditionProbable CauseSolution Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
SJ7002 Inverter Troubleshooting and Maintenance 6–5 Monitoring Trip Events, History, & Conditions Fault Detection and ClearingThe microprocessor in the inverter detects a variety of fault conditions and captures the event, recording it in a history ta ble. The inverter output turns OFF, or “trips” similar to the way a circuit breaker trips due to an over-current condition. Most faults occur when the motor is running (refer to the diagram to the right). However, the inverter could have an internal fault and trip in Stop Mode. In either case, you can clear the fault by pressing the Stop/Reset key. Additionally, you can clear the inverter’s cumulative trip hi story by performing the procedure “ Restoring Factory Default Settings” on page 6–16 (setting B_84=00 will clear the trip history but leave inverter settings intact). Error Status CodesThe conditions at the time of an error provide important clues to help you understand the cause. The SJ700 2 inverter displays a “status at trip point” digit to the right of the decimal point for some error codes. For example, E07.2 means Error 7 occurred and the inverter status was condition # “2” when the error occurred. Run Stop Fault Tr i pFaultRUN STOPRESET STOPRESET Status CodesInverter StatusStatus CodesInverter Status ---.0Reset---.5Run Command active with 0 Hz speed reference ---. 1Stop---.6Starting ---.2Deceleration---.7DC braking ---.3Constant speed---.8Overload restriction ---.4Acceleration---.9SON or FOC operation in progress Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Monitoring Trip Events, History, & Conditions Troubleshooting and Maintenance 6–6 Error CodesAn error code will appear on the display automati cally when a fault causes the inverter to trip. The following table lists the cause associated with the error. OPE / SRW DisplayNameDescriptionTroubleshooting and Corrective Action E0 1.-Over-current protection If the motor is constrained or suddenly accelerated or decelerated, a high current will flow in the inverter and the inverter may fail. To avoid this problem, the inverter shuts off its output and displays the error code shown on the left when it detects a current higher than a specified level. This protective function uses a DC current detector (CT) to detect over-current. When a current as high as about 220% of the inverters rated output current is detected, the protective circuit operates and the inverter trips. During constant speed operation•Check whether the load has fluctuated sharply. •Check for the short circuit of output connections (check the output cables). •Check for a ground fault (check the output cables and motor). OC.Drive E02.-Over-current protection During deceleration•Check whether the inverter has deceler- ated the motor quickly increase the decel- eration time). OC.Decel E03.-Over-current protection During acceleration•Check whether the inverter has acceler- ated the motor quickly (increase the acceleration time). •Check whether the motor has been locked (check the motor and wiring). •Check whether the to rque boost current has been set too high (reduce the boost current). OC.Accel E04.-Over-current protection Other conditions•Check whether the DC braking force is too high (reduce the braking force). •Check whether the current detector (CT) is normal (replace or repair the CT). Over.C E05.-Overload protection (*1) (*4) This protective function monitors the inverter output current, and shuts off the inverter output and di splays the error code shown on the left when the internal electronic thermal protection circuit detects a motor overload. If the error occurs, the inverter wi ll trip according to the setting of the electronic thermal function.•Check whether the motor load is too high. (reduce the load factor). •Check whether the thermal level is appro- priate (adjust the le vel appropriately). Note: The electronic thermal protection is easily triggered when the output frequency is 5 Hz or less. If the moment of inertia of the load is large, this protective function may operate when the inverter accelerates the motor and the acceleration may be disabled. If this problem occurs, increase the torque boost current or adjust other settings as needed. OL.BRD E06.-Braking resistor overload protection When the BRD operation rate exceeds the setting of B090, this protective function shuts off the inverter output and displays the error code shown on the left.•Check whether the inverter has decreased the motor quickly (inc rease the decelera- tion time). •Check whether the operation cycle is too short (prolong the operation cycle) •Check whether the set BRD operation rate is too low (adjust the setting to an appropriate level). Note: Confirm the maximum allowable capacity of the resistor. OL.BRD Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
SJ7002 Inverter Troubleshooting and Maintenance 6–7 Note 1: The inverter will not accept any reset command within about 90 seconds after tripping (i.e., after the prot ective function operates). Be sure to turn OFF the input power supply after waiting two minutes for cooling. Note 2: The inverter will not accept any reset co mmand after an EEPROM error occurs with error code displayed. Turn off the inverter power once. If error code E08 is displayed when the inverter power is turned on subs equently, the internal memory device may have failed or parameters may have not been stored correctly. In such cases, initialize the inverter, and then reset the parameters. Note 3: The inverter will not accept reset commands input via the RS terminal or entered by the STOP/RESET key. Therefore, turn off the inverter power. Note 4: Be sure to reduce the inverter’s output current and the motor load before restarting after overload protection (E05). If the cont inuous reset/restart operations for error E05 could cause damage to the inverter. NOTE: If an EEPROM error E08 occurs, be sure to confirm the parameter data values are still correct. E07.-Over-voltage protectionIf the DC voltage across the P and N terminals rises too high, an inverter failure may result. To avoid this problem, this protective function shuts off the inverter output and displays the error code shown on the left when the DC voltage across the P and N terminals exceeds a specified level because of an increase in the energy regenerated by the motor or the input voltage (dur ing operation). The inverter will trip if the DC voltage across the P and N terminals exceeds about 400 VDC (in case of the 200 V class models) or about 800 VDC (in case of the 400 V class models).•Check whether the inverter has decreased the motor quickly (inc rease the decelera- tion time). •Check for a ground fault (check the output cables and motor). •Check whether the moto r has been rotated by the action of th e load (reduce the regenerative energy). Over.V E08.-EEPROM error (*2) (*3) When an internal-EEPROM is caused by external noise or an abnormal temperature rise, the inverter shuts off its output and displays the error code shown on the left. Note: An EEPROM error may result in a CPU error.•Check for the noise sources located near the inverter (remove noise sources). •Check whether the cooling efficiency has deteriorated (check the heat sink for clogging and clean it). •Check the cooling fan (replace if needed). EEPROM E09.-Under-voltage If the inverter input voltage drops, the control circuit of the inverter cannot function normally. Ther efore, the inverter shuts off its output wh en the input voltage falls below a specified level. The inverter will trip if the DC voltage across the P and N terminals exceeds about 175 VDC (in case of the 200 V class models) or about 345 VDC (in case of the 400 V class models).•Check whether the power supply voltage has dropped (check the power supply). •Check whether the power supply capacity is sufficient (check the power supply). •Check whether the thyristor has been damaged (check the thyristor). Under.V E 10.-CT error If an erro r occurs in the internal current detector (CT), the inverter will shut off its output and display the error code shown on the left. The inverter will trip when the CT outputs about 0.6 V or more at power-on.•Check whether the inverter has failed (repair the inverter). CT OPE / SRW DisplayNameDescriptionTroubleshooting and Corrective Action Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Monitoring Trip Events, History, & Conditions Troubleshooting and Maintenance 6–8 Note 5: The inverter will not accept reset commands input via the [RS] terminal or entered by the STOP/RESET key. Therefore, turn off the inverter power. OPE / SRW DisplayNameDescriptionTroubleshooting and Corrective Action E 1 1.-CPU error (*5) If the internal CPU malfunctions or an error occurs in it, the inverter will shut OFF its output and display the error code shown on the left. Note: Reading abnormal data from the EEPROM may result in a CPU error.•Check for the noise sources located near the inverter (remove noise sources). •Check whether the inverter has failed (repair the inverter). CPU E 12.-External trip If an error occurs in the external equip- ment or device connected to the inverter, the inverter will latch the error signal and shut off its output. (This protective function is active when the external trip function is enabled.)•If the inverter’s external trip function is enabled, check whether an error has occurred in external equipment (clear the error in the external equipment). EXTERNAL E 13.-USP error A USP error is indicated when the inverter power is turn ed on with an input operation signal remaining in the inverter. (This protective function is active when the USP function is enabled.)•If the USP function has been enabled, check whether the inverter power has been turned on with an input operation signal remaining in th e inverter (reset the operation command, and then turn ON the inverter power). USP E 14.-Ground fault protection (*5) When the inverter power is turned ON, this protective function detects the ground fault between the inve rter output circuit and the motor to protec t the inverter. (This function does not operate when a residual voltage remains in the motor.)•Check for the ground fault (check the output cables and motor). •Check the inverter itself for abnormality (remove the output cables from the inverter, and then check the inverter). •Check the main circ uit for abnormality (use testing methods described in this chapter and repair the inverter). GND.Flt E 15.-Input over- voltage protection This protective function determines an error if the input volta ge is kept above the specification level fo r 100 seconds while the inverter is stopp ed. The inverter will trip if the DC voltage of the main circuit is kept above about 390 VDC (in case of the 200 V class models) or about 780 VDC (in case of the 400 V class models).•Check whether the input voltage is high while the inverter is stopped (lower the input voltage, suppress the power voltage fluctuation, or connect an AC reactor between the power supply and the inverter input.) OV.SRC E 16.-Instantaneous power failure protection If an instantaneous power failure lasts 15 ms or more, the inverter will shut off its output. When the power failure duration is long, the inverter assumes a normal power-OFF. If a restart mode has been selected and an operation command remains in the inverter, the inverter will restart after the power is recovered.•Check whether the power supply voltage has dropped (recover the power supply). •Check the MCB and magnetic contactors for poor contacts (replace the MCB and the magnetic contactor). Inst.P-F E20.-Temperature error due to low cooling- fan speed The inverter will display the error code shown on the left if the lowering of cooling fan speed is detected at the occur- rence of the temperat ure error described below.•Check whether the cooling efficiency has been lowered (replace the cooling fan). •Check the heat sink for clogging (clean the heat sink). OH.stFAN E2 1.-Temperature error If the main circuit temperature rises because of a high ambient temperature or for other reasons, the inverter will shut OFF its output.•Check whether the inverter is installed vertically (check the installation.) •Check whether the ambient temperature is high (lower the ambient temperature). OH.fin Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
SJ7002 Inverter Troubleshooting and Maintenance 6–9 OPE / SRW DisplayNameDescriptionTroubleshooting and Corrective Action E23.-Gate array communica- tion error If an error occurs in the communication between the internal CPU and gate array, the inverter will trip.•Check for the noise sources located near the inverter (remove noise sources). •Check whether the communication cable has been disconnected (check the connec- tors). GA.COM E24.-Phase loss input protec- tion When the phase loss input protection has been enabled (B006 = 01), the inverter will trip to avoid dama ge if an phase loss input is detected. The inverter trips when the phase loss input continues for about 1 second or more.•Check for the phase loss power input. (check the power supply input wiring). •Check the MCB and ma gnetic contactors for poor contacts (replace the MCB and magnetic contactors). PH.fail E25.-Main circuit error (*6) The inverter will trip if the gate array cannot confirm the ON/OFF state of IGBT because of a malfunction due to noise, short or damage to the main circuit element.•Check for the noise sources located near the inverter (remove noise sources.) •Check the main circuit element for damage. Check the output circuit for a short circuit (check the IGBT). •Check the inverter fo r abnormality (repair the inverter). Main.Cir E30.-IGBT error (*7) If instantaneous over-c urrent occurs, the main circuit elemen t temperature is abnormal, or the ma in circuit element drive power drops, the inverter will turn OFF its output to protect the main circuit element. (After tripping because of this protective function, the inverter cannot retry the operation.)•Check the output circuit for a short circuit (check the output cables). •Check for the ground fault (check the output cables and motor). •Check the main circuit element for damage (check the IGBT). •Check the heat sink for clogging (clean the heat sink). IGBT E35.-Thermistor error The inverter monitors the resistance of the thermistor (in the motor) connected to the inverter’s [TH] terminal, and will turn OFF the inverter output if the motor temperature rises.•Check whether the motor temperature is high (check the motor temperature). •Check whether the internal thermistor of the motor has been damaged (check the thermistor). •Check whether noise has been mixed in the thermistor signal (separate the therm- istor wiring from other wirings). TH E36.-Braking error When “01” has been specified for B120 Brake Control Enable, the inverter will trip if it cannot receive the braking confir- mation signal within B124 Brake Wait Time for Confirmation after the output of the brake release signal.•Check whether the brake has been turned on and off or not (check the brake). •Check whether the wait time (B124) is too short (increase the wait time B124). •Check whether the braking confirmation signal has been input (check the wiring). BRAKE E37.-Emergency stop (*8) If the EMR signal (on three terminals) is turned ON when the slide switch (SW1) on the logic board is set to ON, the inverter hardware will turn OFF the inverter output and display the error code shown on the left. The malfunction is due to incoming noise when EMR terminal is not ON.•Check whether an e rror has occurred in the external equipment since the emergency stop function was enabled. (recover the external equipment from the error.) •Check for the noise sources located near the inverter (remove noise sources). EMR E38.-Low-speed overload protection If overload occurs during the motor operation at a very low speed at 0.2 Hz or less, the electronic thermal protection circuit in the inverter will detect the overload and shut off the inverter output (2nd electronic thermal control). Note: A high frequency may be recorded as the error history data.•Check whether the motor load is too high (reduce the load factor). OL-LowSP Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Monitoring Trip Events, History, & Conditions Troubleshooting and Maintenance 6–10 Note 6: The inverter will not accept reset commands input via the RS terminal or entered by the STOP/RESET key. Therefore, turn off the inverter power. Note 7: The inverter applied for 004 to 110L/H will not accept reset commands input via the RS terminal or entered by the STOP/RESET key. Therefore, turn off the inverter power. Note 8: The inverter will not accept the reset co mmand entered from the digital operator. Therefore, reset the inverter by turning on the RS terminal. NOTE: If an EEPROM error (E08) occurs, be sure to confirm the parameter data values are still correct. E41.-ModBus communica- tion errorIf time-out occurs because of line discon- nection during the communication in ModBus-RTU mode, the inverter will display the error code shown on the left. (The inverter will trip according to the setting of C076.)•Check whether the communication speed setting is correct. •Check whether the wiring distance is appropriate (check the connections). NET.ERR E60.- to E69.-Option 1 error The inverter de tects errors in the option board mounted in the optional slot 1. For details, refer to the instruction manual for the mounted option board.•Check whether the option board is mounted correctly (check the board mounting). •Check whether the option board is used correctly (refer to th e instruction manual for the option board SJ-FB, SJ-DG, or SJ-DN). OP1-0 OP1-9 OPE / SRW DisplayNameDescriptionTroubleshooting and Corrective Action Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
SJ7002 Inverter Troubleshooting and Maintenance 6–11 Expansion Card Error CodesThe inverter monitors the operation of the expansion cards (optional) that may be installed in the expansion bay. On the inverter’s digital operator, error codes in the E60 range refer to the upper card position. Error codes in the E70 range refer to the lower card position. For the remote operator display, error codes are in the OP1 or OP2 ranges, respectively. If an error occurs, the inverter trips (displays the corresponding error code and turns OFF the motor output). Encoder Input Card – Use the following table to diagnose errors caused by an encoder input expansio n card. Each error will cause the inverter to trip, turning OF F its output and displaying an error code. If an encoder expansion card does not operate normally, use the following table to check the DIP switch settings on the card. Encoder Input Expansion Card Errors Error Code: OPE / SRWNameProbable Cause(s) E60.- E70.-Encoder disconnect Encoder wiring to the expansion card is disconnected OP1-0 OP2-0The encoder is faulty The encoder type is not correct (no line driver output, etc.) E6 1.- E7 1.-Excessive speed The motor speed increased to the maximum frequency (A004) times the over-speed error detection level (P026) OP1-1 OP2-1 E62.- E72.-Positioning error While in position control mode the position error (command minus actual) reached 1,000,000 pulses or more OP1-2 OP2-2 E63.- E73.-Position control range tripWhile in absolute position control mode, the actual position exceeded the forward (P072) or reverse (P073) position range value OP1-3 OP2-3 E69.- E79.-SJ-FB connection errorThe SJ-FB expansion ca rd is not mounted properly or the card is faulty OP1-9 OP2-9 DIP SwitchSwitch NumberSetting SWENC 1 ON setting enables encoder disc onnect function for loss of A or B channel 2 ON setting enables encoder disc onnect function for loss of Z channel SWR 1 ON setting connects the 150 Ω termination resistor across terminals [SAP] and [SAN] 2 ON setting connects the 150 Ω termination resistor across terminals [SBP] and [SBP] E6x or OP1 Error range: E7x or OP2 Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Monitoring Trip Events, History, & Conditions Troubleshooting and Maintenance 6–12 Digital Input Card – Use the following table to diagnose errors caused by a digital input expansion card. Each error will cause the inverter to trip, turning OFF its output and displaying an error code. The input mode is determined by a combination of DIP switch and rotary switch settings. If the expansion card does not operate normally, use the following table to check the DIP switch and rotary switch settings. The check marks indicate input modes specified by switch settings. For more details, refer to the expansion card instruction manual. Digital Input Expansion Card Errors Error Code: OPE / SRWNameProbable Cause(s) E60.- E70.-Digital input expansion card error A communications time-out between the inverter and the digital input card has occurred OP1-0 OP2-0 DIP SwitchRotary SwitchFrequency Setting, HzAccel / Decel Time, SecondsTorque limit SettingPosition Setting 12Code0.010.11Rate0.010.111%1 pulse OFF: BIN (binary input) / ON: BCD (binary coded decimal input) OFF: PAC (batch input mode) 0 1 2 3 4 ✔ 5 6 ✔ ON: DIV (divided input mode 0 ✔✔✔✔ 1 ✔ 2 ✔ 3 ✔✔ 4 ✔ 5 ✔ 6 ✔✔ 7 ✔ 8 ✔ 9 ✔✔ A ✔ B ✔ Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
SJ7002 Inverter Troubleshooting and Maintenance 6–13 DeviceNet Expansion Card – Use the following table to diagnose errors caused by a DeviceNet expansion card. Each er ror will cause the inverter to trip (according to parameter settings P045 and P048), turning OFF it s output and displaying an error code. If the expansion card does not operate normally, use the following diagrams to check the DIP switch settings. For more details, refer to the expansion card instruction manual. DeviceNet Expansion Card Errors Error Code: OPE / SRWNameProbable Cause(s) E60.- E70.-DeviceNet Communication ErrorThe communication speed may be incorrect OP1-0 OP2-0The network wiring length may not be appropriate A connector is loose (or wire not connected) E6 1.- E7 1.-Duplicate MAC ID Two or more devices on the network have the same MAC ID OP1-1 OP2-1 E62.- E72.-External trip Check the Force Fault/Trip bit. Attribute 17 in the Instance 1 of Class 19 may be set to 1. If so, clear the bit to 0. OP1-2 OP2-2 E69.- E79.-Inverter communication error The expansion card may not be properly connected to the inverter OP1-9 OP2-9 DR1 DR0DRDR1 DR0DRDR1 DR0DR 125 kbps250 kbps500 kbps DeviceNet Baud Rate Setting MAC ID DIP switch example DeviceNet MAC ID Setting NA32 NA16 NA8 NA4 NA2 NA1 Description of switch setting 543210 = 29h (hex) = 41 (decimal) Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]