    							NDA-24306 CHAPTER 3
    Page 83
    Revision 1.0
    Figure 008-2  Connection of Power and Ground Cables to Power Receiving Terminal
    NAP-200-008
    Sheet 3/12
    Connection of Power and Ground Cables 
    from the Power Equipment
    Note 1:For 1/2 PIM configuration, connect the cable only to the A terminal.
    Note 2:An example of End Jointing (using A Type-Clamp terminal) is explained in Section 3 of this NAP.
    +80V:Terminal
    -48V:B Terminal
    G:B Terminal
    -48V:A Terminal
    G:A Terminal
    FE Terminal
    POWER AND GROUND CABLES
    POWER RECEIVING TERMINAL
    REAR VIEWBASE-U
    PIM0
    Note 1
    LPM/TSWM/DUMMY 
    						
    							CHAPTER 3 NDA-24306
    Pag e 8 4
    Revision 1.0
    2. CONNECTION OF DC-DC CONVERTER FOR TELEPHONE SETS EQUIPPED WITH
    MESSAGE WAITING LAMPS
    NAP-200-008
    Sheet 4/12
    Connection of Power and Ground Cables 
    from the Power Equipment
    START
    Cable Running Referring to Figure 008-3, run the power and ground 
    cables.
    Removal of shorting piece and cable 
    connectionReferring to Figure 008-4, remove the shorting piece 
    from the +80 V connector of PZ-M371 card, then 
    connect the cable provided on the +80 V Power 
    Receiving Terminal Block to the +80 V connector.
    Confirm that the Circuit Breaker (NFB) of the Rectifier is OFF.
    Connection of Power and Ground 
    CablesReferring to Figures 008-3 and 008-4, connect the 
    power and ground cable to each terminal of the 
    equipment.
    Check  after  cable  connections Using a continuity tester, confirm that the –48 V and 
    +80 V power cable are not short-circuiting with the 
    G power cable or FE ground cables.
    END 
    						
    							NDA-24306 CHAPTER 3
    Page 85
    Revision 1.0
    Figure 008-3  Example Connection Diagram-DC-DC Converter for Message Waiting Lamps
    NAP-200-008
    Sheet 5/12
    Connection of Power and Ground Cables 
    from the Power Equipment
    Note:The current capacity of the DC-DC Converter is calculated by multiplying the (current capacity of the
    message waiting lamp) by the number of telephone sets.
    PBX
    IV(WHITE)+80V
    DC-DC 
    CONVERTER
    OUTPUT
    INPUT G +80V
    G –48V
    IV(BL)
    IV(R)
    IV(G) TO RECTIFIERF 
    G 
    						
    							CHAPTER 3 NDA-24306
    Pag e 8 6
    Revision 1.0
    Figure 008-4  Removal of Shorting Piece and Cable Connection
    NAP-200-008
    Sheet 6/12
    Connection of Power and Ground Cables 
    from the Power Equipment
    BASEU Power Receiving Terminal Block
    Remove the shorting piece
    Connect the Cable to the +80V Connector of PZ-M371 cardPZ-M371
    +80V +80V
    Powe r C a bl e 
    						
    							NDA-24306 CHAPTER 3
    Page 87
    Revision 1.0
    3. END JOINTING OF POWER AND GROUND CABLES
    NAP-200-008
    Sheet 7/12
    Connection of Power and Ground Cables 
    from the Power Equipment
    START
    Stripping of Insulation Sheath Strip the wire to exceed the length of the terminal body 
    by 1 - 2 mm (1/8 inch).
    Clamping Referring to Figure 008-5, place the terminal body on 
    the die with the soldered part facing upward.
    Referring to Figure 008-6, insert the stripped wire into 
    the terminal body up to the insulation-sheath edge, and 
    clamp the terminal.
    Wipe the terminal with a dry cloth.
    END
    WIRE SHEATH
    CONDUCTOR
    CLAMP TERMINAL
    1 - 2 mm 
    						
    							CHAPTER 3 NDA-24306
    Pag e 8 8
    Revision 1.0
    Figure 008-5  Placing the Clamp Terminal on the Die
    Figure 008-6  Clamping Method
    NAP-200-008
    Sheet 8/12
    Connection of Power and Ground Cables 
    from the Power Equipment
    CONVEX DIE
    SOLDERED PART
    TERMINAL
    CONCAVE DIE
    1/8 inch (1 - 2mm)
    CONVEX DIE
    A
    A
    INSULATION SHEATH
    TERMINAL
    CONCAVE DIE
    SOLDERED PART
    CLAMPED PORTION
    CLAMPED PORTION
    CONDUCTOR
    A-A 
    						
    							NDA-24306 CHAPTER 3
    Page 89
    Revision 1.0
    4. BRANCHING OF POWER CABLES
    NAP-200-008
    Sheet 9/12
    Connection of Power and Ground Cables 
    from the Power Equipment
    START
    Stripping Main and Branch Cable Referring to Figure 008-7, strip insulation coating with 
    an electrician’s knife. Avoid damage to the conductor 
    during the stripping process.
    Inserting of Cables into Terminal Insert the stripped main wire and branch wire into the 
    terminal as shown in Figure 008-8.
    Clamping for Branch Jointing Place T-Type terminal on the die of the clamping tool, 
    T-20 - T-44 terminals should be placed on the center of 
    the die.
    T-60 - T-365 terminals should be placed on the die in 
    such a way that the terminal will be pressed on the part 
    marked with the roulette.
    Proceed with the operation of the clamping tool by 
    referring to Figure 008-9.
    Clean the terminal with a dry cloth.
    Taping and Covering Referring to Figures 008-10 and 008-11, put an 
    installation cover over the clamped portion, after taping 
    with installation tape.
    END
    3 ROULETTES 
    T-154-T-365 NO ROULETTE 
    T-20-T-442 ROULETTES 
    T-60-T-122 
    						
    							CHAPTER 3 NDA-24306
    Pag e 9 0
    Revision 1.0
    Figure 008-7  Stripped Length of Main and Branch Cable
    NAP-200-008
    Sheet 10/12
    Connection of Power and Ground Cables 
    from the Power Equipment
    Table 008-1  Stripped Length
    APPLICABLE TERMINALSTRIPPED MAIN-WIRE LENGTH I
    1
    [inch (mm)]STRIPPED MAIN-WIRE LENGTH I
    2
    [inch (mm)]
    T-20 Approx. 1.2 (28) Approx. 1.0 (24)
    T-26 1.3 (32) 1.2 (28)
    T-44 1.5 (37) 1.3 (33)
    T-60 1.6 (40) 1.5 (36)
    T-76 1.7 (42) 1.6 (39)
    T-98 1.8 (44) 1.7 (41)
    T-122 1.7–1.9 (43–46) 1.6–1.7 (40–43)
    T-154 2.0 (49) 1.9 (46)
    T-190 2.3 (57) 2.2 (54)
    T-240 2.5 (63) 2.4 (60)
    T-288 2.8 (69) 2.6 (66)
    T-365 3.0 (75) 2.9 (72)
    T- 9 8
    Sum of the cross sections of the main and branching, or the main and extension cables.
    Type of clamp terminal (T type)
    I 1
    MAIN CABLE
    CONDUCTOR
    BRANCH CABLE
    I 2
    T TYPE 
    CLAMP- 
    TERMINAL 
    						
    							NDA-24306 CHAPTER 3
    Page 91
    Revision 1.0
    Figure 008-8  Inserting of Cables into Terminal
    Figure 008-9  Clamping for Branch Jointing
    NAP-200-008
    Sheet 11/12
    Connection of Power and Ground Cables 
    from the Power Equipment
     1/8 inch (1 - 2 mm)
    BRANCH 
    CABLEMAIN CABLE
    BEND PRIOR TO INSERTION
    T TYPE 
    TERMINAL
    Note:• Prevent the wires from slipping out of the clamp termi-
    nal by holding them firmly.
     Check the indication of the pressure regulator.
     Operate the pressure release lever to release the wires
    from the die.
    CLAMPED PORTION
    DIET TYPE 
    TERMINAL
    CONDUCTOR 
    (MAIN AND 
    BRANCH CABLE) 
    						
    							CHAPTER 3 NDA-24306
    Pag e 9 2
    Revision 1.0
    Figure 008-10  Taping
    Figure 008-11  Covering
    NAP-200-008
    Sheet 12/12
    Connection of Power and Ground Cables 
    from the Power Equipment
    Note:Taping should be done in two rounds with the tape
    overlapping half the tape width.
    INSULATION TAPE
    0.4- 1.2 in. ABOVE 0.4 in. (10 mm)
    (10 - 30 mm)
    INSULATION COVER 
    						