Home > Toshiba > Communications System > Toshiba Perception 1 2 User Manual

Toshiba Perception 1 2 User Manual

    Download as PDF Print this page Share this page

    Have a look at the manual Toshiba Perception 1 2 User Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 566 Toshiba manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							2. Press the 1 button to access 
    alpha characters. 
    3. Press the 0 button to move the 
    cursor (-) to the desired 
    position. 
    4. Press the button 
    corresponding to the letter 
    which you want to enter. 
    5. If you want to enter a number, 
    press the 1 button to change 
    to numeric characters. Press 
    the fl button again to return to 
    alpha characters. (Refer to the figure on the following page for an explanation of the 
    dialpad buttons.) 
    (The left edge of the display to program a new message, or two spaces 
    to the right of the preprogrammed message to add information.) 
    Use them button to shift from letter to letter on that button. For example: 
    n If you press 1, a D will be displayed. By pressing 1, the D will change 
    to E. By pressing 1 again, the E will change to F. Press 1 again and 
    the F will change to D. 
    n To enter spaces, press 0. 
    Numbers are also entered on the dialpad. 
    Each button has three letters that 
    are used in messaging; the 1 button 
    is used to shift between the letters 
    0 button moves 
    I, 
    cursor to the right 
    (also used to ----+J~lFJ 
    access special fl~iT/ 
    characters) 
    l=FJ@jm 01 button alternates 
    between alpha 
    0 button moves the 
    cursor to the left Pm 
    q q w and numeric 
    characters 
    1 button is used to shift between 
    the three letters on each alpha button 
    (also used to access special characters) 
    48 
    46 
    0 
    51 
    ii 52 ii 53 ij 54 
    ii m button,.press the m 
    button. 
    49 
    50 
    51  
    						
    							FAULT FINDING 
    SECTlDN200-255-500 
    MARCH1991 
    FAULT FINDING PROCEDURES  
    						
    							FAULT FINDING 
    SECTION 200-255-500 
    MARCH 1991 
    PARAGRAPH 
    1. 
    2. 
    3. 
    4. 
    5. 
    TABLE SUBJECT 
    PAGE 
    A 
    B 
    C FLOWCHARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 
    1 
    ELECTRONIC TELEPHONE CABLE CONTINUITY READINGS 
    USING A VOLTMETER 
    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 
    ELECTRONIC TELEPHONE CABLE CONTINUITY READINGS 
    USING AN OHMMETER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 
    PERCEPTIONeh, 
    FAULT FINDING 
    TABLE OF CONTENTS 
    SUBJECT 
    PAGE 
    GENERAL ......................................................................................................... 1 
    FAULT CLASSIFICATION.. ............................................................................... 1 
    FAULT CLEARING PROCEDURES ................................................................. 1 
    DEFECTIVE APPARATUS RETURNS ............................................................. 2 
    FAULT IDENTIFICATION AND ELIMINATION PROCEDURES.. 
    ..................... 2 
    FLOWCHARTS 
    CHART NO. I-FAULT CLASSIFICATION .................................................. 4 
    CHART NO. 2-LOADING 
    FAULTS ............................................................. 
    9 
    CHART NO. 3-POWER FAULTS.. .............................................................. 12 
    CHART NO. b--RINGING POWER FAULTS ............................................... 14 
    CHART NO. 5-TIME SWITCH CLOCK FAULTS ........................................ 15 
    CHART NO. 6-NPRU FAULTS ................................................................... 16 
    CHART NO. 7-NRCU FAULTS ................................................................... 17 
    CHART NO. 8-NCOU/NEMU/NLSU FAULTS.. ........................................... 
    18 
    CHART NO. 9-NEKU/NDKU/NSTU/NDSU FAULTS .................................. 19 
    CHART NO. lO--SMDR, TTY, OR MODEM FAULTS.. 
    ................................ 20 
    CHART NO. 1 l-VOICE COMMUNICATION STATION FAULTS ............... 22 
    CHART NO. 12-lNIT/LOAD KEY FAULTS.. ................................................ 23 
    CHART NO. 13-MAJOR ALARM FAULTS (MAJ LED ON) ........................ 24 
    CHART NO. 14-CO/DIDTTIE TRUNK FAULTS 
    ........................................... 25 
    CHART NO. 15-ATTENDANT CONSOLE FAULTS ................................... 26 
    CHART NO. 16-COMMON STATION FEATURE FAULTS ........................ 27 
    CHART NO. 17-SPEECH PATH OR DIAL TONE FAULTS.. ...................... 31 
    CHART NO. 18-DATA/SPEECH PATH OR DIAL TONE FAULTS ............. 34 
    CHART NO. 19-DIALING FAULTS ............................................................. 36 
    CHART NO. 20-RINGING/RINGBACK TONE FAULTS ............................. 38 
    CHART NO. Zl-MISCELLANEOUS FAULTS.. ........................................... 40 
    CHART NO. 22-NMDU/NDCU FAULTS 
    ..................................................... 41 
    CHART NO. 23-DATA COMMUNICATION STATION FAULTS ................. 43 
    CHART NO. 24-DATA COMMUNICATION TRUNK FAULTS .................... 45 
    TABLE LIST  
    						
    							FAULT FINDING 
    SECTION 200-255-500 
    MARCH 1991 
    FIGURE LIST 
    FIGURE TITLE 
    PAGE 
    1 
    2 
    3 FLOWCHART SYMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..~. 
    PERCEPTION, POWER SUPPLY VOLTAGE CHECKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5: 
    PERCEPTION, POWER SUPPLY VOLTAGE CHECKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 
    .~.. . 
    ,. 
    -ii-  
    						
    							FAULT FINDING 
    SECTION 200-255-500 
    MARCH 1991 
    1. GENERAL 
    1.01 
    This section describes the maintenance 
    procedures that are used for the diagnosis of faults 
    in the PERCEPTlONe and PERCEPTIONex Dig- 
    ital Hybrid/ PBX systems. To eliminate system 
    faults, faults must first be classified and then cleared 
    by replacing the defective apparatus. Operational 
    tests can then be performed to verify correct appa- 
    ratus operation. To perform operational tests, fol- 
    low the fault-clearing flowcharts and the steps 
    noted in section 5. 
    2. FAULT CLASSIFICATION 
    2.01 
    To ensure that fault clearing is pursued in a 
    logical sequence, a Fault Classification Flowchart 
    is provided in Chart No. 1. 
    2.02 Each Fault Finding flowchart denotes the 
    steps necessary to clear specific types of faults 
    (power faults, specific PCB faults, etc.). Most of the 
    provided flowcharts are based on an assumption 
    that the system fault was discovered and reported 
    by a station user. Therefore, all faults are classified 
    according to the way they would appear at an 
    electronic telephone, standard telephone, DDIU, 
    data terminal/computer, DSS console, attendant 
    console, or equipment cabinet. 
    2.03 Faults and their associated flowcharts are 
    organized into the following categories: 
    TABLE A-FLOWCHARTS 
    Flowchart Title 
    1 
    Fault Classification 
    2 
    Loading Faults 
    3 Power Faults 
    4 Ringing Power Faults 
    5 Time Switch Clock Faults 
    6 NPRU Faults 
    7 
    NRCU Faults 
    8 NCOWNEMWNLSU Faults 
    9 NEKU/NDKU/NSTU/NDSU Faults 
    10 SMDR, TTY, or MODEM Faults 
    11 
    Voice Communication Station Faults 
    12 lNlT/LOAD Key Faults 
    13 MAJOR ALARM Faults 
    14 CO/DID/TIE Faults 
    15 Attendant Console Faults 
    16 Common Station Feature Faults 
    I TABLE A-FLOWCHARTS (continued) 
    Flowchart 
    17 
    18 
    19 
    20 
    21 
    22 
    23 
    24 Title 
    Speech Path or Dial Tone Faults 
    Data/Speech Path or Dial Tone Fault: 
    Dialing Faults 
    Ringing/Ringback Tone Faults 
    Miscellaneous Faults 
    NMDU/NDCU Faults 
    Data Communication Station Faults 
    Data Communication Trunk Faults 
    3. FAULT CLEARING PROCEDURES 
    3.01 Before attempting to clear any fault, ensure 
    that the fault exists in the system and is not being 
    caused by any associated external equipment, 
    such as wiring, a Music-on-Hold source, etc. 
    IMPORTA NT! 
    Many PERCEPTION,,, features are as- 
    signed, enabled, or disabled by using 
    software entries described in the Pro- 
    gramming Procedures manual. Before 
    troubleshooting system hardware, it is im- 
    portant to veriv that system programming 
    is correct and functional. 
    3.02 Faults occurring in PERCEPTION,,,, sys- 
    tems are cleared by replacing PCBs, electronic 
    telephones, standard telephones, DIUs, attendant 
    consoles, or power supply(ies), according to in- 
    structions in the provided flowcharts. 
    3.03 Five different symbols are used in the flow- 
    charts. Each is identified in Figure 1. 
    3.04 The flowcharts are arranged sequentially to 
    permit rapid fault localization within the system. All 
    fault clearing must begin with the Fault Classifica- 
    tion Flowchart (Flowchart I), which denotes the 
    correct sequence to be followed in fault localiza- 
    tion. 
    3.05 If more than one station has a fault classified 
    as a station fault (see flowcharts), then only one 
    station can be corrected at a time. 
    3.06 An alarm or fault indicator is used as an aid in 
    locating a particular fault. However, if a fault occurs 
    and its corresponding indicator does not function, 
    -l-  
    						
    							FAULTFINDING 
    SECTIONZOO-255-500 
    MARCH1991 
    Start and end of a flow- 
    chart sequence 
    Important notes affecting 
    the fault clearing procedure 
    .-----i 
    Question to be answered 
    YES or NO. 
    0 
    Progression TO or FROM 
    another flowchart. Page 
    numbers indicate the loca- 
    tion of the flowchart within 
    this manual. Lettersdenote 
    0, 
    the exact entrance or exit 
    point in the flowchart. 
    Statement of a required 
    action 
    -.A..-- A -. -...a..m-- -.-mm--. I 
    the affected PCB should be replaced. Alarm and 
    fault indicators that have failed cannot be cor- 
    rected. 
    3.07 The following precautions must be observed 
    when handling PCBs: 
    DO NOT: 
    l Drop a PCB. 
    l Stack one PC8 on top of another. 
    l Handle a PCB without discharging any static 
    electricity from your person by touching a metal 
    part of the grounded system cabinet. 
    l Touch PCB contacts with your fingers. 
    IMPORTANT! 
    If the fault is not cleared by substituting a 
    PCB, the original PCB must be reinstalled 
    in the system cabinet before proceeding to 
    the next flowchart. 
    4. DEFECTIVE APPARATUS RETURNS 
    4.01 To return a defective system apparatus for 
    repair, the apparatus must be prepared for ship- ping by enclosing the item in a suitable container J- 
    (preferably its original box). The following guide- $,,-, 
    lines must be followed: 
    a) All PCBs must be enclosed in anti-static con- 
    tainers. 
    b) All electronic telephones, DIUs, attendant con- 
    soles, etc. must be enclosed in plastic bags 
    before being inserted into their shipping con- 
    tainers. yy’. 
    4.02 NEVER WRITE ON THE APPARATUS IT- .I- 
    SELF! Instead, describe the nature of the defect on 
    a Toshiba return (TSD RA) tag, and attach the tag ’ 
    to the front of the defective unit with string (not d 
    wire). This will allow the tag to remain attached 
    during the testing and repair process. 
    4.03 If diff erent and/or additional faults are created 
    in the system by substituting a PCB, tag and return 
    the substitute PCB as a defective unit. 
    5. FAULT IDENTIFICATION and ELIMINATION 
    /h-- 
    PROCEDURES {j s 
    ‘*\.- ., 
    5.01 
    In the provided flowcharts, single line tele- 
    phones are referred to in different ways. These are 
    defined as follows: 
    l 2500-type-Refers to a DTMF standard tele- 
    phone with a “touch-tone” dialpad. 
    l ST-T-Refers to both DTMF and rotary dial tele- 
    phones. 
    l 500-type-Refers to a standard rotary dial tele- 
    phone. 
    5.02 Checkelectronic/digital telephone cable con- 
    tinuity by using a voltmeter, as follows: 
    1) Check all station cables at the modular block 
    and check all cables from NEKUINDKU PCBs to 
    the MDF, at the MDF. 
    2) Disconnect the electronic telephone. 
    3) Using a DC voltmeter, measure between the 
    two pairs to verify the presence of the readings , 
    shown in Table 6. 
    -2-  
    						
    							TABLEB-ELECTRONICTELEPHONE 
    CABLECONTINUITYREADINGS 
    (Using a voltmeter) 
    *Nominal voltage- within the power supply 
    limits of 23.2 w 28.2 VDC, while under AC 
    power. 
    3) An improper reading indicates an open, crossed, 
    or shorted wire. 
    4) Forthe MDF-to-electronic/digital telephone/DSS 
    console cable, a more precise check can be 
    made by using an ohmmeter (See 5.03). 
    5.03 Check electronic/digital telephone and DSS 
    console cable continuity by using an ohmmeter, as 
    follows: 
    1) 
    2) 
    3) 
    4) 
    Disconnect the electronic/digital telephone or 
    DSS console. 
    At the MDF, remove the bridging clips. 
    Using an ohmmeter, measure the resistance 
    between all combinations of the four wires at the 
    modular block. All measurements should ex- 
    ceed 
    1 MOhm. 
    At the modular block, measure the resistance 
    between all wire combinations. The proper 
    readings are shown in Table C. 
    NOTES: 
    1. The green-red and black-yellow measure- 
    ments should be within 10% of each other. 
    2. The maximum reading is 55 ohms. 
    5.04 Check single line telephone (XT) cable con- 
    tinuity as follows: FAULTFINDING 
    s~cTloN 200-255-500 
    MARCH1991 
    TABLEC-ELECTRONICTELEPHONE 
    CABLECONTINUITY READINGS 
    (Usinn an ohmmeter) 
    Pair 
    I FROM TO VOLTAGE* 
    Wire Color Pair Wire Color 
    T Green 2 T Black 1 MOhm 
    R Red 2 T Black 1 MOhm 
    T Green 2 R Yellow 
    1 MOhm 
    R Red 2 R Yellow 1 MOhm 
    T Green 1 R Red 5 55 Ohms* 
    T Black 2 R Yellow I 55 Ohms* 
    Check all DDIWPDIU cables at the modular 
    block, and check all cables from NSTU PCBs to 
    the MDF, at the MDF. 
    2) 
    3) 
    4) 
    5) 
    6) 
    Disconnect the STT at the wall. 
    At the MDF, remove the bridging clips. 
    Using an ohmmeter, measure the resistance 
    between the two wires at the modular block. All 
    measurements should exceed 1 MOhm. 
    At the MDF, place shorting jumper wires be- 
    tween the two wires (T and R). 
    At the modular block, measure the resistance 
    between T and Ft. Verify the maximum of 300 
    ohms. 
    5.05 Check DDWPDIU cablecontinuityasfollows: 
    1) 
    2) 
    3) 
    4) 
    5) 
    Check all DDIWPDIU cables at the modular 
    block, and check all cables from NDCUINMDUI 
    NDKU PCB to the MDF, at the MDF. 
    At the MDF, remove the bridging clips. 
    Using an ohmmeter, measure the resistance 
    between the two wires at the modular block. All 
    measurements should exceed 1 MOhm . 
    At the MDF, place shorting jumper wires be- 
    tween the two wires (T and R). 
    At the modular block, measure the resistance 
    between T and R. Verify the maximum of 300 
    ohms. 
    -3-  
    						
    							FAULTFINDING 
    SECTlON200-255-500 
    MARCH1991 
    CHART NO. 1 
    FAULT CLASSIFICATION 
    xi ---------------------- pijfjy 
    J 
    To 
    / 
    ‘i 
    START 
    I NO 
    Switch the main circuit 
    breaker (power) 
    to ON. 
    - Wait approx. 30 
    seconds for the 
    system to load. 
    YES 
    __-___ 
    ---_ 
    YES I- 
    NOTE: See Section 
    200-255-200, 
    Installation, 
    Chapter 4 
    Paragraphs 7.01& 7.02 
    (System Power Up). 
    -4-  
    						
    							FAULT FINDING 
    SECRDN 200-255-500 
    MARCH 1991 
    CHART NO. 1 
    FAULT CLASSIFICATION (continued) 
    date on attendant 
    console or with 
    the DTRF Program 
    NOTE: It station’s 
    voice comm. (including 
    all related features) - 
    is free of faults, the 
    answer is YES. system functional 
    -5-  
    						
    							FAULT FINDING 
    SECTION 200-255-500 
    MARCH 1991 
    CHART NO. 1 
    FAULT CLASSIFICATION (continued) 
    From 
    FC3 
    Page 5 
    2 Press the INIT 
    key on the NPRU 
    momentarily. 
    ‘Wait a few 
    seconds for 
    initialize to 
    complete. 
    Press the LOAD 
    key on the NPRU 
    momentarily. 
    * Wait approx. 30 
    seconds for re-load 
    to complete. 
    I I 
    I 
    A To- 
     
    1 YES 
    NOTE: See Section 
    200-255-200, 
    /nsra//ation, --- 
    Chapter 4, 
    Paraaraphs 7.01 and 7.02 
    ’ FC4 
    Paoe 7 
    -6-  
    						
    All Toshiba manuals Comments (0)

    Related Manuals for Toshiba Perception 1 2 User Manual