2SystemSpecifications Thischapterprovidesinformationonthebasicsystemconfiguration,physicalspecifications, andrequirementsfortheHP9000rp3410orrp3440server. SystemConfiguration Table2-1liststheminimumandmaximumconfigurationoptionsfortheHP9000rp3410and rp3440servers. Table2-1MinimumandMaximumSystemConfigurations rp3440rp3410Component Oneortwodualprocessormoduleseach containingtwoPARISCprocessors.Each processoris800MHz/1.5MBcacheor1 GHz/1.5MBwith32MBor64MBL2cache. Onedualprocessormodulewithoneortwo PARISCprocessorsenabled.Eachprocessor is800MHz/1.5MBcachewith32MBor64 MBL2cache. Microprocessors Supportsupto12doubledatarate(DDR) registeredECCmemory,inPC2100DIMMs. Maximummemorycapacityis32GBif4GB DIMMsareused.SupportedDDRDIMM sizes:256MB,512MB,1GB,2GB,and4GB. Supportsupto12doubledatarate(DDR) registeredECCmemory,inPC2100DIMMs. Maximummemorycapacityis6GB. SupportedDDRDIMMsizes:256MB,512 MB,and1GB. Memory Three36GB,15KRPMUltra320SCSIhot-plug disksorthree73GB,15KRPMUltra320SCSI hot-plugdisksorthree146GB,10KRPM Ultra320SCSIhot-plugdisks. Three36GB,15KRPMUltra320SCSI hot-plugdisksorthree73GB,15KRPM Ultra320SCSIhot-plugdisksorthree146 GB,10KRPMUltra320SCSIhot-plugdisks. HDDs IntegratedUltra-3SCSIdual-channel controller;80MB/stransferratewithone internal68-pinconnectorandoneexternal 68-pinconnector. IntegratedUltra-3SCSIdual-channel controller;80MB/stransferratewithone internal68-pinconnectorandoneexternal 68-pinconnector. SCSI PCIGB,fastEthernetcontroller.PCIGB,fastEthernetcontroller.LAN Four64-bitPCI-Xslots,133MHz,3.3Vslots.Two64-bitPCI-Xslots,133MHz,3.3Vslots.PCIslots Oneserialport,fourUSB2.0ports,integrated RJ-45LANoniLOMPcard. Oneserialport,fourUSB2.0ports, integratedRJ-45LANoniLOMPcard. CoreI/O IDEinterface;48xspeed.None.DVD Optional.Optional.Externalstorage One650Wpowersupply.Youcaninstalla secondpowersupplytoprovideredundant (N+1)capability. One650Wpowersupply.Youcaninstalla secondpowersupplytoprovideredundant (N+1)capability. Powersupply DimensionsandValues Table2-2listsdimensionsandvaluesoftheHP9000rp3410andrp3440servers. Table2-2ServerDimensionsandValues ValuesDimension 26.8in(67.9cm)max.x19.0in(48.3cm)x3.4in(8.6cm) 26.6in(67.5cm)x11.6in(29.5cm)x19.5in(49.4cm) Rackdimensions(depthxwidthxheight) Pedestaldimensions(depthxwidthxheight) Minimum:38.6lbs(17.5kg) Maximum:49.0lbs22.2kg Minimum:49.4lbs22.4kg Maximum:56.3lbs25.5kg Rackweight Pedestalweight SystemConfiguration41
Table2-2ServerDimensionsandValues(continued) ValuesDimension 0.2m2(2.1sq.ft.)Pedestalfootprint 2URackunits Grounding ThesitebuildingshallprovideasafetygroundorprotectiveearthforeachACserviceentrance toallcabinets. InstallaPE(protectiveearthing)conductorthatisidenticalinsize,insulationmaterial,and thicknesstothebranch-circuitsupplyconductors.ThePEconductormustbegreenwithyellow stripes.Theearthingconductoristobeconnectedfromtheunittothebuildinginstallationearth or,ifsuppliedbyaseparatelyderivedsystem,atthesupplytransformerormotor-generatorset groundingpoint. ElectricalSpecifications Thissectionprovideselectricalspecificationsfortheserver. ACPowerCables Table2-3liststhepowercablesavailableforusewiththeHP9000rp3410andrp3440servers. Table2-3PowerCables CountryDescriptionPartNumber SouthAfricaPowerCordC15/SAfrica2.5mblackCAASSY9178120-5341 UnitedKingdom HongKong Singapore PowerCordC13/BS-13632.3mblackCAASSY9008120-1351 AustraliaPowerCordC13/AS-31122.0mgrayCAASSY9018120-1369 EuropePowerCordC13/CEE72.0mblackCAASSY9028120-1689 SwitzerlandPowerCordC13/SEV122.0mblackCAASSY9068120-2104 DenmarkPowerCordOPT-9123-COND2.25-M-LG9128120-6814 NorthAmerica(250#V) Japan PowerCordC13/6-15P0.0mblackCAASSY904/9188120-0698 IsraelPowerCordOPT-9193-COND2.3-M-LG9198120-6800 ArgentinaPowerCordC15/CEI23-162.5mblackCAASSY9208120-8390 ChilePowerCordC15/CEI23-162.5mblackCAASSY9218120-8389 ChinaPowerCordC13/GB-10022.236mgrayCAASSY9228120-8376 SouthAmericaPowerCordOPT-9273-COND2.3-M-LGFLNT9278121-0668 AllC13/C14Jumpercord8120-6514 CircuitBreaker Themarkedelectricalfortheserveris7.2amps.Therecommendedcircuitbreakersizeis12amps perlinecord(twomaximum)forNorthAmerica.ForcountriesoutsideNorthAmerica,consult thelocalelectricalauthoritythathasjurisdictionfortherecommendedcircuitbreakersize. 42SystemSpecifications
SystemPowerSpecifications Availablepower(output)isthemaximumDCpowerthatthepowersupplycansupplytothe system. MaximuminputpoweriswhatthepowersupplyrequiresfromtheAClinetodeliverthe maximumDCoutput(givenworstcaseefficiencyandmaximumloading). Maximuminputcurrentistheworstcaseorhighestcurrentgiventhelowestinputvoltageand themaximuminputpower. Table2-4liststhesystempowerspecifications. Table2-4SystemPowerSpecifications Max.perPCI-XSockets64-bit,133MHzPeak(15 sec) TotalRatingParameter OffOff100–240VACInputvoltage OffOff7.2Aat115VACor 3.6Aat220VAC Inputcurrent(max) OffOff50to60HzInputfrequency OffOff560WMeasuredinputpower 85WtotalforPCIsocketsOff650WAvailablepower(output) Off0.5A49AMaximumcurrentat+12V 0.1AOff0.35AMaximumcurrentat–12V 4.6AOff34AMaximumcurrentat+3.3V 3A31A18AMaximumcurrentat+5V OffOff3.5AMaximumcurrentat+3.3V standby Ifanoverloadtriggersthepowersupplyoverloadprotection,thesystemisimmediatelypowered off.Toresetthepowersupplyunit,followthesesteps: 1.Disconnectthepowercord. 2.DeterminewhatcausedtheoverloadbycontactingaHPsupportrepresentative. 3.Reconnectthepowercord. 4.Rebootthesystem. Ifanoverloadoccurstwice,thereisanundetectedshortcircuitsomewhere. WhenyouusethefrontpanelPowerbuttontopowerofftheserver,powerconsumptionfalls belowthelowpowerconsumption,butdoesnotreachzero.Toreachzeropowerconsumption in“off”mode,eitherunplugtheserveroruseapowerblockwithaswitch. PowerandCooling Typicalpowerconsumptionforaserveris600W/2050Btu/h.Thepowerconsumptionslistedin Table2-5arevalidforastandardconfigurationasshipped(one1GHzprocessor,6GBofmemory, 650Wpowersupply,threeharddiskdrives,onegraphicscard,oneLVDSCSIcard). Allinformationinthissectionisbasedonprimarypowerconsumptions. Table2-5listsadditionalcomponentpowerconsumptioninformation. ElectricalSpecifications43
Table2-5AdditionalComponentPowerConsumption PowerConsumptionAdditionalComponent 443.6Btu/h130WProcessor 78.4Btu/h23WSCSIharddiskdrive(withI/Oaccess) 54.5Btu/h16WSCSIharddiskdrive(idle) 34.12Btu/hto85.30Btu/h10Wto25WPCIcard EnvironmentalSpecifications Thissectionprovidesthetemperatureandhumidityrequirements,noiseemission,andairflow specificationsfortheserver. Operatingtemperatureandhumidityrangesmightvarydependingontheinstalledmassstorage devices.Highhumiditylevelscancauseimproperdiskoperation.Lowhumiditylevelscan aggravatestaticelectricityproblemsandcauseexcessivewearofthedisksurface. Table2-6liststheenvironmentalspecificationsforasystemprocessingunitwithaharddisk drive. Table2-6EnvironmentalSpecifications ValueParameter +5degreesCto+35degreesC(+40degreesFto+95degrees F) Operatingtemperature –40degreesCto+70degreesC(–40degreesFto+158 degreesF) Storagetemperature +40degreesC(+104degreesF)Over-temperatureshutdown 15%to80%relative(noncondensing)Operatinghumidity 8%to85%relative(noncondensing)Storagehumidity Soundpowerlevel1Acousticnoiseemission(ISO7779) Pedestalsystem LwA=5.1BATypicalconfiguration(diskidle)2 LwA=5.4BAMaximumconfiguration(diskidle)3 LwA=6.2BAMaximumconfiguration(diskactive)3 Racksystem LwA=6.4BATypicalconfiguration(diskidle)2 LwA=6.4BAMaximumconfiguration(diskidle)3 LwA=7.2BAMaximumconfiguration(diskactive)3 3048m(10,000ft.)maxOperatingaltitude 4600m(15,000ft.)maxStoragealtitude 1Typicalconfigurationatroomtemperature(25degreesC). 2Oneprocessorenabled,oneortwoSCSIharddiskdrivesandlessthan8GBofmemory. 3Twodualprocessors,oneortwoSCSIharddiskdrivesandlessthan8GBofmemory. OperatingEnvironment Thesystemisdesignedtoruncontinuouslyandmeetreliabilitygoalsinanambienttemperature of5°Cto35°C(+40°Fto+95°F)atsealevel.Themaximumallowabletemperatureisde-rated1°C 44SystemSpecifications
per1,000feetofelevationabove5,000feetabovesealevelupto30°Cat10,000feet.Foroptimum reliabilityandperformance,therecommendedoperatingrangeis20°Cto25°Cand40%–55% relativehumidity. Ambientintakeairtemperatureisoftendifferentfromambientroomtemperature.Measurethe operatingtemperatureandhumiditydirectlyinfrontofthecabinetcoolingairintakesrather thanjustcheckingambientroomconditions. EnvironmentalTemperatureSensor Theserverincludesinternalsensorsthatmonitorinputairtemperatureandserveroperating temperatures.TheambientairtemperatureismeasuredusingasensorplacedonthesystemI/O board.Datafromthesensorisusedtocontrolthefanspeedandtoinitiatesystemovertemperature shutdown. NonoperatingEnvironment Thesystemisdesignedtowithstandambienttemperaturesbetween-40°Cto70°Cunder nonoperatingconditions. Cooling Thissectionprovidesinformationonthecoolingsystemsintheserver. CPUandMemoryCooling Theserverincorporatesfronttobackairflowacrosstheprocessorandmemoryextenderboards andthroughtheHDDbackplane.Two127mmdualfanassemblies,mountedverticallyinthe centerofthechassis,pullairthroughtheprocessorandmemorysectionandpushairthrough thePCIsection. Eachprocessorandmemorydedicateddualfanassemblyiscontrolledbysmartfancontrol circuitsembeddedinthesystemI/Oboard.Thesmartfancontrolcircuitreceivesfancontrol inputfromthesystemfancontrollerintheI/Oboard,andreturnsfanstatusinformationtothe systemfancontroller.Thesmartfancircuitcontrolsthepowerandthepulse-width-modulated controlsignaltothefanandmonitorsthespeedindicatorbackfromeachofthefans.Thefan statusLEDisdrivenbythesmartfancircuit.ThefanstatusLEDislocatedonthediagnostic boardinsidethesystem. BulkPowerSupplyCooling Coolingforthebulkpowersuppliesisprovidedbyone120mmdualfanassemblyandone externallymounted60mmpowersupplyfan.Airispushedintobothpowersupplybaysbythe 120mmfanassemblyandexhaustedouttherearbythe60mmfan(oneperpowersupply). Airflowsoutoftherearofthechassiswithminimalleakageintothecellairflowplenum. NOTE:Apowersupplyfillerisrequiredintheunusedpowersupplyslottomaintainproper airflowthroughoutthesystem. PCIandMassStorageSectionCooling TwodualfanassemblieslocatedatthecenterofthechassisprovideairflowforallthePCIslots. AirflowisovertheprocessorandmemoryextenderboardsandintothePCIsection.Thefans arecontrolledbythesystemtemperatureandrunatthespeednecessarytomaintainproper internaltemperaturethroughoutthechassis. EnvironmentalSpecifications45
Theairispulledthroughopeningsinthefrontcoverandthemassstoragedevicesandpushed throughthePCIcardcage.PerforationisprovidedbetweenandabovethePCIcardcagetoenable properexhaustventilationtomaintaintherequiredtemperatureratingofthePCIcards. CAUTION:Formaximumcoolingeffects,ensurethatthechassisventilationholesarenot blockedorcoveredafterinstallation. AcousticNoiseSpecification TheacousticnoisespecificationfortheHP9000rp3410orrp3440serversis53dbLpA(sound pressurelevelatbystanderpositioninadedicatedcomputerroomenvironmenttemperatureof
3InstallingtheSystem Thischapterprovidesinformationonhowtoinstallthesystem. Introduction TheHP9000rp3410serverisa1P/1C,1P/2C,rack-orpedestal-mountserver.Similarly,theHP 9000rp3440serverisa1P/1C,1P/2C,2P/2Cor2P/4Crack-orpedestal-mountserver.Bothof theseserversarebasedonthePA-RISCprocessorfamilyarchitecture. Theserveraccommodatesupto12DIMMsandinternalperipheralsincludingdisksandDVD. Itshigh-availabilityfeaturesincludehot-swappablepowersuppliesandhot-pluggabledisk drives. ThesupportedoperatingsystemisHP-UX11iv1(andnewerHP-UXversionsthatsupport PA-RISCsystems). ServerViews Figure3-1,Figure3-2,Figure3-3,andFigure3-4showthefront,rear,andpedestal-mountviews oftheHP9000rp3410andrp3440servers. Figure3-1HP9000rp3410/rp3440Server-FrontView Figure3-2HP9000rp3410/rp3440Server-FrontViewwithBezelRemoved Figure3-3HP9000rp3410/rp3440Server-RearView Introduction47
Figure3-4HP9000rp3410/rp3440Server-PedestalMount DetailedServerDescription ThefollowingsectionslistthemainsubsystemswithintheHP9000rp3410andrp3440servers. Features Table3-1liststhefeaturesoftheHP9000rp3410andrp3440servers. Table3-1HP9000rp3410andrp3440ServerFeatures rp3440rp3410Features Onetofourprocessorsat800MHz(or1GHz) and1GHzwith1.5MBL1cache/32MBL2cache Oneortwoprocessorsat800MHzwith1.5MB L1cache/32MBL2cache PA-8800 Processors Onetofourprocessorsat800MHz(or1GHz) and1GHzwith1.5MBL1cache/64MBL2cache Oneortwoprocessorsat800MHzwith1.5MB L1cache/64MBL2cache PA-8900 Processors Supportsupto24GBSupportsupto6GBMemory Three36GB,15KRPMUltra320SCSIHotPlug Diskor3-73GB,15KRPMUltra320SCSIHot PlugDiskorthree146GB,10KRPMUltra320 SCSIHotPlugDisk Three36GB,15KRPMUltra320SCSIHotPlug Diskor3-73GB,15KRPMUltra320SCSIHot PlugDiskorthree146GB,10KRPMUltra320 SCSIHotPlugDisk HDDs A6150BPCIcard(optional)A6150BPCIcard(optional)Video 48InstallingtheSystem
Table3-1HP9000rp3410andrp3440ServerFeatures(continued) rp3440rp3410Features IntegratedUltra-3SCSIdual-channelcontroller; 80MBstransferratewithoneinternal68pin connectorandoneexternal68pinconnector. N/ASCSI PCIGigabit,fastEthernetcontrollerPCIGigabit,fastEthernetcontrollerLAN Four64bithot-pluggablePCI-Xslots,133MHz, 3.3Vslots Two64bithot-pluggablePCI-Xslots,133MHz, 3.3Vslots PCISlots Threeserialports,4USB2.0ports,integrated RJ-45LANoniLOMPcard. Threeserialports,4USB2.0ports,integrated RJ-45LANoniLOMPcard. CoreI/O IDEinterface;48xspeedN/ADVD Two-portU320PCI-XRAIDSmartArray6402 (A9890AController) Two-portU320PCI-XRAIDSmartArray6402 (A9890AController) ExternalStorage Redundant,(2N+1)714WattRedundant,(2N+1)714WattPowerSupply HP-UX11iv1,HP-UX11iv2,andHP-UX11iv3 (choiceofEnterprise,Mission-Critical,Technical Computing,andFoundationoperating environments) HP-UX11iv1,HP-UX11iv2,andHP-UX11i v3(choiceofEnterprise,Mission-Critical, TechnicalComputing,andFoundation operatingenvironments) Operating Systems Firmware Firmwareconsistsofmanyindividuallylinkedbinaryimagesthatareboundtogetherbyasingle frameworkatruntime.Internally,thefirmwareemploysasoftwaredatabasecalledadevice treetorepresentthestructureofthehardwareplatformandtoprovideameansofassociating softwareelementswithhardwarefunctionality. ThefirmwareincorporatesBootConsoleHandler(BCH)whichprovidesaninterfacebetween theoperatingsystemandtheplatformfirmware. ThefirmwaresupportstheHP-UX11iversion1(andhigherHP-UXversionsthatsupport PA-RISCsystems)operatingsystemthroughtheHP9000processorfamilystandardsand extensions,andhasnooperatingsystem-specificfunctionalityincluded.Theoperatingsystem ispresentedwiththesameinterfacetosystemfirmware,andallfeaturesareavailabletothe operatingsystem. EventIDsforErrorsandEvents TheserverfirmwaregenerateseventIDssimilartochassiscodesforerrors,events,andforward progresstotheiLOMPthroughcommonsharedmemory.TheiLOMPinterpretsandstores eventIDs.Reviewingtheseeventshelpsyoudiagnoseandtroubleshootproblemswiththeserver. DimensionsandValues Table3-2liststhedimensionsandtheirvaluesoftheHP9000rp3410andrp3440servers. Table3-2ServerDimensionsandValues ValuesDimensions 26.8in(67.9cm)maxx19.0in(48.3cm)x3.4in(8.6cm) 26.6in(67.5cm)x11.6in(29.5cm)x19.5in(49.4cm) Rackdimensions(depthxwidthxheight) Pedestaldimensions(depthxwidthxheight) Minimum:38.6lbs(17.5kg) Maximum:49.0lbs(22.2kg) Minimum:49.4lbs(22.4kg) Maximum:56.3lbs(25.5kg) Rackweight Pedestalweight Introduction49
Table3-2ServerDimensionsandValues(continued) ValuesDimensions 2.1sqft(0.2m2)Pedestalfootprint 2URackunits SafetyInformation Usecaretopreventinjuryandequipmentdamagewhenperformingremovalandreplacement procedures.Voltagesmightbepresentwithintheserver.Manyassembliesaresensitivetodamage byelectrostaticdischarge. Followthesafetyconventionslistedbelowtoensuresafehandlingofcomponents,toprevent injury,andtopreventdamagetotheserver: •Whenremovingorinstallinganyservercomponent,followtheinstructionsprovidedinthis guide. •Ifinstallingahot-swappableorhot-pluggablecomponentwhenpowerisapplied(fansare running),reinstalltheservercoverimmediatelytopreventoverheating. •Ifinstallingahot-pluggablecomponent,completetherequiredsoftwareinterventionbefore removingthecomponent. •Ifinstallinganassemblythatisneitherhot-swappable,norhot-pluggable,disconnectthe powercablefromtheexternalserverpowerreceptacle. WARNING!Ensurethattheserverispoweredoffandallthepowersourcesaredisconnected fromtheserverbeforeremovingorinstallingserverhardwareunlessyouareremovingor installingahot-swappableorhot-pluggablecomponent. VoltagesarepresentatvariouslocationswithintheserverwheneveraDCpowersourceis connected.Thisvoltageispresentevenwhenthemainpowerswitchisturnedoff. Failuretoobservethiswarningcanresultinpersonalinjuryordamagetoequipment. •Donotwearlooseclothingthatcansnagorcatchontheserveroronotheritems. •Donotwearclothingsubjecttostaticchargebuildup,suchaswoolorsyntheticmaterials. •Ifinstallinganinternalassembly,wearanantistaticwriststrapanduseagroundingmat, suchasthoseincludedintheElectricallyConductiveFieldServiceGroundingKit(HP 9300-1609). •Handleaccessoryboardsandcomponentsbytheedgesonly.Donottouchanymetal-edge connectorsoranyelectricalcomponentsonaccessoryboards. InstallationSequenceandChecklist Toensuresuccessfulinstallationoftheserver,followthestepsinTable3-3sequentially. Table3-3InstallationSequenceChecklist CompletedDescriptionStep Unpackandinspecttheservershippingcontainer;inventorythecontentsusingthe packingslip. 1 Installadditionalcomponentsshippedwiththeserver.2 Installtheserverintoarack-orpedestal-mount.3 Connectcablestotheserver.4 ConnectDCinputpowercable.4a ConnectLANcoreI/Ocable.4b 50InstallingtheSystem