    Have a look at the manual Lucent Technologies DEFINITY Enterprise Communication Server Release 8.2 Upgrades And Additions Manual online for free. It’s possible to download the document as PDF or print. UserManuals.tech offer 413 Lucent Technologies manuals and user’s guides for free. Share the user manual or guide on Facebook, Twitter or Google+.

    							DEFINITY ECS Release 8.2
    Upgrades and Additions for R8.2si  555-233-122  Issue 1
    April 2000
    Upgrading R7si to R8si 
    5-11 Upgrade the Software 
    5
    2. Type the day in English (Sunday through Saturday) in the Day of the 
    Week: field. See Table 5-2
     for English day names. When done, press Ta b 
    to move to next field.
    3. Type the current month in English (January through December) in the 
    Month: field. See Table 5-3
     for English month names. When done, press 
    Ta b to move to next field.
    4. Type the day of month (1 through 31) in the Day of the Month: field 
    and press 
    Ta b to move to the next field.
    5. Type the current year in the Year: field and press 
    TA B to move to the next 
    field.
    6. Type the current hour for a 24-hour clock in the Hour: field and press
     Ta b to 
    move to the next field.
    7. Type the current minute (0 through 59) in the Minute: field (seconds 
    cannot be set). When done, press 
    Ta b to move to next field
    Table 5-2. English Day of the Week Names
    Day Number Day Name
    1 Sunday
    2 Monday
    3 Tuesday
    4 Wednesday
    5 Thursday
    6Friday
    7 Saturday
    Table 5-3. English Month Names
    Number Name Number Name
    1 January 7 July
    2 February 8 August
    3 March 9 September
    4 April 10 October
    5 May 11 November
    6 June 12 December 
    						
    							DEFINITY ECS Release 8.2
    Upgrades and Additions for R8.2si  555-233-122  Issue 1
    April 2000
    Upgrading R7si to R8si 
    5-12 Upgrade the Software 
    5
    8. Type standard or daylight savings in the Type field, according to the 
    current time in the local time zone. For example, if currently on standard 
    time, type standard.
    9. Type the rule number in the Daylight Savings Rule field.
    10. When all the information is correct, press 
    En te r.
    11. Type display time and press 
    En t e r to verify date and time data.
    Verify Additional Administration
    For standard reliability:
    1. Type list configuration software-version and press 
    En t e r to verify the 
    system software version (in the Memory Resident field).
    For high or critical reliability:
    1. Type list configuration software-version long and press 
    En t e r to verify 
    the system software version (in the Memory Resident field)
    For all reliabilities:
    2. Perform a sanity check on the system by executing the following 
    commands to ensure the translations were read in properly:
    a. list station
    b. list trunk-group
    c. list hunt-group
    This ensures there is no translation corruption and the translations can be 
    saved with the new software.
    3. Notify the switch administrator that for any previous login names and 
    passwords that still exist, the passwords expire in 24 hours. When 
    changed, the new login names and passwords must conform to the 
    following requirements:
    As before, a login name must have 3 to 6 alphanumeric characters. A 
    password must have 4 to 11 characters, including at least 1 alphabetic 
    character and 1 numeric character. 
    4. Since an R1V3.0 G3-MA cannot notify users about expiring passwords, 
    disable password aging for any login name used with an R1V3.0 G3-MA.
    Enable TTI
    NOTE:
    Do this step only if the TTI is disabled and you want it enabled.
    1. Type change system-parameters features and press 
    En te r to change the 
    TTI field back to its value before the upgrade. 
    						
    							DEFINITY ECS Release 8.2
    Upgrades and Additions for R8.2si  555-233-122  Issue 1
    April 2000
    Upgrading R7si to R8si 
    5-13 Upgrade the Software 
    5
    Enable Scheduled Maintenance
    1. Type change system-parameters maintenance and press En t e r to enable 
    the scheduled daily maintenance.
    2. Check the Start Time and Stop Time fields.
    Enable Customer Options and Alarm Origination
    1. Get the DOSS order number of the upgrade from the project manager and 
    ask the regional Customer Software Administration to complete the steps 
    in the shaded box. See ‘‘Where to Call for Technical Support’’ on page -xx
     
    for telephone numbers.
    NOTE:
    As part of the system registration process, the INADS Database 
    Administrator enables Alarm Origination.
    2. When administration is completed, log in as craft at the Login: prompt.
    Resolve Alarms
    1. Type display alarms and press En te r to examine the alarm log. Resolve 
    any alarms that may exist using 
    DEFINITY Enterprise Communications 
    Server Maintenance for R8si
    . 
    init login administration:
    1. Log in as init.
    2. Type change system-parameters customer-options and press 
    En t e r 
    to verify that the customer options are properly set.
    3. Go to screen 6, QSIG Optional Features, and set the Basic Call 
    Setup field to y if the customer was using Supplementary Services 
    Protocol b or d on an ISDN-PRI trunk group before the upgrade.
    4. Type change system-parameters offer-options and press 
    En t e r.
    5. If the Activate Offer field is n, set it to y and press 
    Ta b. A warning 
    message lets you know whether you need to save translations and 
    reboot to make the change permanent.
    6. Press 
    En te r to effect the changes or Canc el if there were no changes.
    7. Contact the requester when done. 
    						
    							DEFINITY ECS Release 8.2
    Upgrades and Additions for R8.2si  555-233-122  Issue 1
    April 2000
    Upgrading R7si to R8si 
    5-14 Upgrade the Software 
    5
    Check Link Status
    1. Type display communication-interface links and press En t e r. 
    2. Type status link 
    number and press En t e r. Verify that the service 
    status field is set to in service. Repeat this step for each link.
    Save Translations
    1. Type save translation and press En t e r to copy upgraded translations in 
    memory to the translation card, which takes about 10 minutes.
    Restore Announcements (if necessary)
    1. Type restore announcements and press En t e r to copy announcements 
    from the translation card to memory, which takes about 40 minutes.
    Return Replaced Equipment
    1. Return replaced equipment to Lucent Technologies according to the 
    requirements outlined in:
    BCS/Material Logistics, MSL/Attended Stocking Locations
    Methods and Procedures for Basic Material Returns
    2. Return the old translation card to Lucent Technologies. 
    						
    							Adding or Removing Hardware 
    6-1 Add Circuit Packs 
    6
    DEFINITY ECS Release 8.2
    Upgrades and Additions for R8.2si  555-233-122  Issue 1
    April 2000
    6
    Adding or Removing Hardware
    This chapter details the information required to install some equipment associated 
    with upgrading an existing system. 
    For more information about installing cabinets, refer to DEFINITY Enterprise 
    Communications Server Release 8 Installation and Test for Single-Carrier 
    Cabinets.
    For more information about installing adjuncts and peripheral devices, refer to 
    DEFINITY Enterprise Communications Server Release 8 Installation for Adjuncts 
    and Peripherals
    .
    Add Circuit Packs
    When installing additional features or equipment, it may be necessary to install 
    additional circuit packs.  This is a general procedure to use when adding features 
    or equipment that require adding circuit packs.
    1. Log onto the system and answer y to the 
    Suppress Alarm Origination 
    question during login.
    2. Install the circuit pack into the carrier.
    3. Log off the system after the addition (and any required administration) is 
    complete.
    For information about administering circuit packs and other equipment, refer to 
    DEFINITY Enterprise Communications Server Release 8 Administrator’s Guide. 
    						
    							DEFINITY ECS Release 8.2
    Upgrades and Additions for R8.2si  555-233-122  Issue 1
    April 2000
    Adding or Removing Hardware 
    6-2 List of Circuit Packs 
    6
    List of Circuit Packs 
    Table 6-1 lists the c irc uit p ac ks sorted  b y ap p aratus c od e, inc lud ing c irc uit 
    p ac ks used  in non-United  States installations.
    Table 6-1. Circuit Packs and Circuit Modules 
    Apparatus Code Name Type
    631DA1 AC Power Unit Power
    631DB1 AC Power Unit Power
    644A1 DC Power Unit Power
    645B1 DC Power Unit Power
    649A DC Power Unit Power
    676B/C DC Power Supply Power
    982LS Current Limiter Power
    CFY1B Current Limiter Power
    CPP1 Memory Expansion  Control
    ED-1E546
    (TN2169)
    (TN2170)
    (TN566)
    (TN567)DEFINITY AUDIX R3 System Port 
    Assembly
    ED-1E546
    (TN2208)
    (TN2170)Call Visor ASAI over the DEFINITY (LAN) Gateway R1 Port 
    Assembly
    J58890M1
    TN801)CallVisor ASAI/CallVisor PC/LAN over the DEFINITY 
    LAN Gateway R2Port 
    Assembly
    TN417 Auxiliary Trunk Port
    TN419B Tone-Clock Control
    TN420B/C Tone Detector Service
    TN429B/C/D Direct Inward/Outward Dialing (DIOD) Trunk Port
    TN433 Speech Synthesizer Service
    TN436B Direct Inward Dialing Trunk Port
    TN437 Tie Trunk - Australia Port
    TN438B Central Office Trunk Port
    TN439 Tie Trunk Port
    TN447 Central Office Trunk Port
    TN457 Speech Synthesizer Service
    Continued on next page 
    						
    							DEFINITY ECS Release 8.2
    Upgrades and Additions for R8.2si  555-233-122  Issue 1
    April 2000
    Adding or Removing Hardware 
    6-3 List of Circuit Packs 
    6
    TN458 Tie Trunk - U.K. Port
    TN459B Direct Inward Dialing Trunk Port
    TN464C/D/E/F DS1 Interface - T1, 24 Channel - E1, 32 Channel Port
    TN465/B/C Central Office Trunk Port
    TN467 Analog Line Port
    TN468B Analog Line Port
    TN479 Analog Line Port
    TN497 Tie Trunk - Italy Port
    TN553 Packet Data Line Port
    TN556B/C/D ISDN-BRI 4-Wire S/T-NT Interface Port
    TN570/B/C Expansion Interface Port
    TN722B DS1 Tie Trunk Port
    TN725B Speech Synthesizer Service
    TN726/B Data Line Port
    TN735 MET Line Port
    TN742 Analog Line Port
    TN744/B Call Classifier Service
    TN744/C/D Call Classifier - Detector Service
    TN746/B Analog Line Port
    TN747/B Central Office Trunk Port
    TN748/B/C/D Tone Detector Service
    TN750/B/C Announcement Service
    TN753/B Direct Inward Dialing Trunk Port
    TN754/B/C Digital Line 4-Wire DCP Port
    TN755/B Neon Power Unit Power
    TN758 Pooled Modem Port
    TN760B/C/D/E Tie Trunk Port
    TN762/B Hybrid Line Port
    TN763B/C/D Auxiliary Trunk Port
    TN765 Processor Interface Control
    TN767B/C/D/E DS1 Interface - T1, 24 Channel Port
    TN768 Tone-Clock Control
    TN769 Analog Line Port
    TN771/D Maintenance/Test Service
    Table 6-1. Circuit Packs and Circuit Modules  — Continued
    Apparatus Code Name Type
    Continued on next page 
    						
    							DEFINITY ECS Release 8.2
    Upgrades and Additions for R8.2si  555-233-122  Issue 1
    April 2000
    Adding or Removing Hardware 
    6-4 List of Circuit Packs 
    6
    TN773 Processor Control
    TN775/B/C Maintenance Service
    TN776 Expansion Interface Port
    TN780 Tone-Clock Control
    TN786/B Processor Control
    TN787F/G/H/J/K Multimedia Interface Service
    TN788B Multimedia Voice Conditioner  Service
    TN789 Radio Controller Control
    TN790/B Processor Control
    TN792 Duplication Interface (DUPINT) Control
    TN793 Analog Line (24-port) Port
    TN794 Network Control/Packet Interface Control
    TN794/TN2400 Network Control Interface Assembly (combination of 
    the TN794 and TN2400 circuit packs)Control
    TN796B Processor Control
    TN797 Analog CO Trunk and Line Combo Port
    TN799B Control-LAN (C-LAN) Port
    TN802B IP Interface Assembly Port
    TNPRI/BRI PRI to BRI Converter Port
    TN2135 Analog Line Port
    TN2136 Digital Line 2-Wire DCP Port
    TN2138 Central Office Trunk Port
    TN2139 Direct Inward Dialing Trunk Port
    TN2140/B Tie Trunk - Hungary, Italy Port
    TN2144 Analog Line Port
    TN2146 Direct Inward Dialing Trunk Port
    TN2147/C Central Office Trunk Port
    TN2149 Analog Line Port
    TN2180 Analog Line Port
    TN2181 Digital Line 2-Wire DCP Port
    TN2182/B Tone-Clock -Tone Detector and Call Classifier Control
    TN2183 Analog Line Port
    TN2184 DIOD Trunk Port
    TN2198 ISDN-BRI 2-Wire U Interface Port
    TN2199 Central Office Trunk Port
    Table 6-1. Circuit Packs and Circuit Modules  — Continued
    Apparatus Code Name Type
    Continued on next page 
    						
    							DEFINITY ECS Release 8.2
    Upgrades and Additions for R8.2si  555-233-122  Issue 1
    April 2000
    Adding or Removing Hardware 
    6-5 Installing Fiber Optic Cable Pass-Thru Kit (SCC) 
    6
    Installing Fiber Optic Cable Pass-Thru 
    Kit (SCC)
    This section details the installation of the DEFINITY fiber optic pass-thru kit for 
    Single-Carrier Cabinets (SCC) only. This kit (comcode 848029278) provides the 
    equipment necessary to install the fiber optic connectors and associated cabling. 
    Unpack and Inspect
    1. Verify the equipment received. See Figure 6-1. Actual equipment may vary 
    in appearance and may ship in separate packages. 
    2. See Table 6-2
     for a list of part comcodes. TN2202 Ring Generator Power
    T N 222 4/B Digital Line, 24-Port, 2-Wire D C P P or t
    TN2305 ATM Interface (Multimode) Port
    TN2306 ATM Interface (Single Mode) Port
    TN2313 DS1 Interface Port
    WP-91153 AC Power Supply (Single-Carrier Cabinet) Power
    Table 6-1. Circuit Packs and Circuit Modules  — Continued
    Apparatus Code Name Type
    Continued on next page 
    						
    							DEFINITY ECS Release 8.2
    Upgrades and Additions for R8.2si  555-233-122  Issue 1
    April 2000
    Adding or Removing Hardware 
    6-6 Installing Fiber Optic Cable Pass-Thru Kit (SCC) 
    6
    Figure 6-1. Fiber Pass-Thru Kit EquipmentFigure Notes
    1. Pass-thru Tool
    2. SC-SC Fiber Optic Adapter
    3. ST-SC Fiber Optic Adapter
    4. Fiber Optic Cable5. Fiber Optic Cable Disconnect Label
    6. I/O Connector Adapter Bracket
    7. Cable Tie
    8. Cable Tie Mount
    indapkit RPY 012398
    1
    2
    3
    4
    5
    6
    7
    8 
    						