NEC Neax 2400 Imx Installation Manual
Have a look at the manual NEC Neax 2400 Imx Installation Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 1168 NEC manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.
NDA-24234 CHAPTER 3 Page 191 Revision 3.0 INSTALLATION PROCEDURE 2. CABLE RUNNING FROM THE PBX TO THE MAT AND SMDR NAP-200-013 Sheet 6/13 Cable Running from the PBX to MDF, ATTCON, MAT, and SMDR START MAT (Refer to NAP-200-017) Referring to NAP-200-017, connect 68PH S 2 PORTS CA-A and the installation cable (25P). At the PBX side, confirm the connector name on the LPR backplane, then run 68PH S 2 PORTS CA-A up to the connector position. At the MAT side, run RS-232-CA “0” up to the MAT. SMDR (Refer to NAP-200-018) Referring to NAP-200-018, connect the PBX and the SMDR equipment. At the PBX side, confirm the connector name on the LPR backplane, then run 68PH S 2 PORTS CA-A up to the connector position. At the SMDR equipment side, run the installation cable (25P) up to the SMDR equipment. END
CHAPTER 3 NDA-24234 Pag e 19 2 Revision 3.0 INSTALLATION PROCEDURE 3. CONNECTIONS AT THE PBX SIDE 4. CABLE TYING AT THE PBX NAP-200-013 Sheet 7/13 Cable Running from the PBX to MDF, ATTCON, MAT, and SMDR START LT Connectors Confirm each connector name on the backplane and the corresponding LT connector, then connect the two. 16PH EX ALM Connect the 16PH EX ALM CA to the EXALM rear connector on the LPR backplane. NCU Connectors Connect the NCU cable to the connector on the front of the PFT card. IOC Connectors Connect 68 PH S 2PORTS CA-A to the MISC connectors on the LPR backplane. END START Referring to Figure 013-3, secure the connector cables to the Module. END
NDA-24234 CHAPTER 3 Page 193 Revision 3.0 INSTALLATION PROCEDURE Figure 013-3 Example of Cable Tying Using Tie-Wrap NAP-200-013 Sheet 8/13 Cable Running from the PBX to MDF, ATTCON, MAT, and SMDR Backplane LT6 PL O L T3 L T2 LT5LT 4 L T0 L T 1 REAR SIDETIE-WRAP
CHAPTER 3 NDA-24234 Pag e 19 4 Revision 3.0 INSTALLATION PROCEDURE 5. TERMINATION OF THE CABLES BETWEEN THE PBX AND THE MDF OR ATTCON ONTO THE CABLE SUPPORT ASSEMBLY NAP-200-013 Sheet 9/13 Cable Running from the PBX to MDF, ATTCON, MAT, and SMDR START Remove of the Cable Support Assembly. Remove the Cable Support Assembly from the BASEU. (See Figure 013-4.) Peel the cable cover Referring to Table 13-1, confirm the cable terminating locations on the Cable Support Assembly. Per the cable terminating locations, peel the cable cover as shown on Figure 013-5. Terminate the cable Referring to Figure 013-5, wind the M-clamp onto the cable portion from which the cover has been peeled off. Referring to Figure 013-6, terminate the cable onto the Cable Support Assembly. When all the cables have been terminated to the Cable Support Assembly A, likewise terminate the cables onto the Cable Support Assembly B, C, D, E in the order named. END
NDA-24234 CHAPTER 3 Page 195 Revision 3.0 INSTALLATION PROCEDURE Figure 013-4 Cable Support Assembly NAP-200-013 Sheet 10/13 Cable Running from the PBX to MDF, ATTCON, MAT, and SMDR AB C D (LPM, TSWM or DUMMY) REAR VIEW(BASEU) CABLE SUPPORT ASSEMBLY FRONT SIDE VIEW (LPM, TSWM or DUMMY)
CHAPTER 3 NDA-24234 Pag e 19 6 Revision 3.0 INSTALLATION PROCEDURE Note: For LPM only. NAP-200-013 Sheet 11/13 Cable Running from the PBX to MDF, ATTCON, MAT, and SMDR Table 013-1 Cable Support Assembly BACKPLANE CABLE SUPPORT No.USE REMARKS MODULE CONNECTOR NAME LPRMISCnA, MISCnB Afor I/O Equipment (MAT, Printer, etc.) Spare cable (15 cables) are to be used as Cable Support Assembly extra cables. The number of cables for the whole system is limited to maximum 100. EXALM NoteAfor Alarm Indicating Panel, etc. A (Extra)Spare (15 cables) PIM0Front of Circuit Card BThe number of cables is limited to three for one side, and six for both sides.In case the required number of cables exceeds 20, the Cable Support Assembly extra cables should be used. LT0 - LT11 B LT cable PIM1Front of Circuit Card CThe number of cables is limited to three for one side, and six for both sides.In case the required number of cables exceeds 20, the Cable Support Assembly extra cables should be used. LT0 - LT11 C LT cable PIM2Front of Circuit Card DThe number of cables is limited to three for one side, and six for both sides.In case the required number of cables exceeds 20, the Cable Support Assembly extra cables should be used. LT0 - LT11 D LT cable PIM3Front of Circuit Card EThe number of cables is limited to three for one side, and six for both sides.In case the required number of cables exceeds 20, the Cable Support Assembly extra cables should be used. LT0 - LT11 E LT cable
NDA-24234 CHAPTER 3 Page 197 Revision 3.0 INSTALLATION PROCEDURE Figure 013-5 Clamp Winding NAP-200-013 Sheet 12/13 Cable Running from the PBX to MDF, ATTCON, MAT, and SMDR Shield cableApprox. 18 mm (0.72 inch)CLAMP (M-398902)
CHAPTER 3 NDA-24234 Pag e 19 8 Revision 3.0 INSTALLATION PROCEDURE Figure 013-6 Termination of Installation Cables NAP-200-013 Sheet 13/13 Cable Running from the PBX to MDF, ATTCON, MAT, and SMDR (FRONT) CABLE CABLE SUPPORT ASSEMBLY CABLE SUPPORT ASSEMBLY CLAMP CABLEPANHEAD SCREW (PL-C, P, B, MS 4X8X3 GF)
NDA-24234 CHAPTER 3 Page 199 Revision 3.0 INSTALLATION PROCEDURE This NAP explains the procedures for terminating cables at the MDF. CAUTION:When terminating Cables to the MDF, the line/trunk circuit card should extend about 50 mm (2 inches) from the module and must not contact the backplane connector. NAP-200-014 Sheet 1/1 Termination of Cables on MDF (Wire Accommodation of Each Cable) START Cable trying at the MDF Secure the CHAMP Connector cables, which have been extended to the MDF as per NAP-200-012, to the cable supports on the MDF after confirming their positions on the terminal block. Cutting of excess cable Shorten each CHAMP connector cable, leaving enough length so that they can be neatly terminated to the terminal block. Cable termination to the MDF Referring to the Circuit Card Manual, punch down the CHAMP connector cables to the MDF. Confirmation of connections After confirming that no erroneous connections have been made on the Module Group side, use an IC buzzer on similar device to verify the connections at the MDF. END
CHAPTER 3 NDA-24234 Pag e 20 0 Revision 3.0 INSTALLATION PROCEDURE This NAP explains the following work items: NAP-200-015 Sheet 1/30 Cable Termination and Cross Connections from MDF to Peripheral Equipment, C. O. Lines, and Tie Lines MDF C.O. Line/ Tie LineCross Connection of Stations Cross Connection of Trunks (C.O. Lines and Tie Lines) Cross Connections for PFT Cross connection of Alarm Indicating Panel and Cross connections for TAS indicator Cross connections for External Switches Connection of Announcement Machine Connection of Paging Equipment Cross connections for Dterm Series E Cross Connections for Digital Interfaces PBX Page 201 Page 202 Page 204 Page 207 Page 212 Page 215 Page 217 Page 219 Page 221 Page 223 Music on Hold