Home > Hitachi > Inverter > Hitachi Sj7002 Owners Manual

Hitachi Sj7002 Owners Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Hitachi Sj7002 Owners Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 913 Hitachi manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							Troubleshooting
    Troubleshooting
    and Maintenance
    6–4
    The motor speed will not reach  the target frequency (desired 
    speed). •
    If using the analog input, is there 
    current or voltage at [O] or [OI]? •
    Check the wiring.
    • Check the potentiometer or signal 
    generating device.
    • Is the load too heavy? •Reduce the load.
    • Heavy loads activate the overload 
    restriction feature  (reduces output as 
    needed).
    • Is the inverter internally limiting the 
    output frequency? •
    Check max frequency setting 
    (A004)
    •
    Check frequency upper limit 
    setting (A061)
    •If using analog inputs, check 
    their settings (A101– A104) or 
    (A111–A114), or (A011–A014)
    The rotation is unstable. •
    Is the load fluctuation too great?
    • Is the supply voltage unstable?
    • Is the problem occurring at a particular 
    frequency? •
    Increase the motor capacity (both 
    inverter and motor).
    • Fix power supply problem.
    • Change the ou tput frequency 
    slightly, or use the jump frequency 
    setting to skip the problem 
    frequency.
    The RPM of the motor does not  match the inverter output 
    frequency setting. •
    Is the maximum  frequency setting 
    A004 correct?
    • Does the monitor function D001 
    display the expected output frequency? •
    Verify the V/F settings match motor 
    specifications.
    • Make sure all scaling (such as A011 
    to A014) is properly set.
    A parameter  will not 
    change after  an edit 
    (reverts to 
    old setting). True for certain 
    parameters
    •
    Is the inverter in Run Mode? Some 
    parameters cannot be edited during 
    Run Mode. •
    Put inverter in Stop Mode (press the 
    Stop/reset key). Then edit the 
    parameter.
    True for all 
    parameters •
    If you’re using the [SFT] intelligent 
    input (software lock function)—is the 
    [SFT] input ON? •
    Change the state of the SFT input, 
    and check the B031 parameter (SFT 
    mode).
    Symptom/conditionProbable CauseSolution
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Troubleshooting
    and Maintenance
    6–5
    Monitoring Trip Events, History, & Conditions
    Fault Detection 
    and ClearingThe microprocessor in the inverter detects a 
    variety of fault conditions and captures the event, 
    recording it in a history ta ble. The inverter output 
    turns OFF, or “trips” similar to the way a circuit 
    breaker trips due to an over-current condition. 
    Most faults occur when the motor is running (refer 
    to the diagram to the right). However, the inverter 
    could have an internal fault and trip in Stop Mode. 
    In either case, you can clear the fault by pressing 
    the Stop/Reset key. Additionally, you can clear the 
    inverter’s cumulative trip hi story by performing the procedure  “
    Restoring Factory Default 
    Settings” on page 6–16 (setting B_84=00 will clear the trip  history but leave inverter settings 
    intact).
    Error Status 
    CodesThe conditions at the time of an error provide  important clues to help you understand the cause. 
    The SJ700
    2 inverter displays a “status at trip point”  digit to the right of the decimal point for 
    some error codes. For example, 
    E07.2 means Error 7 occurred and  the inverter status was 
    condition # “2” when the error occurred.
    Run Stop
    Fault Tr i pFaultRUN
    STOPRESET
    STOPRESET
    Status 
    CodesInverter StatusStatus CodesInverter Status
    ---.0Reset---.5Run Command active with 0 Hz 
    speed reference
    ---. 1Stop---.6Starting
    ---.2Deceleration---.7DC braking
    ---.3Constant speed---.8Overload restriction
    ---.4Acceleration---.9SON or FOC operation in 
    progress
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							Monitoring Trip Events, History, & Conditions
    Troubleshooting
    and Maintenance
    6–6
    Error CodesAn error code will appear on the display automati cally when a fault causes the inverter to trip. 
    The following table lists the cause associated with the error.
    OPE / SRW 
    DisplayNameDescriptionTroubleshooting and Corrective Action
    E0 1.-Over-current protection If the motor is constrained 
    or suddenly accelerated or 
    decelerated, a high current 
    will flow in the inverter 
    and the inverter may fail. 
    To avoid this problem, the 
    inverter shuts off its output 
    and displays the error code 
    shown on the left when it 
    detects a current higher 
    than a specified level. This 
    protective function uses a 
    DC current detector (CT) 
    to detect over-current. 
    When a current as high as 
    about 220% of the 
    inverters rated output 
    current is detected, the 
    protective circuit operates 
    and the inverter trips. During 
    constant 
    speed 
    operation•Check whether the load has fluctuated 
    sharply.
    •Check for the short circuit of output 
    connections (check the output cables).
    •Check for a ground fault (check the 
    output cables and motor).
    OC.Drive
    E02.-Over-current 
    protection During 
    deceleration•Check whether the inverter has deceler-
    ated the motor quickly increase the decel-
    eration time).
    OC.Decel
    E03.-Over-current 
    protection During 
    acceleration•Check whether the inverter has acceler-
    ated the motor quickly (increase the 
    acceleration time).
    •Check whether the motor has been locked 
    (check the motor and wiring).
    •Check whether the to
    rque boost current 
    has been set too high (reduce the boost 
    current).
    OC.Accel
    E04.-Over-current 
    protection Other 
    conditions•Check whether the DC braking force is 
    too high (reduce the braking force).
    •Check whether the current detector (CT) 
    is normal (replace or repair the CT).
    Over.C
    E05.-Overload 
    protection
    (*1) (*4) This protective function monitors the 
    inverter output current, and shuts off the 
    inverter output and di
    splays the error code 
    shown on the left when the internal 
    electronic thermal protection circuit 
    detects a motor overload. If the error 
    occurs, the inverter wi ll trip according to 
    the setting of the electronic thermal 
    function.•Check whether the motor load is too high. 
    (reduce the load factor).
    •Check whether the thermal level is appro-
    priate (adjust the le vel appropriately).
    Note: The electronic thermal protection is 
    easily triggered when  the output frequency is 
    5 Hz or less. If the moment of inertia of the 
    load is large, this  protective function may 
    operate when the inverter accelerates the 
    motor and the acceleration may be disabled. 
    If this problem occurs,  increase the torque 
    boost current or adjust other settings as 
    needed.
    OL.BRD
    E06.-Braking 
    resistor 
    overload 
    protection
    When the BRD operation rate exceeds the 
    setting of B090, this protective function 
    shuts off the inverter output and displays 
    the error code shown on the left.•Check whether the inverter has decreased 
    the motor quickly (inc
    rease the decelera-
    tion time).
    •Check whether the operation cycle is too 
    short (prolong the  operation cycle)
    •Check whether the set BRD operation 
    rate is too low (adjust the setting to an 
    appropriate level).
    Note: Confirm the maximum allowable 
    capacity of the resistor.
    OL.BRD
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Troubleshooting
    and Maintenance
    6–7
    Note 1: The inverter will not accept any reset  command within about 90 seconds after 
    tripping (i.e., after the prot ective function operates). Be  sure to turn OFF the input 
    power supply after waiting  two minutes for cooling.
    Note 2: The inverter will not accept any reset co mmand after an EEPROM error occurs with 
    error code displayed. Turn off the inverter  power once. If error code E08 is displayed 
    when the inverter power is turned on subs equently, the internal memory device may 
    have failed or parameters may have not been  stored correctly. In such cases, initialize 
    the inverter, and then reset the parameters.
    Note 3: The inverter will not accept reset commands input via the RS terminal or entered by 
    the STOP/RESET key. Therefore, turn off the inverter power.
    Note 4: Be sure to reduce the inverter’s output  current and the motor load before restarting 
    after overload protection (E05). If the cont inuous reset/restart operations for error 
    E05 could cause damage  to the inverter.
    NOTE: If an EEPROM error E08 occurs, be sure to  confirm the parameter data values are still 
    correct.
    E07.-Over-voltage 
    protectionIf the DC voltage across the P and N 
    terminals rises too high, an inverter 
    failure may result. To avoid this problem, 
    this protective function shuts off the 
    inverter output and displays the error code 
    shown on the left when the DC voltage 
    across the P and N terminals exceeds a 
    specified level because 
    of an increase in 
    the energy regenerated by the motor or 
    the input voltage (dur ing operation). The 
    inverter will trip if the DC voltage across 
    the P and N terminals exceeds about 400 
    VDC (in case of the 200 V class models) 
    or about 800 VDC (in case of the 400 V 
    class models).•Check whether the inverter has decreased 
    the motor quickly (inc rease the decelera-
    tion time).
    •Check for a ground fault (check the 
    output cables and motor).
    •Check whether the moto r has been rotated 
    by the action of th e load (reduce the 
    regenerative energy).
    Over.V
    E08.-EEPROM 
    error
    (*2) (*3)
    When an internal-EEPROM is caused by 
    external noise or an abnormal temperature 
    rise, the inverter shuts off its output and 
    displays the error code shown on the left.
    Note:
     An EEPROM error may result in a
    CPU error.•Check for the noise sources located near 
    the inverter (remove noise sources).
    •Check whether the cooling efficiency has 
    deteriorated (check the heat sink for 
    clogging and clean it).
    •Check the cooling fan (replace if needed).
    EEPROM
    E09.-Under-voltage If the inverter input voltage drops, the 
    control circuit of the inverter cannot 
    function normally. Ther efore, the inverter 
    shuts off its output wh en the input voltage 
    falls below a specified level. The inverter 
    will trip if the DC voltage across the P 
    and N terminals exceeds about 175 VDC 
    (in case of the 200 V class models) or 
    about 345 VDC (in case of the 400 V 
    class models).•Check whether the power supply voltage 
    has dropped (check the power supply).
    •Check whether the power supply capacity 
    is sufficient (check  the power supply).
    •Check whether the thyristor has been 
    damaged (check the thyristor).
    Under.V
    E 10.-CT error If an erro
    r occurs in the internal current 
    detector (CT), the inverter will shut off its 
    output and display the error code shown 
    on the left. The inverter will trip when the 
    CT outputs about 0.6 V or more at 
    power-on.•Check whether the inverter has failed 
    (repair the inverter).
    CT
    OPE / SRW 
    DisplayNameDescriptionTroubleshooting and Corrective Action
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							Monitoring Trip Events, History, & Conditions
    Troubleshooting
    and Maintenance
    6–8
    Note 5: The inverter will not accept reset commands  input via the [RS] terminal or entered by 
    the STOP/RESET key. Therefore, turn off the inverter power.
    OPE / SRW 
    DisplayNameDescriptionTroubleshooting and Corrective Action
    E 1 1.-CPU error (*5) If the internal CPU malfunctions or an  error occurs in it, the inverter will shut 
    OFF its output and display the error code 
    shown on the left.
    Note: Reading abnormal data from the 
    EEPROM may result in a CPU error.•Check for the noise sources located near 
    the inverter (remove noise sources).
    •Check whether the inverter has failed 
    (repair the inverter).
    CPU
    E 12.-External trip If an error occurs in the external equip-
    ment or device connected to the inverter, 
    the inverter will latch the error signal and 
    shut off its output. (This protective 
    function is active when the external trip 
    function is enabled.)•If the inverter’s external trip function is 
    enabled, check whether an error has 
    occurred in external equipment (clear the 
    error in the external equipment).
    EXTERNAL
    E 13.-USP error A USP error is
     indicated when the 
    inverter power is turn ed on with an input 
    operation signal remaining in the inverter. 
    (This protective function is active when 
    the USP function is enabled.)•If the USP function  has been enabled, 
    check whether the inverter power has 
    been turned on with an input operation 
    signal remaining in th e inverter (reset the 
    operation command, and then turn ON the 
    inverter power).
    USP
    E 14.-Ground fault 
    protection (*5)
    When the inverter power is turned ON, 
    this protective function detects the ground 
    fault between the inve
    rter output circuit 
    and the motor to protec t the inverter. (This 
    function does not operate when a residual 
    voltage remains in the motor.)•Check for the ground fault (check the 
    output cables and motor).
    •Check the inverter itself for abnormality 
    (remove the output cables from the 
    inverter, and then check the inverter).
    •Check the main circ uit for abnormality 
    (use testing methods described in this 
    chapter and repair the inverter).
    GND.Flt
    E 15.-Input over-
    voltage 
    protection
    This protective function determines an 
    error if the input volta
    ge is kept above the 
    specification level fo r 100 seconds while 
    the inverter is stopp ed. The inverter will 
    trip if the DC voltage  of the main circuit 
    is kept above about 390 VDC (in case of 
    the 200 V class models) or about 780 
    VDC (in case of the 400 V class models).•Check whether the input voltage is high 
    while the inverter is stopped (lower the 
    input voltage, suppress the power voltage 
    fluctuation, or connect an AC reactor 
    between the power supply and the inverter 
    input.)
    OV.SRC
    E 16.-Instantaneous 
    power failure 
    protection
    If an instantaneous power failure lasts 
    15 ms or more, the inverter will shut off 
    its output. When 
    the power failure 
    duration is long, the inverter assumes a 
    normal power-OFF. If a restart mode has 
    been selected and an operation command 
    remains in the inverter, the inverter will 
    restart after the power is recovered.•Check whether the power supply voltage 
    has dropped (recover the power supply).
    •Check the MCB and magnetic contactors 
    for poor contacts (replace the MCB and 
    the magnetic contactor).
    Inst.P-F
    E20.-Temperature 
    error due to 
    low cooling-
    fan speed The inverter will display the error code 
    shown on the left if the lowering of 
    cooling fan speed is detected at the occur-
    rence of the temperat
    ure error described 
    below.•Check whether the cooling efficiency has 
    been lowered (replace the cooling fan).
    •Check the heat sink for clogging (clean 
    the heat sink).
    OH.stFAN
    E2 1.-Temperature 
    error
    If the main circuit temperature rises 
    because of a high ambient temperature or 
    for other reasons, the inverter will shut 
    OFF its output.•Check whether the inverter is installed 
    vertically (check 
    the installation.)
    •Check whether the ambient temperature 
    is high (lower the ambient temperature).
    OH.fin
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Troubleshooting
    and Maintenance
    6–9
    OPE / SRW 
    DisplayNameDescriptionTroubleshooting and Corrective Action
    E23.-Gate array 
    communica-
    tion error If an error occurs in the communication 
    between the internal CPU and gate array, 
    the inverter will trip.•Check for the noise sources located near 
    the inverter (remove noise sources).
    •Check whether the communication cable 
    has been disconnected (check the connec-
    tors).
    GA.COM
    E24.-Phase loss 
    input protec-
    tion
    When the phase loss 
    input protection has 
    been enabled (B006 = 01), the inverter 
    will trip to avoid dama ge if an phase loss 
    input is detected. The inverter trips when 
    the phase loss input  continues for about 
    1 second or more.•Check for the phase loss power input. 
    (check the power supply input wiring).
    •Check the MCB and ma gnetic contactors 
    for poor contacts (replace the MCB and 
    magnetic contactors).
    PH.fail
    E25.-Main circuit 
    error (*6)
    The inverter will trip if the gate array 
    cannot confirm the ON/OFF state of 
    IGBT because of a malfunction due to 
    noise, short or damage to the main circuit 
    element.•Check for the noise sources located near 
    the inverter (remove noise sources.)
    •Check the main circuit element for 
    damage. Check the output circuit for a 
    short circuit (check the IGBT).
    •Check the inverter fo
    r abnormality (repair 
    the inverter).
    Main.Cir
    E30.-IGBT error 
    (*7)
    If instantaneous over-c
    urrent occurs, the 
    main circuit elemen t temperature is 
    abnormal, or the ma in circuit element 
    drive power drops, the inverter will turn 
    OFF its output to protect the main circuit 
    element. (After tripping because of this 
    protective function, the inverter cannot 
    retry the operation.)•Check the output circuit for a short circuit 
    (check the output cables).
    •Check for the ground fault (check the 
    output cables and motor).
    •Check the main circuit element for 
    damage (check the IGBT).
    •Check the heat sink for clogging (clean 
    the heat sink).
    IGBT
    E35.-Thermistor 
    error
    The inverter monitors 
    the resistance of the 
    thermistor (in the motor) connected to the 
    inverter’s [TH] terminal, and will turn 
    OFF the inverter output if the motor 
    temperature rises.•Check whether the motor temperature is 
    high (check the motor temperature).
    •Check whether the internal thermistor of 
    the motor has been damaged (check the 
    thermistor).
    •Check whether noise has been mixed in 
    the thermistor signal (separate the therm-
    istor wiring from other wirings).
    TH
    E36.-Braking error When “01” has been specified for B120 
    Brake Control Enable, the inverter will 
    trip if it cannot receive the braking confir-
    mation signal within B124 Brake Wait 
    Time for Confirmation  after the output of 
    the brake release signal.•Check whether the brake has been turned 
    on and off or not (check the brake).
    •Check whether the wait time (B124) is 
    too short (increase the wait time B124).
    •Check whether the braking confirmation 
    signal has been input (check the wiring).
    BRAKE
    E37.-Emergency 
    stop (*8)
    If the EMR signal (on three terminals) is 
    turned ON when the slide switch (SW1) 
    on the logic board is set to ON, the 
    inverter hardware will turn OFF the 
    inverter output and display the error code 
    shown on the left. The malfunction is due 
    to incoming noise when EMR terminal is 
    not ON.•Check whether an e
    rror has occurred in 
    the external equipment since the 
    emergency stop function was enabled. 
    (recover the external equipment from the 
    error.)
    •Check for the noise sources located near 
    the inverter (remove noise sources).
    EMR
    E38.-Low-speed 
    overload 
    protection
    If overload occurs during the motor 
    operation at a very low speed at 0.2 Hz or 
    less, the electronic
     thermal protection 
    circuit in the inverter will detect the 
    overload and shut off the inverter output 
    (2nd electronic thermal control).
    Note:  A high frequency  may be recorded 
    as the error history data.•Check whether the motor load is too high 
    (reduce the load factor).
    OL-LowSP
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							Monitoring Trip Events, History, & Conditions
    Troubleshooting
    and Maintenance
    6–10
    Note 6: The inverter will not accept  reset commands input via the RS terminal or entered by 
    the STOP/RESET key. Therefore, turn off the inverter power.
    Note 7: The inverter applied for 004 to 110L/H will  not accept reset commands input via the 
    RS terminal or entered by the STOP/RESET key. Therefore, turn off the inverter 
    power.
    Note 8: The inverter will not accept the reset co mmand entered from the digital operator. 
    Therefore, reset the inverter by turning on the RS terminal.
    NOTE: If an EEPROM error (E08) occurs, be sure to  confirm the parameter data values are 
    still correct.
    E41.-ModBus 
    communica-
    tion errorIf time-out occurs because of line discon-
    nection during the communication in 
    ModBus-RTU mode, the inverter will 
    display the error code shown on the left. 
    (The inverter will trip according to the 
    setting of C076.)•Check whether the communication speed 
    setting is correct.
    •Check whether the wiring distance is 
    appropriate (check the connections).
    NET.ERR
    E60.-
    to
    E69.-Option 1 error The inverter de
    tects errors in the option 
    board mounted in the optional slot 1. For 
    details, refer to the instruction manual for 
    the mounted option board.•Check whether the option board is 
    mounted correctly (check the board 
    mounting).
    •Check whether the option board is used 
    correctly (refer to th e instruction manual 
    for the option board SJ-FB, SJ-DG, or 
    SJ-DN).
    OP1-0
    OP1-9
    OPE / SRW 
    DisplayNameDescriptionTroubleshooting and Corrective Action
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Troubleshooting
    and Maintenance
    6–11
    Expansion Card 
    Error CodesThe inverter monitors the operation of the 
    expansion cards (optional) that may be 
    installed in the expansion bay. 
    On the inverter’s digital operator, error 
    codes in the E60 range refer to the upper 
    card position. Error codes in the E70 range 
    refer to the lower card position. For the 
    remote operator display, error codes are in 
    the OP1 or OP2 ranges, respectively. If an 
    error occurs, the inverter trips (displays the 
    corresponding error code and turns OFF the 
    motor output). 
    Encoder Input Card –  Use the following 
    table to diagnose errors caused by an 
    encoder input expansio n card. Each error 
    will cause the inverter to trip, turning OF F its output and displaying an error code.
    If an encoder expansion card does not operate  normally, use the following table to check the 
    DIP switch settings on the card.
    Encoder Input Expansion Card Errors
    Error Code: OPE / SRWNameProbable Cause(s)
    E60.- E70.-Encoder disconnect Encoder wiring  to the expansion card is 
    disconnected
    OP1-0     OP2-0The encoder is faulty
    The encoder type is  not correct (no line 
    driver output, etc.)
    E6 1.-  E7 1.-Excessive speed The motor speed increased to the  maximum frequency (A004) times the 
    over-speed error detection level (P026)
    OP1-1     OP2-1
    E62.- E72.-Positioning error While in position control mode the position error (command minus actual) 
    reached 1,000,000 pulses or more
    OP1-2     OP2-2
    E63.- E73.-Position control 
    range tripWhile in absolute position control mode, 
    the actual position exceeded the forward 
    (P072) or reverse (P073) position range 
    value
    OP1-3     OP2-3
    E69.- E79.-SJ-FB connection 
    errorThe SJ-FB expansion ca
    rd is not mounted 
    properly or the card is faulty
    OP1-9     OP2-9
    DIP SwitchSwitch 
    NumberSetting
    SWENC 1 ON setting enables encoder disc
    onnect function for loss of A 
    or B channel
    2 ON setting enables encoder disc onnect function for loss of Z 
    channel
    SWR 1 ON setting connects the 150
    Ω termination resistor across 
    terminals [SAP] and [SAN]
    2 ON setting connects the 150 Ω termination resistor across 
    terminals [SBP] and [SBP]
    E6x or OP1 Error range:
    E7x or OP2
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							Monitoring Trip Events, History, & Conditions
    Troubleshooting
    and Maintenance
    6–12
    Digital Input Card –  Use the following table to diagnose errors caused by a digital input 
    expansion card. Each error will  cause the inverter to trip, turning OFF its output and displaying 
    an error code.
    The input mode is determined by a combination of  DIP switch and rotary switch settings. If the 
    expansion card does not operate normally, use the following table to check the DIP switch and 
    rotary switch settings. The check marks indicate  input modes specified by switch settings. For 
    more details, refer to the expansion card instruction manual.
    Digital Input Expansion Card Errors
    Error Code: OPE / SRWNameProbable Cause(s)
    E60.- E70.-Digital input 
    expansion card error A communications time-out between the 
    inverter and the digital input card has 
    occurred
    OP1-0     OP2-0
    DIP SwitchRotary 
    SwitchFrequency Setting, HzAccel / Decel Time,  SecondsTorque 
    limit 
    SettingPosition  Setting
    12Code0.010.11Rate0.010.111%1 pulse
    OFF: BIN 
    (binary input) /  ON: BCD 
    (binary coded 
    decimal input) OFF: PAC 
    (batch input  mode) 0
    1
    2
    3
    4
    ✔
    5
    6 ✔
    ON: DIV 
    (divided input 
    mode 0
    ✔✔✔✔
    1 ✔
    2 ✔
    3 ✔✔
    4 ✔
    5 ✔
    6 ✔✔
    7 ✔
    8 ✔
    9 ✔✔
    A ✔
    B ✔
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    							SJ7002 Inverter
    Troubleshooting
    and Maintenance
    6–13
    DeviceNet Expansion Card –  Use the following table to diagnose errors caused by a 
    DeviceNet expansion card. Each er ror will cause the inverter to trip (according to parameter 
    settings P045 and P048), turning OFF it s output and displaying an error code.
    If the expansion card does not  operate normally, use the following diagrams to check the DIP 
    switch settings. For more details, refer  to the expansion card instruction manual.
    DeviceNet Expansion Card Errors
    Error Code: OPE / SRWNameProbable Cause(s)
    E60.- E70.-DeviceNet Communication 
    ErrorThe communication speed may be 
    incorrect
    OP1-0     OP2-0The network wiring length may 
    not be appropriate
    A connector is loose (or wire not 
    connected)
    E6 1.-  E7 1.-Duplicate MAC ID Two or 
    more devices on the 
    network have the same MAC ID
    OP1-1     OP2-1
    E62.- E72.-External trip Check the Force Fault/Trip bit. 
    Attribute 17 in the Instance 1 of 
    Class 19 may be set to 1. If so, 
    clear the bit to 0.
    OP1-2     OP2-2
    E69.- E79.-Inverter communication 
    error The expansion card may not be 
    properly connected to the inverter
    OP1-9     OP2-9
    DR1 DR0DRDR1 DR0DRDR1 DR0DR
    125 kbps250 kbps500 kbps
    DeviceNet Baud Rate Setting
    MAC ID
    DIP switch example
    DeviceNet MAC ID Setting
    NA32 NA16 NA8 NA4 NA2 NA1
    Description of switch setting
    543210
    = 29h (hex) = 41 (decimal)
    
    Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]  
    						
    All Hitachi manuals Comments (0)