NEC Neax 2400 Imx Installation Manual
Have a look at the manual NEC Neax 2400 Imx Installation Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 1168 NEC manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
NDA-24234 CHAPTER 4 Page 301 Revision 3.0 SYSTEM STARTUP Figure 022-2 LED Indications of IMG0 in Normal Operation (Multiple IMG Configuration) 13 14 MUX ACT MUX(PH-PC36) MUX(PH-PC36) 13 14 MUX ACT MUX(PH-PC36) MUX(PH-PC36) 13 14 MUX ACT MUX(PH-PC36) MUX(PH-PC36) 13 14 MUX ACT 03 04 IOC(PH-IO24) EMA(PH-PC40) OPE OPE/MB TOPU PIM3 PIM2 PIM1 PIM0 LPM BASEUFA N U FRONT VIEW : Lamp is ON (Green) : Lamp is OFF: Lamp is Flashing (Green) Legend CPU 0 → ACT TSW 0 → ACT PLO 0 → ACT System State CPU OPEIMG 0 DSP 1 (PZ-DK224) DSP 0 (PZ-DK224) CPU OPE FRONTMUX MUX ACT MB This figure shows the LED indications (example) for a fully expanded IMG0 system. MUX(PH-PC36) MUX(PH-PC36) IMG 0
CHAPTER 4 NDA-24234 Page 302 Revision 3.0 SYSTEM STARTUP Figure 022-3 LED Indications of IMG1 in Normal Operation (Multiple IMG Configuration) 13 14 MUX(PH-PC36) MUX(PH-PC36) 13 14 MUX(PH-PC36) MUX(PH-PC36) 13 14 MUX(PH-PC36) MUX(PH-PC36) MUX(PH-PC36) MUX(PH-PC36) 13 14 08 DLKC (PH-PC20) DLKC (PH-PC20) GT (PA-GT09) TSW 00 (PH-SW12) TSW 01 (PH-SW12) TSW 02 (PH-SW12) TSW 03 (PH-SW12) TSW 10 (PH-SW12) TSW 11 (PH-SW12) TSW 12 (PH-SW12) TSW 13 (PH-SW12)PLO Note PLO Note (RES) GT (PA-GT09) TOPU PIM3 PIM2 PIM1 PIM0 TSWM BASEU FA N U FRONT VIEW : Lamp is ON : Lamp is OFF LegendSystem State IMG1 TSW 0 -> ACT PLO 0 -> ACT DLKC 0 -> ACT 23 22 0910 1112 13 14 15 16 17 18 19 20 21 This figure shows the LED indications (example) for a fully expanded IMG1 system. Note that this example assumes that all of the four IMGs are used in an integrated multimedia exchange service. FRONTDLKC OPE/MB MB PLO FRONTMB ACT TSW FRONTMB TSW ACT TSW ACT GT MBR FRONTMB OPE/MB MBR MUX FRONTMB MUX ACT Note:PH-CK16/PH-CK17, or PH-CK16-A/PH-CK17-A
NDA-24234 CHAPTER 4 Page 303 Revision 3.0 SYSTEM STARTUP Figure 022-4 LED Indications of IMG 2/3 in Normal Operation (example) (Multiple IMG Configuration) This figure shows the LED indications (example) of a fully expanded system of IMG 2/3. 1 314 MUX (PH-PC 36) M UX(PH -PC36) 1314 MU X(PH- PC36) MUX(P H-PC3 6) 13 14 MUX( PH-PC3 6) MUX (PH-PC 36) MUX (PH-PC 36) M UX(PH -PC36) 1314 TOP U P IM3 PI M2 PIM1 PIM0 DUMM Y BASE U F ANU FRO NT V IEW : Lamp is ON IM G 2/3 Leg end : Lamp is OFF System State TSW 0 -> ACT FRON T M UX MU X ACT MB
CHAPTER 4 NDA-24234 Page 304 Revision 3.0 SYSTEM STARTUP Test Outline: The System has Alarm Lamps on the TOPU. Figure 023-1 shows the Alarm Lamps on the TOPU. For more information about each lamp, see the NEAX2400 IMX System Operations and Maintenance Manual. Figure 023-1 Alarm Lamps on the TOPU Note: SMJ and SMN are used in multiple IMG configuration only. NAP-200-023 Sheet 1/2 Check of Alarm Lamps of the TOPU ATTENTIONContents Static Sensitive Handling Precautions Required PWR ONMJMN SUP GRR GY SMJ SMNG ALM
NDA-24234 CHAPTER 4 Page 305 Revision 3.0 SYSTEM STARTUP NAP-200-023 Sheet 2/2 Check of Alarm Lamps of the TOPU START Test of MJ (MAJOR) Lamp Set the circuit breakers of the Power Supplies (PWR0, 1) in a PIM to OFF (About 10 seconds later, set the circuit breaker(s) back ON. Confirm that the MJ lamp (red) on the TOPU turns ON. Cancel the alarm indicating by pressing the ALM RST button on the TOPU. Test of MN (MINOR) Lamp Take an act side RGU Fuse out of the PWR card. Confirm that the MN lamp (red) on the TOPU turns ON. Cancel the alarm indication by pressing the ALM RST button on the TOPU. Test of SUP (SUPERVISORY) LampOn the EMA Circuit card, flip the MB switch DOWN- UP-DOWN Confirm that the SUP lamp (yellow) on the TOPU turns ON. Cancel the alarm indication by pressing the ALM RST button on the TOPU. END ATTENTIONContents Static Sensitive Handling Precautions Required
CHAPTER 4 NDA-24234 Page 306 Revision 3.0 SYSTEM STARTUP This page is for your notes.
NDA-24234 CHAPTER 5 Page 307 Revision 3.0 CHAPTER 5 INSTALLATION TEST PROCEDURE 1. HOW TO ENTER DATA IN THE TEST CHECK COLUMN Each NAP in this Chapter has check column for test result entry for each test item (see Figure 5-1). This para- graph explains the method of entering test result into the check column concerned using Figure 5-1 as an exam- ple. 1. Method of Entry Each check column consists of two sections of “PROVIDED” and “CHECK”. If the equipment or service feature pertaining to the test item is provided in the system, enter “*” in the PROVIDED section. At the time of performing installation tests, the test item with “*” marked in the PROVIDED section must be test- ed without exception. In the “CHECK” column, enter the results of each test as follows: When the test result is good:“OK” When the test result is no good:“ ×” 2. Fault Recovery If a fault is discovered as a result of an installation test, enter “ √” into the related check sheet. After finish- ing all tests in the same category, be sure to repair the detected fault before proceeding to the next test. 3. Entry into Check Column after Fault Recovery After fault recovery work has been completed, a test must be performed to confirm that the fault has been completely corrected. If the result of this confirmation indicates that the fault has been corrected, enter “OK” next to the “ ×” entered previously. This entry should appear as: “ × OK”.
CHAPTER 5 NDA-24234 Pag e 30 8 Revision 3.0 INSTALLATION TEST PROCEDURE Figure 5-1 Example of Entry to Test Check Column This example is NAP-200-024: DT Connection Test When “*” is already printed in the “PROVIDED” section, the item concerned is a basic function of the system. Test the item without exception. When “PROVIDED” section is blank, the installer should enter “*” mark as per the Job Specification. The item marked with “*” must be tested without exception. Check whether the OPE lamp (G) is turning ON on the RST circuit cards. Check whether the OPE lamp (G) is turning ON on the LC circuit cards. Lift handset. Confirm DT (Dial Tone). Check whether the Busy lamp (R) is turning ON for the connected ORT and LC. Continue listening to DT for about 12 seconds. Confirm that DT changes to Reorder Tone (ROT). Continue listening to ROT for about 30 seconds. When System Data (SYS1, INDEX 64, b 3 = 0, b4 = 0) are assigned.Confirm that ROT changes to “no tone.” When System Data (SYS1, INDEX 64, b 3 = 0, b4 = 1 or b 3 = 1, b4 = 0) are assigned.Confirm that howler tone is heard after ROT stops. (Analog Ports only) Hang up and release the connection. These are the Test Check Columns, the left column is “PROVIDE” column and the right columns is the “CHECK” columns. START END * * * * *
NDA-24234 CHAPTER 5 Page 309 Revision 3.0 INSTALLATION TEST PROCEDURE 2. BASIC CONNECTION TEST 2.1 Outline After the system has been started up, establish some basic connections and verify that the system operates nor- mally. 2.2 Basic Connection Test Procedure Perform tests on the operations of the processors and the system by referring to the NAP Number indicated to the right of each item in the following flowchart. If an operation cannot be performed satisfactorily, perform the necessary repair procedure(s) based on Chapter 6, “FAULT RECOVERY DURING TESTS”. START DT (Dial Tone) Connection Test:NAP-200-024 Station-to-Station Connection Test:NAP-200-025 END
CHAPTER 5 NDA-24234 Pag e 31 0 Revision 3.0 INSTALLATION TEST PROCEDURE NAP-200-024 Sheet 1/1 DT (Dial Tone) Connection Test START Check whether the OPE lamp (G) is turning ON on the RST circuit cards. Check whether the OPE lamp (G) is turning ON on the LC circuit cards. Lift handset. Confirm DT (Dial Tone). Check whether the Busy lamp (R) is turning ON for the connected ORT and LC. Continue listening to DT for about 12 seconds. Confirm that DT changes to Reorder Tone (ROT). Continue listening to ROT for about 30 seconds. When System Data (SYS1, INDEX 64, b 3 = 0, b4 = 0) are assigned.Confirm that ROT changes to “no tone”. When System Data (SYS1, INDEX 64, b 3 = 0, b4 = 1 or b 3 = 1, b4 = 0) are assigned.Confirm that howler tone is heard after ROT stops. (Analog Ports only) Hang up and release the connection. END LCORTADT, ROT * * * * *